- 05000289/LER-1983-038-03, /03L-0:on 831017,valve V-2 on Purge Exhaust RMS RM-A-9 Discovered in Position 2 Rather than Position 1, Causing Reactor Bldg Purge Sample Flow to Shut Off.Caused by Personnel Error.Valve Restored + (ML20082H313)
- ML20082H316 + (ML20082H316)
- 05000293/LER-1983-055-03, /03L-0:on 831020,fire Pump Diesel Failed to Start. Caused by Battery Failure.Batteries Replaced & Replacement Batteries Stocked + (ML20082H325)
- ML20082H326 + (ML20082H326)
- ML20082H327 + (ML20082H327)
- ML20082H330 + (ML20082H330)
- ML20082H342 + (ML20082H342)
- ML20082H351 + (ML20082H351)
- 05000302/LER-1983-047-03, /03L-0:on 831021,two Seismic Monitoring Instrumentation Channels Assumed to Have Been Inoperable for at Least 30 Days.Caused by Inadequate Procedure,Allowing Cassettes to Be Used Past Natural end-of-life + (ML20082H353)
- ML20082H356 + (ML20082H356)
- ML20082H357 + (ML20082H357)
- ML20082H358 + (ML20082H358)
- ML20082H359 + (ML20082H359)
- ML20082H360 + (ML20082H360)
- 05000369/LER-1983-105-03, /03L-0:on 831018,RCS Subcooling Margin Monitor Declared Inoperable When Margin Incorrect Due to Failure of Thermal Outputs Computer Program.Caused by Suspected Error in Program.Error Corrected + (ML20082H367)
- ML20082H369 + (ML20082H369)
- ML20082H370 + (ML20082H370)
- ML20082H375 + (ML20082H375)
- 05000366/LER-1983-124-03, /03L-0:on 831108,during Performance of Procedure HNP-2-3309,HPCI Steam Supply Primary Containment Outboard Isolation Valve Failed to Isolate.Caused by Motor Operator Torquing Out.Torque Setting Adjusted + (ML20082H378)
- 05000321/LER-1983-106-03, /03L-0:on 831102,during Normal Operation,High Level Alarm in HPCI Oil Tank Received.Caused by High Humidity in HPCI Pump Room Causing Condensation to Form on Oil Tank.Water Contaminated Oil Replaced + (ML20082H379)
- 05000370/LER-1983-066-03, /03L-0:on 831019,invalid Fire Alarm for Fire Detection Zone Efa 173 Would Not Reset at Control Room Data Gathering Panel.Caused by Component Malfunction Due to Dirt Accumulation.Detector Replaced + (ML20082H383)
- ML20082H384 + (ML20082H384)
- ML20082H385 + (ML20082H385)
- ML20082H388 + (ML20082H388)
- ML20082H390 + (ML20082H390)
- ML20082H392 + (ML20082H392)
- ML20082H393 + (ML20082H393)
- BSEP-83-3748, Responds to 830826 Intergranular Stress Corrosion Cracking Order Confirming Shutdown & 830304 IE Bulletin 83-02 by Providing Results of Ultrasonic Test Insp of ASME Code Class I Stainless Steel Piping.Work in Progress on Overlay Repair + (ML20082H397)
- ML20082H398 + (ML20082H398)
- ML20082H401 + (ML20082H401)
- ML20082H406 + (ML20082H406)
- ML20082H409 + (ML20082H409)
- ML20082H413 + (ML20082H413)
- ML20082H417 + (ML20082H417)
- ML20082H418 + (ML20082H418)
- 05000366/LER-1983-122-03, /03L-0:on 831104,while Performing HPCI Steam Line Delta P Instrument Ft & C Procedure,Hpci Steam Line Flow High Switch Found Actuating Above Tech Spec Limit.Caused by Setpoint Drift.Switch Calibr + (ML20082H420)
- ML20082H424 + (ML20082H424)
- 05000280/LER-1983-048-03, /03L-0:on 831024,discharge Pressure of Charging Pump B Pump CC Decreased to Point Which Automatically Started Redundant Pump.Caused by Closed Valve LCV-CC-001 + (ML20082H430)
- ML20082H441 + (ML20082H441)
- 05000220/LER-1983-033-03, /03L-0:on 831018,during Normal Operation,Visual Insp of Snubber 39-4S-21 Revealed Oil Reservoir Indicated off-scale Toward Low End.Snubber Removed & Proven Operable. Snubber Replaced 831019 to Insure Operability + (ML20082H444)
- ML20082H445 + (ML20082H445)
- 05000278/LER-1983-015-03, /03L-0:on 831013,during HPCI Sys Testing,Both HPCI Turbine Exhaust Rupture Discs Failed Due to High Pressure.Hpci Declared Inoperable.Caused by Water in Exhaust Line During Turbine Start.Disc Replaced + (ML20082H446)
- ML20082H448 + (ML20082H448)
- ML20082H451 + (ML20082H451)
- ML20082H452 + (ML20082H452)
- 05000219/LER-1983-021-03, /03L-0:on 831012,loss of Main Bus 1A & Emergency Bus 1C Rendered One Standby Gas Treatment Sys Train Inoperable.Stack Gas Sampling Capability Lost for Approx 3 Had Pump a Shutdown Due to Loss of Power + (ML20082H454)