- 05000458/LER-1991-003, :on 910322,damper Isolations & Automatic Swap of Divisional Control Bldg Ventilation/Chiller Occurred Due to Inadequate Work Plan.Work Plan Revised to Document Removal & Restoration of Hot & Neutral Wiring + (ML20079L965)
- ML20079L966 + (ML20079L966)
- ML20079L967 + (ML20079L967)
- 05000387/LER-1983-171-03, /03L-0:on 831217,both Reactor Water Cleanup Sys High Dp Channel Calibr Switches Had as-found Trip Settings Greater than Tech Spec Requirements.One Switch out-of-calibr Due to Bellows Failure.Other Switch Recalibr + (ML20079L969)
- ML20079L970 + (ML20079L970)
- ML20079L975 + (ML20079L975)
- 05000387/LER-1983-010-01, /01P-0:on 830209,runout Flow on Feedwater Pumps Found in Excess of 135% Assumption in Feedwater Controller Failure/Max Demand Transient Analysis.Feedwater Motor Speed Changer Reduced to Limit Flow.Stops Will Be Adjusted + (ML20079L978)
- ML20079L979 + (ML20079L979)
- ML20079L980 + (ML20079L980)
- ML20079L981 + (ML20079L981)
- ML20079L983 + (ML20079L983)
- ML20079L986 + (ML20079L986)
- ML20079L987 + (ML20079L987)
- 05000272/LER-1983-066-01, /01T-0:on 831225 & 26,fire Suppression Water Storage Tank Capacity Dropped Below Min.Caused by Ruptured Elbow on Sprinkler Riser Due to Freezing.Elbow Replaced & Number of Operating Pumps Increased + (ML20079L988)
- ML20079L989 + (ML20079L989)
- ML20079L990 + (ML20079L990)
- 05000333/LER-1982-059, Forwards LER 82-059/03L-0 + (ML20079L992)
- ML20079L995 + (ML20079L995)
- ML20079L999 + (ML20079L999)
- 05000346/LER-1983-002, Forwards LER 83-002/03L-0 + (ML20079M001)
- ML20079M009 + (ML20079M009)
- ML20079M013 + (ML20079M013)
- ML20079M016 + (ML20079M016)
- ML20079M017 + (ML20079M017)
- ML20079M023 + (ML20079M023)
- ML20079M024 + (ML20079M024)
- 05000333/LER-1982-059-03, /03L-0:on 821226,MSIV B Outboard 10% Switch Would Not Reset When Tested Per Tech Spec 3.1-1.Caused by Mismatch Between Activation & Striker Plate in Reset Direction of Valve Travel.Striker Plate Mechanically Reworked + (ML20079M025)
- ML20079M028 + (ML20079M028)
- 05000346/LER-1983-002-03, /03L-0:on 830114 & 15,after Reactor Trips,Rcs Dose Equivalent I-131 Exceeded Tech Spec Limit.Caused by Slight Leakage of Fission Products Through Fuel Cladding.Caused by Temp & Pressure Changes.Situation Monitored + (ML20079M031)
- 05000387/LER-1983-170-03, /03L-0:on 831213,charcoal Filters in Train a of Control Room Emergency Outside Air Supply Sys Did Not Satisfy Test Specs During Freon Leak Test.Caused by Insufficient Charcoal in Charcoal Filter + (ML20079M032)
- 05000220/LER-1983-045-03, /03L-0:on 831221,site Operations Review Committee Failed to Review Temporary Change Re Fuel Handling Procedure N1-FHP-32, Fort St Vrain Cask Handling, within 7 Day Tech Spec Limitation + (ML20079M038)
- 05000317/LER-1983-071-03, /03L-0:on 831210,pressurizer Pressure Decreased to 2,180 Psia.Pressure Switch in Stator Liquid Cooling Sys Failed,Causing Turbine Runback.Caused by Loose Screw Holding Switch Actuator to Bourdon Tube.Screw Replaced + (ML20079M043)
- 05000328/LER-1983-008, Forwards LER 83-008/03L-0 + (ML20079M046)
- ST-HL-AE-1045, Final Deficiency Rept Re Control & Issuance of Design Related Drawings.Initially Reported on 831216.Configuration Control Program Assures Compliance W/Technical Requirements. Item Not Reportable Per 10CFR50.55(e) + (ML20079M047)
- 05000333/LER-1983-041-04, /04T-0:on 831228,mollusk Samples Exceeded 10 Times Control Sample for Mn-54.Caused by High Release of Mn-54 Via Liquid Effluent,Producing High Concentration Factor in Mollusks.Release within Tech Spec Limits + (ML20079M050)
- ML20079M051 + (ML20079M051)
- ML20079M052 + (ML20079M052)
- A09899, Responds to NRC Re Violations Noted in Safety Insp Rept 50-423/91-15 & 911002 Notice of Violation & Forwards Civil Penalty in Amount of $50,000.Design Change Implemented to Address Mussel Fouling + (ML20079M058)
- ML20079M059 + (ML20079M059)
- ML20079M060 + (ML20079M060)
- 05000328/LER-1983-008-03, /03L-0:on 830118,while in Mode 1 During Review of SI-90.32,discovered Pressurizer Pressure Channel 2-PS-68-334 Out of Tolerance on 821215.Cause Unknown.Channel Monitored for Bistable Drift.Setpoints Reset + (ML20079M062)
- ML20079M063 + (ML20079M063)
- 05000334/LER-1983-040-03, /03L-0:on 831213,chemical Addition Pump Discharge Valve MOV-QS-1048 Failed to Close Electrically as Required by Tech Spec 3.6.2.3.Caused by Faulty Torque Switch. Compression Spring Replaced + (ML20079M066)
- 05000366/LER-1982-018-03, Evidence of Main Steam Pipe Hanger Embed Plate Pulling from Ceiling Found.Caused by Concrete Spalling Around Embed Plate Due to Localized Detective Matl &/Or Faulty Installation + (ML20079M067)
- 05000272/LER-1983-072-01, /01T-0:on 831229,fire Suppression Water Storage Tanks Indicated Level Below Min Capacity Allowed.Caused by Incorrect Fire Suppression Storage Tank Capacity Curves.New Tank Capacity Curves Generated + (ML20079M068)
- ML20079M070 + (ML20079M070)
- ML20079M077 + (ML20079M077)
- 05000244/LER-1983-002, Forwards LER 83-002/03L-0 + (ML20079M084)
- ML20079M092 + (ML20079M092)
- 05000333/LER-1983-005, Forwards LER 83-005/03L-0 + (ML20079M095)
- ML20079M096 + (ML20079M096)