Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- ML20071N744 + (ML20071N744)
- ML20071N746 + (ML20071N746)
- ML20071N750 + (ML20071N750)
- ML20071N751 + (ML20071N751)
- 05000328/LER-1983-068-03, /03L-0:on 830504,during Routine Filling of Cold Leg 2 Accumulator,Safety Injection Pump Inadvertently Left On,Resulting in Accumulator Being Overfilled & Overpressurized.Caused by Personnel Error + (ML20071N753)
- 05000416/LER-1982-066-03, /03L-0:on 820909,smoke Detector Zone Covering Hallway Area Elevation 93-ft Auxiliary Bldg & HPCS Pump Room Alarmed & Would Not Clear.Caused by Dust Accumulation on Ionization Smoke Detectors.Detectors Cleaned + (ML20071N755)
- ML20071N756 + (ML20071N756)
- ML20071N758 + (ML20071N758)
- ML20071N764 + (ML20071N764)
- ML20071N774 + (ML20071N774)
- ML20071N775 + (ML20071N775)
- 05000416/LER-1982-065, Forwards LER 82-065/03L-0 + (ML20071N777)
- 05000311/LER-1982-112-01, /01P:on 821005,svc Water Discovered Leaking at Rate of 1 Gallon Per Minute Inside Containment Bldg on Fan Coil Unit 21.Cause Not Stated.Leak Isolated.Investigation Continuing.Detailed Rept Forthcoming + (ML20071N782)
- AECM-83-0306, RO 83-039/0:on 830414,fire Detection Zone 2-18 Alarmed & Would Not Reset.Caused by Dust Particles on Ionization Detector.Detectors Cleaned & Restored to Operability on 830505 + (ML20071N790)
- 05000416/LER-1982-065-03, /03L-0:on 820907,smoke Detectors in Fuel Handling Area & Main Steam Tunnel Alarmed & Would Not Clear.Caused by Dust Accumulation on Ionization Smoke Detector.Detectors Cleaned + (ML20071N791)
- ML20071N792 + (ML20071N792)
- AECM-83-0301, RO 83-036/0:on 830418,fire-rated Penetration DE-20A Opened to Route Cable to Supply Temporary Power to Div I Lighting Transformer 1X113 During Planned Electrical Outage. Restoration Scheduled for 830615 + (ML20071N793)
- ML20071N795 + (ML20071N795)
- ML20071N798 + (ML20071N798)
- 05000249/LER-1981-033-01, Unit 2/3 Diesel Generator (D/G) Tripped Due to High Cooling Water Temp & Unit 3 D/G Manually Tripped During Testing.Caused by Failure of Cooling Water Pump Discharge Valve + (ML20071N801)
- 05000255/LER-1983-034-01, /01T-0:on 830516,D Safety Injection Tank T-82D Level Fell Below Tech Spec Limit During Routine Sampling. Caused by Delay in Fill Operations Due to Failure of Relief Valve RV-3161 to Reseat within 1 H + (ML20071N806)
- ML20071N811 + (ML20071N811)
- ML20071N816 + (ML20071N816)
- GO2-82-806, Interim Deficiency Rept Re Improper Installation of Concrete Expansion Anchors & Unacceptable Concrete & Grout Work. Initially Reported on 820403.Corrective Actions Continuing. Next Rept Will Be Submitted on 821218 + (ML20071N817)
- ML20071N821 + (ML20071N821)
- 05000259/LER-1983-022-03, /03L-0:on 830429,downstream HEPA Filters in Standby Gas Treatment Sys Trains a & B Exceeded Tech Spec 18-month Test Frequency.Caused by Personnel Error.Procedure SI 4.7.B-4 Review Rescheduled + (ML20071N824)
- ML20071N825 + (ML20071N825)
- ML20071N827 + (ML20071N827)
- 05000281/LER-1983-022-03, /03L-0:on 830430,PT-27 Revealed Amp Readings for Heat Tracing Panel 8,circuits 5A & 22A,below Acceptance Criteria.Caused by Excessive Heat.Defective Heat Tracing Replaced & Tested.Design Change Prepared + (ML20071N828)
- ML20071N830 + (ML20071N830)
- 05000281/LER-1983-023-03, /03L-0:on 830511,PT 27B Revealed Amp Readings for Heat Tracing Panel 9,circuit 28A,below Acceptance Criteria. Caused by Boric Acid Buildup on Heat Tape,Corroding Terminals & Resulting in Open Circuit.Heat Tracing Replaced + (ML20071N835)
- 05000237/LER-1983-036-03, /03L-0:on 830502,drywell Floor Drain Leakage Exceeded Tech Spec Limits Due to Bonnet Leakage on Feedwater Check Valve 2-220-58B.Caused by Failed Bonnet Seal Ring.Seal Ring Replaced.Leakage to Be Monitored + (ML20071N840)
- 05000255/LER-1983-032-03, /03L-0:on 830429,declaration of Operability Signature Found Incomplete for Maint Order on Fire Barrier Penetration.Caused by Personnel Oversight Re New Maint Order Closeout Procedures + (ML20071N843)
- ML20071N851 + (ML20071N851)
- 05000366/LER-1983-028-03, /03L-0:on 830420,B Plant Svc Water Isolation Valve 2P41-F316B Failed to auto-close Upon loss-of-sys- Pressure Signal Initiation.Cause Under Investigation + (ML20071N872)
- ML20071N880 + (ML20071N880)
- ML20071N882 + (ML20071N882)
- RBG-15-130, Interim Deficiency Rept DR-93 Re Documentation & Code Stamping of Interconnecting Piping Between Reactor Water Cleanup Hxs.Util Awaiting Info from Supplier Atlas Industrial Mfg Co.Next Rept Will Be Submitted by 830708 + (ML20071N884)
- 05000296/LER-1983-028-03, /03L-0:on 830429,while Investigating Blown Fuse in Annunication,Relay 16A-K79 Failed.Caused by Coil Over Heating Melting Spool Matl & Stuck Armature in Energized Position.Relay Replaced + (ML20071N887)
- ML20071N890 + (ML20071N890)
- ML20071N892 + (ML20071N892)
- ML20071N895 + (ML20071N895)
- ML20071N897 + (ML20071N897)
- ML20071N899 + (ML20071N899)
- 05000302/LER-1983-022-01, /01T-0:on 830516,two Pinhole Leaks Found in Piping on Downstream Side of Two Nuclear Svc HX Discharge Isolation Valves.Caused by Insufficient Surveillance & Design Inadequacy on Inner PVC Liner + (ML20071N903)
- ML20071N904 + (ML20071N904)
- 05000339/LER-1983-037-03, /03L-0:on 830502,containment Particulate (RM-259) & Gaseous (RM-260) Activity Monitors Found Isolated W/ Containment Purge & Exhaust Sys in Operation.Caused by Failure to Reopen Manual Isolation Valve + (ML20071N905)
- ML20071N907 + (ML20071N907)
- 05000338/LER-1983-028-03, /03L-0:on 830507,inside Containment Recirculation Spray Pump 1-RS-P-1B Tripped During Surveillance Testing. Caused by Faulty B Phase Overcurrent Device in Breaker. Replacement Breaker Installed + (ML20071N912)
- 05000255/LER-1983-033-03, /03L-0:on 830428,D Safety Injection Tank T-82D Sampling Indicated Boron Concentration Below Tech Spec Limit.Caused by Minor Leakage Past Loop Check Valve & SIT Check Valve or Fill & Drain Valve + (ML20071N914)
- ML20071N916 + (ML20071N916)