Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- 05000247/LER-1982-042-03, /03L-0:on 820923,one of Two Level Alarm Setpoints Found Above Max Level Per Tech Specs.Caused by Level Alarm Bistable Setpoint Drift.Setpoint Reset to Required Value. Surveillance Frequency Increased + (ML20066A933)
- 05000302/LER-1982-062, Forwards LER 82-062/01T-0 + (ML20066A935)
- ML20066A939 + (ML20066A939)
- 05000302/LER-1982-062-01, /01T-0:on 821014,received Confirmation That Pressurizer Code Safety Valves RCV-8 & RCV-9 Ring Settings May Cause Valves to Chatter or Fail to Reach Rated Lift. Caused by Inadequate Understanding.Valves Replaced + (ML20066A948)
- 05000456/LER-1990-020-02, :on 901129,auxiliary Bldg Inaccessible Filter Plenum Charcoal Booster Fan OB,OVA03CB Spuriously Auto Started.Caused by Component Failure.Relay Replaced & Fan Circuitry & Breaker Checked + (ML20066A950)
- 05000395/LER-1982-010, Forwards LER 82-010/03L-0.Detailed Event Analysis Encl + (ML20066A952)
- 05000311/LER-1982-002, Supplemental LER 82-002/03X-1:on 820111,battery Charger 2A1 Tripped.Charger Tripped Again Upon Resetting Breaker.Caused by Difference Between Battery & Battery Charger Voltages. Operating Instructions Revised to Adjust Float Vo + (ML20066A956)
- 05000395/LER-1982-010-03, /03L-0:on 821001,PORV Block Valve MVG-8000A Would Not Reopen at Conclusion of Reactor Vessel O-ring Leak Test. Caused by Wear in Valve Stem Packing Which Contributed to Overtorque Condition.Stem Packing Replaced + (ML20066A959)
- ML20066A965 + (ML20066A965)
- B13692, Requests Relief from ASME Code Section XI Requirements,Per 10CFR50.55a(g)(6)(i) to Allow Svc Water Pump C to Be Declared Operable & Returned to Normal Operational Lineup + (ML20066A971)
- ML20066A982 + (ML20066A982)
- RBG-13-651, Final Deficiency Rept DR-70 Re Use of isoprene-based Rubber Matl for Governor Coupling Drive Element of Emergency Diesel Generator Engines.Initially Reported on 820827.Replacement Parts Supplied.Also Reported Per Part 21 + (ML20066A984)
- ML20066A999 + (ML20066A999)
- 05000311/LER-1982-072, Supplemental LER 82-072/03X-1:on 820820,during Surveillance Testing,Discovered That Reactor Trip Breaker B Would Not Trip.Caused by Binding of Undervoltage Coil Solenoid.Coil Replaced & Breaker Reinstalled + (ML20066B009)
- ML20066B014 + (ML20066B014)
- 05000272/LER-1982-004, Supplemental LER 82-004/03X-1:on 820108,charging Pump 13 Declared Inoperable Due to Component Cooling Water Sys Being Tagged Out for Planned Maint.On 820109,positive Reactivity Change Found in RCS Boron Concentration + (ML20066B019)
- ML20066B020 + (ML20066B020)
- 05000387/LER-1982-033, Forwards LER 82-033/03L-0 + (ML20066B025)
- ML20066B026 + (ML20066B026)
- 05000277/LER-1982-035-01, /01P:on 821021,diesel Generator Bldg Cardox Tank Pressure Found at 20 Psig Below Tech Spec Limit of 280 Psig. Caused by Tank Not Being Pressurized Correctly During Recent Filling Operation.Tank Pressurized within 16-h + (ML20066B031)
- ML20066B032 + (ML20066B032)
- 05000293/LER-1982-044, Forwards LER 82-044/03L-0 + (ML20066B034)
- ML20066B035 + (ML20066B035)
- 05000387/LER-1982-033-03, /03L-0:on 820929,reactor Bldg Special Particulate Iodine Noble Gas Monitor Pump Tripped Off & Would Not Restart.Caused by Motor Problem.Motor Rewound & Pump Rebuilt + (ML20066B037)
- LIC-90-1000, Forwards Response to Violations Noted in Insp Rept 50-285/90-25.Response Withheld + (ML20066B040)
- 05000387/LER-1982-024, Forwards LER 82-024/01T-0 + (ML20066B053)
- ML20066B055 + (ML20066B055)
- ML20066B065 + (ML20066B065)
- ML20066B077 + (ML20066B077)
- 05000282/LER-1990-018-01, :on 901130,discovered That Certain Valves Subject to ASME Section XI Testing Found in Design Basis Reconstitution.Cause Will Be Discussed in Supplemental Rept. Valves Cycled to Obtain Baseline Data + (ML20066B084)
- ML20066B087 + (ML20066B087)
- ML20066B095 + (ML20066B095)
- 05000293/LER-1982-044-03, /03L-0:on 820930,at 75% Power,Alarm Received for Low Nitrogen Pressure in CRD 22-51 Accumulator.After Recharging,Alarm Again Received.Caused by Leaking Accumulator.Spare,Rebuilt Accumulator Installed & Tested + (ML20066B098)
- 05000293/LER-1982-041, Forwards LER 82-041/03L-0 + (ML20066B106)
- 05000293/LER-1982-041-03, /03L-0:on 820927,during Semiannual Surveillance of Reactor Bldg Ventilating Sys,One Damper (AO-N92) Found Inoperable.Caused by Broken Nylon Drive Gear.Other Gears on AO-N92 & AO-N90 Found Cracked.Broken/Cracked Gears Replace + (ML20066B117)
- 05000387/LER-1982-025, Forwards LER 82-025/01T-0.Detailed Event Analysis Encl + (ML20066B121)
- ML20066B124 + (ML20066B124)
- ML20066B127 + (ML20066B127)
- ML20066B129 + (ML20066B129)
- 05000302/LER-1982-060, Forwards LER 82-060/03L-0 + (ML20066B139)
- 05000302/LER-1982-060-03, /03L-0:on 820927,Feb 1982 Monthly Surveillance of Containment Cooling Sys Not Performed.Caused by Personnel Error.Personnel Instructed on Importance of Using Controlled Document in Daily Operations + (ML20066B144)
- ML20066B145 + (ML20066B145)
- 1CAN108209, Forwards Results of Impingement Monitoring at Intake for Sept 1982,per Tech Spec 4.1.2.1(2) + (ML20066B153)
- ML20066B155 + (ML20066B155)
- ML20066B157 + (ML20066B157)
- ML20066B159 + (ML20066B159)
- ML20066B160 + (ML20066B160)
- ML20066B161 + (ML20066B161)
- ML20066B176 + (ML20066B176)
- ML20066B178 + (ML20066B178)
- ML20066B182 + (ML20066B182)