Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- ML20063M804 + (ML20063M804)
- 05000366/LER-1982-087, Forwards LER 82-087/03L-0 + (ML20063M808)
- ML20063M810 + (ML20063M810)
- ML20063M811 + (ML20063M811)
- 05000366/LER-1982-087-03, /03L-0:on 820805,HPCI Steamline Differential Pressure Instrument Actuated at Setpoint Exceeding Tech Spec Limit.Caused by Setpoint Drift.Instrument Calibr & Tested Satisfactorily + (ML20063M812)
- ML20063M814 + (ML20063M814)
- 05000321/LER-1982-070, Forwards LER 82-070/03L-0 + (ML20063M816)
- 05000369/LER-1982-062, Forwards LER 82-062/03L-0 + (ML20063M819)
- ML20063M821 + (ML20063M821)
- 05000369/LER-1982-062-03, /03L-0:on 820801,RCS Nc Leakage Calculation Initiated,Revealing Unidentified Leakage of Approx 4.5 Gpm. Caused by Coolant Passing Through Chemical & Vol Control Sys Valve Packing.Valve Backseated + (ML20063M823)
- 05000277/LER-1982-020-03, /03L-0:on 820806,drywell Pressure Recorders PR-2508A & PR-2508B Failed Downscale Due to Blown Fuses. Caused by Intentional Ground on Positive Side of Transmitters.Mod to Eliminate Ground Completed on 820811 + (ML20063M826)
- ML20063M827 + (ML20063M827)
- 05000318/LER-1982-039, Forwards LER 82-039/01T-0 + (ML20063M836)
- 05000416/LER-1982-046, Forwards LER 82-046/03L-0 + (ML20063M838)
- 05000318/LER-1982-039-01, /01T-0:on 820824,employee Opened Inner Emergency Air Lock Door When Outer Door Not Secured.Release Calculated at 4.83E-8MR.Caused by Possible Misadjustment of Swing Actuating Rods + (ML20063M840)
- 05000247/LER-1982-033, Forwards LER 82-033/99X-0 + (ML20063M842)
- ML20063M845 + (ML20063M845)
- 05000416/LER-1982-046-03, /03L-0:on 820810,daily Fire Door Checks Discovered Not Conducted on 820617 & 24.Caused by Incomplete Communication Between Operating Shifts.Personnel Awareness Increased + (ML20063M846)
- 05000247/LER-1982-033-99, /99X-0:on 820819,svc Water Tube Leak Identified in Main Cooling Coil of Fan Cooler Unit 21.Coil 8 Found Leaking & Tube Bundle Isolated W/O Heat Transfer Capability, Thus Falling Below FSAR Assumption + (ML20063M849)
- AECM-82-394, Final Deficiency Rept Re Unsuitable Governor Drive Coupling on Transamerica Delaval Diesel Generators.Initially Reported on 820824.Flexible Isoprene Elements to Be Replaced W/ Neoprene Elements.Also Reportable Per Part 21 for Unit 1 + (ML20063M851)
- 05000416/LER-1982-045, Forwards LER 82-045/01T-0 + (ML20063M854)
- 05000321/LER-1982-076, Forwards LER 82-076/03L-0 + (ML20063M856)
- 05000321/LER-1982-076-03, /03L-0:on 820806,while in Steady State Operation W/Routine Calibr in Progress,Two Relative Humidity Controllers Found Inoperable on B Standby Gas Treatment Filter Train.Caused by Component Failure Due to Corrosion + (ML20063M858)
- 05000311/LER-1982-084-01, /01T-0:on 820829,discovered Svc Water Leak of 0.5 Gpm on Containment Fan Coil Unit 23.Caused by Erosion of Copper Nickel Cooling Coils.Coil Repaired W/Belzona + (ML20063M859)
- 05000321/LER-1982-069, Forwards LER 82-069/03L-0 + (ML20063M860)
- 05000416/LER-1982-045-01, /01T-0:on 820826,temporary Loss of Power Caused Reactor Scram.Caused by Tree Cutting Maint Near 500 Kv Transmission Line When Worker Felled Tree Across Line.Worker Consequently Killed.Power Restored & Scram Reset + (ML20063M862)
- 05000296/LER-1982-034, Forwards LER 82-034/03L-0 + (ML20063M863)
- 05000311/LER-1982-004, Forwards LER 82-004/03X-1.Detailed Event Analysis Encl + (ML20063M865)
- 05000296/LER-1982-034-03, /03L-0:on 820810,heat Detector Panel 3-25-288 Did Not Give Alarm Signal During Testing,Causing Cable Tray Fixed Spray Automatic Initiation Circuit to Fail.Caused by Failure of Fire Detector Control Card + (ML20063M868)
- 05000321/LER-1982-069-03, /03L-0:on 820805,reactor Core Isolation Cooling Sys Declared Inoperable Due to Failure of Exhaust Vacuum Breaker.Caused by Low Steam Line/High Drywell Pressure Relay Cover Binding Relay Contacts + (ML20063M869)
- ML20063M870 + (ML20063M870)
- 05000369/LER-1982-063, Forwards LER 82-063/03L-0 + (ML20063M871)
- ML20063M873 + (ML20063M873)
- 05000316/LER-1982-070-03, /03L-0:on 820810,while Performing QA Tour of Auxiliary Bldg,Hole Noticed in Fire Seal W-7292,rendering Seal Nonfunctional.Cause Unknown.Seal Restored to Functional Status + (ML20063M875)
- 05000316/LER-1982-071-03, /03L-0:on 820809,during Outage,Operators Switched from West to East Centrifugal Charging Pump.Charging Pumps Shifted Prior to Removing AB Diesel Generator from Svc to Replace Diaphragm in Quick Exhaust Valve + (ML20063M876)
- B10545, Final Deficiency Rept Re Reactor Containment Liner Fire Damage.Initially Reported on 820830.Rept Describes Testing & Repair Procedures Taken or to Be Taken to Repair Liner.Three Oversize Drawings Encl.Aperture Cards Available in PDR + (ML20063M889)
- 05000369/LER-1982-063-03, /03L-0:on 820802,low Flow Alarm Failed to Initiate & Switch for Liquid Waste Monitor Continued to Indicate Flow Through EMF After Termination of Liquid Waste Release. Caused by Sticking Flow Switch + (ML20063M900)
- 05000313/LER-1982-021, Forwards LER 82-021/03L-0 + (ML20063M917)
- ML20063M919 + (ML20063M919)
- 05000373/LER-1982-086, Forwards LER 82-086/03L-0 + (ML20063M921)
- ML20063M925 + (ML20063M925)
- 05000334/LER-1980-074, Forwards Updated LER 80-074/03X-1 + (ML20063M926)
- 05000313/LER-1982-021-03, /03L-0:on 820808,while in Heatup W/Rcs at 458 F, RCS Leakage Increased to Approx 28 Gpm Due to Failure of Reactor Coolant Pump C Seal.Cause of Seal Failure Not Determined.Seal Improvement Program Underway + (ML20063M930)
- ML20063M931 + (ML20063M931)
- 05000395/LER-1982-001, Forwards LER 82-001/03L-0 + (ML20063M936)
- 05000334/LER-1980-074-03, 1C Charging Pump Discharge Check Valve Did Not Reset.Caused by Binding of Antirotation Devices on Valve Disc & Disc Arm,Due to Flow or Pressure Surges on Sys Causing Disc to Rotate + (ML20063M938)
- ML20063M939 + (ML20063M939)
- 05000373/LER-1982-086-03, /03L-0:on 820809,while in Startup Mode at Rated Temp & Pressure (550 F,1,000 Psig),Average Drywell Temp Exceeded 135 F.Caused by Sensible Heat Removal Capability Not Meeting Sensible Heat Load in Drywell + (ML20063M941)
- 05000395/LER-1982-001-03, /03L-0:on 820813,while Performing Test on Feeder Breaker for Control Room Train B Normal Ventilation Fan, Breaker Would Not Manually Reset.Caused by Random Failure of Square D Breaker (Fhl 36050-15M).Breaker Replaced + (ML20063M947)
- 05000311/LER-1981-106, Forwards LER 81-106/03X-1.Detailed Event Analysis Encl + (ML20063M952)
- ML20063M957 + (ML20063M957)