- 05000334/LER-1980-020, Forwards LER 80-020/03L-0 + (ML19309G381)
- ML19309G382 + (ML19309G382)
- 05000346/LER-1980-030, Forwards LER 80-030/01T-0 + (ML19309G383)
- ML19309G384 + (ML19309G384)
- 05000155/LER-1980-008-03, /03L-0:on 800411,following Intermittent Automatic Test Circuit Alarms,Sensor Channel D of Reactor Depressurizing Sys Was Removed from Svc to Correct Problem. Caused by Drift.Unit Was Readjusted + (ML19309G385)
- 05000334/LER-1980-020-03, /03L-0:on 800329,during Operations to Increase Level in RCS Loops,Vol Control Tank Outlet MOV-CH-115C Found Closed.Vol Control Tank Level Indicated Normally.Caused by Bad Fuse Holder for Level Bistable.Fuse Holder Replaced + (ML19309G386)
- ML19309G387 + (ML19309G387)
- 05000346/LER-1980-030-01, /01T-0:on 800418,contrary to Tech Spec 3.4.1,decay Heat Pump 1-2 Stopped When RCS Water Level Decreased to 37 Inches Above Hot Leg Piping Centerline.Caused by Valve Operator Component Failure.Work Order Issued for Adjustment + (ML19309G388)
- ML19309G389 + (ML19309G389)
- ML19309G390 + (ML19309G390)
- ML19309G391 + (ML19309G391)
- 05000312/LER-1980-022, Forwards LER 80-022/03L-0 + (ML19309G392)
- 05000313/LER-1980-012-03, /03L:on 800406,while Performing Monthly Inservice Valve Stroke Test,Emergency Feedwater Supply valves,CV2667 & CV2617,failed to Fully Open.Caused by Binding Due to Loose Bolts Securing Actuator + (ML19309G394)
- ML19309G395 + (ML19309G395)
- ML19309G396 + (ML19309G396)
- 05000312/LER-1980-022-03, /03L-0:on 800406,refueling Test Revealed Valve Sfv 53603 Returned to Open Position After Signal Reset.Caused by Sticking Blpb Open Contacts.Blpb Replaced & Valve Successfully Tested + (ML19309G397)
- 05000266/LER-1980-004, Forwards LER 80-004/03L-0 + (ML19309G398)
- ML19309G399 + (ML19309G399)
- ML19309G400 + (ML19309G400)
- 05000282/LER-1980-012, Forwards LER 80-012/03L-0 + (ML19309G402)
- ML19309G403 + (ML19309G403)
- ML19309G404 + (ML19309G404)
- 05000282/LER-1980-012-03, /03L-0:on 800331,during Review of Electrical Surveillance Program,Discovered That Individual Float Cell Voltage Measurements Were Not Done in Mar 1980 on Battery Monthly Test.Caused by Personnel Oversight + (ML19309G405)
- ML19309G408 + (ML19309G408)
- 05000293/LER-1980-015, Forwards LER 80-015/03L-0 + (ML19309G409)
- ML19309G410 + (ML19309G410)
- ML19309G411 + (ML19309G411)
- 05000266/LER-1980-004-03, /03L-0:on 800409,w/plant at Normal Steady State, Emergency Diesel Generator Failed to Start During Routine Surveillance Test.Second Attempt Unsuccessful.Caused by Broken Vane in Starting Air Motor.Air Motor Replaced + (ML19309G412)
- 05000293/LER-1980-015-03, /03L-0:on 800401,during Performance of Surveillance Test,Dry Chemical Fire Protection Sys Failed to Automatically Initiate.Caused by Erratic Pyrotronics, Dtf 190 heat-actuated Device.Unit Replaced + (ML19309G413)
- ML19309G414 + (ML19309G414)
- ML19309G415 + (ML19309G415)
- ML19309G416 + (ML19309G416)
- ML19309G418 + (ML19309G418)
- 05000317/LER-1980-018, Forwards LER 80-018/03L-0 + (ML19309G419)
- ML19309G420 + (ML19309G420)
- ML19309G421 + (ML19309G421)
- 05000317/LER-1980-018-03, /03L-0:on 800401,Number 11 Control Room Air Conditioning Unit Taken Out of Operation for Maint.Caused by Need to Calibr Outside Air Temp Transmitter 0-TT-5350. Transmitter Calibr & Placed Back in Svc + (ML19309G422)
- ML19309G423 + (ML19309G423)
- ML19309G424 + (ML19309G424)
- 05000295/LER-1980-017, Forwards LER 80-017/03L-0 + (ML19309G426)
- ML19309G428 + (ML19309G428)
- ML19309G429 + (ML19309G429)
- 05000295/LER-1980-017-03, /03L-0:on 800402,during Load Test on Diesel Generator O to Facilitate Taking Diesel Generator 1A Out of Svc,Diesel Generator O Tripped from Full Load,Placing Auxiliary Power Sys in Degraded Condition + (ML19309G430)
- ML19309G431 + (ML19309G431)
- 05000317/LER-1980-013, Forwards Updated LER 80-013/03X-1 + (ML19309G432)
- ML19309G433 + (ML19309G433)
- ML19309G434 + (ML19309G434)
- 05000317/LER-1980-013-03, During Surveillance Test, Channel D Containment High Pressure Setpoint Less Conservative than Tech Specs.Caused by Failed Signal Isolator 1-E/E-5313D.Instrument Returned for Repair + (ML19309G436)
- ML19309G437 + (ML19309G437)
- ML19309G438 + (ML19309G438)
- ML19309G439 + (ML19309G439)