- 05000324/LER-1980-023, Forwards LER 80-023/01T-0 + (ML19309C329)
- ML19309C330 + (ML19309C330)
- ML19309C331 + (ML19309C331)
- ML19309C332 + (ML19309C332)
- 05000324/LER-1980-023-01, /01T-0:on 800319,during Liquid Penetrant Test of Reducing Insert for 2B Reactor Recirculation Pump,Linear Indication Was Found at Toe of Weld Between Reducer & Nipple.Cause Unknown.Analysis Planned + (ML19309C333)
- ML19309C334 + (ML19309C334)
- 05000155/LER-1980-005, Forwards LER 80-005/03L-0 + (ML19309C335)
- ML19309C337 + (ML19309C337)
- ML19309C338 + (ML19309C338)
- 05000155/LER-1980-005-03, /03L-0:on 800301,following Several Intermittent Automatic Test Circuit Alarms,Sensor Channel D of Reactor Depressurizing Sys Removed from Svc.Caused by Setpoint Drift on Transmitter LT-3183.Transmitter Vented & Returned to S + (ML19309C339)
- ML19309C341 + (ML19309C341)
- ML19309C342 + (ML19309C342)
- 05000318/LER-1980-013, Forwards LER 80-013/03L-0 + (ML19309C343)
- ML19309C344 + (ML19309C344)
- 05000133/LER-1980-002, Forwards LER 80-002/03L-0 + (ML19309C345)
- ML19309C348 + (ML19309C348)
- 05000133/LER-1980-002-03, /03L-0:on 800310,while in Cold Shutdown for Refueling & Seismic Mods,Fossil Unit Trip Test Was Not Performed within Allowable Interval.Caused by Present Status Being Unresolved.Test Will Be Performed Prior to Startup + (ML19309C349)
- 05000318/LER-1980-013-03, /03L-0:on 800303,channel Zf Pressure Input Signal for Steam Generator Isolation 22 Was Bypassed.Caused by Signal Isolater 2-E/E-1023C Being Out of Calibr Due to Nonlinear Response + (ML19309C350)
- 05000029/LER-1980-009, Forwards LER 80-009/03L-0 + (ML19309C351)
- ML19309C353 + (ML19309C353)
- ML19309C354 + (ML19309C354)
- ML19309C355 + (ML19309C355)
- ML19309C356 + (ML19309C356)
- ML19309C357 + (ML19309C357)
- 05000029/LER-1980-009-03, /03L-0:on 800307,during Maint Outage in Mode 5 While Performing Safety Injection Time Delay Verification procedure,TDC2 Setpoint Found Out of Tech Spec Limit.Caused by Setpoint Drift.Relay Adjusted to within Tech Spec Limit + (ML19309C358)
- ML19309C359 + (ML19309C359)
- ML19309C360 + (ML19309C360)
- ML19309C361 + (ML19309C361)
- 05000317/LER-1980-002, Forwards LER 80-002/04T-0 + (ML19309C362)
- ML19309C363 + (ML19309C363)
- ML19309C364 + (ML19309C364)
- ML19309C365 + (ML19309C365)
- 05000267/LER-1980-011, Forwards LER 80-011/03L-0 + (ML19309C366)
- ML19309C367 + (ML19309C367)
- ML19309C368 + (ML19309C368)
- 05000317/LER-1980-002-04, /04T-0:on 800322,instantaneous Hourly Average for Condenser Temp Rise Observed in Excess of Tech Spec Limit. Caused by Operator Inattention to Temp Rise Across Condenser & Environ Conditions + (ML19309C370)
- ML19309C371 + (ML19309C371)
- ML19309C372 + (ML19309C372)
- ML19309C373 + (ML19309C373)
- 05000267/LER-1980-011-03, /03L-0:on 800306-21,reactor Dewpoint Limiting Conditions for Operation Were Exceeded on One Occasion & Operation in Degraded Mode Occurred on Three Occasions. Caused by Problems W/Buffer Helium Sys + (ML19309C374)
- ML19309C375 + (ML19309C375)
- ML19309C376 + (ML19309C376)
- 05000327/LER-1980-008, Forwards LER 80-008/03L-0 + (ML19309C377)
- ML19309C378 + (ML19309C378)
- ML19309C379 + (ML19309C379)
- ML19309C380 + (ML19309C380)
- 05000327/LER-1980-008-03, /03L-0:on 800303,cooling Tower Blowdown Effluent Line Flow Monitor O-FR-27-175 Was Declared Inoperable.Flow Monitor Consistently Indicated Higher Flowrate than Actually Existed.Cause Unknown.Different Instrument to Be Instal + (ML19309C381)
- 05000338/LER-1980-033, Forwards LER 80-033/03L-0 + (ML19309C382)
- ML19309C384 + (ML19309C384)
- 05000338/LER-1980-033-03, /03L-0:on 800303,during Monthly Verification of Proper Auxiliary Feedwater Sys Valve Lineup,Discovered That Position of Valve MOV-FW100B as Written in Procedure Was Incorrect.Caused by Typographical Error in Procedure + (ML19309C385)