Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- ML17319A795 + (ML17319A795)
- ML17319A796 + (ML17319A796)
- ML17319A798 + (ML17319A798)
- ML17319A799 + (ML17319A799)
- 05000316/LER-1981-004-03, /03L-0:on 810308,ISI Data Review for Ba Transfer Pump 3 Was Not Reviewed within 96-h Time Limit.Caused by Test Data Being Inadvertently Overlooked by Technical Inservice Insp Coordinator.Card File Developed + (ML17319A800)
- ML17319A801 + (ML17319A801)
- 05000315/LER-1980-029-03, /03L-0:on 801217,during NRC Audit of Surveillance Records of Essential Svc Water Sys,Operations Dept Procedure 01-OHP 4030.STP.022,Revision 5,found Deficient in Meeting Tech Spec Requirements.Caused by Personnel Error + (ML17319A802)
- ML17319A803 + (ML17319A803)
- ML17319A806 + (ML17319A806)
- ML17319A808 + (ML17319A808)
- ML17319A810 + (ML17319A810)
- ML17319A811 + (ML17319A811)
- ML17319A812 + (ML17319A812)
- ML17319A813 + (ML17319A813)
- IR 05000315/1981006 + (ML17319A815)
- ML17319A818 + (ML17319A818)
- ML17319A819 + (ML17319A819)
- ML17319A820 + (ML17319A820)
- 05000316/LER-1981-008-03, /03L-0:on 810407,during Fire Protection Spray Sys Surveillance Test,Eight Spray Nozzles for Engineered Safety Features Vent Charcoal Filter 2-HV-AES-1 & 14 Nozzles for 2-HV-AES-2 Were Found Partially Plugged.Sys Flushed + (ML17319A823)
- ML17319A824 + (ML17319A824)
- 05000315/LER-1981-009-03, /03L-0:on 810408,during Fire Protection Spray Sys Surveillance Test,Eight Spray Nozzles for Engineered Safety Feature Charcoal Filter 1-HV-AES-1 Were Found Partially Plugged.Caused by Buildup of Debris in Nozzles.Sys Flushed + (ML17319A825)
- ML17319A826 + (ML17319A826)
- ML17319A827 + (ML17319A827)
- 05000316/LER-1981-009-03, /03L-0:on 810331,after Entering Mode 6 & Floodup of Reactor Cavity,Routine Analysis of RCS Indicated Chloride Concentration of 0.26 Ppm.Cause Is Undetermined. Contamination Was Reduced by Purification + (ML17319A828)
- ML17319A829 + (ML17319A829)
- ML17319A830 + (ML17319A830)
- ML17319A831 + (ML17319A831)
- ML17319A832 + (ML17319A832)
- ML17319A836 + (ML17319A836)
- ML17319A839 + (ML17319A839)
- 05000316/LER-1981-010-03, /03L-0:on 810411,snubbers 1 & 29 Were Found Inoperable.Caused by Fluid Leak on 29 Due to Separation of Joint at End Seal O-ring.O-ring Replaced.Snubber 1 Upside Down Due to Loose Extension Rod Locknut.Locknut Tightened + (ML17319A841)
- 05000316/LER-1981-011-03, /03L-0:on 810411,steam Line Pressure Transmitter MPP-210 Was Found Exceeding Allowable Value for Differential Pressure Between Steam Lines.Caused by Instrument Drift. Transmitter Recalibr + (ML17319A842)
- 05000316/LER-1981-012-03, /03L-0:on 810413,cracks Found in Divider Barrier Seal.Cause Unknown.Defective Portions Replaced + (ML17319A843)
- 05000315/LER-1981-010-03, /03L-0:on 810414,root Isolation Valve for Containment Pressure Transmitter PPP-301 Was Found Closed. Cause Unknown.Valve Opened & Modified So That Valve Movement Will Be More Apparent + (ML17319A844)
- ML17319A845 + (ML17319A845)
- 05000316/LER-1981-013-03, /03L-0:on 810428,all Charging Pumps Were Removed from Svc Contrary to Tech Spec Requirements.Caused by Leak on East Pump Discharge Isolation Valve CS-300E.Valve Repacked.Drain Valve CS-349 Also Repacked + (ML17319A846)
- ML17319A847 + (ML17319A847)
- ML17319A850 + (ML17319A850)
- ML17319A852 + (ML17319A852)
- ML17319A853 + (ML17319A853)
- ML17319A854 + (ML17319A854)
- ML17319A855 + (ML17319A855)
- ML17319A857 + (ML17319A857)
- ML17319A863 + (ML17319A863)
- ML17319A865 + (ML17319A865)
- ML17319A867 + (ML17319A867)
- 05000316/LER-1981-015-03, /03L-0:on 810416,degraded Grid Voltage Relays Were Discovered Out of Spec on T 21A,T 21B,T 21C & T 21D Buses. Cause Not stated.Re-evaluation of Relay Tolerances Underway + (ML17319A868)
- 05000316/LER-1981-016-03, /03L-0:on 810416,setpoint Value for Turbine Impulse Chamber Pressure Bistable Was Discovered to Be Wrong.Caused by Incorrect Tech Specs.Bistables Reset.Tech Spec Change in Progress + (ML17319A869)
- ML17319A871 + (ML17319A871)
- ML17319A873 + (ML17319A873)
- IR 05000315/1980020 + (ML17319A877)