ML17319A839

From kanterella
Jump to navigation Jump to search
Forwards LERs 81-010/03L-0,81-011/03L-0,81-012/03L-0 & 81-013/03L-0
Date released: 05/31/2018 Download: ML17319A839


LER 81-013/03L-0:on 810428,all Charging Pumps Were Removed from Svc Contrary to Tech Spec Requirements.Caused by Leak on East Pump Discharge Isolation Valve CS-300E.Valve Repacked.Drain Valve CS-349 Also Repacked
ML17319A846
Person / Time
Site: Cook 
Issue date: 05/05/1981
From: Wizner D
INDIANA MICHIGAN POWER CO. (FORMERLY INDIANA & MICHIG
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
Download: ML17319A846 (9)
LER 81-012/03L-0:on 810413,cracks Found in Divider Barrier Seal.Cause Unknown.Defective Portions Replaced
ML17319A843
Person / Time
Site: Cook 
Issue date: 05/05/1981
From: Wizner D
INDIANA MICHIGAN POWER CO. (FORMERLY INDIANA & MICHIG
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
Download: ML17319A843 (2)
LER 81-011/03L-0:on 810411,steam Line Pressure Transmitter MPP-210 Was Found Exceeding Allowable Value for Differential Pressure Between Steam Lines.Caused by Instrument Drift. Transmitter Recalibr
ML17319A842
Person / Time
Site: Cook 
Issue date: 05/05/1981
From: Rischling J
INDIANA MICHIGAN POWER CO. (FORMERLY INDIANA & MICHIG
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
Download: ML17319A842 (2)
LER 81-010/03L-0:on 810411,snubbers 1 & 29 Were Found Inoperable.Caused by Fluid Leak on 29 Due to Separation of Joint at End Seal O-ring.O-ring Replaced.Snubber 1 Upside Down Due to Loose Extension Rod Locknut.Locknut Tightened
ML17319A841
Person / Time
Site: Cook 
Issue date: 05/05/1981
From: Wizner D
INDIANA MICHIGAN POWER CO. (FORMERLY INDIANA & MICHIG
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
Download: ML17319A841 (2)
Forwards LERs 81-010/03L-0,81-011/03L-0,81-012/03L-0 & 81-013/03L-0
ML17319A836
Person / Time
Site: Cook 
Issue date: 05/05/1981
From: Shaller D
INDIANA MICHIGAN POWER CO. (FORMERLY INDIANA & MICHIG
To: KEPPLER J G
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
Download: ML17319A836 (2)