Semantic search

Jump to navigation Jump to search
 Issue dateTitleTopic
ML20028H27813 November 1990Special Rept:On 901029,condenser Evacuation Sys Noble Gas Monitor Inoperable for More than 72 H.Monitor Will Return to Svc by 901119,following Completion of Satisfactory Channel Calibr
ML20042E1254 April 1990Special Rept:On 900325,meteorologic Tower Declared Inoperable for More than 7 Days.Caused by Failure of Primary Delta Temp Channel
ML20012D92020 March 1990Special Rept:On 900312,planned Maint Outage of 1E Bs Bus Initiated to Complete 5-yr Bus Cleaning Surveillance, Rendering All Fire Dectection Sys Alarms & Sprinkler Sys Inoperable.Containment Air Temps Monitored Hourly
ML20011E3211 February 1990Special Rept:On 891227,pressurizer Base Support Strong Motion Accelerometer 2XT-8020D Declared Inoperable for More than 30 Days Due to Playback Readings Outside Test Acceptance Criteria.Repairs Planned During Next Outage
ML20005D69711 December 1989Special Rept:On 891127,wide Range Gas Monitor Removed from Svc for Performance of 18-month Channel Calibr Surveillance. Monitor Will Be Returned to Svc by 891216 Following Completion of Satisfactory Channel Calibr
ML19332F17930 November 1989Ro:Air Ejector Exhaust Treatment Sys Inoperable for More than 31 Days.Sys Declared Inoperable.Failure to Implement Reporting Requirement Attributed to Inadequate Guidance in Interpretation of Intent & Requirement of Tech Spec
ML19325E29218 October 1989Followup Ro:In Sept 1989,identified Fire Doors Found Inoperable During Routine Surveillances Consisting of 17 Latching Mechanism Failures & 8 Closure Mechanism Failures. No Doors Found to Be Blocked Open
ML20024D50419 July 1983RO 83-067:on 830718,review of Fire Protection Surveillance Program Revealed That Fire Detectors Failed Routine Surveillance Testing & Were Not Declared Inoperable.Fire Watches Not Posted
ML20024C77729 June 1983RO:C-E Has Advised Util That RCS Hot Leg Sampling Line Nozzle Loads Exceed Stress Limits.Acceptability of ASME Requirements Being evaluated.Fourteen-day Rept Will Be Submitted by 830712
ML20052H6906 May 1982Ro:Submits Corrections to Equipment Tag Number Errors in LER 82-007 on 820407
ML20052E22028 April 1982RO 82-011:on 820427,both Channels on Control Room Airborne Radiation Monitor Found Inoperable.Caused by Failure to Maintain Emergency Mode for Air Cleanup Sys During 820313 Preventive Maint
ML20050M3871 April 1982RO Re Deficiency in Establishment of Sufficient Fire Watches,Per Tech Spec Section 3.7.9,App a Limiting Conditions for Operation.Continuous Fire Watches Established.Impact Evaluation Will Be Submitted in 14 DaysContinuous fire watch
ML20050B70326 March 1982Ro:On 820324,w/reactor in Mode 5,unplanned Dilution Occurred While Filling RCS Water Storage Tank from Refueling Water Storage TankShutdown Margin
Reactor Vessel Water Level
ML20050A00015 March 1982Ro:On 820314,low Pressure Safety Injection Pump Lost Due to Air in Pump.Pumps Vented & Shutdown Cooling Restored. Investigation in Progress.Results Will Be Forwarded w/14-day Rept & Two LERs