Southem Califomla Edison Company 23 PARKER STREET
. IRVINE. CALIFORNIA 92718 March 20,.1990 F. R. N ANDY ~
TELEPHONE edANAGER OF NUCLEAR UCEN31NO 1714:5976400 U.
S.
Nuclear Regulatory Commission Document Control-Desk
. Washington,:D.C. !20555'.
~
Subject:
Docket Nos. 50-361 and 50-362
~Special Report-San Onofre Nuclear-Generating Station, Units-2 and 3.
t
. The ' purpose. of;.this submittal is to.. provide the Special. Report required by-Technical-Specification' section 3.7.8.2, Action (b),
t
_of: Facility Operating' Licenses.NPF-10'and'NPF-15, San Onofre Units 2
and 3,
concerning containment spray / sprinkler-systems being.
inoperable for greater than 24' hours.-
.On1 March 12,.1990,1a planned ma ntenance. outage of the 1E 'BS'.bu's-i
>was initiated'to complete a 5-year bus cleaning surveillance.- This'
~
outage rendered all -fire. detection system alarms'and pre-action?
sprinkler systems of-the. Units 2 and 3 fire protection cystem, inoperable since these systems are powered from.the 1E
'BS' bus.
However,~ temporary non-1E power was provided to the.'BS' bus during
- the outage'.
In addition, compensatory measures required by all.'the 1 Technical' Specifications associated with.the inoperable systems were
- provided, including ~' hourly-monitoring-of the-containment air s
temperatures for abnormal indications'in accordance with TS 3.3.3.7 Action (a.4).
l The fire detection systems and the spray / sprinkler: systems' for Units-i
- 2 ;- and 3 were returned to service on '. March 17,
- 1990, followings
~
completion!of.the 1E 'BS' bus outage.
If'you require any additional information, please let me know.
very truly yours,-
[
/
(ik g%