Semantic search
Jump to navigation
Jump to search
Issue date | Title | Topic | |
---|---|---|---|
ML20196J178 | 28 July 1997 | NPDES Noncompliance Notification:On 970707,weekly Monitoring for Total Residual Chlorine Was Not Conducted.Plant Performed Addl Training for New Personnel & Review Process to Ensure,Routine Monitoring Required Performed | |
ML20117D876 | 2 May 1996 | NPDES Noncompliance Notification:Between 960416 & 24,30-day Average & 7-day Average for BOD5 Results for Samples for Outfall 007 Exceeded.Cause of Increased BOD5 Results Unknown.Util Plans to Use Increased Aeration | |
ML20084A266 | 9 May 1995 | NPDES Noncompliance Notification:On 950405-0502,samples for Outfall 007 Exceeded.Cause Unknown.Personnel Inspecting Sewage Lagoon for Aerator Operation & Excessive Solids. Appropriate Maint Activity & C/A Will Be Performed | |
ML20084A269 | 11 April 1995 | NPDES Noncompliance Notification:On 950410,discharges from Goosequill Ditch (Outfall 001B) in Excess of Ph Permit Limit.Water from Shallow Wells Used for Makeup in Order to Lower Ph of Water Discharged from Goosequill Ditch | |
ML20080G071 | 27 December 1994 | NPDES Noncompliance Notification:On 941221,sample Collected at Discharge Exhibited Elevated Ph of 9.3 S.U.Caused by Biological Activity.Permit Amend Submitted Deleting Ph Limitation for Outfall 001A | |
ML20080G066 | 13 December 1994 | NPDES Noncompliance Notification:On 941213,sample Collected at Discharge Point 001A Exhibited Elevated Ph of 9.5 S.U. Caused by Biological Activity.Permit Amend Submitted Deleting Ph Limitations for Outfall 001A | |
ML20080G059 | 1 December 1994 | NPDES Noncompliance Notification:On 941201,sample Collected at Discharge Point 001A Exhibited Ph of 9.7 S.U.Caused by Biological Activity.Permit Amend Submitted to Delete Ph Limitation for Outfall 001A | |
ML20078P737 | 23 November 1994 | NPDES Noncompliance Notification:On 941122,sample Collected at Discharge Point 001A Exhibited Ph of 9.8 Su.Biological (Photoplankton) Activity in Farm Pond Caused Elevation | |
ML20078P734 | 16 November 1994 | NPDES Noncompliance Notification:On 941114,discharge from Facility to Goosequill Ditch at Rate of 1275 Gpm Caused Overflow of Water After Monitoring Point at Outfall 001B. Overflow Attributed to Excessive Vegetation Growth in Ditch | |
ML20078P731 | 9 November 1994 | NPDES Noncompliance Notification:On 941108,sample Collected at Discharge Point 001A Exhibited Ph of 9.60 Su.Biological (Photoplankton) Activity in Farm Pond Caused Elevated Ph | |
ML20078P728 | 3 November 1994 | NPDES Noncompliance Notification:On 941102,sample Collected at Discharge Point 001A Exhibited Ph of 9.60 Su.Biological (Photoplankton) Activity in Farm Pond Caused Elevated Ph | |
ML20149G814 | 1 November 1994 | NPDES Noncompliance Notification:On 941026,sample Collected at Discharge Point 001A Exhibited Ph of 9.50 Su.Caused by Biological Activity in Farm Pond.Permit Amend Will Be Submitted to Delete Ph Limitations for Outfall 001A | |
ML20076L701 | 24 October 1994 | NPDES Noncompliance Notification:On 941019,sample Collected at Discharge Point 001A Exhibited Ph of 9.30 Su.Caused by Elevated Ph Biological Activity in Farm Pond | |
ML20065L753 | 6 April 1994 | NPDES Noncompliance Notification:On 940404,discovered Elevated Ph in Sample Collected at Discharge Point 001B. Caused by Algal Activity in Raw Water make-up Ponds.Added Addl make-up Water to Ponds to Lower Ph | |
ML20063A980 | 20 December 1993 | NPDES Noncompliance Notification:On 931201,discovered That Monthly Parameters Not Analyzed for Goosequill Ditch Discharge Path,Resulting in Missed Analytical Data for Outfall 001B for Month of 1993.Parameters Analyzed | |
ML20045C955 | 16 June 1993 | Non-compliance Repts Re Fsv NPDES Permit & Proposed Changes to NPDES Permit.Repts Cover Period from 1989 Through Present | |
ML20097H227 | 12 June 1992 | NPDES Noncompliance Notification:On 920506,one Iron Sample Was Out of Compliance & Duplicate Analysis Did Not Fall within Acceptable Standard Deviation.System Monitored Closely & Analytical Procedures Reviewed | |
ML20154P287 | 23 September 1988 | NPDES Noncompliance Notification:On 880711,iron Exceeded 1 mg/1 Limit,Max Measured 2.8 mg/1.Caused by Consequence of Draining Sys 41.Sys 41 No Longer Being Drained.Procedures Will Be Reviewed to Determine Best Course of Action | |
ML20154C184 | 9 May 1988 | NPDES Noncompliance Notification:On 880407,circulating Expansion Joint Ruptured & Flooded Adjacent Pit & Sys Basin Resulting in Discharge.Water Will Be Pumped at Lower Vol If Future Emergency Problems Arise | |
ML20101G729 | 6 December 1984 | NPDES Noncompliance:On 841129 Weekly Analysis of Discharge Point 001 Showed Oil & Grease Concentration Above Tech Spec Limits.Caused by Large Amount of Oil in Turbine Bldg Sump. Sump Pump Shut Off & Sump Pumped Out |