3' h Public Service'

=';"1 P.O. Box 840 Denver. CO 80201 0840 May 9,1995 Ms. Kathleen Sullivan industrial Enforcement Engineer Permits and Enforcement Section Water Quality Control Division Colorado Department of Health 4300 Cherry Creek Drive South Denver, CO 80222-1530 RE:

Public Service Company of Colorado - Fort St. Vrain CDPS Permit Number CO-0001121

Dear Kathleen:

Attached please find the noncompliance report for Public Service Company of Colorado Fort St. Vrain's outfall 007. The noncompliance report details the discharges from the Sewage Treatment System for April 1995 with BOD concentrations in 3

excess of the permitted 30-day average.

If you have any questions concerning this report, please contact me at 294-2440.

Sincerely, b

Eldon Lindt, Sr. Environmental Analyst Attachment cc:

U.S. EPA Region Vill Alan Albrandt - PSC Mary Fisher - FSV Sam Chestnut - FSV Jesse Brungardt - FSV 9505300282 950516 PDR ADOCK 05000267 S

PDR

NPDES DISCHARGE PERMIT NONCOMPLIANCE REPORTING FORM Date: 05/09/95 Applicable Permit No.: CO-0001121 Discharge No.: 007 I.

GENERAL Company: Public Service Comoany of Colorado Mailing Address: ILO. Box 840 Denver. CO 80201 Plant Name: Fort St. Vrain Station Plant Location: Near Platteville. Colorado County: Weld IL NONCOMPLIANCE REPORT A. Description and Cause of Noncompliance: The 30-day average BOD result for April 1995 3

samples for outfall 007 exceeded the permit limit of 30 mg/1. Sample dates for April 1995 were 4/5,4/12,4/20, and 4/27. The average BOD result for the four samples was 37.2 mg/1. The 3

BOD result for a May 2,1995 sample was 19.7 mg/1.

3 B. Noncompliance Period:

Started:

A.M.

P.M. 04/05/95 Date Ended:

A.M.

P.M. 05/02/95 Date C. Action Taken to Reduce, Eliminate, Prevent: Presently, the cause of the increased BOD 3 results is unknown. Fort St. Vrain personnel are inspecting the Sewage Lagoon for aerator operation and excessive solids. Following the inspection, appropdate maintenance activity and corrective action will be performed.

i D. Person Initiating Written Report: Eldon Lindt Signature: [fL 3 h E. Water Quality Control Division Notification Requirements:

Telephone (24 hrs.):

05/04/95 Date Ms. Kathleen Sullivan Notified 02:20 n.m.

Written (5 days):

05/09/95 Date Notified SUHNIIT REPORT 10:

Als. Kathleen Sullivan Regional Administrator Colorado Department of Public liralth and I:nvironment U.S. EPA Water Quality Control Divishn One Denver Place, Suite 500 Wnitoring & Enforcement Swtion 999 INth Street N WM.C 4300 Cherry Creek Drive South Denver, CO N0202 2405 Dentrr, CO N02221530 Attn.: Enforcement. Permit Program In the event o7 nor.<ompliance for the l'SV Statiim, a verhai report must he made to the Nuclear Regulatory Commission hy the FSV shift supervisor (620-1090) within four hours after verhally notifying the Water Quality Control Divisiim.

Verbal notification to FsV Control Room on 05/04/95 at 08:52 a m.

. ~, -

- - -. - - -