NL-23-0806, Technical Requirements Manual

From kanterella
Jump to navigation Jump to search
Technical Requirements Manual
ML23319A085
Person / Time
Site: Farley  Southern Nuclear icon.png
Issue date: 10/31/2023
From:
Southern Nuclear Operating Co
To:
Office of Nuclear Reactor Regulation
Shared Package
ML23318A074 List:
References
NL-23-0806
Download: ML23319A085 (115)


Text

Technical Requirements Manual (TRM)

Joseph M. Farley Nuclear Plant Units 1 and 2

List of Effective Pages Page Version Page Version Page Version TRM Cover Page 13.3.4-4 .............. 60.0 13.7.4-1 .............. 60.0 13.3.5-1 ................ 8.0 13.7.5-1 .............. 60.0 Table of Contents 13.3.6-1 .............. 60.0 13.7.5-2 ................ 8.0 i .......................... 60.0 13.3.6-2 .............. 46.0 13.7.6-1 .............. 47.0 ii ......................... 60.0 13.3.6-3 .............. 29.0 Section 13.8 Tab iii......................... 29.0 13.3.7-1 .............. 29.0 13.3.7-2 .............. 29.0 13.8.1-1 .............. 60.0 Section 11.0 Tab 13.3.8-1 .............. 53.0 13.8.1-2 .............. 60.0 11.0-1 ................. 60.0 13.3.9-1 .............. 60.0 13.8.1-3 .............. 53.0 11.0-2 ................. 60.0 13.3.9-2 .............. 60.0 13.8.2-1 .............. 60.0 11.0-3 ................. 60.0 13.3.9-3 .............. 54.0 13.8.2-2 .............. 58.0 13.3.10-1 ............ 55.0 13.8.2-3 .............. 58.0 Section 13.0 Tab 13.3.10-2 ............ 55.0 13.8.2-4 .............. 58.0 13.0-1 ................. 60.0 13.3.10-3 ............ 55.0 13.8.2-5 .............. 58.0 13.0-2 ................. 60.0 13.8.2-6 .............. 60.0 Section 13.4 Tab 13.0-3 ................. 60.0 13.8.3-1 ............. .53.0 13.0-4 ................. 60.0 13.4.1-1 .............. 60.0 Section 13.9 Tab 13.4.1-2 .............. 60.0 Section 13.1 Tab 13.4.1-3 .............. 60.0 13.9.1-1 .............. 60.0 13.1.1-1 ................ 8.0 13.4.2-1 .............. 60.0 13.9.2-1 .............. 60.0 13.1.2-1 .............. 60.0 13.4.2-2 .............. 60.0 13.9.3-1 .............. 60.0 13.1.2-2 .............. 53.0 13.4.3-1 .............. 60.0 13.9.3-2 .............. 60.0 13.1.3-1 .............. 60.0 13.4.3-2 .............. 60.0 13.9.4-1 .............. 60.0 13.1.3-2 .............. 60.0 13.4.4-1 .............. 60.0 13.9.5-1 ............. .60.0 13.1.4-1 .............. 60.0 13.4.5-1 .............. 60.0 13.9.5-2 .............. 37.0 13.1.4-2 .............. 60.0 13.4.5-2 ................ 8.0 13.9.6-1 .............. 60.0 13.1.5-1 .............. 60.0 13.9.7-1 ................ 8.0 Section 13.5 Tab 13.1.5-2 ................ 9.0 Section 13.12 Tab 13.1.6-1 .............. 60.0 13.5.1-1 .............. 60.0 13.1.6-2 .............. 60.0 13.5.1-2 .............. 32.0 13.12.1-1 ............ 60.0 13.1.7-1 .............. 60.0 13.5.1-3 .............. 17.0 13.12.1-2 ............ 60.0 13.1.7-2 .............. 60.0 13.12.1-3 .............. 8.0 Section 13.6 Tab 13.1.8-1 .............. 60.0 13.12.2-1 ............ 60.0 13.1.9-1 .............. 60.0 13.6.1-1 ................ 8.0 13.12.3-1 ............ 60.0 13.1.9-2 ................ 8.0 13.6.1-2 .............. 61.0 13.12.3-2 ............ 60.0 13.1.10-1 ............ 60.0 13.6.2-1 .............. 60.0 13.12.3-3 ........... .60.0 13.6.2-2 .............. 50.0 13.12.4-1 ............ 60.0 Section 13.3 Tab 13.6.2-3 .............. 57.0 13.12.4-2 .............. 8.0 13.3.1-1 .............. 55.0 13.6.2-4 .............. 12.0 Section 13.13 Tab 13.3.1-2 .............. 60.0 Section 13.7 Tab 13.3.1-3 .............. 34.0 13.13.1-1 ............ 60.0 13.3.1-4 .............. 34.0 13.7.1-1 .............. 60.0 13.13.1-2 ............ 60.0 13.3.2-1 .............. 60.0 13.7.1-2 .............. 60.0 13.3.2-2 .............. 25.0 13.7.2-1 .............. 60.0 13.3.3-1 .............. 60.0 13.7.2-2 .............. 60.0 13.3.3-2 .............. 60.0 13.7.2-3 .............. 60.0 13.3.4-1 .............. 60.0 13.7.2-4 .............. 60.0 13.3.4-2 .............. 60.0 13.7.3-1 .............. 60.0 13.3.4-3 .............. 60.0 13.7.3-2 ................ 8.0 13.7.3-3 ................ 8.0 Farley Units 1 and 2 Page 1 of 1 Version 61.0 Technical Requirements

Table of Contents Note on section numbering: The TRM and TRM Bases numbering is intended to correspond to the associated ITS Specification. The numbering convention is to use the ITS Specification number, with the addition of a leading 1. For example, TRM spec 13.8, Electrical Power Systems, corresponds to ITS spec 3.8. Since all ITS specifications do not have associated TRM specifications, the TRM numbers do not run consecutively.

11.0 USE AND APPLICATION 11.1 Definitions ................................................................................................... 11.0-1 11.2 Logical Connectors ..................................................................................... 11.0-1 11.3 Completion Times....................................................................................... 11.0-1 11.4 Frequency................................................................................................... 11.0-1 11.5 Technical Requirement (TR) and Technical Requirement Surveillance (TRS) Implementation ............................................................ 11.0-1 11.6 Technical Requirement Manual Revisions ................................................. 11.0-2 11.7 Alternative Actions (e.g., Initiate a Condition Report, Continue Action to Restore, Determination of Alternate Course of Action) .............................. 11.0-2 13.0 TECHNICAL REQUIREMENT (TR) APPLICABILITY 13.0.1 .................................................................................................................... 13.0-1 13.0.2 .................................................................................................................... 13.0-1 13.0.3 .................................................................................................................... 13.0-1 13.0.4 Not Used..................................................................................................... 13.0-1 13.0.5 Not Used..................................................................................................... 13.0-2 13.0.6 Not Used..................................................................................................... 13.0-2 13.0.7 .................................................................................................................... 13.0-2 13.0 TECHNICAL REQUIREMENT SURVEILLANCE (TRS) APPLICABILITY 13.0.1 .................................................................................................................... 13.0-3 13.0.2 .................................................................................................................... 13.0-3 13.0.3 Not Used..................................................................................................... 13.0-3 13.0.4 Not Used..................................................................................................... 13.0-3 13.1 REACTIVITY CONTROL SYSTEMS 13.1.1 SHUTDOWN MARGIN (SDM) - MODES 1and 2 ................................... 13.1.1-1 13.1.2 Boration Flow Path - Shutdown ............................................................... 13.1.2-1 13.1.3 Boration Flow Paths - Operating ............................................................. 13.1.3-1 13.1.4 Boration Pump - Shutdown...................................................................... 13.1.4-1 13.1.5 Charging Pumps - Operating ................................................................... 13.1.5-1 13.1.6 Borated Water Source - Shutdown .......................................................... 13.1.6-1 13.1.7 Borated Water Sources - Operating ........................................................ 13.1.7-1 13.1.8 Position Indication System - Shutdown ................................................... 13.1.8-1 13.1.9 Test Exception for Position Indication System - Shutdown ..................... 13.1.9-1 13.1.10 Not Used................................................................................................ 13.1.10-1 13.3 INSTRUMENTATION 13.3.1 Movable Incore Detectors........................................................................ 13.3.1-1 13.3.2 High Energy Line Break Isolation Sensors .............................................. 13.3.2-1 (continued)

Farley Units 1 and 2 i Version 60.0 Technical Requirements

Table of Contents 13.3.3 Turbine Overspeed Protection................................................................. 13.3.3-1 13.3.4 Radiation Monitoring Instrumentation ...................................................... 13.3.4-1 13.3.5 Electric Hydrogen Recombiners Instrumentation and Control Circuits ........................................................................................ 13.3.5-1 13.3.6 Seismic Monitoring Instrumentation ........................................................ 13.3.6-1 13.3.7 Meteorological Monitoring Instrumentation.............................................. 13.3.7-1 13.3.8 Containment Hydrogen Monitors ............................................................. 13.3.8-1 13.3.9 Ultrasonic Mode Calorimetric .................................................................. 13.3.9-1 13.3.10 Power Distribution Monitoring System (PDMS) ..................................... 13.3.10-1 13.4 REACTOR COOLANT SYSTEM (RCS) 13.4.1 Not Used.................................................................................................. 13.4.1-1 13.4.2 Not Used.................................................................................................. 13.4.2-1 13.4.3 Reactor Vessel Head Vents .................................................................... 13.4.3-1 13.4.4 Safety Valves - Shutdown ....................................................................... 13.4.4-1 13.4.5 RCS Pressure Isolation Valve (PIV) Leakage ......................................... 13.4.5-1 13.5 EMERGENCY CORE COOLING SYSTEMS (ECCS) 13.5.1 Emergency Core Cooling System (ECCS) .............................................. 13.5.1-1 13.6 CONTAINMENT SYSTEMS 13.6.1 Containment Ventilation System Leakage Rate ...................................... 13.6.1-1 13.6.2 Containment Isolation Valves .................................................................. 13.6.2-1 13.7 PLANT SYSTEMS 13.7.1 Not Used.................................................................................................. 13.7.1-1 13.7.2 Not Used.................................................................................................. 13.7.2-1 13.7.3 Sealed Source Contamination ................................................................. 13.7.3-1 13.7.4 Not Used.................................................................................................. 13.7.4-1 13.7.5 Area Temperature Monitoring (Unit 2 Only) ............................................ 13.7.5-1 13.7.6 Main Steam Isolation Valves ................................................................... 13.7.6-1 13.8 ELECTRICAL POWER SYSTEMS 13.8.1 Motor Operated Valves Thermal Overload Protection Devices (Unit 2 Only)............................................................................... 13.8.2-1 13.8.2 Emergency Diesel Generators (EDG) Maintenance and Inspection Requirements ......................................................................... 13.8.3-1 13.9 REFUELING OPERATIONS 13.9.1 Decay Time ............................................................................................. 13.9.1-1 13.9.2 Communications ...................................................................................... 13.9.2-1 13.9.3 Manipulator Crane ................................................................................... 13.9.3-1 13.9.4 Crane Travel - Spent Fuel Storage Building ........................................... 13.9.4-1 13.9.5 Spent Fuel Cask Crane ........................................................................... 13.9.5-1 13.9.6 Not Used................................................................................... 13.9.6-TR 13.9.6 13.9.7 Average Reactor Coolant Temperature................................................... 13.9.7-1 (continued)

Farley Units 1 and 2 ii Version 60.0 Technical Requirements

Table of Contents 13.12 EXPLOSIVE GAS AND STORAGE TANK RADIOACTIVITY MONITORING (EGSTRAM) PROGRAM 13.12.1 Waste Gas Monitoring Instrumentation ................................................. 13.12.1-1 13.12.2 Liquid Holdup Tanks .............................................................................. 13.12.2-1 13.12.3 Waste Gas Monitoring ........................................................................... 13.12.3-1 13.12.4 Gas Storage Tanks................................................................................ 13.12.4-1 13.13 EMERGENCY RESPONSE FACILITIES 13.13.1 Emergency Response Facilities ............................................................ 13.13.1-1 (continued)

Farley Units 1 and 2 iii Version 29.0 Technical Requirements

Use and Application 11.0 11.0 Use and Application 11.1 Definitions The definitions contained in the Technical Specifications Section 1.1, Definitions, apply to the Technical Requirements contained in this manual. In the Technical Requirements, defined terms are shown in all capital letters, consistent with the Technical Specifications. In addition, the following term is defined for the TRM and TRM Bases.

Functional/Functionality - Functionality is an attribute of Structures, Systems and Components (SSCs) that is not controlled by Technical Specifications (TSs). An SSC is functional or has functionality when it is capable of performing its specified function, as set forth in the Current Licensing Basis (CLB). Functionality does not apply to specified safety functions, but does apply to the ability of non-TS SSCs to perform other specified functions that have a necessary support function.

11.2 Logical Connectors The guidance provided for the use and application of logical connectors in Section 1.2, Logical Connectors, of the Technical Specifications is applicable to the Technical Requirements contained in this manual.

11.3 Completion Times The guidance provided for the use and application of Completion Times in Section 1.3, Completion Times, of the Technical Specifications is applicable to the Technical Requirements contained in this manual.

11.4 Frequency The guidance provided for the use and application of Frequency requirements in Section 1.4, Frequency, of the Technical Specifications is applicable to the Technical Requirements contained in this manual.

11.5 Technical Requirement (TR) and Technical Requirement Surveillance (TRS)

Implementation TRs and TRSs are implemented the same as Technical Specifications (see 13.0).

However, TRs and TRSs are treated as plant procedures and are not part of the Technical Specifications. Therefore the following exceptions apply:

a. Violations of the Action or Surveillance requirements in a TR are not reportable as conditions prohibited by, or deviations from, the Technical Specifications per 10 CFR 50.72 or 10 CFR 50.73, unless specifically required by the TR.
b. Power reductions or plant shutdowns required to comply with the Actions of a TR are not reportable per 10 CFR 50.72 or 10 CFR 50.73.

(continued)

Farley Units 1 and 2 11.0 - 1 Version 60.0 Technical Requirements

Use and Application 11.0 11.0 Use and Application

c. Violations of TR or TRS requirements, except as provided for in Section 13.0 of this manual, shall be treated the same as plant procedure violations.

11.6 Technical Requirement Manual Revisions Changes to this manual are controlled in accordance with 10 CFR 50.59.

11.7 Alternative Actions (e.g., Initiate a Condition Report, Continue Action to Restore, Determination of Alternate Course of Action)

Alternative Actions, such as initiating a condition report or management determination of alternate course of action are provided for selected TRs. Priority should be on restoration of compliance with the TR. The alternative Actions are to provide allowances for a course of action that would continue to provide for the safe operation of the plant.

Alternative Actions would allow for evaluation of the specific circumstances and plant conditions present at the time to determine if a safe alternative to TR compliance exists.

Alternative Actions may be appropriate for situations where the Required Actions are not warranted; for example, if the specified limits in the TR were only slightly exceeded and sufficient margin is available, or if a Completion Time or Surveillance Frequency extension would allow the restoration of the limits or component FUNCTIONALITY, or if an alternate means for determining the FUNCTIONALITY of a component can be identified If the Alternative Action is taken, a plan for restoring compliance with the TR should be documented.

The plan for restoring compliance with the TR should consider:

The technical basis of the requirement, The safety significance of continued operation beyond any stated Completion Time, A qualitative or quantitative evaluation of the operational risk associated with the TR not being met (e.g., online or outage risk assessments or engineering technical justifications),

If required, compensatory actions put in place during the time the TR is not met, and Approval by the appropriate level of management prior to expiration of any Completion Time.

If the Alternate Action is taken it should be documented in a CR, ODMI, or other appropriate means and should contain the following:

Farley Units 1 and 2 11.0 - 2 Version 60.0 Technical Requirements

Use and Application 11.0 11.0 Use and Application The reason the TR could not be restored within any allowed Completion Time, The results of the evaluation of operational risk, Any compensatory measures, and The operational conditions necessary to restore compliance with the TR.

The appropriate level of management is, as a minimum, the Shift Manager. However, the Shift Manager should consider the safety significance and operational risks associated with the TR noncompliance and engage senior management in the decision to implement the alternative Action, as required.

Farley Units 1 and 2 11.0 - 3 Version 60.0 Technical Requirements

TR Applicability 13.0 13.0 Technical Requirement (TR) Applicability TR 13.0.1 TRs shall be met during the MODES or other specified conditions in the Applicability, except as provided in TR 13.0.2 and TR 13.0.7.

TR 13.0.2 Upon discovery of a failure to meet a TR, the Required Actions of the associated Conditions shall be met, with the exceptions specified below:

a. If the TR is met or is no longer applicable prior to expiration of the specified Completion Time(s), completion of the Required Action(s) is not required unless otherwise stated.
b. Administrative controls may be employed in lieu of the specified Required Actions if necessary to perform testing to verify the FUNCTIONALITY of the equipment being returned to service or the FUNCTIONALITY or OPERABILITY of other equipment.

TR 13.0.3 When a TR is not met and the associated ACTIONS are not met, an associated ACTION is not provided, or if directed by the associated ACTION, initiate a Condition Report in accordance with the Corrective Action Program.

TR 13.0.4 Not Used.

(continued)

Farley Units 1 and 2 13.0 - 1 Version 60.0 Technical Requirements

TR Applicability 13.0 13.0 Technical Requirement (TR) Applicability TR 13.0.5 Not used TR 13.0.6 Not used TR 13.0.7 Test Exception TR 13.1.9 allows TR 13.1.8, Position Indication -

Shutdown to be changed to permit performance of special tests and operations. Unless otherwise specified, all other TR requirements remain unchanged. Compliance with the Test Exception TR is optional. When the Test Exception TR is desired to be met but is not met, the ACTIONS of the Test Exception TR shall be met. When the Test Exception TR is not desired to be met, entry into a MODE or other specified condition in the Applicability shall be made in accordance with the other applicable TRs.

Farley Units 1 and 2 13.0 - 2 Version 60.0 Technical Requirements

TR Applicability 13.0 13.0 Technical Requirement Surveillance (TRS) Applicability TRS 13.0.1 TRSs shall be met during the MODES or other specified conditions in the Applicability for individual TRs, unless otherwise stated in the TRS.

Failure to meet a Surveillance, whether such failure is experienced during the performance of the Surveillance or between performances of the Surveillance, shall be failure to meet the TR. Failure to perform a Surveillance within the specified Frequency shall be failure to meet the TR except as provided in TRS 13.0.3. Surveillances do not have to be performed on nonfunctional equipment or variables outside specified limits.

TRS 13.0.2 The specified Frequency for each TRS is met if the Surveillance is performed within 1.25 times the interval specified in the Frequency, as measured from the previous performance or as measured from the time a specified condition of the Frequency is met.

Should a TRS not be performed within the specified Frequency a Condition Report shall be initiated to determine if the associated TR is met. The TRS shall be performed at the next reasonable opportunity.

For Frequencies specified as "once," the above interval extension does not apply.

If a Completion Time requires periodic performance on a "once per . . ."

basis, the above Frequency extension applies to each performance after the initial performance.

Exceptions to this requirement are stated in the individual TRSs.

TRS 13.0.3 Not used.

Farley Units 1 and 2 13.0-3 Version 60.0 Technical Requirements

TR Applicability 13.0 13.0 Technical Requirement Surveillance (TRS) Applicability TRS 13.0.4 Not used.

Farley Units 1 and 2 13.0-4 Version 60.0 Technical Requirements

SDM MODES 1 and 2 TR 13.1.1 13.1 Reactivity Control Systems TR 13.1.1 SHUTDOWN MARGIN (SDM) - MODES 1 AND 2 TR 13.1.1 SDM shall be within the limits provided in the COLR.

APPLICABILITY: MODE 1 and MODE 2 with keff 1.0 ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. SDM not within limit. A.1 Initiate boration to restore Immediately SDM to within limit.

TECHNICAL REQUIREMENT SURVEILLANCES SURVEILLANCE FREQUENCY TRS 13.1.1.1 Verify SDM within limit with the control banks at the Prior to initial maximum insertion limit specified in the COLR and operation above 5%

considering the following factors: RTP after each fuel loading.

1) RCS boron concentration,
2) Control rod position,
3) RCS average temperature,
4) Fuel burnup based on gross thermal energy generation,
5) Xenon concentration, and
6) Samarium concentration Farley Units 1 and 2 13.1.1 - 1 Version 8.0 Technical Requirements

Boration Flow Path - Shutdown TR 13.1.2 13.1 Reactivity Control Systems TR 13.1.2 Boration Flow Path - Shutdown TR 13.1.2 One of the following boron injection flow paths shall be FUNCTIONAL:

a. A flow path from a FUNCTIONAL boric acid storage tank via a boric acid transfer pump and a charging pump to the Reactor Coolant System, or
b. In MODE 6 only, a flow path from a FUNCTIONAL boric acid storage tank via a boric acid transfer pump through an idle charging pump to the Reactor Coolant System, or
c. A flow path from the FUNCTIONAL Refueling Water Storage Tank via a charging pump to the Reactor Coolant System.

APPLICABILITY: MODE 5, MODE 6 with any valve used to isolate an unborated water source not secured in the closed position.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. Required Flow Path A.1 Initiate action to suspend Immediately nonfunctional. positive reactivity changes.

TECHNICAL REQUIREMENT SURVEILLANCES SURVEILLANCE FREQUENCY TRS 13.1.2.1 ---------------------------------NOTE--------------------------------

Only required to be performed when a flow path from the boric acid storage tanks is required FUNCTIONAL and the ambient air temperature of the auxiliary building is 65 F.

Verify that the temperature of the flow path is 65 F. 31 days Farley Units 1 and 2 13.1.2 - 1 Version 60.0 Technical Requirements

Boration Flow Path - Shutdown TR 13.1.2 TECHNICAL REQUIREMENT SURVEILLANCES SURVEILLANCE FREQUENCY TRS 13.1.2.2 Verify that each manual, power operated, or automatic 184 days valve in the flow path that is not locked, sealed, or otherwise secured in position, is in its correct position.

TRS 13.1.2.3 ---------------------------------NOTE--------------------------------

Only required to be performed when the boric acid transfer pump is required FUNCTIONAL.

Verify that, on recirculation flow, the boric acid transfer 184 days pump develops a discharge pressure of 100 psig.

Farley Units 1 and 2 13.1.2 - 2 Version 53.0 Technical Requirements

Boration Flow Paths - Operating TR 13.1.3 13.1 Reactivity Control Systems TR 13.1.3 Boration Flow Paths - Operating TR 13.1.3 Two of the following three boron injection flow paths shall be FUNCTIONAL.

a. The flow path from the boric acid storage tanks via a boric acid transfer pump and a charging pump to the Reactor Coolant System.
b. Two flow paths from the Refueling Water Storage Tank via charging pumps to the Reactor Coolant System.

APPLICABILITY: MODES 1, 2, 3, and 4 ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. One required flow path A.1 Restore at least two required 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> nonfunctional in MODE 1 flow paths to FUNCTIONAL or 2. status.

B. One required flow path B.1 Restore at least two required 7 days nonfunctional in MODE 3 flow paths to FUNCTIONAL or 4. status.

C. Required Actions and C.1 Initiate a Condition Report. In accordance with associated Completion the Corrective Action Times not met. AND Program C.2 Continue action to restore Immediately the required flow path to FUNCTIONAL status.

Farley Units 1 and 2 13.1.3 - 1 Version 60.0 Technical Requirements

Boration Flow Paths - Operating TR 13.1.3 TECHNICAL REQUIREMENT SURVEILLANCES SURVEILLANCE FREQUENCY TRS 13.1.3.1 ---------------------------------NOTE--------------------------------

Only required to be performed when a flow path from the boric acid storage tanks is required FUNCTIONAL and the ambient air temperature of the auxiliary building is 65 F.

Verify that the temperature of the flow path from the 31 days boric acid storage tanks is 65 F.

TRS 13.1.3.2 Verify that each manual, power operated, or automatic 184 days valve in the flow path that is not locked, sealed, or otherwise secured in position, is in its correct position.

TRS 13.1.3.3 ---------------------------------NOTE--------------------------------

Only required to be performed when the boric acid transfer pump is required FUNCTIONAL.

Verify that, on recirculation flow, the boric acid transfer 184 days pump develops a discharge pressure of 100 psig.

TRS 13.1.3.4 Verify required flow path from boric acid storage tanks While proceeding to delivers 30 gpm to the Reactor Coolant System. or in MODE 5 if not performed in the previous 12 months Farley Units 1 and 2 13.1.3 - 2 Version 60.0 Technical Requirements

Boration Flow Paths - Shutdown TR 13.1.4 13.1 Reactivity Control Systems TR 13.1.4 Boration Pump - Shutdown TR 13.1.4 The required boration pump (charging or boric acid transfer) in the boron injection flow path required by TR 13.1.2 shall be FUNCTIONAL and capable of being powered from an OPERABLE emergency bus.


NOTE---------------------------------------------

The boric acid transfer pump may only be used in place of the charging pump in MODE 6 consistent with flow path b. in TR 13.1.2.

APPLICABILITY: MODE 5, MODE 6 with any valve used to isolate an unborated water source not secured in the closed position.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. Required charging pump A.1 Initiate action to suspend Immediately nonfunctional. positive reactivity changes.

Farley Units 1 and 2 13.1.4 - 1 Version 60.0 Technical Requirements

Boration Flow Paths - Shutdown TR 13.1.4 TECHNICAL REQUIREMENT SURVEILLANCES SURVEILLANCE FREQUENCY TRS 13.1.4.1 ---------------------------------NOTE--------------------------------

Not required to be performed when the RCS is in a water solid condition.

Verify that, on recirculation flow, the charging pump In Accordance with required by TR 13.1.2 develops a differential pressure the Inservice Testing of 2323 psid. Program TRS 13.1.4.2 TRS 13.1.2.3. is applicable when the boric acid transfer In accordance with pump is required FUNCTIONAL. TRS 13.1.2.3 Farley Units 1 and 2 13.1.4 - 2 Version 60.0 Technical Requirements

Charging Pumps - Operating TR 13.1.5 13.1 Reactivity Control Systems TR 13.1.5 Charging Pumps - Operating TR 13.1.5 Two charging pumps shall be FUNCTIONAL.

APPLICABILITY: MODES 1, 2, 3, and 4 ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. One required charging A.1 Restore at least two 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> pump nonfunctional in charging pumps to MODE 1 or 2. FUNCTIONAL status.

B. One required charging B.1 Restore at least two 7 days pump nonfunctional in charging pumps to MODE 3 or 4. FUNCTIONAL status.

C. Required Action and C.1 Initiate a Condition Report. In accordance with the associated Completion Corrective Action Time not met. AND Program C.2 Continue action to restore Immediately the required charging pump to FUNCTIONAL status.

Farley Units 1 and 2 13.1.5 - 1 Version 60.0 Technical Requirements

Charging Pumps - Operating TR 13.1.5 TECHNICAL REQUIREMENT SURVEILLANCES SURVEILLANCE FREQUENCY TRS 13.1.5.1 Verify that, on recirculation flow, each required charging In Accordance with pump develops a differential pressure of 2323 psid. the Inservice Testing Program Farley Units 1 and 2 13.1.5 - 2 Version 9.0 Technical Requirements

Borated Water Source - Shutdown TR 13.1.6 13.1 Reactivity Control Systems TR 13.1.6 Borated Water Source - Shutdown TR 13.1.6 One of the following borated water sources shall be FUNCTIONAL:

a. A boric acid storage system, or
b. The refueling water storage tank (RWST)

APPLICABILITY: MODE 5, MODE 6 with any valve used to isolate an unborated water source not secured in the closed position.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. Required borated water A.1 Initiate action to suspend Immediately source nonfunctional. positive reactivity changes.

TECHNICAL REQUIREMENT SURVEILLANCES


NOTES----------------------------------------------------------

1. TRS 13.1.6.1, TRS 13.1.6.2, and TRS 13.1.6.3 are only required to be performed when the RWST is the required borated water source.
2. TRS 13.1.6.4, TRS 13.1.6.5, and TRS 13.1.6.6 are only required to be performed when the boric acid storage tank is the required borated water source.

Farley Units 1 and 2 13.1.6 - 1 Version 60.0 Technical Requirements

Borated Water Source - Shutdown TR 13.1.6 TECHNICAL REQUIREMENT SURVEILLANCES SURVEILLANCE FREQUENCY TRS 13.1.6.1 --------------------------------NOTE---------------------------------

Only required to be performed when the outside air temperature is 35 F.

Verify RWST solution temperature is 35 F. 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> TRS 13.1.6.2 Verify the RWST boron concentration is 2,300 ppm. 7 days TRS 13.1.6.3 Verify RWST borated water volume is 30,000 gallons. 31 days TRS 13.1.6.4 Verify the boric acid storage tank solution temperature 31 days is 65 F.

TRS 13.1.6.5 Verify the boron concentration of the boric acid storage 31 days tank solution is between 7,000 ppm and 7,700 ppm.

TRS 13.1.6.6 Verify the contained borated water volume in the boric 31 days acid storage tank is 2,000 gallons.

Farley Units 1 and 2 13.1.6 - 2 Version 60.0 Technical Requirements

Borated Water Sources - Operating TR 13.1.7 13.1 Reactivity Control Systems TR 13.1.7 Borated Water Sources - Operating TR 13.1.7 A boric acid storage system, including at least one boric acid storage tank, shall be FUNCTIONAL.

APPLICABILITY: MODES 1, 2, 3, and 4.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. Required boric acid A.1 Restore boric acid storage 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> storage system system to FUNCTIONAL nonfunctional in MODE 1 status.

or 2.

B. Required boric acid B.1 Restore the boric acid 7 days storage system storage system to nonfunctional in MODE 3 FUNCTIONAL status.

or 4.

C. Required Actions and C.1 Initiate a Condition Report. In accordance with associated Completion the Corrective Action Times of Condition A or B AND Program not met.

C.2 Continue action to restore Immediately the boric acid storage system to FUNCTIONAL status.

Farley Units 1 and 2 13.1.7 - 1 Version 60.0 Technical Requirements

Borated Water Sources - Operating TR 13.1.7 TECHNICAL REQUIREMENT SURVEILLANCES


NOTE--------------------------------------------------------

1. TRS 13.1.7.1, TRS 13.1.7.2, and TRS 13.1.7.3 are only required to be performed when the boric acid storage tank is a required borated water source, based on the boration flow path requirements of TR 13.1.3.

SURVEILLANCE FREQUENCY TRS 13.1.7.1 Verify the boric acid storage system solution 31 days temperature is 65 F.

TRS 13.1.7.2 Verify the boron concentration of the boric acid storage 92 days system solution is between 7,000 ppm and 7,700 ppm.

TRS 13.1.7.3 Verify the contained borated water volume in the boric 31 days acid storage system is 11,336 gallons.

Farley Units 1 and 2 13.1.7 - 2 Version 60.0 Technical Requirements

Position Indication System - Shutdown TR 13.1.8 13.1 Reactivity Control Systems TR 13.1.8 Position Indication System - Shutdown TR 13.1.8 One digital rod position indication (DRPI) channel (excluding demand position indication) shall be FUNCTIONAL and capable of determining the control rod position within 12 steps for each shutdown or control rod not fully inserted.

APPLICABILITY: When the reactor trip breakers are closed and Rod Control System capable of rod withdrawal in MODES 3, 4, or 5.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. Required DRPI channel A.1 Initiate action to open the Immediately for one or more shutdown reactor trip breakers.

or control rods nonfunctional.

TECHNICAL REQUIREMENT SURVEILLANCES SURVEILLANCE FREQUENCY TRS 13.1.8.1 For each DRPI channel required FUNCTIONAL, verify 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> the demand position indication system and the DRPI channels agree to within 12 steps.

Farley Units 1 and 2 13.1.8 - 1 Version 60.0 Technical Requirements

Test Exception for Position Indication System - Shutdown TR 13.1.9 13.1 Reactivity Control Systems TR 13.1.9 Test Exception for Position Indication System - Shutdown TR 13.1.9 The requirements of TR 13.1.8, Position Indication System - Shutdown, may be suspended during the performance of individual shutdown and control rod drop time measurements provided:

a. Only one shutdown or control bank is withdrawn from the fully inserted position at a time, and
b. The DRPI is FUNCTIONAL during the withdrawal of the rods.

APPLICABILITY: During performance of rod drop time measurements in MODES 3, 4, or 5.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. One or more required A.1 Initiate action to open the Immediately DRPI nonfunctional during reactor trip breakers.

rod withdrawal.

OR More than one bank of rods withdrawn.

Farley Units 1 and 2 13.1.9 - 1 Version 60.0 Technical Requirements

Test Exception for Position Indication System - Shutdown TR 13.1.9 TECHNICAL REQUIREMENT SURVEILLANCES SURVEILLANCE FREQUENCY TRS 13.1.9.1 Verify the demand position indication system and the Within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> prior rod position indication system agree: to initiation of rod drop time

a. Within 12 steps when the rods are stationary, and measurements
b. Within 24 steps during rod motion. AND 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> thereafter Farley Units 1 and 2 13.1.9 - 2 Version 8.0 Technical Requirements

Rod Drop Time TR 13.1.10 13.1 Reactivity Control Systems TR 13.1.10 Not Used Farley Units 1 and 2 13.1.10 - 1 Version 60.0 Technical Requirements

Movable Incore Detectors TR 13.3.1 13.3 Instrumentation TR 13.3.1 Movable Incore Detectors TR 13.3.1 The movable incore detection system shall be FUNCTIONAL with:

1.1 38 detector thimbles, with 2 detector thimbles per quadrant as identified in Figure 13.3.1-1, OR 1.2 32 and < 38 detector thimbles, with 3 detector thimbles per quadrant as identified in Figures 13.3.1-1 and 13.3.1-2, OR 1.3 25 and < 32 detector thimbles, with 4 detector thimbles per quadrant as identified in Figures 13.3.1-1 and 13.3.1-2.

AND

2. Sufficient movable detectors, drives, and readout equipment to map these thimbles.

NOTES------------------------------------------------------

1. 38 detector thimbles, with 2 detector thimbles per quadrant as identified in Figure 13.3.1-1 are required during initial startup after a refueling outage up to and including performance of the first flux map at 100% RTP. An exception is discussed in the Bases for TR 13.3.1 for recalibration of the excore neutron flux detection system and for monitoring QPTR. However, a flux map with 38 detector thimbles, with 2 detector thimbles per quadrant as identified in Figure 13.3.1-1 is still required prior to reaching 50% RTP to detect a core misload event.
2. If a detector thimble is located on either the major axes of Figure 13.3.1-1 or minor axes of Figure 13.3.1-2, the detector thimble can be included in both quadrants that are divided by the axis for the purpose of determining the minimum number of detector thimbles per core quadrant.
3. Refer to TR 13.3.10 for movable incore detector requirements for the BEACON Power Distribution Monitoring System (PDMS).

APPLICABILITY: When the movable incore detection system is used for:

a. Recalibration of the excore neutron flux detection system, or
b. Monitoring the Quadrant Power Tilt Ratio (QPTR), or
c. Measurement of FNH , FQ (Z) and Fxy .

Farley Units 1 and 2 13.3.1 - 1 Version 55.0 Technical Requirements

Movable Incore Detectors TR 13.3.1 ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. Movable incore detection A.1 Restore the movable incore Prior to using the system nonfunctional. detection system to system for the above FUNCTIONAL status. listed monitoring and calibration functions.

TECHNICAL REQUIREMENT SURVEILLANCES SURVEILLANCE FREQUENCY TRS 13.3.1.1 Verify movable incore system FUNCTIONALITY by During use when normalizing each required detector output. required for the above listed monitoring and calibration functions Farley Units 1 and 2 13.3.1 - 2 Version 60.0 Technical Requirements

Movable Incore Detectors TR 13.3.1 Figure 13.3.1-1 Movable Incore Detector Locations in Major Axes Quadrants Farley Units 1 and 2 13.3.1 - 3 Version 34.0 Technical Requirements

Movable Incore Detectors TR 13.3.1 Figure 13.3.1-2 Movable Incore Detector Locations in Minor Axes Quadrants (For use with TR 13.3.1 option for 25 and < 38 thimbles)

Farley Units 1 and 2 13.3.1 - 4 Version 34.0 Technical Requirements

High Energy Line Break Isolation Sensors TR 13.3.2 13.3 Instrumentation TR 13.3.2 High Energy Line Break Isolation Sensors TR 13.3.2 The high energy line break isolation instrumentation channels listed in Table 13.3.2-1 shall be FUNCTIONAL.

APPLICABILITY: MODES 1, 2 and 3.

ACTIONS


NOTE-----------------------------------------------------------

Separate Condition entry is allowed for each isolation Function.

CONDITION REQUIRED ACTION COMPLETION TIME A. One or more required high A.1 Restore the nonfunctional 7 days energy line break isolation channel to FUNCTIONAL instrumentation channels status.

nonfunctional.

B. Required Action and B.1 Initiate a Condition Report. In accordance with associated Completion the Corrective Action Time of Condition A not AND Program met.

B.2 Continue action to restore Immediately the required channel(s) to FUNCTIONAL status.

TECHNICAL REQUIREMENT SURVEILLANCES SURVEILLANCE FREQUENCY TRS 13.3.2.1 Perform a COT on each required instrument channel In accordance with listed in Table 13.3.2-1. Table 13.3.2-1.

Farley Units 1 and 2 13.3.2 - 1 Version 60.0 Technical Requirements

High Energy Line Break Isolation Sensors TR 13.3.2 Table 13.3.2-1 High-Energy Line Break Isolation Instrumentation Instrument Channel Sensor Location Required Surveillance Channels Frequency

1. Pressure Switches
a. PDSH 3367 A,B RHR Heat Exchanger Room El. 83 ft. 1
b. PSH 2850 A,D Auxiliary Feedwater Pump Room El. 100 ft. 1 B,F Equipment Room El. 100 ft. 1 C,E Auxiliary Feedwater Pump Room Corridor El. 1 100 ft.
c. PSH 2851 A,F Recycle Holdup Tank Room El. 121 ft. 1 B,C Moderating Heat Exchanger Room El. 121 ft. 1 D,E Moderating Heat Exchanger Valve Room El. 1 121 ft.
d. PSH 2852 A,H Piping Penetration Room El. 100 ft. 1 B,C, Letdown Heat Exchanger Room El. 100 ft. 1 18 months D,E Recycle Holdup Tank Room El. 121 ft. 1 F,G
e. PSH 2853 A,B Piping Penetration Room El. 121 ft. 1 C,D Blowdown Heat Exchanger Room El. 130 ft. 1 E,F Corridor El. 121 ft. (Unit 1) / Recycle Evaporator 1 Room El. 121 ft. (Unit 2)
f. PSH 2853 G,H Recycle Evaporator Room El. 121 ft. 1 I,J Corridor El. 121 ft. (I) and 1 Sluice Filter Room El. 121 ft. (J - Unit 1) /

Blowdown Surge Tank Room El. 130 ft. (J -

Unit 2)

2. Flooding Detectors
a. LSH 2828 Main Steam Room El. 127 ft. 2 36 months A,B,C Main Steam Room El. 127 ft. 2
b. LSH 2829 A,B,C Farley Units 1 and 2 13.3.2 - 2 Version 25.0 Technical Requirements

Turbine Overspeed Protection TR 13.3.3 13.3 Instrumentation TR 13.3.3 Turbine Overspeed Protection TR 13.3.3 At least one turbine overspeed protection system shall be FUNCTIONAL.

APPLICABILITY: MODE 1 MODES 2 and 3 except when all main steam line isolation valves and associated bypass valves are closed and all other steam flow paths to the turbine are isolated.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. Required turbine A.1 Initiate a Condition Report. In accordance with overspeed protection the Corrective Action nonfunctional. Program Farley Units 1 and 2 13.3.3 - 1 Version 60.0 Technical Requirements

Turbine Overspeed Protection TR 13.3.3 TECHNICAL REQUIREMENT SURVEILLANCES None.

Farley Units 1 and 2 13.3.3 - 2 Version 60.0 Technical Requirements

Radiation Monitoring Instrumentation TR 13.3.4 13.3 Instrumentation TR 13.3.4 Radiation Monitoring Instrumentation TR 13.3.4 The radiation monitoring instrumentation channels listed in Table 13.3.4-1 shall be FUNCTIONAL with their alarm/trip setpoints within the specified limits.

APPLICABILITY: As shown in Table 13.3.4-1 ACTIONS


NOTE-----------------------------------------------------------

Separate Condition entry is allowed for each monitor Function.

CONDITION REQUIRED ACTION COMPLETION TIME A. The fuel storage pool area A.1 Perform area surveys of the 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> (R-5) radiation monitoring monitored area with portable channel nonfunctional. monitoring instrumentation. AND Once per 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> thereafter Farley Units 1 and 2 13.3.4 - 1 Version 60.0 Technical Requirements

Radiation Monitoring Instrumentation TR 13.3.4 ACTIONS (continued)


NOTE-------------------------------------------------------------

Separate Condition entry is allowed for each monitor Function.

CONDITION REQUIRED ACTION COMPLETION TIME B. One or more process B.1 Initiate the preplanned 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> (R-29B, R-60A, B or C, alternate method of monitoring R-15B) radiation monitoring the appropriate parameter(s).

channels nonfunctional.

Farley Units 1 and 2 13.3.4 - 2 Version 60.0 Technical Requirements

Radiation Monitoring Instrumentation TR 13.3.4


NOTE-----------------------------------------------------------

Refer to Table 13.3.4-1 to determine which SRs apply for each radiation monitor channel.

TECHNICAL REQUIREMENT SURVEILLANCES SURVEILLANCE FREQUENCY TRS 13.3.4.1 Perform a CHANNEL CHECK. 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> TRS 13.3.4.2 Perform a COT. 92 days TRS 13.3.4.3 Perform a CHANNEL CALIBRATION. 18 months Farley Units 1 and 2 13.3.4 - 3 Version 60.0 Technical Requirements

Radiation Monitoring Instrumentation TR 13.3.4 Table 13.3.4-1 Radiation Monitoring Instrumentation Radiation Monitoring Applicable Alarm/Trip Required Technical Instrument Channel Modes or Setpoint Channels Requirement Other Surveillance specified Conditions

1. Area Monitors
a. Fuel Storage Pool With fuel in 15 mr/hr 1 TRS 13.3.4.1 Area (R-5) the storage TRS 13.3.4.2 pool TRS 13.3.4.3
2. Process Monitors (Noble Gas Effluent Monitors)
a. Plant Vent Stack 1, 2, 3, 4 N/A 1 TRS 13.3.4.1 Effluent Monitor TRS 13.3.4.3 (R-29B)
b. Main Steam 1, 2, 3 N/A 3 TRS 13.3.4.1 Line (R-60A, B, C) TRS 13.3.4.3
c. Turbine Building 1, and N/A 1 TRS 13.3.4.1 Ventilation With vacuum TRS 13.3.4.3 Exhaust in the (includes condenser condenser air ejector exhaust)

(R-15B)

Farley Units 1 and 2 13.3.4 - 4 Version 60.0 Technical Requirements

Electric Hydrogen Recombiners Instrumentation and Control Circuits TR 13.3.5 13.3 Instrumentation TR 13.3.5 Electric Hydrogen Recombiners Instrumentation and Control Circuits TR 13.3.5 The electric hydrogen recombiner instrumentation and control circuits shall be in calibration.

APPLICABILITY: MODES 1 and 2.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. One or more electric A.1 Initiate action to restore the Immediately hydrogen recombiner circuit(s) to within calibration instrumentation or control limits.

circuit(s) not in calibration.

TECHNICAL REQUIREMENT SURVEILLANCES SURVEILLANCE FREQUENCY TRS 13.3.5.1 Perform a CHANNEL CALIBRATION of all recombiner 18 months instrumentation and control circuits.

Farley Units 1 and 2 13.3.5 - 1 Version 8.0 Technical Requirements

Seismic Monitoring Instrumentation TR 13.3.6 13.3 Instrumentation TR 13.3.6 Seismic Monitoring Instrumentation TR 13.3.6 The seismic monitoring instrumentation shown in Table 13.3.6-1 shall be FUNCTIONAL.

APPLICABILITY: At all times.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. One or more required A.1 Initiate action to restore the Immediately seismic monitoring seismic monitoring instrument channels instrument channel(s) to nonfunctional. FUNCTIONAL status.

Farley Units 1 and 2 13.3.6 - 1 Version 60.0 Technical Requirements

Seismic Monitoring Instrumentation TR 13.3.6 TECHNICAL REQUIREMENT SURVEILLANCES SURVEILLANCE FREQUENCY TRS 13.3.6.1 Perform a CHANNEL CHECK. 184 days TRS 13.3.6.2 Perform a CHANNEL OPERATIONAL TEST. 184 days TRS 13.3.6.3 Perform a CHANNEL CALIBRATION. 18 months Farley Units 1 and 2 13.3.6 - 2 Version 46.0 Technical Requirements

Seismic Monitoring Instrumentation TR 13.3.6 Table 13.3.6-1 Seismic Monitoring Instrumentation Instrumentation Sensor Location Measurement Range Required Channels Number Strong Motion Triaxial Accelographs 1A Containment Base(1) .5g full scale 1 1B Containment(1) 1.0g full scale 1 1C Free Field .5g full scale 1 2 Pond Intake Structure .5g full scale 1 3 Diesel Generator Building .5g full scale 1 Notes:

(1) Sensor located in Unit 1.

Farley Units 1 and 2 13.3.6 - 3 Version 46.0 Technical Requirements

Meteorological Monitoring Instrumentation TR 13.3.7 13.3 Instrumentation TR 13.3.7 Meteorological Monitoring Instrumentation TR 13.3.7 The meteorological monitoring instrumentation shown in Table 13.3.7-1 shall be FUNCTIONAL.

APPLICABILITY: At all times.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. One or more required A.1 Initiate action to restore the Immediately meteorological monitoring meteorological monitoring instrument channels instrument channel(s) to nonfunctional. FUNCTIONAL status.

TECHNICAL REQUIREMENT SURVEILLANCES SURVEILLANCE FREQUENCY TRS 13.3.7.1 Perform a CHANNEL CHECK. 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> TRS 13.3.7.2 ----------------------------NOTE-------------------------------------

CHANNEL CALIBRATIONS for the wind speed instruments shall be performed according to the manufacturers recommendations.

Perform a CHANNEL CALIBRATION. 184 days Farley Units 1 and 2 13.3.7 - 1 Version 29.0 Technical Requirements

Meteorological Monitoring Instrumentation TR 13.3.7 Table 13.3.7-1 Meteorological Monitoring Instrumentation Instrument Required Channels

1. WINDSPEED
a. Meteorological tower, 10 m/32.8 ft 1 of 2
b. Meteorological tower, 45.7 m/150 ft 1 of 2
2. WIND DIRECTION
a. Meteorological tower, 10 m/32.8 ft 1 of 2
b. Meteorological tower, 45.7 m/150 ft 1 of 2
3. AIR TEMPERATURE DIFFERENCE
a. Meteorological tower, 60 m 10 m (196.9 ft to 32.8 ft) 1 of 2 Notes:

All heights are nominal above ground level (AGL).

There are two channels of each of the instruments listed in the table above (the second channel is mounted at the same height).

Farley Units 1 and 2 13.3.7 - 2 Version 29.0 Technical Requirements

Containment Hydrogen Monitors TR 13.3.8 13.3 Instrumentation TR 13.3.8 Containment Hydrogen Monitors TR 13.3.8 Two containment hydrogen monitor instrumentation channels shall be FUNCTIONAL.

APPLICABILITY: MODES 1, 2, and 3.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. One or more containment A.1 Initiate action to restore the Immediately hydrogen monitor containment hydrogen instrument channels monitor instrument nonfunctional. channel(s) to FUNCTIONAL status.

TECHNICAL REQUIREMENT SURVEILLANCES SURVEILLANCE FREQUENCY TRS 13.3.8.1 Perform a CHANNEL CHECK. 18 months TRS 13.3.8.2 Perform a CHANNEL CALIBRATION. 18 months Farley Units 1 and 2 13.3.8 - 1 Version 53.0 Technical Requirements

Ultrasonic Mode Calorimetric TR 13.3.9 13.3 Instrumentation TR 13.3.9 Ultrasonic Mode Calorimetric TR 13.3.9 The Ultrasonic Mode Calorimetric shall be FUNCTIONAL with:

a. The Caldon LEFMTM CheckPlusTM system FUNCTIONAL, and
b. The Integrated Plant Computer (IPC) calorimetric (QC4621)

FUNCTIONAL and calorimetric calculation is in automatic mode or in manual mode with LEFM selected.

APPLICABILITY: MODE 1 with THERMAL POWER > 2775 MWt ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. LEFM CheckPlus system A.1 Initiate action to switch the Immediately nonfunctional. calorimetric calculation on the calorimetric main menu display to a mode such that Normalized Venturi is selected, either by verifying that auto mode has selected it already or by selecting manual mode and choosing Normalized Venturi.

AND A.2 Restore the LEFM 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> CheckPlus system to FUNCTIONAL status.

Farley Units 1 and 2 13.3.9 - 1 Version 60.0 Technical Requirements

Ultrasonic Mode Calorimetric TR 13.3.9 ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME B. Required Actions and B.1 Verify the calorimetric Immediately associated Completion calculation on the Times of Condition A not calorimetric menu display is met. set to Venturi.

AND B.2 Initiate action to reduce Immediately reactor core power to 2775 MWt.

C. IPC Calorimetric C.1 Verify reactor core power 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> (QC4621) nonfunctional. 2821 MWt by ensuring the higher of average Power Range NIS or Delta-T indications 100% RTP.

AND C.2 Restore the IPC Calorimetric Prior to performing (QC4621) to FUNCTIONAL the next required status. power range channel calorimetric heat balance comparison per SR 3.3.1.2 D. Required Actions and D.1 Initiate action to reduce Immediately associated Completion reactor core power to 2775 Times of Condition C not MWt ensuring the higher of met. average Power Range NIS or Delta-T indications 98.3% RTP (2775 MWt).

Farley Units 1 and 2 13.3.9 - 2 Version 60.0 Technical Requirements

Ultrasonic Mode Calorimetric TR 13.3.9 TECHNICAL REQUIREMENT SURVEILLANCES SURVEILLANCE FREQUENCY TRS 13.3.9.1 Verify availability of the LEFM using the self-diagnostics Prior to performance feature indicated by the LEFM Normal, Minor-Alert, of SR 3.3.1.2 Major-Alert, Failed status indication, as displayed on the plant computer system, is not in Major-Alert (Alert Status 2) or Failed (Failed Status 3) status.

Farley Units 1 and 2 13.3.9 - 3 Version 60.0 Technical Requirements

Power Distribution Monitoring System (PDMS)

TR 13.3.10 13.3 INSTRUMENTION TR 13.3.10 Power Distribution Monitoring System (PDMS)

TR 13.3.10 The PDMS shall be Functional with the minimum inputs in Table 13.3.10-1 APPLICABILITY: MODE 1 25% RTP.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. TR not met. A.1 Suspend the use of the Immediately PDMS.

TECHNICAL REQUIREMENT SURVEILLANCES SURVEILLANCE FREQUENCY TRS 13.3.10.1 Perform a CHANNEL CHECK. 31 days TRS 13.3.10.2 Perform a calibration of the PDMS using the movable Once after each incore detector system with at least 75% of the detector refueling prior to thimbles and at least 2 detector thimbles per quadrant, THERMAL POWER using the minimum thermocouple coverage, and with exceeding 75% RTP THERMAL POWER > 25% RTP.

Farley Units 1 and 2 13.3.10 - 1 Version 55.0 Technical Requirements

Power Distribution Monitoring System (PDMS)

TR 13.3.10 SURVEILLANCE FREQUENCY TRS 13.3.10.3 Perform calibration of the PDMS using the movable 31 EFPD with incore detector system with at least 50% of the detector minimum thimbles and at least 2 detector thimbles per quadrant, thermocouple using the minimum thermocouple coverage, and with coverage THERMAL POWER > 25% RTP OR 180 EFPD with optimum thermocouple coverage Farley Units 1 and 2 13.3.10 - 2 Version 55.0 Technical Requirements

Power Distribution Monitoring System (PDMS)

TR 13.3.10 Table 13.3.10-1 (Page 1 of 1)

Power Distribution Monitoring System FUNCTION MINIMUM REQUIRED INPUTS

1. Control Bank Position 4 control banks(a)
2. RSC Cold Leg 2 RCS loops(b)

Temperature T-Cold

3. Reactor Power 1(c)

Level

4. Power Range Excore 3(d)

Detector Signals

5. Core Exit 25% with 2 per quadrant Thermocouple Temperatures (a) Determined from either valid demand position indication or the average of individual DRPI indications.

(b) Either narrow range or wide range RTDs.

(c) Either valid secondary calorimetric, average power range neutron flux power, or average RSC loop T (d) An input is a channel which consists of corresponding upper and lower detector sections.

Farley Units 1 and 2 13.3.10 - 3 Version 55.0 Technical Requirements

RCS Chemistry TR 13.4.1 13.4 Reactor Coolant System (RCS)

TR 13.4.1 Not Used.

Farley Units 1 and 2 13.4.1- 1 Version 60.0 Technical Requirements

RCS Chemistry TR 13.4.1 DELETED Farley Units 1 and 2 13.4.1- 2 Version 60.0 Technical Requirements

RCS Chemistry TR 13.4.1 DELETED Farley Units 1 and 2 13.4.1- 3 Version 60.0 Technical Requirements

Pressurizer TR 13.4.2 13.4 Reactor Coolant System TR 13.4.2 Not used.

Farley Units 1 and 2 13.4.2 - 1 Version 60.0 Technical Requirements

Pressurizer TR 13.4.2 DELETED Farley Units 1 and 2 13.4.2 - 2 Version 60.0 Technical Requirements

Reactor Vessel Head Vents TR 13.4.3 13.4 Reactor Coolant System (RCS)

TR 13.4.3 Reactor Vessel Head Vents TR 13.4.3 At least one of the two reactor vessel head vent system paths, consisting of two valves in series powered from the Auxiliary Building D. C. Distribution System, shall be FUNCTIONAL and closed.

APPLICABILITY: MODES 1, 2, 3, and 4.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. Both reactor vessel head A.1 Initiate action to maintain the Immediately vent system paths nonfunctional vent paths nonfunctional. closed with power removed from the valve actuators of all valves in the nonfunctional vent paths.

AND A.2 Restore the at least one vent 30 days path to FUNCTIONAL status.

B. Required Action and B.1 Initiate a Condition Report. In accordance with associated Completion the Corrective Action Time not met. AND Program B.2 Continue action to restore Immediately the required vent path(s) to FUNCTIONAL status.

Farley Units 1 and 2 13.4.3 - 1 Version 60.0 Technical Requirements

Reactor Vessel Head Vents TR 13.4.3 TECHNICAL REQUIREMENT SURVEILLANCES SURVEILLANCE FREQUENCY TRS 13.4.3.1 Verify each valve in the reactor vessel head vent 18 months system operates through one complete cycle of full travel from the control room during MODE 5 or 6.

TRS 13.4.3.2 Verify flow through the reactor vessel head vent 18 months systems by venting during MODE 5 or 6.

Farley Units 1 and 2 13.4.3 - 2 Version 60.0 Technical Requirements

Safety Valves - Shutdown TR 13.4.4 13.4 Reactor Coolant System (RCS)

TR 13.4.4 Safety Valves - Shutdown TR 13.4.4 A minimum of one pressurizer code safety valve shall be FUNCTIONAL with a lift setting of 2485 psig 1%.


NOTE------------------------------------------------------

The lift setting pressure shall correspond to ambient conditions of the valve at nominal operating temperature and pressure.

APPLICABILITY: MODE 4 with any RCS cold leg temperatures the LTOP System applicability temperature specified in the PTLR.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. Required pressurizer code A.1 Initiate action to suspend Immediately safety valve positive reactivity changes nonfunctional.

AND A.2 Initiate action to provide overpressure relief Immediately capability.

TECHNICAL REQUIREMENT SURVEILLANCES SURVEILLANCE FREQUENCY TRS 13.4.4.1 Verify requirements of the Inservice Testing Plan are In Accordance with met for the required pressurizer code safety valve. the Inservice Testing Program Farley Units 1 and 2 13.4.4 - 1 Version 60.0 Technical Requirements

RCS Pressure Isolation Valve (PIV) Leakage TR 13.4.5 13.4 Reactor Coolant System (RCS)

TR 13.4.5 RCS Pressure Isolation Valve (PIV) Leakage


(NOTE)---------------------------------------------------------

Table 13.4.5-1 contains a listing of RCS Pressure Isolation Valves (PIVs) subject to Technical Specification 3.4.14, including SR 3.4.14.1.

Farley Units 1 and 2 13.4.5 - 1 Version 60.0 Technical Requirements

RCS Pressure Isolation Valve (PIV) Leakage TR 13.4.5 Table 13.4.5-1 Reactor Coolant System Pressure Isolation Valves Valve Number Description Maximum Allowable Leakage Q1/2E11V001A 12 Gate 5.000 gpm Q1/2E11V001B 12 Gate 5.000 gpm Q1/2E11V016A 12 Gate 5.000 gpm Q1/2E11V016B 12 Gate 5.000 gpm Q1/2E11V021A 6 Check 3.000 gpm Q1/2E11V021B 6 Check 3.000 gpm Q1/2E11V021C 6 Check 3.000 gpm Q1/2E21V032A 12 Check 5.000 gpm Q1/2E21V032B 12 Check 5.000 gpm Q1/2E21V032C 12 Check 5.000 gpm Q1/2E21V037A 12 Check 5.000 gpm Q1/2E21V037B 12 Check 5.000 gpm Q1/2E21V037C 12 Check 5.000 gpm Q1/2E11V042A 10 Check 5.000 gpm Q1/2E11V042B 10 Check 5.000 gpm Q1/2E21V076A 6 Check 3.000 gpm Q1/2E21V076B 6 Check 3.000 gpm Q1/2E21V077A 6 Check 3.000 gpm Q1/2E21V077B 6 Check 3.000 gpm Q1/2E21V077C 6 Check 3.000 gpm Note: See TS 3.4.14 for applicable Actions and Surveillance Requirements Farley Units 1 and 2 13.4.5 - 2 Version 8.0 Technical Requirements

ECCS TR 13.5.1 13.5 Emergency Core Cooling System TR 13.5.1 Emergency Core Cooling System (ECCS)

TR 13.5.1 The ECCS subsystems required OPERABLE in accordance with Technical Specifications 3.5.2 and 3.5.3 shall be maintained with:

a. Not used.
b. Throttle valves in correct position, and
c. Flow balanced.

APPLICABILITY: MODES 1, 2, 3, and 4 ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. One or more ECCS A.1 Refer to Technical Immediately subsystems inoperable. Specification 3.5.2 or 3.5.3, as applicable, and associated Required Actions.

TECHNICAL REQUIREMENT SURVEILLANCES SURVEILLANCE FREQUENCY TRS 13.5.1.1 Not used Farley Units 1 and 2 13.5.1 - 1 Version 60.0 Technical Requirements

ECCS TR 13.5.1 TECHNICAL REQUIREMENT SURVEILLANCES SURVEILLANCE FREQUENCY TRS 13.5.1.2 Verify correct position of each mechanical position Once within 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> stop for the following ECCS throttle valves: following completion of each valve CVC-V-8991 A/B/C stroking operation or CVC-V-8989 A/B/C maintenance on the CVC-V-8996 A/B/C valve when the CVC-V-8994 A/B/C ECCS subsystems are required to be OPERABLE.

TRS 13.5.1.3 Verify that the mechanical stops are intact for the Prior to entry into following low head safety injection valves: MODE 3 from MODE 4.

RHR-HV-603 A/B TRS 13.5.1.4 Perform a flow balance test, during shutdown, and Once following verify the following flow rates: completion of modifications to the a) For HHSI System - single pump that provides the ECCS subsystem(s) greatest flow: that alter the subsystem(s) flow 193 gpm for each cold leg injection line, and characteristics.

183 gpm for each hot leg injection line Verify that the developed head of the other HHSI pumps is greater than or equal to the limits in Table 13.5.1-1 and within 580 feet of the developed head of the HHSI pump that provides the greatest flow.

b) For LHSI System - single pump:

3911 gpm (total injection)

Farley Units 1 and 2 13.5.1 - 2 Version 32.0 Technical Requirements

ECCS TR 13.5.1 Table 13.5.1-1 Minimum Allowable HHSI Pump Performance PUMP FLOW PUMP HEAD (gpm) (ft) 0 5420 125 5320 225 5220 260 5120 305 4920 390 4420 460 3920 520 3420 580 2920 635 2420 700 1770 Farley Units 1 and 2 13.5.1 - 3 Version 17.0 Technical Requirements

Containment Ventilation System Leakage Rate TR 13.6.1 13.6 Containment Systems TR 13.6.1 Containment Ventilation System Leakage Rate TR 13.6.1 The containment ventilation system leakage rate shall be within limits.

APPLICABILITY: MODES 1, 2, 3, and 4.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. Indications of excess A.1 Perform an engineering Prior to entering valve degradation (for the evaluation to determine what MODE 4 following containment purge supply corrective action, if any, is the next entry into and exhaust penetrations) necessary. MODE 5 if the based on comparison of existing leakage is the leakage rate for each determined during containment purge supply testing per Technical and exhaust penetration Specification SR to the previously 3.6.3.5 measured leakage rate.

OR Prior to entering MODE 4 if excess leakage is determined during MODE 5 per SR 3.6.3.5 Farley Units 1 and 2 13.6.1 - 1 Version 8.0 Technical Requirements

Containment Ventilation System Leakage Rate TR 13.6.1 TECHNICAL REQUIREMENT SURVEILLANCES SURVEILLANCE FREQUENCY TRS 13.6.1.1 Compare the leakage rate for each containment purge Prior to entering supply and exhaust penetration to the previously MODE 4 from measured leakage rate (for the containment purge MODE 5 if not supply and exhaust penetrations) to detect excess valve performed in the degradation. previous 92 days Farley Units 1 and 2 13.6.1 - 2 Version 61.0 Technical Requirements

Containment Isolation Valves TR 13.6.2 13.6 Containment Systems TR 13.6.2 Containment Isolation Valves


(NOTE)---------------------------------------------------------

Table 13.6.2-1 contains a listing of Containment Isolation Valves subject to Technical Specification SR 3.6.3.4.

Farley Units 1 and 2 13.6.2 - 1 Version 60.0 Technical Requirements

Containment Isolation Valves TR 13.6.2 Table 13.6.2-1 (Page 1 of 3)

Containment Isolation Valves Isolation Time Valve Number Function (sec)

A. Phase A Isolation

1. CVC-HV-8871 Accum. Test Line to RWST Iso. Valve 10
2. CVC-HV-8961 Accum. Test Line to RWST Iso. Valve 10
3. CVC-HV-8880 N2 Supply to Isolation Accum. 10
4. RC-HV-8047 Pressurizer Relief Tank N2 Supply 10
5. RC-HV-8033 Pressurizer Relief Tank N2 Supply 10
6. RC-HV-8028 Reactor Makeup Water to PRT Iso. Valve 10
7. LWP-LCV-1003 Reactor Coolant Drain Tank LCV 10
8. LWP-HV-7136 RCDT Pumps Discharge Line Iso. 10
9. CBV-MOV-3318A CTMT Differential Press. Iso. Valve 15
10. CBV-MOV-3318B CTMT Differential Press. Iso. Valve 15
11. CVC-HV-8152 Letdown Line CTMT Iso. Valve 10
12. CVC-HV-8149A Letdown Orifice Isolation Valve 45 gpm 10
13. CVC-HV-8149B Letdown Orifice Isolation Valve 60 gpm 10
14. CVC-HV-8149C Letdown Orifice Isolation Valve 60 gpm 10
15. CVC-MOV-8100 RCP Seal Water Return Iso. Valve 15
16. CVC-MOV-8112 RCP Seal Water Return Iso. Valve 15
17. SS-HV-3104 Pressurizer Steam Sample Iso. Valve 10
18. SS-HV-3331 Pressurizer Steam Sample Iso. Valve 10
19. SS-HV-3103 Pressurizer Liquid Sample Iso. Valve 10
20. SS-HV-3332 Pressurizer Liquid Sample Iso. Valve 10
21. SS-HV-3765 Reactor Loops 2 and 3 Sample Iso. Valve 10
22. SS-HV-3333 Reactor Loops 2 and 3 Sample Iso. Valve 10
23. CBV-HV-3657 Containment Air Sample Iso. Valve 10
24. CBV-MOV-3660 Containment Air Sample Iso. Valve 15
25. CBV-HV-3658 Containment Air Sample Iso. Valve 10
26. CBV-HV-3198A Containment Purge Exhaust Iso. Valve 5
27. CBV-HV-3198D Containment Purge Supply Iso. Valve 5
28. LWP-HV-3376 Containment Sump Discharge Valve 10
29. LWP-HV-3377 Containment Sump Discharge Valve 10
30. CCW-HV-3095 CCW to Excess Letdown/RCDT HXs. 10
31. CCW-HV-3443 CCW from Excess Letdown/RCDT HXs 10 (continued)

Farley Units 1 and 2 13.6.2 - 2 Version 50.0 Technical Requirements

Containment Isolation Valves TR 13.6.2 Table 13.6.2-1 (Page 2 of 3)

Containment Isolation Valves Isolation Time Valve Number Function (sec)

A. Phase A Isolation (continued)

32. CCW-HV-3067 CCW from Exc. Letdown / RCDT HXs 10
33. CVC-HV-8860 Accum. Fill Line Isolation 10
34. SS-HV-3766 Accum. Tanks Sample Iso. Valve 10
35. SS-HV-3334 Accum. Tanks Sample Iso. Valve 10
36. LWP-HV-7126 RCDT Vent Line Iso. Valve 10
37. LWP-HV-7150 RCDT Vent Line Iso. Valve 10
38. LWP-HV-3380 CTMT Sump Recirculation Valve 10
39. CTS-HV-3659 Demin. Water to Reactor HD Storage 10
40. CBV-HV-3196 CTMT Purge Exhaust Iso. Valve 5
41. CBV-HV-3197 CTMT Purge Supply Iso. Valve 5
42. CBV-HV-2867C CTMT Mini-Purge Exhaust Iso. Valve 5
43. CBV-HV-2867D CTMT Mini-Purge Exhaust Iso. Valve 5
44. CBV-HV-2866C CTMT Mini-Purge Supply Iso. Valve 5
45. CBV-HV-2866D CTMT Mini-Purge Supply Iso. Valve 5 B. Phase B Isolation
1. CCW-MOV-3052 CCW to RCP Coolers < 15
2. CCW-MOV-3046 CCW from RCP Oil Coolers < 36
3. CCW-MOV-3182 CCW from RCP Oil Coolers < 15
4. CCW-HV-3184 CCW from RCP Thermal Barrier < 10
5. CCW-HV-3045 CCW from RCP Thermal Barrier < 10
6. IA-HV-3611 CTMT Instrument Air Supply Valve < 10
7. IA-HV-2228 Pressurizer PORV Backup Air/N2 < 10 Supply Valve C. Safety Injection Signal
1. CVC-MOV-8107 Charging Pumps to Regenerative HX < 10
2. CVC-MOV-8108 Charging Pumps to Regenerative HX < 10
3. SW-MOV-3135 SW to RCP Motor Air Coolers < 36
4. SW-MOV-3131 SW From RCP Motor Air Coolers < 36
5. SW-MOV-3134 SW From RCP Motor Air Coolers < 36 (continued)

Farley Units 1 and 2 13.6.2 - 3 Version 57.0 Technical Requirements

Containment Isolation Valves TR 13.6.2 Table 13.6.2-1 (Page 3 of 3)

Containment Isolation Valves Isolation Time Valve Number Function (sec)

D. Manual

1. Q1/2G31V012 Refueling Cavity Supply N/A
2. Q1/2G21V005 Reactor Coolant Drain Tank N/A
3. RHR-MOV-8701A Reactor Coolant LP C to RHR Pump A < 120
4. RHR-MOV-8702A Reactor Coolant LP A to RHR Pump B < 120
5. Q1/2P18V001 Service Air N/A
6. Q1/2P18V002 Service Air N/A
7. CBV-MOV-3238 CTMT Leak Rate Test Valve N/A
8. CBV-MOV-3239 CTMT Leak Rate Test Valve N/A
9. RHR-MOV-8811A CTMT Sump to RHR Pump A < 17
10. RHR-MOV-8811B CTMT Sump to RHR Pump B < 17
11. RHR-MOV-8812A CTMT Sump to RHR Pump A < 17
12. RHR-MOV-8812B CTMT Sump to RHR Pump B < 17
13. CS-MOV-8826A CS Pump A CTMT Sump Suction Iso. < 17
14. CS-MOV-8826B CS Pump B CTMT Sump Suction Iso. < 17
15. CS-MOV-8827A CS Pump A CTMT Sump Suction Iso. < 17
16. CS-MOV-8827B CS Pump B CTMT Sump Suction Iso. < 17
17. Q1/2B13V026B Pressurizer Pressure Generator N/A
18. CBV-MOV-3528A CTMT Post-LOCA Sampling Valve 1 N/A
19. CBV-MOV-3528B CTMT Post-LOCA Sampling Valve 2 N/A
20. CBV-MOV-3528C CTMT Post-LOCA Sampling Valve 3 N/A
21. CBV-MOV-3528D CTMT Post-LOCA Sampling Valve 4 N/A
22. CBV-MOV-3739A CTMT Post-LOCA Sampling Iso. Valve N/A
23. CBV-MOV-3739B CTMT Post-LOCA Sampling Iso. Valve N/A
24. CBV-MOV-3745A CTMT Post-LOCA Sampling Rtn. Valve N/A
25. CBV-MOV-3745B CTMT Post-LOCA Sampling Rtn. Valve N/A
26. CBV-MOV-3835A CTMT Post-LOCA Sampling Rtn. Valve N/A
27. CBV-MOV-3835B CTMT Post-LOCA Sampling Rtn. Valve N/A
28. CBV-MOV-3740 CTMT Post-LOCA Vent Iso. Valve N/A
29. CBV-MOV-3530 CTMT Post-LOCA Vent Iso. Valve N/A
30. Q2P18V004 Breathing Air (Service Air) (Unit 2 Only) N/A
31. Q2P18V005 Breathing Air (Service Air) (Unit 2 Only) N/A
32. Q1/2P19V1099 HV2228 Bypass Manual Isolation Valve N/A Farley Units 1 and 2 13.6.2 - 4 Version 12.0 Technical Requirements

Steam Generator Pressure/Temperature Limitation TR 13.7.1 13.7 Plant Systems TR 13.7.1 Not used.

Farley Units 1 and 2 13.7.1 - 1 Version 60.0 Technical Requirements

Steam Generator Pressure/Temperature Limitation TR 13.7.1 DELETED Farley Units 1 and 2 13.7.1 - 2 Version 60.0 Technical Requirements

Snubbers TR 13.7.2 13.7 Plant Systems TR 13.7.2 Not used.

Farley Units 1 and 2 13.7.2 - 1 Version 60.0 Technical Requirements

Snubbers TR 13.7.2 DELETED Farley Units 1 and 2 13.7.2 - 2 Version 60.0 Technical Requirements

Snubbers TR 13.7.2 DELETED Farley Units 1 and 2 13.7.2 - 3 Version 60.0 Technical Requirements

Snubbers TR 13.7.2 DELETED Farley Units 1 and 2 13.7.2 - 4 Version 60.0 Technical Requirements

Sealed Source Contamination TR 13.7.3 13.7 Plant Systems TR 13.7.3 Sealed Source Contamination TR 13.7.3 The removable contamination shall be 0.005 microcuries for each sealed source containing radioactive material 100 microcuries of beta and/or gamma emitting material or 5 microcuries of alpha emitting material.

APPLICABILITY: At all times.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. Sealed source removable A.1 Remove sealed source from Immediately contamination not within use.

limit.

AND A.2.1 Decontaminate and repair Prior to returning the the sealed source sealed source to use OR A.2.2 Dispose of sealed source in In accordance with accordance with Commission Commission regulations. regulations Farley Units 1 and 2 13.7.3 - 1 Version 60.0 Technical Requirements

Sealed Source Contamination TR 13.7.3 TECHNICAL REQUIREMENT SURVEILLANCES


NOTES----------------------------------------------------------

1. The licensee, or other persons specifically authorized by the Commission or an Agreement State, shall perform the Technical Requirement Surveillances.
2. The test methods shall have a detection sensitivity of at least 0.005 microcuries per test sample.

SURVEILLANCE FREQUENCY TRS 13.7.3.1 ---------------------------------NOTES------------------------------

1. Not applicable to startup sources and fission detectors previously subjected to core flux.
2. Only applicable to sources in use with:
a. Half-lives 30 days, excluding Hydrogen 3, and
b. In any form other than gas.

Verify removable contamination is within limit for each 6 months sealed source.

TRS 13.7.3.2 ---------------------------------NOTES------------------------------

1. Only applicable to stored sources not in use.
2. Sealed sources and fission detectors transferred without a certificate indicating the last test date shall be tested prior to being placed into use.

Verify the removable contamination is within limit for Within 6 months each sealed source and fission detector. prior to use or transfer to another licensee.

Farley Units 1 and 2 13.7.3 - 2 Version 8.0 Technical Requirements

Sealed Source Contamination TR 13.7.3 TECHNICAL REQUIREMENT SURVEILLANCES SURVEILLANCE FREQUENCY TRS 13.7.3.3 --------------------------------NOTE---------------------------------

Only applicable to sealed startup sources and fission detectors not in use.

Verify the removable contamination is within limit for Within 31 days prior each sealed startup source and fission detector. to being subjected to core flux or being installed in the core.

AND Following repair or maintenance to the source.

Farley Units 1 and 2 13.7.3 - 3 Version 8.0 Technical Requirements

The Ultimate Heat Sink (UHS) Support Structures TR 13.7.4 13.7 Plant Systems TR 13.7.4 Not used.

Farley Units 1 and 2 13.7.4 - 1 Version 60.0 Technical Requirements

Area Temperature Monitoring (Unit 2 Only)

TR 13.7.5 13.7 Plant Systems TR 13.7.5 Area Temperature Monitoring (Unit 2 Only)

TR 13.7.5 The temperature of each area shown in Table 13.7.5-1 shall be maintained within the limits indicated in Table 13.7.5-1.


NOTE-----------------------------------------------------------

The area temperature may exceed the limit specified in Table 13.7.5-1 for 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />.

APPLICABILITY: Whenever the equipment in an affected area is required to be FUNCTIONAL or OPERABLE.

ACTIONS


NOTE--------------------------------------------------------

Separate condition entry is allowed for each affected area.

CONDITION REQUIRED ACTION COMPLETION TIME A. One or more areas not A.1 Initiate action to prepare an Immediately within limits for more than analysis to determine the 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />. effect on OPERABILITY and/or FUNCTIONALITY of equipment in the affected area(s).

AND A.2 Perform an engineering 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> evaluation to determine the effects of the out of limit temperature on the service life of the equipment located in the area(s).

TECHNICAL REQUIREMENT SURVEILLANCES SURVEILLANCE FREQUENCY TRS 13.7.5.1 Verify the temperature in each of the areas in Table 7 days 13.7.5-1 is within limits.

Farley Unit 2 13.7.5 - 1 Version 60.0 Technical Requirements

Area Temperature Monitoring (Unit 2 Only)

TR 13.7.5 Table 13.7.5-1 Area Temperature Monitoring Area Temperature Limit (F)

1. ESF Pump Rooms
a. RHR Pump 2A 150 F
b. RHR Pump 2B 150 F
c. AFW Pump 2A 150 F
d. AFW Pump 2B 150 F
e. CCW Pump Room 150 F
f. Containment Spray Pump 2A 150 F
g. Containment Spray Pump 2B 150 F
h. Charging Pump Room 2A 150 F
i. Charging Pump Room 2B 150 F
j. Charging Pump Room 2C 150 F
2. Electrical Areas
k. MCC 2A Room 150 F
l. MCC 2B Room 150 F
m. 600 Volt Load Center 2D Room 150 F
n. 600 Volt Load Center 2E Room 150 F
o. Battery Charger Room A 120 F
p. Battery Charger Room B 120 F
q. Battery Room A 120 F
r. Battery Room B 120 F
s. Diesel Generator Rooms 150 F
t. Diesel Generator Switchgear Rooms 150 F Farley Unit 2 13.7.5 - 2 Version 8.0 Technical Requirements

Main Steam Isolation Valves TR 13.7.6 13.7 Plant Systems TR 13.7.6 Main Steam Isolation Valves (MSIVs)


NOTE-----------------------------------------------------------

This Technical Requirement contains a listing of the MSIVs subject to Technical Specification SR 3.7.2.1.

Table 13.7.6-1 Main Steam Isolation Valves VALVE NUMBER ISOLATION TIME (SECONDS)

HV-3369A 7 HV-3369B 7 HV-3369C 7 HV-3370A 7 HV-3370B 7 HV-3370C 7 Farley Unit 2 13.7.6 - 1 Version 47.0 Technical Requirements

Containment Penetration Conductor Overcurrent Protective Devices (Unit 2 Only)

TR 13.8.1 13.8 Electrical Power Systems TR 13.8.1 Containment Penetration Conductor Overcurrent Protective Devices (Unit 2 Only)

TR 13.8.1 Each required penetration conductor overcurrent protective device shall be FUNCTIONAL for each containment penetration provided with required penetration conductor overcurrent protection. Required circuits for all other containment penetrations shall be deenergized unless energized under administrative control.

APPLICABILITY: MODES 1, 2, 3, and 4.

ACTIONS


NOTE--------------------------------------------------------

Separate condition entry is allowed for each component.

CONDITION REQUIRED ACTION COMPLETION TIME A. One or more required A.1.1 Initiate a Condition Report. In accordance with containment penetration the Corrective Action conductor overcurrent Program protective device(s) nonfunctional.

Farley Unit 2 13.8.1 - 1 Version 60.0 Technical Requirements

Containment Penetration Conductor Overcurrent Protective Devices (Unit 2 Only)

TR 13.8.1 TECHNICAL REQUIREMENT SURVEILLANCES SURVEILLANCE FREQUENCY TRS 13.8.1.1 -------------------------------NOTE----------------------------------

Only required to be performed on one reactor coolant pump circuit every 36 months provided that all reactor coolant pump circuits are demonstrated FUNCTIONAL at least once per 108 months.

Verify FUNCTIONALITY of at least one 4.16 kV reactor 36 months coolant pump circuit, by performance of:

a. A CHANNEL CALIBRATION of the associated protective relays, and
b. An integrated system functional test which includes simulated automatic actuation of the system and verification that each relay and associated circuit breakers and control circuits function as designed, and
c. For each circuit breaker found nonfunctional during these functional tests, an additional representative sample of at least one of the circuit breakers of the nonfunctional type shall also be functionally tested until no more failures are found or all circuit breakers of that type have been functionally tested.

Farley Unit 2 13.8.1 - 2 Version 60.0 Technical Requirements

Containment Penetration Conductor Overcurrent Protective Devices (Unit 2 Only)

TR 13.8.1 TECHNICAL REQUIREMENT SURVEILLANCES SURVEILLANCE FREQUENCY TRS 13.8.1.2 --------------------------------NOTES-------------------------------

1. Circuit breakers selected for functional testing shall be selected on a rotating basis.
2. The functional test shall consist of injecting a current input at the specified setpoint to each selected circuit breaker and verifying that each circuit breaker functions as designed.
3. For each circuit breaker found nonfunctional during these functional tests, an additional representative sample of 10% of all the circuit breakers of the nonfunctional type shall also be functionally tested until no more failures are found or all circuit breakers of that type have been functionally tested.

Perform a functional test on a representative sample of 18 months 10% of each type of lower voltage circuit breakers.

TRS 13.8.1.3 Inspect and perform preventive maintenance on each circuit breaker in accordance with procedures prepared in conjunction with its manufacturers recommendations.

For reactor coolant pump circuit breakers 108 months For all other circuit breakers 72 months TRS 13.8.1.4 Verify power sources feeding circuits required to be 18 months deenergized are interrupted by an open breaker or removed fuse.

Farley Unit 2 13.8.1 - 3 Version 53.0 Technical Requirements

Motor Operated Valves Thermal Overload Protection Devices (Unit 2 Only)

TR 13.8.2 13.8 Electrical Power Systems TR 13.8.2 Motor Operated Valves Thermal Overload Protection Devices (Unit 2 Only)

TR 13.8.2 The thermal overload protection devices, integral with the motor starter, of each valve listed in Table 13.8.2-1 shall be FUNCTIONAL.

APPLICABILITY: Whenever the motor operated valve is required to be OPERABLE.

ACTIONS


NOTE------------------------------------------------------------

Separate condition entry is allowed for each component.

CONDITION REQUIRED ACTION COMPLETION TIME A. TR 13.8.2 not met A.1 Initiate action to evaluate Immediately component(s)

FUNCTIONALITY or OPERABILITY and enter appropriate TS or TRM required actions for inoperable or nonfunctional component(s).

TECHNICAL REQUIREMENT SURVEILLANCES SURVEILLANCE FREQUENCY TRS 13.8.2.1 -------------------------------NOTE----------------------------------

CHANNEL CALIBRATION must be performed on each thermal overload device at least once per 12 years.

Verify the required thermal overload protection devices 36 months FUNCTIONAL by performance of a CHANNEL CALIBRATION of a representative sample of at least 25% of all thermal overload devices.

Farley Unit 2 13.8.2 - 1 Version 60.0 Technical Requirements

Motor Operated Valves Thermal Overload Protection Devices (Unit 2 Only)

TR 13.8.2 Table 13.8.2-1 (Page 1 of 4)

Motor Operated Valves Thermal Overload Protection Devices (Note 1)

Valve Number Function Bypass Device MOV-3052 CCW to RCP Coolers No MOV-3046 CCW from RCP Coolers No MOV-3182 CCW from RCP Coolers No MOV-3019A SW to Coolers (SI open) No MOV-3019B SW to Coolers (SI open) No MOV-3019C SW to Coolers (SI open) No MOV-3019D SW to Coolers (SI open) No MOV-3441A SW from Coolers No MOV-3441B SW from Coolers No MOV-3441C SW from Coolers No MOV-3441D SW from Coolers No MOV-3024A SW from Coolers No MOV-3024B SW from Coolers No MOV-3024C SW from Coolers No MOV-3024D SW from Coolers No MOV-3149 SW to Blowdown Hx No MOV-3150 SW from Blowdown Hx No MOV-3135 RCP Air Cooler SW Isolation No MOV-3134 RCP Air Cooler SW Isolation No MOV-3764A MD Discharge Isolation (AFW) No MOV-3764B MD Discharge Isolation (AFW) No MOV-3764C MD Discharge Isolation (AFW) No MOV-3764D MD Discharge Isolation (AFW) No MOV-3764E MD Discharge Isolation (AFW) No MOV-3764F MD Discharge Isolation (AFW) No MOV-3350A AFW Header Isolation No MOV-3350B AFW Header Isolation No MOV-3350C AFW Header Isolation No MOV-3209A Service Water for AFW Suction No MOV-3209B Service Water for AFW Suction No MOV-3210A Service Water for AFW Suction No MOV-3210B Service Water for AFW Suction No MOV-3216 Service Water for AFW Suction No MOV-3318A CTMT Differential Pressure Isolation No MOV-3318B CTMT Differential Pressure Isolation No MOV-2768A Control Room Vent. Damper No MOV-2768B Control Room Vent. Damper No (continued)

Farley Unit 2 13.8.2 - 2 Version 58.0 Technical Requirements

Motor Operated Valves Thermal Overload Protection Devices (Unit 2 Only)

TR 13.8.2 Table 13.8.2-1 (Page 2 of 4)

Motor Operated Valves Thermal Overload Protection Devices (Note 1)

Valve Number Function Bypass Device MOV-2769A Control Room Vent. Damper No MOV-2769B Control Room Vent. Damper No MOV-3478A Control Room Vent. Damper No MOV-3478B Control Room Vent. Damper No MOV-8106 Charging Pump Mini Flow Isolation No MOV-8826A CTMT Spray Suction from CTMT Sump No MOV-8826B CTMT Spray Suction from CTMT Sump No MOV-8827A CTMT Spray Suction from CTMT Sump No MOV-8827B CTMT Spray Suction from CTMT Sump No MOV-8817A CTMT Spray Suction from RWST No MOV-8817B CTMT Spray Suction from RWST No MOV-8820A Discharge to Spray Ring No MOV-8820B Discharge to Spray Ring No MOV-8886 Charging Pump Discharge to Hot Leg No MOV-8884 Charging Pump Discharge to Hot Leg No MOV-8885 Charging Pump Discharge to Cold Leg No MOV-8808A SIS Accumulator Outlet No MOV-8808B SIS Accumulator Outlet No MOV-8808C SIS Accumulator Outlet No MOV-8811A RHR Suction from CTMT Sump No MOV-8811B RHR Suction from CTMT Sump No MOV-8812A RHR Suction from CTMT Sump No MOV-8812B RHR Suction from CTMT Sump No MOV-8809A RHR Suction from RWST No MOV-8809B RHR Suction from RWST No MOV-8887A RHR Discharge Crossconnect No MOV-8887B RHR Discharge Crossconnect No FCV-602A RHR Pump Mini Flow No FCV-602B RHR Pump Mini Flow No MOV-8889 RHR Discharge to Hot Leg No MOV-8888A RHR Discharge to Cold Leg No MOV-8888B RHR Discharge to Cold Leg No MOV-8706A RHR Discharge to Charging Pump Suction No MOV-8706B RHR Discharge to Charging Pump Suction No (continued)

Farley Unit 2 13.8.2 - 3 Version 58.0 Technical Requirements

Motor Operated Valves Thermal Overload Protection Devices (Unit 2 Only)

TR 13.8.2 Table 13.8.2-1 (Page 3 of 4)

Motor Operated Valves Thermal Overload Protection Devices (Note 1)

Valve Number Function Bypass Device QSP25V513 RW to Pond Isolation No QSP25V514 RW to Pond Isolation No QSP25V517 RW to Wet Pit Isolation No QSP25V518 RW to Wet Pit Isolation No MOV-3536 CTMT Air Purge Isolation No MOV-3530 Post LOCA Vent Isolation No MOV-3740 Post LOCA Vent Isolation No MOV-3528A CTMT Air Sample Isolation No MOV-3528B CTMT Air Sample Isolation No MOV-3528C CTMT Air Sample Isolation No MOV-3528D CTMT Air Sample Isolation No MOV-3739A CTMT Air Sample Isolation No MOV-3739B CTMT Air Sample Isolation No MOV-3745A CTMT Air Sample Isolation No MOV-3745B CTMT Air Sample Isolation No MOV-3835A CTMT Air Sample Isolation No MOV-3835B CTMT Air Sample Isolation No MOV-3362A Penetration Room Vent Damper No MOV-3362B Penetration Room Vent Damper No MOV-3361A Penetration Room Vent Damper No MOV-3361B Penetration Room Vent Damper No MOV-3406 Turbine Trip and Throttle No Q2P16V514 Turbine Building Isolation No Q2P16V515 Turbine Building Isolation No Q2P16V516 Turbine Building Isolation No Q2P16V517 Turbine Building Isolation No Q2P16V538 Pond Recirculation No Q2P16V539 Pond Recirculation No MOV-8131A Charging Pump Suction Crossconnect No (continued)

Farley Unit 2 13.8.2 - 4 Version 58.0 Technical Requirements

Motor Operated Valves Thermal Overload Protection Devices (Unit 2 Only)

TR 13.8.2 Table 13.8.2-1 (Page 4 of 4)

Motor Operated Valves Thermal Overload Protection Devices (Note 1)

Valve Number Function Bypass Device MOV-8131B Charging Pump Suction Crossconnect No MOV-8130A Charging Pump Suction Crossconnect No MOV-8130B Charging Pump Suction Crossconnect No MOV-8132A Charging Pump Discharge Crossconnect No MOV-8132B Charging Pump Discharge Crossconnect No MOV-8133A Charging Pump Discharge Crossconnect No MOV-8133B Charging Pump Discharge Crossconnect No MOV-8109A Charging Pump Mini Flow Isolation No MOV-8109B Charging Pump Mini Flow Isolation No MOV-8109C Charging Pump Mini Flow Isolation No Note 1: Licensee may delete valves from this table provided the thermal overload protection devices are permanently bypassed.

Farley Unit 2 13.8.2 - 5 Version 58.0 Technical Requirements

Emergency Diesel Generators (EDGs) Maintenance and Inspection Requirements TR 13.8.3 13.8 Electrical Power Systems TR 13.8.3 Emergency Diesel Generators (EDGs) Maintenance and Inspection Requirements TR 13.8.3 The Emergency Diesel Generators (EDGs) shall be maintained in accordance with applicable maintenance and inspection requirements.

APPLICABILITY: When associated EDG is required to be OPERABLE.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. One or more EDG A.1 Initiate action to restore Immediately maintenance or inspection compliance with requirements not met. maintenance and inspection requirements.

TECHNICAL REQUIREMENT SURVEILLANCES SURVEILLANCE FREQUENCY TRS 13.8.3.1 Verify that the following EDG lockout features prevent 36 months the EDGs from starting only when required:

a. Oil Temperature High (OTH)
b. Coolant Temperature High (CTH)
c. Coolant Pressure Low (CPL)
d. Crankcase Pressure High (CCPH)

TRS 13.8.3.2 Verify that the permanently connected and auto- 18 months on a connected loads to each EDG do not exceed the 2000- STAGGERED TEST hour rating of 4353 kw for the 4075 kw generators and BASIS 3100 kw for the 2850 kw generator.

Farley Units 1 and 2 13.8.3 - 1 Version 53.0 Technical Requirements

Decay Time TR 13.9.1 13.9 Refueling Operations TR 13.9.1 Decay Time TR 13.9.1 The Reactor shall be subcritical for 100 hours0.00116 days <br />0.0278 hours <br />1.653439e-4 weeks <br />3.805e-5 months <br />.

APPLICABILITY: During movement of irradiated fuel in the reactor pressure vessel.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. Reactor subcritical for A.1 Initiate action to suspend all Immediately 100 hours0.00116 days <br />0.0278 hours <br />1.653439e-4 weeks <br />3.805e-5 months <br />. operations involving movement of irradiated fuel in the reactor pressure vessel.

TECHNICAL REQUIREMENT SURVEILLANCES SURVEILLANCE FREQUENCY TRS 13.9.1.1 Verify the reactor has been subcritical for 100 hours0.00116 days <br />0.0278 hours <br />1.653439e-4 weeks <br />3.805e-5 months <br /> Prior to movement of by confirming the date and time of subcriticality. irradiated fuel in the reactor pressure vessel.

Farley Units 1 and 2 13.9.1 - 1 Version 60.0 Technical Requirements

Communications TR 13.9.2 13.9 Refueling Operations TR 13.9.2 Communications TR 13.9.2 Direct Communications shall be maintained between the control room and personnel at the refueling station.

APPLICABILITY: During CORE ALTERATIONS ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. Direct communications A.1 Initiate action to suspend Immediately between control room and all CORE ALTERATIONS.

refueling station not maintained.

TECHNICAL REQUIREMENT SURVEILLANCES SURVEILLANCE FREQUENCY TRS 13.9.2.1 Verify direct communication exists between control Once within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> room and refueling station. prior to start of CORE ALTERATIONS AND 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> thereafter during CORE ALTERATIONS Farley Units 1 and 2 13.9.2 - 1 Version 60.0 Technical Requirements

Manipulator Crane TR 13.9.3 13.9 Refueling Operations TR 13.9.3 Manipulator Crane TR 13.9.3 The manipulator crane and auxiliary hoist shall be used for movement of drive rods or fuel assemblies and shall be FUNCTIONAL with:

a. The manipulator crane used for movement of fuel assemblies having:
1) A minimum capacity of 3250 pounds, and
2) An overload cut off limit less than or equal to 2850 pounds.
b. The auxiliary hoist used for movement of control rods having:
1) A minimum capacity of 700 pounds, and
2) Load indicators which shall be used to assure that loads in excess of 600 pounds are not lifted.

APPLICABILITY: During movement of drive rods or fuel assemblies within the reactor pressure vessel.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. Manipulator crane A.1 Initiate action to suspend Immediately nonfunctional. use of manipulator crane from operations involving the movement of fuel assemblies within the reactor pressure vessel.

Farley Units 1 and 2 13.9.3 - 1 Version 60.0 Technical Requirements

Manipulator Crane TR 13.9.3 ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME B. Auxiliary hoist B.1 Initiate action to suspend Immediately nonfunctional. use of auxiliary hoist from operations involving the movement of control rods within the reactor pressure vessel.

TECHNICAL REQUIREMENT SURVEILLANCES SURVEILLANCE FREQUENCY TRS 13.9.3.1 Verify manipulator crane FUNCTIONALITY by: Once within 100 hours0.00116 days <br />0.0278 hours <br />1.653439e-4 weeks <br />3.805e-5 months <br /> prior to the

a. Performing a load test of 3250 pounds, and start of movement of fuel assemblies
b. Demonstrating operation of the automatic load within the reactor cutoff when the crane load exceeds 2850 pressure vessel pounds.

TRS 13.9.3.2 Verify auxiliary hoist and associated load indicator Once within 100 FUNCTIONAL by performance of a load test 700 hours prior to the pounds. start of movement of drive rods within the reactor pressure vessel Farley Units 1 and 2 13.9.3 - 2 Version 60.0 Technical Requirements

Crane Travel - Spent Fuel Storage Building TR 13.9.4 13.9 Refueling Operations TR 13.9.4 Crane Travel - Spent Fuel Storage Building TR 13.9.4 Loads 3000 pounds shall be prohibited from travel over fuel assemblies in the storage pool.

APPLICABILITY: With fuel assemblies in the storage pool.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. Technical Requirement A.1 Initiate action to place the Immediately not met. crane load in a safe condition.

TECHNICAL REQUIREMENT SURVEILLANCES SURVEILLANCE FREQUENCY TRS 13.9.4.1 Verify loads 3000 pounds. Prior to movement over irradiated fuel assemblies in the storage pool Farley Units 1 and 2 13.9.4 - 1 Version 60.0 Technical Requirements

Spent Fuel Cask Crane TR 13.9.5 13.9 Refueling Operations TR 13.9.5 Spent Fuel Cask Crane TR 13.9.5 The spent fuel cask crane shall be FUNCTIONAL.

APPLICABILITY: When handling the spent fuel cask.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. Ambient air temperature A.1 Initiate action to perform cold Immediately less than the cold proof proof test at the established test temperature AND lower temperature OR material testing has not perform material testing as been performed. prescribed in the UFSAR Section 9.1.4.4.

B. Lifting components not B.1 Initiate action to suspend Immediately meeting any of the criteria lifting of loads with the main of TRS 13.9.5.2. hoist until the degraded components are repaired or replaced.

Farley Units 1 and 2 13.9.5 - 1 Version 60.0 Technical Requirements

Spent Fuel Cask Crane TR 13.9.5 TECHNICAL REQUIREMENT SURVEILLANCES SURVEILLANCE FREQUENCY TRS 13.9.5.1 Perform a cold proof test at 125% of rated load As needed pursuant to ANSI-B.30.2.0 OR perform Material Testing as described in UFSAR 9.1.4.4.

TRS 13.9.5.2 Perform testing and inspection of the lifting components As needed pursuant to ANSI-B.30.2.0 and the manufacturers recommendations.

Farley Units 1 and 2 13.9.5 - 2 Version 37.0 Technical Requirements

Storage Pool Ventilation (Fuel Storage)

TR 13.9.6 13.9 Refueling Operations TR 13.9.6 Not Used.

Farley Units 1 and 2 13.9.6 - 1 Version 60.0 Technical Requirements

Average Reactor Coolant Temperature TR 13.9.7 13.9 Refueling Operations TR 13.9.7 Average Reactor Coolant Temperature TR 13.9.7 The average reactor coolant temperature shall be 140 F.

APPLICABILITY: MODE 6 ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. Average reactor coolant A.1 Initiate action to restore Immediately temperature 140 F. average reactor coolant temperature to within limit.

TECHNICAL REQUIREMENT SURVEILLANCES SURVEILLANCE FREQUENCY TRS 13.9.7.1 Verify average reactor coolant temperature 140 F. 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> Farley Units 1 and 2 13.9.7 - 1 Version 8.0 Technical Requirements

Waste Gas Monitoring Instrumentation TR 13.12.1 13.12 Explosive Gas and Storage Tank Radioactivity Monitoring (EGSTRAM) Program TR 13.12.1 Waste Gas Monitoring Instrumentation TR 13.12.1 The following waste gas monitoring instrumentation channels shall be FUNCTIONAL with their alarm/trip setpoints set to ensure that the limits of TR 13.12.3 are not exceeded:

a. One hydrogen monitor per recombiner, and
b. Two oxygen monitors per recombiner.

APPLICABILITY: During recombiner operation.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. --------------NOTE------------ A.1 Initiate action to isolate the Immediately Not applicable during oxygen supply to the affected testing of oxygen recombiner(s).

monitors.

One oxygen monitor for one or more recombiners nonfunctional.

B. Both oxygen monitors for B.1 Analyze grab samples from 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> one or more recombiners the affected on-service waste nonfunctional. decay tank during addition of waste gas.

AND (continued)

Farley Units 1 and 2 13.12.1 - 1 Version 60.0 Technical Requirements

Waste Gas Monitoring Instrumentation TR 13.12.1 ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME B. (continued) B.2 Verify oxygen concentration 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> remains less than 1 percent.

C. Required hydrogen C.1 Analyze grab samples from 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> monitor for one or more the affected on-service waste recombiners decay tank during addition of nonfunctional.1 waste gas.

AND C.2 Verify oxygen concentration 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> remains less than 1 percent.

D. Required Actions and D.1 Initiate action to suspend Immediately associated Completion addition of waste gas to the Times of Conditions A, B system.

or C not met.

Farley Units 1 and 2 13.12.1 - 2 Version 60.0 Technical Requirements

Waste Gas Monitoring Instrumentation TR 13.12.1 TECHNICAL REQUIREMENT SURVEILLANCES SURVEILLANCE REQUIREMENTS FREQUENCY TRS 13.12.1.1 -------------------------------NOTE----------------------------------

Only required to be performed during recombiner operation.

Perform CHANNEL CHECK 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> TRS 13.12.1.2 -------------------------------NOTE----------------------------------

Only required to be performed during recombiner operation.

Perform COT 31 days TRS 13.12.1.3 -------------------------------NOTES--------------------------------

1. Only required to be performed during recombiner operation.
2. For the hydrogen monitors, the CHANNEL CALIBRATION shall include the use of standard gas samples in accordance with the manufacturers recommendations.
3. For the oxygen monitors, the CHANNEL CALIBRATION shall include the use of standard gas samples in accordance with the manufacturers recommendations. In addition, a standard gas sample of nominally four volume percent oxygen, balance nitrogen shall be used for inlet oxygen monitor linearity check.

Perform CHANNEL CALIBRATION 92 days Farley Units 1 and 2 13.12.1 - 3 Version 8.0 Technical Requirements

Liquid Holdup Tanks TR 13.12.2 13.12 Explosive Gas and Storage Tank Radioactivity Monitoring (EGSTRAM) Program TR 13.12.2 Liquid Holdup Tanks TR 13.12.2 The quantity of radioactive material contained in any outside temporary tank, excluding liners being used to solidify radioactive wastes, shall be limited to 10 curies, excluding tritium and dissolved or entrained noble gases.

APPLICABILITY: At all times.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. Quantity of radioactive A.1 Initiate action to suspend Immediately material in any outside addition of radioactive temporary tank, excluding material to the tank.

liners being used to solidify radioactive AND wastes, in excess of limit.

A.2 Reduce the tank contents to 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> within limit.

TECHNICAL REQUIREMENT SURVEILLANCES SURVEILLANCE FREQUENCY TRS 13.12.2.1 Verify quantity of radioactive material contained in 7 days when each outdoor temporary tank, excluding liners being radioactive materials used to solidify radioactive wastes, to be less than the are being added to a limit by analyzing a representative sample of the tank tank.

contents.

Farley Units 1 and 2 13.12.2 - 1 Version 60.0 Technical Requirements

Waste Gas Monitoring TR 13.12.3 13.12 Explosive Gas and Storage Tank Radioactivity Monitoring (EGSTRAM) Program TR 13.12.3 Waste Gas Monitoring TR 13.12.3 The concentration of oxygen in any portion of the gaseous radwaste treatment system shall be limited to:

A. 2% by volume whenever the hydrogen concentration in that portion of the gaseous radwaste treatment system exceeds 4% by volume and the hydrogen and oxygen monitors required by TR 13.12.1 are FUNCTIONAL; or B. 1% by volume whenever the hydrogen concentration in that portion of the gaseous radwaste treatment system exceeds 4% by volume and the hydrogen and oxygen monitors required by TR 13.12.1 are not FUNCTIONAL.

APPLICABILITY: At all times.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. Monitors in TR 13.12.1 A.1 Reduce oxygen 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> FUNCTIONAL. concentration to 2% by volume.

AND Concentration of oxygen in the gaseous radwaste treatment system 2% by volume but 4% by volume.

Farley Units 1 and 2 13.12.3 - 1 Version 60.0 Technical Requirements

Waste Gas Monitoring TR 13.12.3 ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME B. Monitors in TR 13.12.1 not B.1 Analyze grab samples from 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> FUNCTIONAL. the affected on-service waste decay tank during AND addition of waste gas.

Concentration of oxygen in AND the gaseous radwaste treatment system 1% by B.2 Reduce oxygen 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> volume but 4% by concentration to 1% by volume. volume.

C. Required Actions and C.1 Initiate action to suspend Immediately associated Completion addition of waste gas to the Times of Conditions A or B system.

not met.

D. Concentration of oxygen in D.1 Initiate action to suspend all Immediately the gaseous radwaste additions of waste gases to treatment system > 4% by the system.

volume.

AND 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> D.2 Reduce oxygen concentration to 4%.

AND 49 hours5.671296e-4 days <br />0.0136 hours <br />8.101852e-5 weeks <br />1.86445e-5 months <br /> D.3 Reduce oxygen concentration to within limit.

Farley Units 1 and 2 13.12.3 - 2 Version 60.0 Technical Requirements

Waste Gas Monitoring TR 13.12.3 TECHNICAL REQUIREMENT SURVEILLANCES SURVEILLANCE FREQUENCY TRS 13.12.3.1 Verify concentration of hydrogen or oxygen in the During addition of gaseous radwaste treatment system to be less than waste gases to the the limit by monitoring the waste gases in the gaseous gaseous radwaste radwaste treatment system. treatment system:

by use of the hydrogen and/or oxygen monitors required by TR 13.12.1, when FUNCTIONAL OR by analyzing grab samples from the affected waste decay tank at least once every 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />.

Farley Units 1 and 2 13.12.3 - 3 Version 6.0 Technical Requirements

Gas Storage Tanks TR 13.12.4 13.12 Explosive Gas and Storage Tank Radioactivity Monitoring (EGSTRAM) Program TR 13.12.4 Gas Storage Tanks TR 13.12.4 The quantity of radioactivity contained in each gas storage tank shall be limited to 70,500 curies of noble gases (considered as Xe-133).

APPLICABILITY: At all times.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A.1 Quantity of radioactive A.1 Initiate action to suspend all Immediately material in any gas additions of radioactive storage tank exceeding material to the tank.

limit.

AND A.2 Reduce the tank contents to 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> within the limit.

TECHNICAL REQUIREMENT SURVEILLANCES SURVEILLANCE FREQUENCY TRS 13.12.4.1 Verify quantity of radioactive material contained in Once per 7 days each gas storage tank to be less than the limit. when radioactive materials have been added to the tank during the previous 7 days.

Farley Units 1 and 2 13.12.4 - 1 Version 60.0 Technical Requirements

Gas Storage Tanks TR 13.12.4 TECHNICAL REQUIREMENT SURVEILLANCES SURVEILLANCE FREQUENCY TRS 13.12.4.2 In the event of confirmed major fuel failure (> 1%), Once per 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> verify quantity of radioactive material contained in when radioactive each waste gas storage tank to be less than the limit. materials have been added to the tank during the previous 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

Farley Units 1 and 2 13.12.4 - 2 Version 8.0 Technical Requirements

Emergency Response Facilities TR 13.13.1 13.13 Emergency Response Facilities TR 13.13.1 Emergency Response Facilities TR 13.13.1 The Technical Support Center, the Operations Support Center, and the Emergency Operations Facility shall be FUNCTIONAL.

APPLICABILITY: At all times.

ACTIONS


NOTE-------------------------------------------------------

Separate condition entry is allowed for each Emergency Response Facility (ERF).

CONDITION REQUIRED ACTION COMPLETION TIME A. One or more emergency A.1 Restore emergency 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> facilities nonfunctional. facilities to FUNCTIONAL status.

AND A.2 Initiate action to verify Immediately availability of alternate locations for performing ERF functions.

B. Required Action A and B.1 Initiate compensatory Immediately associated Completion actions, as necessary, to Time not met. provide emergency response functions.

AND (continued)

Farley Units 1 and 2 13.13.1 - 1 Version 60.0 Technical Requirements

Emergency Response Facilities TR 13.13.1 ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME B. (continued) B.2 Initiate action to review Immediately NMP-AD-031 for potential reporting criteria.

AND Immediately B.3 Proceed with actions to return ERFs to `

FUNCTIONAL status with a high priority.

TECHNICAL REQUIREMENT SURVEILLANCES SURVEILLANCE FREQUENCY TRS 13.13.1.1 Perform testing to ensure FUNCTIONALITY of an In accordance with ERF. applicable procedures.

TRS 13.13.1.2 Perform inventory to ensure FUNCTIONALITY of an In accordance with ERF. applicable procedures.

Farley Units 1 and 2 13.13.1 - 2 Version 60.0 Technical Requirements