ML22278A245

From kanterella
Jump to navigation Jump to search
Rev. 21 to Updated Final Safety Analysis Report, Chapter 8, Section 8.3-1(a), Sequence of Events in the Automatic Application of Emergency AC Loads on Loca and Loop
ML22278A245
Person / Time
Site: Limerick  
(NPF-039, NPF-085)
Issue date: 09/19/2022
From:
Constellation Energy Generation
To:
Office of Nuclear Reactor Regulation
Shared Package
ML22278A223 List: ... further results
References
Download: ML22278A245 (66)


Text

LGS UFSAR CHAPTER 08 8.3-52 REV. 13, SEPTEMBER 2006 Table 8.3-1(a)

SEQUENCE OF EVENTS IN THE AUTOMATIC APPLICATION OF EMERGENCY AC LOADS ON LOCA(1)

AND LOOP EVENT TIME (sec)

Signal to start diesel 0

Diesel ready to load; start 10 one RHR pump motor Apply power to 440 V auxiliaries 13 and MOVs Start one core spray pump motor 17 Start one ESW pump motor 55 Control room chiller 177 Reactor building recirculation 193 fan (1)

This sequence applies to one diesel and its associated loads. The other diesels have a similar sequence and load.

LGS UFSAR CHAPTER 08 8.3-53 REV. 13, SEPTEMBER 2006 Table 8.3-1(b)

SEQUENCE OF EVENTS IN THE AUTOMATIC APPLICATION OF EMERGENCY AC LOADS ON LOCA WITH OFFSITE POWER AVAILABLE(1)

EVENTS TIME (sec)

Start RHR pumps C & D 0

Apply power to 440 V 3.5 auxiliaries and MOVs Start RHR pumps A & B 5

Start core spray pumps A & C 10 Start core spray pumps B & D 15 Start 4 ESW pumps 55 Control room chillers 167 Reactor buildings 183.5 recirculation fans (1)

Diesel is started and remains on standby when offsite power is available.

LGS UFSAR CHAPTER 08 8.3-54 REV. 15 SEPTEMBER 2010 TABLE 8.3-2 (Page 1 of 2)

SUMMARY

OF LOADING DIESEL GENERATOR AND EMERGENCY BUSES SAFEGUARD AND SELECTED NON-SAFEGUARD LOADS MAXIMUM LOADING OF ANY ONE DIESEL GENERATOR (kW)

TABLE 0 - 10 10 MIN -

1 HOUR and NO.

DESCRIPTION MIN 1 HOUR LONGER 8.3 - 3 Assignment of safeguard and selected non-safeguard loads to diesel generators and emergency buses Both units in operation Unit 1 DBA; Unit 2 spurious LOCA 8.3 - 9 All D/G in service 2394 1910 1910 8.3 - 10 D11 D/G out-of -service 2397 2165 2165 8.3 - 11 D12 D/G out-of-service 2394 2222 2222 8.3 - 12 D13 D/G out-of-service 2394 1910 1910 8.3 - 13 D14 D/G out-of-service 2394 2190 2190 8.3 - 14 D21 D/G out-of-service 2394 2062 2062 8.3 - 15 D22 D/G out-of-service 2394 1846 1846 8.3 - 16 D23 D/G out-of-service 2394 2048 2048 8.3 - 17 D24 D/G out-of-service 2394 1824 1824 The above loadings are based on the minimum required engineered safeguard and selected non-safeguard laods for the following situation:

  • Unit 1 DBA with a spurious LOCA in Unit 2 for the 0 -10 minute period following by an emergency shutdown of Unit 2.

LGS UFSAR CHAPTER 08 8.3-55 REV. 15 SEPTEMBER 2010 TABLE 8.3-2 (Cont'd)

The case for a Unit 2 DBA is not tabulated. Due to the similarity in loading between Unit 1 and Unit 2, it has been determined that, for a Unit 2 DBA with a spurious LOCA and ESD in Unit 1, Unit 2 data on the following tables are conservative for Unit 1 and Unit 1 data are conservative for Unit 2.

All loads in the 0-10 minute period are automatically applied. Beyond 10 minutes, the major loads are manually connected or disconnected.

Nonsafeguard loads are tripped by the LOCA signal and may be manually added after the 0-10 minute period as permitted by the available capacity of the diesel generators (limited by fuel consumption) and as indicated in the table below.

The required minimum operation of ECCS pumps indicated is shown below:

DESIGN BASIS ACCIDENT EMERGENCY SHUTDOWN 0-10 10 min -

Beyond 0-10 10 min -

Beyond min 1 hr 1 hr min 1 hr 1 hr RHR pumps 3

1 1

0 1

1 CS pumps 2

2 2

0 0

0 RHRSW pumps 0

1 1

0 1

1 Any combination of three-out-of-four divisions (EDGs) is acceptable for a single failure. However, the ECCS requirements (as stated in paragraph 6.3.1.1.2), an EDG operable configuration of two-out-of-four is also acceptable.

LGS UFSAR CHAPTER 08 8.3-56 REV. 15, SEPTEMBER 2010 TABLE 8.3 - 3 (PAGE 1 OF 6)

ASSIGNMENT OF SAFEGUARD AND SELECTED NON-SAFEGUARD LOADS TO DIESEL GENERATORS AND EMERGENCY BUSES STARTUP MODE & OPERATING NUMBER OF OPERATING UNITS UNIT 1 or UNIT 2 UNIT 1 or UNIT 2 DBA EMERGENCY SHUTDOWN (2)

EQUIP CAPACITY RATED HP OPER KW STANDBY STANDBY ITEM LOAD DESCRIPTION COMMENTS NO.

UNIT 1 COMMON UNIT 2 EACH EACH EACH AUTO AUTO MAN MAN AUTO AUTO MAN MAN 01 RHR PUMP (9)

P202 4

0 4

1/3 1250 993 4

0 0

0 0

0 3

1 02 CORE SPRAY PUMP P206 4

0 4

1/2 600 529 4

0 0

0 0

0 0

0 03 RHR SERVICE WATER PUMP P506 0

4 0

F 700 519 0

0 0

2 0

0 0

2 04 ESW PUMP P548 0

4 0

1/2 500 389 4

0 0

0 4

0 0

0 05 125V BATTERY CHARGER D103 4 & 2 0

4 & 2 1/6 0

25 & 9 6

0 0

0 6

0 0

0 06 DRYWELL COOLER FAN V212 16 0

16 1/8 30 20 8

8 0

0 8

8 0

0 07 DG ROOM VENT FAN V512 8

0 8

1/2 20 15 4

4 0

0 4

4 0

0 08 RHR ROOM COOLING UNIT V210 8

0 8

1/2 20 16 4

4 0

0 4

4 0

0 09 CORE SPRAY ROOM COOLING UNIT V211 8

0 8

F 10 7 & 8 4

4 0

0 4

4 0

0 10 HPCI ROOM COOLING UNIT V209 2

0 2

F 15 10 1

1 0

0 1

1 0

0 11 RCIC ROOM COOLING UNIT V208 2

0 2

F 5

4 1

1 0

0 1

1 0

0 12 INSTRUMENT AC POWER SUPPLY Y101 4

0 4

1/4 0

11 & 12 4

0 0

0 4

0 0

0 12 INSTRUMENT AC POWER SUPPLY Y102 0

0 0

0 0

0 0

0 0

0 0

0 0

0 12 INSTRUMENT AC POWER SUPPLY Y103 0

0 0

0 0

0 0

0 0

0 0

0 0

0 12 INSTRUMENT AC POWER SUPPLY Y104 0

0 0

0 0

0 0

0 0

0 0

0 0

0 13 DG START AIR COMPRESSOR o

K513 8

0 8

F 20 7

0 0

4 4

4 4

0 0

14 DG FUEL OIL TRANSFER PUMP P514 4

0 4

F 1-1/2 1

0 0

0 4

0 0

0 4

15 SGTS HEATER E188 0

2 0

F 0

44 2

0 0

0 2

0 0

0 16 SGTS ROOM UNIT COOLER V140 0

2 0

F 1

1 1

1 0

0 1

1 0

0 17 SGTS ROOM ACCESS UNIT COOLER V141 0

2 0

F 7-1/2 6

1 1

0 0

1 1

0 0

18 SGTS EXHAUST FAN V163 0

2 0

F 40 32 1

0 0

0 1

0 0

0 19 RERS FAN V213 2

0 2

F 200 151 1

1 0

0 1

1 0

0 20 HVAC DAMPER POWER Y206 4

0 4

1/4 0

0 4

0 0

0 4

0 0

0 20 HVAC DAMPER POWER Y207 0

0 0

0 0

0 0

0 0

0 0

0 0

0 20 HVAC DAMPER POWER Y163 0

0 0

0 0

0 0

0 0

0 0

0 0

0 20 HVAC DAMPER POWER Y164 0

0 0

0 0

0 0

0 0

0 0

0 0

0 21 CONTROL ROOM CHILLER K112 0

2 0

F 0

329/330 1

1 0

0 1

1 0

0 22 CONTROL ROOM CHILLER WATER PP P162 0

2 0

F 25 16 1

1 0

0 1

1 0

0 23 AUX PNL & COMP RM FAN COIL UNIT V114 0

2 0

F 38.5 24 1

1 0

0 1

1 0

0 24 AUX PNL & COMP RM RETURN AIR UNIT V120 0

2 0

F 20 16 1

1 0

0 1

1 0

0 25 CONTROL ROOM AIR COND UNIT V116 0

2 0

F 40 32 1

1 0

0 1

1 0

0 26 CONTROL ROOM RETURN AIR FAN V121 0

2 0

F 15 12 1

1 0

0 1

1 0

0 27 EMER SWGR & BTRY RM AIR COND UNIT V118 0

2 0

F 15 9

1 1

0 0

1 1

0 0

28 AUX EQUIP & COMP RM AREA HTR

  • ++

E193 0

2 0

F 0

52 0

0 0

0 1

1 0

0 29 CONTROL ROOM AREA HEATER

  • ++

E192 0

2 0

F 0

40 0

0 0

0 1

1 0

0 30 CONT RM FRESH AIR INTAKE HTR E191 0

2 0

F 0

32 0

0 0

0 0

0 0

0 31 SPRAY POND STATION HTG COIL FAN V543 0

4 0

1/2 10 7

2 2

0 0

2 2

0 0

32 SLCS HEATERS

++

S213 1 & 1 0

1 & 1 F

0 8

1 0

0 1

1 0

0 1

33 CONTAINMENT H2 RECOMBINER S403 2

0 2

F 0

48 0

0 1

1 0

0 1

1 34 CONT'L RM EMER FRESH AIR SPLY FAN V127 0

2 0

F 10 6

1 1

0 0

1 1

0 0

35 CONTROL ROOM CHILLER OIL PUMP P168 0

2 0

F 1-1/2 1

1 1

0 0

1 1

0 0

36 DG AUXILIARIES o

G501 4

0 4

F 35KVA 14 4

0 0

0 4

0 0

0 37 DELETED

LGS UFSAR CHAPTER 08 8.3-57 REV. 15, SEPTEMBER 2010 TABLE 8.3 - 3 (Contd)

(PAGE 2 OF 6)

ASSIGNMENT OF SAFEGUARD AND SELECTED NON-SAFEGUARD LOADS TO DIESEL GENERATORS AND EMERGENCY BUSES STARTUP MODE & OPERATING NUMBER OF OPERATING UNITS UNIT 1 or UNIT 2 UNIT 1 or UNIT 2 DBA EMERGENCY SHUTDOWN (2)

EQUIP CAPACITY RATED HP OPER KW STANDBY STANDBY ITEM LOAD DESCRIPTION COMMENTS NO.

UNIT 1 COMMON UNIT 2 EACH EACH EACH AUTO AUTO MAN MAN AUTO AUTO MAN MAN 37 DELETED 38 DELETED 39 CRD PUMP o

P158 2

0 2

F 250 133 0

0 0

0 0

0 1

1 40 DELETED 41 RECW PUMP

++

P210 2

0 2

F 100 68 0

0 1

1 1

1 0

0 42 TECW o

P103 2

0 2

F 15 11 & 12 0

0 1

1 1

1 1

0 43 INSTRUMENT AC POWER SUPPLY o

Y105 4

0 4

1/4 0

0 0

0 0

4 4

0 0

0 43 INSTRUMENT AC POWER SUPPLY o

Y106 0

0 0

0 0

0 0

0 0

0 0

0 0

0 43 INSTRUMENT AC POWER SUPPLY o

Y201 0

0 0

0 0

0 0

0 0

0 0

0 0

0 43 INSTRUMENT AC POWER SUPPLY o

Y202 0

0 0

0 0

0 0

0 0

0 0

0 0

0 44 EMERGENCY LIGHTING o !

MISC 7

6 7

0 0

0 0

0 0

13 0

0 0

13 45 TURBINE GEN BEARING LIFT PUMP o

P109 9

0 9

1/9 5

36 & 45 (TOTAL) 0 0

0 9

9 0

0 0

46 TURBINE GEN TURNING OIL PP o

P111 1

0 1

F 40 32 0

0 0

1 1

0 0

0 47 TURBINE GEN TURNING GEAR o

S103 1

0 1

F 60 48 0

0 0

1 1

0 0

0 48 RFPT GEAR o

S106 3

0 3

F 1-1/2 1

0 0

0 3

3 0

0 0

49 INSTRUMENT GAS COMPRESSOR o (12)

K203 2

0 2

F 5

1 0

0 1

1 1

1 0

0 50 INSTRUMENT AIR COMPRESSOR o

K101 2

0 2

F 100 33 0

0 1

1 1

1 0

0 51 DELETED 52 OSC XFMR PNLS OOL140 & OOL141 X186 0

1 0

0 30 24 0

0 0

1 0

0 0

1 53 TEST ENGINEER'S WORKSHOP X187 0

1 0

0 30 12 0

0 0

1 0

0 0

1 54 NORTH STACK RM ANTENNA SYS XFMR X595 0

1 0

0 15 9

0 0

0 1

0 0

0 1

55 DELETED 56 CRD REPAIR RM COOLING FAN V904 0

1 1

0 0

0 0

0 0

0 0

0 0

0 57 125V BATTERY CHARGER o

D113 2

0 2

1/2 0

96 0

0 0

2 2

0 0

0 58 FIRE ALARM & P/A

  • +

1X5 0

0 0

0 0

12 1

0 0

0 1

0 0

0 59 FUEL POOL COOLING WATER PUMP o

P211 3

0 3

0 50 32 0

0 1

2 0

0 1

2 60 FUEL POOL SVC WTR BSTR PUMP (7)

P212 3

0 3

0 25 19 0

0 0

0 0

0 0

0 61 INSTR. AC PWR SUPPLY (SPRAY POND) o Y501 0

4 0

1/4 0

1 0

0 0

0 2

2 0

0 62 SPRAY POND PP STATION HTG COIL

++

  • E701 0

4 0

1/2 0

96 0

0 0

0 2

2 0

0 63 SGTS RM VENT EXHAUST FAN o *(13)

V131 0

2 0

0 10 7

0 0

1 1

1 1

0 0

64 SECURITY AREAS AIR COND. (11) o*

V565 0

2 0

0 17-1/2 14 0

0 1

1 0

0 0

1 65 PIPING FILL PUMP P256 2

0 2

0 5

3 0

0 0

2 0

0 0

0 66 DRYWELL H2O2 ANALYZER S205 1

0 1

0 1

1 0

0 0

1 0

0 0

1 67 SUPPRESSION POOL H2O2 ANALYZER S206 1

0 1

0 1

1 0

0 0

1 0

0 0

1 68 CHILLER PUMP-OUT COMPRESSOR o

  • K114 0

2 0

0 2

2 0

0 0

0 0

0 0

0 69 SPRAY POND SUMP PUMP o

  • P578 0

4 0

0 5

2 0

0 4

0 0

4 0

0 70 AUX EG. RM & COMP RM ELEC HUMIDFR o

  • E743 0

2 0

0 0

43 0

0 0

0 1

0 0

0 71 CONT RM ELEC HUMIDIFIER o

  • E744 0

2 0

0 0

29 0

0 0

0 1

0 0

0 72 250V BATTERY CHARGER o

D123 1

0 1

0 0

9 0

0 0

1 1

0 0

0 73 ALT. POWER SUPPLY TO 10X161 XFMR o

10X161 1

0 0

0 37-1/2 30 0

0 0

0 0

0 0

0 74 STATIC INVERTER 00-D592 XFMR o

  • 00-X592 0

1 0

0 37-1/2 30 0

0 0

0 0

0 0

0 75 TELEPHONE EQUIP POWER XFMR o

  • X503 0

1 0

0 7-1/2 6

0 0

0 1

1 0

0 0

76 RECOMBINER HYDROGEN ANALYZER o

P947 3

0 3

0 1

1 0

0 0

0 0

0 0

0

LGS UFSAR CHAPTER 08 8.3-58 REV. 15, SEPTEMBER 2010 TABLE 8.3 - 3 (Contd)

(PAGE 3 OF 6)

ASSIGNMENT OF SAFEGUARD AND SELECTED NON-SAFEGUARD LOADS TO DIESEL GENERATORS AND EMERGENCY BUSES STARTUP MODE & OPERATING NUMBER OF OPERATING UNITS UNIT 1 or UNIT 2 UNIT 1 or UNIT 2 DBA EMERGENCY SHUTDOWN (2)

EQUIP CAPACITY RATED HP OPER KW STANDBY STANDBY ITEM LOAD DESCRIPTION COMMENTS NO.

UNIT 1 COMMON UNIT 2 EACH EACH EACH AUTO AUTO MAN MAN AUTO AUTO MAN MAN 77 DIESEL GENERATOR BRIDGE CRANE o

H501 4

0 4

0 23 18 0

0 0

0 0

0 0

0 78 440V POWER RECEPTACLES o

W508 4

0 4

0 60 48 0

0 0

0 0

0 0

0 79 SPRAY POND PUMP HOIST o

  • H511 0

2 0

0 7/12 0.5 0

0 0

0 0

0 0

0 79 SPRAY POND PUMP HOIST o

  • H513 0

0 0

0 0

0 0

0 0

0 0

0 0

0 80 TURB BLDG EQUIP CMPT EXHAUST FAN

++

V106 2

0 2

0 250 198 0

0 0

0 0

0 0

0 81 DRYWELL CHILLER COMPRESSOR

++

K111 2

0 2

0 1302 1379 0

0 0

0 0

0 0

0 82 ROD DRIVE CONTROL CABINET XFMR o

X516 1

0 1

0 10 8

0 0

0 0

1 0

0 0

83 SLCS PUMP P208 3

0 3

0 40 32 0

0 0

0 0

0 0

0 84 RWCU SYSTEM RECIRC PUMP (7)

P221 3

0 3

0 125 92 0

0 0

0 0

0 0

0 85 440V POWER RECEPTACLES o

W201 4,1 & 3 0

4,1 & 3 0

60 48 0

0 0

0 0

0 0

0 85 440V POWER RECEPTACLES o

W202 0

0 0

0 0

0 0

0 0

0 0

0 0

0 85 440V POWER RECEPTACLES o

W205 0

0 0

0 0

0 0

0 0

0 0

0 0

0 86 440V POWER RECEPTACLE o

  • W601 0

1 0

0 60 48 0

0 0

0 0

0 0

0 87 440V POWER RECEPTACLE o

W206 2

0 2

0 60 48 0

0 0

0 0

0 0

0 88 ANNUNCIATOR 4

0 4

0 0

1 0

0 0

4 0

0 0

4 89 TURB GEN TURN GEAR PIGGYBACK S195 0

0 1

0 3

2 0

0 0

1 0

0 0

1 90 RHRSW CORROSION MONITORING

+++

Y215 1

0 0

F 105 77 0

0 0

0 0

0 0

0 91 ADMIN BLDG 480V DIST PNL o+

00B500 0

1 0

0 45 36 0

0 0

0 0

0 0

0 LEGEND:

  • - COMMON EQUIPMENT o - NON SAFEGUARD LOADS THAT ARE TRIPPED BY LOCA SIGNAL AND MANUALLY RESTARTED AFTER 10 MINUTES OR MORE, IF NEEDED.

+ - NON SAFEGUARD LOAD NOT TRIPPED BY A LOAD SIGNAL.

++ - NON SAFEGUARD LOADS TREATED AS SAFEGUARD LOAD BUT TRIPPED BY A LOCA SIGNAL AND CAN BE MANUALLY RESTARTED AFTER 10 MINUTES OR MORE, IF NEEDED.

+++ - NON SAFEGUARD LOAD TRIPPED BY A LOCA OR LOOP SIGNAL AND SHALL NOT BE RESTARTED UNTIL NORMAL PLANT OPERATION IS RESTORED.

LOAD KEPT IN THE INACTIVE STATUS BY PLACING THE MCC BREAKER IN THE OPEN POSITION.

! - EMERGENCY LIGHTING NUMBERS ARE AS FOLLOWS: 1L87*, L10, 1L55*, 1L85*, X26, L16, L17, L130, 1X17*, 1X64, L6, 1L9, L86 (1) - MOV LOADS ARE NOT INCLUDED IN THIS TABLE AND THE DIESEL GENERATOR LOADING TABLES THAT FOLLOW BECAUSE OF THEIR SMALL MAGNITUDE AND SHORT DURATION (2) - ASSIGNMENT OF THE LOADING ON THE DIESEL GENERATORS IS SUCH THAT THE SITUATION OF A DBA ON ONE UNIT AND SPURIOUS LOCA ON THE OTHER UNIT DOES NOT PRECLUDE SAFE SHUTDOWN OF THE UNITS. A SPURIOUS LOCA IS DEFINED AS A LOCA FOR 0-10 MINUTES AND EMERGENCY SHUTDOWN FOR BEYOND 10 MINUTES.

(7) - ALTHOUGH 3 PUMPS ARE INSTALLED, ONLY ONE IS POWERED FROM THE CLASS 1E SYSTEM.

(9) - MOD P00674 REPLACED THE 2A-P202 PUMP MOTOR. THE MOTOR IS MORE EFFICIENT AND THE LOAD ASSIGNMENT FOR THE D/G AND BUS 21 IS REDUCED BY 16 kW.

(10) - DELETED.

(11) - ALTHOUGH 2 AIR CONDITIONERS ARE INSTALLED, ONLY ONE IS POWERED FROM THE CLASS 1E SYSTEM.

(12) -ECR 04-00319 REPLACED THE MOTOR FOR 1A-K203. LOAD IS NOW 2 KW.

(13) - ECR 04-00569 REPLACED THE MOTOR FOR 0A-V131. LOAD IS NOW 7 KW.

LGS UFSAR CHAPTER 08 8.3-59 REV. 15, SEPTEMBER 2010 TABLE 8.3 - 3 (Contd)

(PAGE 4 OF 6)

ASSIGNMENT OF SAFEGUARD AND SELECTED NON-SAFEGUARD LOADS TO DIESEL GENERATORS AND EMERGENCY BUSES ASSIGNMENT OF LOADS TO DIESEL GENERATORS AND EMERGENCY BUSES (IN kw)

UNIT 1 UNIT 2 NUMBER OF OPERATING UNITS (UNIT 1 and UNIT 2 IN OPERATION)

(UNIT 1 and UNIT 2 IN OPERATION)

D/G D/G D/G D/G D/G D/G D/G D/G EQUIP BUS BUS BUS BUS BUS BUS BUS BUS ITEM LOAD DESCRIPTION COMMENTS NO.

UNIT 1 COMMON UNIT 2 D11 D12 D13 D14 D21 D22 D23 D24 01 RHR PUMP (9)

P202 4

0 4

993 993 993 993 977 993 993 993 02 CORE SPRAY PUMP P206 4

0 4

529 529 529 529 529 529 529 529 03 RHR SERVICE WATER PUMP P506 0

4 0

519 519 0

0 519 519 0

0 04 ESW PUMP P548 0

4 0

389 389 0

0 0

0 389 389 05 125V BATTERY CHARGER D103 4 & 2 0

4 & 2 51 50 9

9 51 51 9

9 06 DRYWELL COOLER FAN V212 16 0

16 80 80 80 80 80 80 80 80 07 DG ROOM VENT FAN V512 8

0 8

30 30 30 30 30 30 30 30 08 RHR ROOM COOLING UNIT V210 8

0 8

32 32 32 32 32 32 32 32 09 CORE SPRAY ROOM COOLING UNIT V211 8

0 8

14 16 14 16 14 14 14 14 10 HPCI ROOM COOLING UNIT V209 2

0 2

0 20 0

0 0

20 0

0 11 RCIC ROOM COOLING UNIT V208 2

0 2

8 0

0 0

8 0

0 0

12 INSTRUMENT AC POWER SUPPLY Y101 4

0 4

11 11 12 11 12 12 12 12 12 INSTRUMENT AC POWER SUPPLY Y102 0

0 0

0 0

0 0

0 0

0 0

12 INSTRUMENT AC POWER SUPPLY Y103 0

0 0

0 0

0 0

0 0

0 0

12 INSTRUMENT AC POWER SUPPLY Y104 0

0 0

0 0

0 0

0 0

0 0

13 DG START AIR COMPRESSOR o

K513 8

0 8

14 14 14 14 14 14 14 14 14 DG FUEL OIL TRANSFER PUMP P514 4

0 4

1 1

1 1

1 1

1 1

15 SGTS HEATER E188 0

2 0

44 44 0

0 0

0 0

0 16 SGTS ROOM UNIT COOLER V140 0

2 0

1 1

0 0

0 0

0 0

17 SGTS ROOM ACCESS UNIT COOLER V141 0

2 0

6 6

0 0

0 0

0 0

18 SGTS EXHAUST FAN V163 0

2 0

32 32 0

0 0

0 0

0 19 RERS FAN V213 2

0 2

151 151 0

0 151 151 0

0 20 HVAC DAMPER POWER Y206 4

0 4

4 4

16 20 2

2 0

0 20 HVAC DAMPER POWER Y207 0

0 0

0 0

0 0

0 0

0 0

20 HVAC DAMPER POWER Y163 0

0 0

0 0

0 0

0 0

0 0

20 HVAC DAMPER POWER Y164 0

0 0

0 0

0 0

0 0

0 0

21 CONTROL ROOM CHILLER K112 0

2 0

0 0

329/330 330 0

0 0

0 22 CONTROL ROOM CHILLER WATER PP P162 0

2 0

0 0

16 16 0

0 0

0 23 AUX PNL & COMP RM FAN COIL UNIT V114 0

2 0

0 0

24 24 0

0 0

0 24 AUX PNL & COMP RM RETURN AIR UNIT V120 0

2 0

0 0

16 16 0

0 0

0 25 CONTROL ROOM AIR COND UNIT V116 0

2 0

0 0

32 32 0

0 0

0 26 CONTROL ROOM RETURN AIR FAN V121 0

2 0

0 0

12 12 0

0 0

0 27 EMER SWGR & BTRY RM AIR COND UNIT V118 0

2 0

0 0

9 9

0 0

0 0

28 AUX EQUIP & COMP RM AREA HTR

  • ++

E193 0

2 0

0 0

52 52 0

0 0

0 29 CONTROL ROOM AREA HEATER

  • ++

E192 0

2 0

0 0

40 40 0

0 0

0 30 CONT RM FRESH AIR INTAKE HTR E191 0

2 0

0 0

32 32 0

0 0

0 31 SPRAY POND STATION HTG COIL FAN V543 0

4 0

7 7

0 0

0 0

7 7

32 SLCS HEATERS

++

S213 1 & 1 0

1 & 1 0

0 8

8 0

0 8

8 33 CONTAINMENT H2 RECOMBINER S403 2

0 2

0 0

48 48 0

0 48 48 34 CONT'L RM EMER FRESH AIR SPLY FAN V127 0

2 0

0 0

6 6

0 0

0 0

35 CONTROL ROOM CHILLER OIL PUMP P168 0

2 0

0 0

1 1

0 0

0 0

36 DG AUXILIARIES o

G501 4

0 4

14 14 14 14 14 14 14 14 37 DELETED

LGS UFSAR CHAPTER 08 8.3-60 REV. 15, SEPTEMBER 2010 (PAGE 5 OF 6)

TABLE 8.3 - 3 (Contd)

ASSIGNMENT OF SAFEGUARD AND SELECTED NON-SAFEGUARD LOADS TO DIESEL GENERATORS AND EMERGENCY BUSES ASSIGNMENT OF LOADS TO DIESEL GENERATORS AND EMERGENCY BUSES (IN kw)

UNIT 1 UNIT 2 NUMBER OF OPERATING UNITS (UNIT 1 and UNIT 2 IN OPERATION)

(UNIT 1 and UNIT 2 IN OPERATION)

D/G D/G D/G D/G D/G D/G D/G D/G EQUIP BUS BUS BUS BUS BUS BUS BUS BUS ITEM LOAD DESCRIPTION COMMENTS NO.

UNIT 1 COMMON UNIT 2 D11 D12 D13 D14 D21 D22 D23 D24 37 DELETED 38 DELETED 39 CRD PUMP o

P158 2

0 2

0 0

133 133 0

0 133 133 40 DELETED 41 RECW PUMP

++

P210 2

0 2

0 0

68 68 0

0 68 68 42 TECW PUMP o

P103 2

0 2

11 11 0

0 12 11 0

0 43 INSTRUMENT AC POWER SUPPLY o

Y105 4

0 4

5 10 24 14 24 24 24 24 43 INSTRUMENT AC POWER SUPPLY o

Y106 0

0 0

0 0

0 0

0 0

0 0

43 INSTRUMENT AC POWER SUPPLY o

Y201 0

0 0

0 0

0 0

0 0

0 0

43 INSTRUMENT AC POWER SUPPLY o

Y202 0

0 0

0 0

0 0

0 0

0 0

44 EMERGENCY LIGHTING o !

MISC 7

6 7

11 70 109 99 0

59 80 68 45 TURBINE GEN BEARING LIFT PUMP o

P109 9

0 9

45 0

0 0

36 0

0 0

46 TURBINE GEN TURNING OIL PP o

P111 1

0 1

32 0

0 0

32 0

0 0

47 TURBINE GEN TURNING GEAR o

S103 1

0 1

48 0

0 0

24 0

0 0

48 RFPT GEAR o

S106 3

0 3

2 1

0 0

2 1

0 0

49 INSTRUMENT GAS COMPRESSOR o (12)

K203 2

0 2

1 1

0 0

1 1

0 0

50 INSTRUMENT AIR COMPRESSOR o

K101 2

0 2

0 0

33 33 0

0 33 33 51 DELETED 52 OSC XFMR PNLS OOL140 & OOL141 X186 0

1 0

0 24 0

0 0

0 0

0 53 TEST ENGINEER'S WORKSHOP X187 0

1 0

0 12 0

0 0

0 0

0 54 NORTH STACK RM ANTENNA SYS XFMR X595 0

1 0

0 9

0 0

0 0

0 0

55 DELETED 56 CRD REPAIR RM COOLING FAN V904 0

1 1

0 0

0 0

0 0

0 0

57 125V BATTERY CHARGER o

D113 2

0 2

0 0

0 96 0

0 0

96 58 FIRE ALARM & P/A

  • +

1X5 0

0 0

0 0

0 12 0

0 0

0 59 FUEL POOL COOLING WATER PUMP o

P211 3

0 3

32 32 0

32 32 32 0

32 60 FUEL POOL SVC WTR BSTR PUMP (7)

P212 3

0 3

19 0

0 0

19 0

0 0

61 INSTR. AC PWR SUPPLY (SPRAY POND) o Y501 0

4 0

1 1

0 0

0 0

8 8

62 SPRAY POND PP STATION HTG COIL

++

  • E701 0

4 0

96 96 0

0 0

0 96 96 63 SGTS RM VENT EXHAUST FAN o *(13)

V131 0

2 0

7 7

0 0

0 0

0 0

64 SECURITY AREAS AIR COND. (11) o

  • V565 0

2 0

0 0

14 0

0 0

0 0

65 PIPING FILL PUMP P256 2

0 2

3 3

0 0

3 3

0 0

66 DRYWELL H2O2 ANALYZER S205 1

0 1

0 0

0 1

0 0

0 1

67 SUPPRESSION POOL H2O2 ANALYZER S206 1

0 1

0 0

1 0

0 0

1 0

68 CHILLER PUMP-OUT COMPRESSOR o

  • K114 0

2 0

0 0

2 2

0 0

0 0

69 SPRAY POND SUMP PUMP o

  • P578 0

4 0

2 2

0 0

0 0

2 2

70 AUX EG. RM & COMP RM ELEC HUMIDFR o

  • E743 0

2 0

43 43 0

0 0

0 0

0 71 CONT RM ELEC HUMIDIFIER o

  • E744 0

2 0

29 29 0

0 0

0 0

0 72 250V BATTERY CHARGER o

D123 1

0 1

0 9

0 0

0 9

0 0

73 ALT. POWER SUPPLY TO 10X161 XFMR o

10X161 1

0 0

30 0

0 0

0 0

0 0

74 STATIC INVERTER 00-D592 XFMR o

  • 00-X592 0

1 0

0 0

0 0

30 0

0 0

75 TELEPHONE EQUIP POWER XFMR o

  • X503 0

1 0

6 0

0 0

0 0

0 0

76 RECOMBINER HYDROGEN ANALYZER o

P947 3

0 3

1 2

0 0

1 2

0 0

LGS UFSAR CHAPTER 08 8.3-61 REV. 15, SEPTEMBER 2010 TABLE 8.3 - 3 (Contd)

(PAGE 6 OF 6)

ASSIGNMENT OF SAFEGUARD AND SELECTED NON-SAFEGUARD LOADS TO DIESEL GENERATORS AND EMERGENCY BUSES ASSIGNMENT OF LOADS TO DIESEL GENERATORS AND EMERGENCY BUSES (IN kw)

UNIT 1 UNIT 2 NUMBER OF OPERATING UNITS (UNIT 1 and UNIT 2 IN OPERATION)

(UNIT 1 and UNIT 2 IN OPERATION)

D/G D/G D/G D/G D/G D/G D/G D/G EQUIP BUS BUS BUS BUS BUS BUS BUS BUS ITEM LOAD DESCRIPTION COMMENTS NO.

UNIT 1 COMMON UNIT 2 D11 D12 D13 D14 D21 D22 D23 D24 77 DIESEL GENERATOR BRIDGE CRANE o

H501 4

0 4

18 18 18 18 18 18 18 18 78 440V POWER RECEPTACLES o

W508 4

0 4

48 48 48 48 48 48 48 48 79 SPRAY POND PUMP HOIST o

  • H511 0

2 0

0.5 0

0 0

0 0

0 0.5 79 SPRAY POND PUMP HOIST o

  • H513 0

0 0

0 0

0 0

0 0

0 0

80 TURB BLDG EQUIP CMPT EXHAUST FAN

++

V106 2

0 2

197 198 0

0 198 198 0

0 81 DRYWELL CHILLER COMPRESSOR

++

K111 2

0 2

0 0

1379 1379 0

0 1379 1379 82 ROD DRIVE CONTROL CABINET XFMR o

X516 1

0 1

0 8

0 0

0 8

0 0

83 SLCS PUMP P208 3

0 3

32 32 32 0

32 32 32 0

84 RWCU SYSTEM RECIRC PUMP (7)

P221 3

0 3

0 0

92 0

0 0

92 0

85 440V POWER RECEPTACLES o

W201 4,1 & 3 0

4,1 & 3 0

0 0

144 0

0 0

144 85 440V POWER RECEPTACLES o

W202 0

0 0

0 0

0 0

0 0

0 0

85 440V POWER RECEPTACLES o

W205 0

0 0

0 0

0 0

0 0

0 0

86 440V POWER RECEPTACLE/SP RECIRC o

  • W601 0

1 0

0 0

0 0

0 0

0 48 87 440V POWER RECEPTACLE o

W206 2

0 2

0 48 0

0 0

48 0

0 88 ANNUNCIATOR 4

0 4

1 1

1 1

1 1

1 1

89 TURB GEN TURN GEAR PIGGYBACK S195 0

0 1

0 0

0 0

2 0

0 0

90 RHRSW CORROSION MONITORING

+++

Y215 1

0 0

0 77 0

0 0

0 0

0 91 ADMIN BLDG 480V DISTR PNL o+

00B500 0

1 0

0 0

36 0

0 0

0 0

LEGEND:

  • - COMMON EQUIPMENT o - NON SAFEGUARD LOADS THAT ARE TRIPPED BY LOCA SIGNAL AND MANUALLY RESTARTED AFTER 10 MINUTES OR MORE, IF NEEDED.

+ - NON SAFEGUARD LOAD NOT TRIPPED BY A LOAD SIGNAL.

++ - NON SAFEGUARD LOADS TREATED AS SAFEGUARD LOAD BUT TRIPPED BY A LOCA SIGNAL AND CAN BE MANUALLY RESTARTED AFTER 10 MINUTES OR MORE, IF

+++ - NON SAFEGUARD LOAD TRIPPED BY A LOCA OR LOOP SIGNAL AND SHALL NOT BE RESTARTED UNTIL NORMAL PLANT OPERATION IS RESTORED.

LOAD KEPT IN THE INACTIVE STATUS BY PLACING THE MCC BREAKER IN THE OPEN POSITION.

! - EMERGENCY LIGHTING NUMBERS ARE AS FOLLOWS: 1L87*, L10, 1L55*, 1L85*, X26, L16, L17, L130, 1X17*, 1X64, L6, 1L9*, L86 (1) - MOV LOADS ARE NOT INCLUDED IN THIS TABLE AND THE DIESEL GENERATOR LOADING TABLES THAT FOLLOW BECAUSE OF THEIR SMALL MAGNITUDE AND SHORT DURATION (2) - ASSIGNMENT OF THE LOADING ON THE DIESEL GENERATORS IS SUCH THAT THE SITUATION OF A DBA ON ONE UNIT AND SPURIOUS LOCA ON THE OTHER UNIT DOES NOT PRECLUDE SAFE SHUTDOWN OF THE UNITS. A SPURIOUS LOCA IS DEFINED AS A LOCA FOR 0-10 MINUTES AND EMERGENCY SHUTDOWN FOR BEYOND 10 MINUTES.

(7) - ALTHOUGH 3 PUMPS ARE INSTALLED, ONLY ONE IS POWERED FROM THE CLASS 1E SYSTEM.

(9) - MOD P00674 REPLACED THE 2A-P202 PUMP MOTOR. THE MOTOR IS MORE EFFICIENT AND THE LOAD ASSIGNMENT FOR THE D/G AND BUS 21 IS REDUCED BY 16 kW.

(10) - DELETED.

(11) - ALTHOUGH 2 AIR CONDITIONERS ARE INSTALLED, ONLY ONE IS POWERED FROM THE CLASS 1E SYSTEM.

(12)ECR 04-00319 REPLACED THE MOTOR FOR 1A-K203. LOAD IS NOW 2 KW.

(13)ECR 04-00569 REPLACED THE MOTOR FOR 0A-V131. LOAD IS NOW 7 KW.

LGS UFSAR CHAPTER 08 8.3-62 REV. 14, SEPTEMBER 2008 Tables 8.3-4 through 8.3-8 Tables 8.3-4 through 8.3-8 (Deleted)

LGS UFSAR CHAPTER 08 8.3-63 REV. 15, SEPTEMBER 2010 Table 8.3-9

LGS UFSAR CHAPTER 08 8.3-64 REV. 15, SEPTEMBER 2010 Table 8.3-9 (continued)

LGS UFSAR CHAPTER 08 8.3-65 REV. 15, SEPTEMBER 2010 Table 8.3-9 (continued)

LGS UFSAR CHAPTER 08 8.3-66 REV. 15, SEPTEMBER 2010 Table 8.3-10

LGS UFSAR CHAPTER 08 8.3-67 REV. 15, SEPTEMBER 2010 Table 8.3-10 (continued)

LGS UFSAR CHAPTER 08 8.3-68 REV. 15, SEPTEMBER 2010 Table 8.3-10 (continued)

LGS UFSAR CHAPTER 08 8.3-69 REV. 15, SEPTEMBER 2010 Table 8.3-11

LGS UFSAR CHAPTER 08 8.3-70 REV. 15, SEPTEMBER 2010 Table 8.3-11 (continued)

LGS UFSAR CHAPTER 08 8.3-71 REV. 15, SEPTEMBER 2010 Table 8.3-11 (continued)

LGS UFSAR CHAPTER 08 8.3-72 REV. 15, SEPTEMBER 2010 Table 8.3-12

LGS UFSAR CHAPTER 08 8.3-73 REV. 15, SEPTEMBER 2010 Table 8.3-12 (continued)

LGS UFSAR CHAPTER 08 8.3-74 REV. 15, SEPTEMBER 2010 Table 8.3-12 (continued)

LGS UFSAR CHAPTER 08 8.3-75 REV. 15, SEPTEMBER 2010 Table 8.3-13

LGS UFSAR CHAPTER 08 8.3-76 REV. 15, SEPTEMBER 2010 Table 8.3-13 (continued)

LGS UFSAR CHAPTER 08 8.3-77 REV. 15, SEPTEMBER 2010 Table 8.3-13 (continued)

LGS UFSAR CHAPTER 08 8.3-78 REV. 15, SEPTEMBER 2010 Table 8.3-14

LGS UFSAR CHAPTER 08 8.3-79 REV. 15, SEPTEMBER 2010 Table 8.3-14 (continued)

LGS UFSAR CHAPTER 08 8.3-80 REV. 15, SEPTEMBER 2010 Table 8.3-14 (continued)

LGS UFSAR CHAPTER 08 8.3-81 REV. 15, SEPTEMBER 2010 Table 8.3-15

LGS UFSAR CHAPTER 08 8.3-82 REV. 15, SEPTEMBER 2010 Table 8.3-15 (continued)

LGS UFSAR CHAPTER 08 8.3-83 REV. 15, SEPTEMBER 2010 Table 8.3-15 (continued)

LGS UFSAR CHAPTER 08 8.3-84 REV. 15, SEPTEMBER 2010 Table 8.3-16

LGS UFSAR CHAPTER 08 8.3-85 REV. 15, SEPTEMBER 2010 Table 8.3-16 (continued)

LGS UFSAR CHAPTER 08 8.3-86 REV. 15, SEPTEMBER 2010 Table 8.3-16 (continued)

LGS UFSAR CHAPTER 08 8.3-87 REV. 15, SEPTEMBER 2010 Table 8.3-17

LGS UFSAR CHAPTER 08 8.3-88 REV. 15, SEPTEMBER 2010 Table 8.3-17 (continued)

LGS UFSAR CHAPTER 08 8.3-89 REV. 15, SEPTEMBER 2010 Table 8.3-17 (continued)

LGS UFSAR CHAPTER 08 8.3-90 REV. 16, SEPTEMBER 2012 Table 8.3-18 Table 8.3-18 (Deleted)

LGS UFSAR CHAPTER 08 8.3-91 REV. 16, SEPTEMBER 2012 Table 8.3-18A Table 8.3-18A (Deleted)

LGS UFSAR CHAPTER 08 8.3-92 REV. 16, SEPTEMBER 2012 Table 8.3-19 Table 8.3-19 (Deleted)

LGS UFSAR CHAPTER 08 8.3-93 REV. 16, SEPTEMBER 2012 Table 8.3-20 Table 8.3-20 (Deleted)

LGS UFSAR CHAPTER 08 8.3-94 REV. 16, SEPTEMBER 2012 Table 8.3-21 Table 8.3-21 (Deleted)

LGS UFSAR CHAPTER 08 8.3-95 REV. 16, SEPTEMBER 2012 Table 8.3-22 Table 8.3-22 (Deleted)

LGS UFSAR CHAPTER 08 8.3-96 REV. 16, SEPTEMBER 2012 Table 8.3-23 Table 8.3-23 (Deleted)

LGS UFSAR CHAPTER 08 8.3-97 REV. 16, SEPTEMBER 2012 Table 8.3-24 Table 8.3-24 (Deleted)

LGS UFSAR CHAPTER 08 8.3-98 REV. 16, SEPTEMBER 2012 Table 8.3-25 Table 8.3-25 (Deleted)

LGS UFSAR CHAPTER 08 8.3-99 REV. 16, SEPTEMBER 2012 Table 8.3-26 Table 8.3-26 (Deleted)

LGS UFSAR CHAPTER 08 8.3-100 REV. 13, SEPTEMBER 2006 Table 8.3-27 INSTRUMENT AND CONTROL SYSTEMS POWER SUPPLY PANELS Panel Voltage Division Y101 120 V ac I

Y102 II Y103 III Y104 IV Y105 NS Y106 NS Y201 NS Y202 NS Y109 NS Y110 NS AY160 NS BY160 NS AD102 125 V dc I

BD102 II CD102 III DD102 IV AD108 NS BD108 NS AY185 120 V ac NS BY185 NS 00Y591 NS 00Y592 NS Y163 III Y164 IV NS = Nonsafeguard

LGS UFSAR CHAPTER 08 8.3-101 REV. 16, SEPTEMBER 2012 Table 8.3-28 UNDERVOLTAGE ALARMS SECTION I Number Annunciator Status Lights 1

Division I RHR Out-of-Service RHR Pump Breaker Control Panel AC801, #21 Power Undervoltage RHR Unit Coolers Out-of-Service RHRSW Pump Breaker Control Power Undervoltage Spray Pond MOV Overload/Loss of Power Spray Pond HVAC Out-of-Service RHR Relays Logic Power Failure RHR MOVs Overload/Loss of Power RHR Trip Units Out-of-File/ Loss of Power 2

Division II RHR Out-of-Service Same as #1 Panel CC801, #21 3

Division III RHR Out-of-Service Same as #1 Panel AC801, #36 4

Division IV RHR Out-of-Service Same as #1 Panel CC801, #36 5

Division I Core Spray Out-Core Spray Pump Breaker of-Service Control Power Undervoltage Panel AC801, #1 Core Spray Unit Coolers Out-of-Service Core Spray MOVs Overload/Loss of Power Core Spray Logic Power Failure Core Spray Trip Unit Out-of-File/Power Failure 6

Division II Core Spray Out-Same as #5 of-Service Panel CC801, #1 7

Division III Core Spray Out-Same as #5 of-Service Panel AC801, #11

LGS UFSAR CHAPTER 08 8.3-102 REV. 16, SEPTEMBER 2012 Table 8.3-28 (Cont'd)

Number Annunciator Status Lights 8

Division IV Core Spray Out-Same as #5 of-Service Panel CC801, #11 9

RCIC Out-of-Service RCIC Logic Power Failure Panel C848, #1 RCIC Trip Unit Out of File/Power Failure RCIC Area Temperature Logic Power Failure RCIC Inverter Failure RCIC MOVs Overload/Loss of Power RCIC Unit Coolers Out-of-Service 10 HPCI Out-of-Service HPCI Auxiliary Oil Pump Panel C847, #1 Overload/Loss of Power HPCI Inverter Failure HPCI MOV Overload/Loss of Power HPCI Logic Power Failure HPCI Area Temperaure Logic Power Failure HPCI Trip Unit Out-of-File/

Power Failure HPCI Unit Coolers Out-of-Service 11 Division I ESW Out-of-ESW MOVs Overload/Loss of Service Power Panel AC 867, #1 Spray Pond MOVs Overload Loss of Power Spray Pond HVAC Out-of-Service EWS Pump Breaker Control Power Undervoltage 12 Division II ESW Out-of-Same as #11 Service Panel BC867, #16 13 Division III ESW Out-of-Same as #11 Service Panel AC867, #6 14 Division IV ESW Out-of-Same as #11 Service Panel BC867, #21 15 Division I Standby ac Power DG Cooling Water MOVs System Out-of-Service Overload/Loss of Power Panel AC861, #17 201-DXX Bus Breaker Control Power Undervoltage

LGS UFSAR CHAPTER 08 8.3-103 REV. 16, SEPTEMBER 2012 Table 8.3-28 (Cont'd)

Number Annunciator Status Lights 101-DXX Bus Breaker Control Power Undervoltage Safeguard LC Xmfr. Breaker Control Power Undervoltage CRD Water Pump Breaker Control Power Undervoltage Turbine Enclosure Exhaust Fan Breaker Control Power Undervoltage Drywell Chiller Breaker Control Power Undervoltage DG Not Ready for Autostart 16 Division II Standby ac Same as #15 Power System Out-of-Service Panel BC861, #17 17 Division III Standby ac Same as #15 Power System Out-of-Service Panel CC861, #17 18 Division IV Standby ac Same as #15 Power System Out-of-Service Panel AC802, #17 19 Reactor Isolation System NSSSS Trip Unit Out-of-File/

Outboard Out-of-Service Power Failure Panel AC802, #25 NSSSS MOV Overload/Loss of Power 20 Reactor Isolation System Same as #19 Inboard Out-of-Service Panel AC802, #20 21 Division I ADS Out-of-Relay Logic Power Failure Service Trip Unit Out-of-File/Power Panel C826, #1 Failure 21A Division III ADS Out-of-Same as #21 Service Panel C826, #11 22 RPS System A Trip Unit Out-of-File/

Out-of-Service Power Failure Panel BC803, #5 22A RPS System B Out-of-Same as #22 Service Panel BC803, #10

LGS UFSAR CHAPTER 08 8.3-104 REV. 16, SEPTEMBER 2012 Table 8.3-28 (Cont'd)

SECTION II Number Bus Voltage Alarm Panel/Window 23 10A101 13.2 kV 11 Unit Auxiliary Bus UV 1BC854/6 24 10A102 13.2 kV 12 Unit Auxiliary Bus UV 1BC854/9 25 20A101 13.2 kV 21 Unit Auxiliary Bus UV 2BC854/26 26 20A102 13.2 kV 22 Unit Auxiliary Bus UV 2BC854/29 27 10 13.2 kV 10 Startup Bus UV 00C860/4 28 20 13.2 kV 20 Startup Bus UV 00C860/24 29 101 4.16 kV 101 Safeguard Bus UV 1AC861/28 30 201 4.16 kV 201 Safeguard Bus UV 1AC861/29 31 D11 4.16 kV D11 Safeguard Bus UV 1AC861/6 32 D12 4.16 kV D12 Safeguard Bus UV 1BC861/6 33 D13 4.16 kV D13 Safeguard Bus UV 1CC861/6 34 D14 4.16 kV D14 Safeguard Bus UV 1DC861/6 35 D21 4.16 kV D21 Safeguard Bus UV 2AC861/6 36 D22 4.16 kV D22 Safeguard Bus UV 2BC861/6 37 D23 4.16 kV D23 Safeguard Bus UV 2CC861/6 38 D24 4.16 kV D24 Safeguard Bus UV 2DC861/6 39 AD102 125 V dc PPA1/A3 125 V dc AC861/33 Distribution Panel UV 40 BD501 125 V dc PPA2 125 V dc AC861/34 Distribution Panel UV 41 BD102 125 V dc PPB1/B3 125 V dc BC861/34 Distribution Panel UV 42 BD501 125 V dc PPB2 125 V dc BC861/35 Distribution Panel UV 43 CD102 125 V dc PPC1/C3 125 V dc CC861/32 Distribution Panel UV 44 CD501 125 V dc PPC2 125 V dc CC861/33 Distribution Panel UV

LGS UFSAR CHAPTER 08 8.3-105 REV. 16, SEPTEMBER 2012 Table 8.3-28 (Cont'd)

Number Bus Voltage Alarm Panel/Window 45 DD102 125 V dc PPD1/D3 125 V dc DC861/32 Distribution Panel UV 46 DD501 125 V dc PPD2 125 V dc DC861/33 Distribution Panel UV 47 AD108 125 V dc PP01 125 V dc 1AC854/3 Distribution Panel UV 2BC854/18 48 BD108 125 V dc PP02 125 V dc 1AC854/4 Distribution Panel UV 2BC854/19 49 CD108 125 V dc PP03 125 V dc 1AC854/5 Distribution Panel UV 2BC854/20 50 DD108 125 V dc PP04 125 V dc 1AC854/8 Distribution Panel UV 2BC854/25 SECTION III Number Alarm Panel/Window 51 A RFPT Control Volt Failure BC868/5 52 B RFPT Control Volt Failure BC868/10 53 C RFPT Control Volt Failure BC868/15 54 A RPS/UPS Static Inverter Trouble AC861/5 55 B RPS/UPS Static Inverter Trouble BC861/5 56 RFPT Control Signal Failure AC803/20 57 IRM Downscale AC803/33 58 SRM Downscale AC803/34 59 IRM Upscale/Inop AC803/38 60 SRM Upscale/Inop AC803/39 61 OPRM/APRM Trouble BC803/5 62 Not Used BC803/9 63 Not Used BC803/13 64 RBM Downscale/Trouble BC803/19 65 Not Used BC803/14

LGS UFSAR CHAPTER 08 8.3-106 REV. 16, SEPTEMBER 2012 Table 8.3-28 (Cont'd)

Number Alarm Panel/Window 66 RPIS Inop BC803/25 67 SLCS Squib Valve Loss of BC803/44 Continuity 68 Division 1 Core Spray Trip Unit AC801/5 Inverter Power Failure 69 Division 2 Core Spray Trip Unit CC801/5 Inverter Power Failure 70 Division 3 Core Spray Trip Unit AC801/15 Inverter Power Failure 71 Division 4 Core Spray Trip Unit CC801/15 Inverter Power Failure 72 DELETED 73 DELETED 74 Main Steam Line (A/B) Radiation C800/26 Monitor Downscale 75 Main Steam Line (C/D) Radiation C800/27 Monitor Downscale 76 North Stack Radiation Monitor 00C824/23 Downscale 77 South Stack Radiation Monitor 00C824/28 Downscale 78 A RPS/UPS Distribution Panel AC861/30 Trouble 79 B RPS/UPS Distribution Panel BC861/29 Trouble 80 TSC/Computer Trouble 00C855/4 81 A Drywell Chiller Loss of C881/11 Control Power 82 B Drywell Chiller Loss of C881/16 Control Power 83 SPTMS Trouble Division I AC803/23

LGS UFSAR CHAPTER 08 8.3-107 REV. 16, SEPTEMBER 2012 Table 8.3-28 (Cont'd)

Number Alarm Panel/Window 84 SPTMS Trouble Division II AC803/24 85 RDCS Inop BC803/24 86 INTENTIONALLY LEFT BLANK 87 CRD Trip Unit Out-of-Service BC803/40 88 CRD Accumulator Trouble BC803/26 89 A Recirculation MG Controller AC802/27 Signal Failure (Unit 2 only) 89A A Recirculation ASD Major Failure AC902/07 (Unit 1 only) 90 B Recirculation MG Controller BC802/27 Signal Failure (Unit 2 only) 90A B Recirculation ASD Major Failure AC902/07 (Unit 1 only) 91 1 RFPT Loss of Power AC868/33 92 2 RFPT Loss of Power AC868/38 93 3 RFPT Loss of Power AC868/43 94 Turbine Enclosure HVAC Panel C881/36 C126 Trouble 95 Suppression Atmospheric C800/28 Analyzer Trouble 96 Drywell Atmospheric C800/4 Analyzer Trouble 97 PMS-1 Failover CC861/10

LGS UFSAR CHAPTER 08 8.3-108 REV. 17, SEPTEMBER 2014 Table 8.3-29 PANEL ALARMS WITH LOSS OF POWER AS POSSIBLE INDIRECT CAUSE Panel Indication Alarm No. / Name Y101 Indirect 1

Div. I RHR Out of Service (1) 5 Div. I CS Out of Service (1) 9 RCIC Out of Service (1) 67 Standby Liquid Squib Valve Loss of Continuity 83 Div. I SPOTMOS Trouble 94 Turbine Enclosure HVAC Panel C126 Trouble Y102 Indirect 2

Div. II RHR Out of Service (1) 6 Div. II CS Out of Service (1) 10 HPCI Out of Service (1) 67 Standby Liquid Squib Valve Loss of Continuity 84 Div. II SPOTMOS Trouble 94 Turbine Enclosure HVAC Panel C126 Trouble Y103 Indirect 3

Div. III RHR Out of Service (1) 7 Div. III CS Out of Service (1) 67 Standby Liquid Squib Valve Loss of Continuity Y104 Indirect 4

Div. IV RHR Out of Service (1) 8 Div. IV CS Out of Service (1)

Y105 Indirect 94 Turbine Enclosure HVAC Panel C126 Trouble Y106 Indirect 87 CRD Trip Unit Out of Service 88 CRD Accumulator Trouble Y201 Indirect 56 RFPT Control Signal Failure 66 RPIS INOP 76 North Stack Radiation Monitor Downscale 77 South Stack Radiation Monitor Downscale 81 A DW Chiller Loss of Control Power 93 C RFPT Loss of Power Y202 Indirect 76 North Stack Radiation Monitor Downscale 77 South Stack Radiation Monitor Downscale 82 B DW Chiller Loss of Control Power AY160 Direct 19 Reactor Isolation System Outboard Out of Service 20 Reactor Isolation System Inboard Out of Service 22 RPS System A Out of Service 54 A RPS / UPS Static Invertor Trouble 57 IRM Downscale 58 SRM Downscale 59 IRM Upscale / Inop 60 SRM Upscale / Inop 78 A RPS / UPS Distribution Panel Trouble

LGS UFSAR CHAPTER 08 8.3-109 REV. 17, SEPTEMBER 2014 Table 8.3-29 (Contd)

Panel Indication Alarm No. / Name BY160 Direct 19 Reactor Isolation System Outboard Out of Service 20 Reactor Isolation System Inboard Out of Service 22A RPS System B Out of Service 55 B RPS / UPS Static Inverter Trouble 57 IRM Downscale 58 SRM Downscale 59 IRM Upscale / Inop 60 SRM Upscale / Inop 79 B RPS / UPS Distribution Panel Trouble Y109 Indirect 56 RFPT Control Signal Failure 91 A RFPT Loss of Power Y110 Indirect 56 RFPT Control Signal Failure 92 B RFPT Loss of Power AD102 Direct 1

Div. I RHR Out of Service 5

Div. I CS Out of Service 9

RCIC Out of Service 11 Div. I ESW Out of Service 15 Div. I Standby ac Power System Out of Service 21 Div. I ADS Out of Service 39 PPA1/A3 125V dc Distribution Panel UV BD102 Direct 2

Div. II RHR Out of Service 6

Div. II CS Out of Service 10 HPCI Out of Service 12 Div. II ESW Out of Service 16 Div. II Standby ac Power System Out of Service 41 PPB1/B3 125V dc Distribution Panel UV CD102 Direct 3

Div. III RHR Out of Service 7

Div. III CS Out of Service 9

RCIC Out of Service 13 Div. III ESW Out of Service 17 Div. III Standby ac Power System Out of Service 21A Div. III ADS Out of Service 43 PPC1/C3 125V dc Distribution Panel UV 81 A DW Chiller Loss of Control Power

LGS UFSAR CHAPTER 08 8.3-110 REV. 17, SEPTEMBER 2014 Table 8.3-29 (Contd)

Panel Indication Alarm No. / Name DD102 Direct 4

Div. IV RHR Out of Service 8

Div. IV CS Out of Service 10 HPCI Out of Service 14 Div. IV ESW Out of Service 18 Div. IV Standby ac Power System Out of Service 45 PPD1/D3 125V dc Distribution Panel UV 82 B DW Chiller Loss of Control Power AD108 Direct 47 PP01 125V dc Distribution Panel UV 51 A RFPT Control Voltage Failure BD108 Direct 48 PP02 125V dc Distribution Panel UV 52 B RFPT Control Voltage Failure AY185 Indirect 61 APRM Upscale Trip / Inop 64 RBM Downscale BY185 Indirect 61 APRM Upscale Trip / Inop 64 RBM Downscale 00Y591 Indirect 80 TSC / Computer Trouble 00Y592 Indirect 80 TSC / Computer Trouble Y163 Indirect 95 SP Atmospheric Analyzer Trouble Y164 Indirect 96 DW Atmospheric Analyzer Trouble Note:

(1)

Panel provides backup feed to system trip units; this alarm will sound only upon concurrent loss of the normal dc supply.

LGS UFSAR CHAPTER 08 8.3-111 REV. 13, SEPTEMBER 2006 Table 8.3-30 INSTRUMENTS USED TO ACHIEVE COLD SHUTDOWN Parameter Instrument #

Bus Evaluation Reactor Level LR42-1R608 Y109,Y110 A

LI42-1R605 Y201 A

LI42-1R606A Y109 A

LI42-1R606B Y110 A

LI42-1R606C BD108 A

LI42-1R604 AY160 A

LI42-1R610 Y101,AD102 A

LR42-1R615 Y102,BD102 A

XR42-1R623A Y101,AD102 A

XR42-1R623B Y102,BD102 A

Reactor Pressure XR42-1R623A Y101,AD102 A

XR42-1R623B Y102,BD102 A

XR01-1R609 Y105,Y110 A

PI42-1R605 Y109 A

Vessel Temperature TR42-1R006 Y202 B

TR42-1R007 Y202 B

NMS APRM 1 AY185, BY185 O

APRM 2 AY185, BY185 O

APRM 3 AY185, BY185 O

APRM 4 AY185, BY185 O

RBM A AY185, BY185 O

RBM B AY185, BY185 O

SRM A, C AY160 A

SRM B, D BY160 A

IRM A, C, E, G AY160 A

IRM B, D, F, H BY160 A

SRM Recorder 602A BY160 A

SRM Recorder 602B BY160 A

IRM/APRM Recorder BY160 A

603A IRM/APRM Recorder BY160 A

603B IRM/APRM/RBM BY160 A

Recorder 603C IRM/APRM/RBM BY160 A

Recorder 603D RPIS BY185,Y106,Y201, C

MCC B130 Condenser Vacuum PR05-101 Y106 D

PI05-101A Y106 D

PI05-101B Y106 D

PI05-101C Y106 D

LGS UFSAR CHAPTER 08 8.3-112 REV. 13, SEPTEMBER 2006 Table 8.3-30 (Cont'd)

Parameter Instrument #

Bus Evaluation CST level LR08-102,202 Y106,Y105 F

LI55-112,212 Y106 F

LAHL08-112,212 AD108 F

Standby Liquid LI48-1R601 Y202 E

Control Tank Level Pump Discharge PI48-IN600A Y101,AD102 E

Pressure PI48-IN600B Y102,BD102 E

PI48-IN600C Y103,CD102 E

Suppression Pool TRS-041-101 Y101 A

Temperature TRS-041-103 Y102 A

Suppression Pool LI52-140A Y101,AD102 A

Level LI52-140B Y102 A

LR55-115 Y105,Y106 A

LI55-115-1 Y105,Y106 A

Suppression Pool PR57-101 Y101,AD102 A

Pressure PR42-101 Y102,BD102 A

Drywell Pressure PR57-101 Y101,AD102 A

PI42-170-1 Y102,BD102 A

PI42-101 Y101,AD102 A

PI42-170 Y102,BD102 A

Drywell Temperature TI77-101A-H Y202 A,D TR57-110 Y105 A,D TR57-122 Y101 A,D Turbine 1st Stage PI01-112 Y106,Y105 B

Pressure CRD System Flow FI46-R606 Y106 B

HPCI Instrumentation BD102 G

HPCI Turbine-Pump XR - 036-101 Y201 D

Temperature XR - 036-102 Y106 D

HPCI Turbine VR56-162 Y102 D

Vibration RCIC Instrumentation AD102 H

Core Spray Instrumentation A Loop Flow FI52-1R601A Y101,AD102 K

B Loop Flow FI52-1R601B Y102,BD102 K

A Loop Disch Pressure PI52-1R600A Y101 L

B Loop Disch Pressure PI52-1R600B Y102,BD102 L

LGS UFSAR CHAPTER 08 8.3-113 REV. 13, SEPTEMBER 2006 Table 8.3-30 (Cont'd)

Parameter Instrument #

Bus Evaluation RHR Instrumentation A Loop Flow FI51-1R603A Y101,AD102 M

B Loop Flow FI51-1R603B Y102,BD102 M

C Loop Flow FI51-1R603C Y103 M

D Loop Flow FI51-1R603D Y104 M

RHR HX A Discharge PI51-105A Y101 M

Pressure RHR HX B Discharge PI51-105B Y102 M

Pressure Deleted Deleted Deleted Deleted Deleted Deleted RHR Service Water A RHR HX Service Water FI51-1R602A Y101,AD102 M

Flow B RHR HX Service Water FI51-1R602B Y102,BD102 M

Flow RHR SW Loop A Discharge PI12-001A Y101 N

Pressure RHR SW Loop B Discharge PI12-001B Y102 N

Pressure RHR SW A HX Outlet Rad RR12 - OR616A Y103 N

RHR SW B HX Outlet Rad RR12 - OR616B Y104 N

RHR SW A Loop Return Rad RR12 - OR615A Y101 N

RHR SW B Loop Return Rad RR12 - OR615B Y102 N

Emergency Service Water ESW A Flow FI11-013A Y101 N

ESW B Flow FI11-013B Y102 N

ESW A Supply Pressure PI11-003A Y101 N

ESW B Supply Pressure PI11-003B Y102 N

ADS Relief Valve Position ZYI41-115EF AY185 A

Indication SRV Outlet Temperature XR-036-101 Y201 B

XR-036-102 Y106 B

Containment Instrument Gas A Instrument Gas PI59-103A Y103,CD102 B

Pressure B Instrument Gas PI59-103B Y104,DD102 B

Pressure

LGS UFSAR CHAPTER 08 8.3-114 REV. 13, SEPTEMBER 2006 Table 8.3-30 (Cont'd)

Parameter Instrument #

Bus Evaluation Radiation Monitoring NSE-RMS RMMS 00Y591,00Y592 Y201,Y202 D

SSE-RMS RMMS 00Y591,00Y592 Y201,Y202 D

PCPL-RMS RR26-191A, RMMS Y103,00Y592 A

PCPL-RMS RR26-191B, RMMS Y102,00Y592 A

PCPL-RMS RR26-191C, RMMS Y103,00Y592 A

PCPL-RMS RR26-191D, RMMS Y102,00Y592 A

Containment Atmospheric Control Drywell 02 AI 57-150 Y164 B

Drywell H2 AI 57-151 Y164 B

Pool 02 AI 57-187 Y163 B

Pool H2 AI 57-188 Y163 B

EVALUATIONS A.

There is more than one instrument in the control room to monitor this parameter and these instruments are not fed from the same bus; therefore, the loss of one bus will not affect the operator's ability to determine the value of this parameter.

B.

This parameter can be determined from other parameters or local instruments if needed. Loss of this parameter would not affect the capability of achieving a cold shutdown condition.

C.

The RPIS receives data from the RMCS and is fed from non-Class 1E instrument buses. If power to these buses is lost, rod position indication will be lost in the control room. Loss of rod position indication does not prohibit a manual or automatic SCRAM; therefore, the capability to achieve a cold shutdown condition is not affected by loss of power to the RMCS or the RPIS.

D.

Loss of this parameter does not affect the ability to achieve a cold shutdown condition.

E.

The SLCS has been redesigned per ATWS requirements. The controls and instrumentation of this system have been designed to perform their function with a single failure; therefore, loss of power to a single division will not prevent the achievement of a cold shutdown condition.

LGS UFSAR CHAPTER 08 8.3-115 REV. 13, SEPTEMBER 2006 Table 8.3-30 (Cont'd)

F.

CST level indication will be lost when Y106 is lost; however, the tank HI/LOW level alarm will still be operable.

G.

If power from panel BD102 is lost, the HPCI becomes inoperative. If this occurs, the ADS will be used to depressurize the reactor vessel so that the RCIC and RHR and core spray systems can be used to achieve a cold shutdown condition. Loss of HPCI due to loss of panel BD102 will not affect the ability to achieve a cold shutdown condition.

H.

If power from panel AD102 is lost, the RCIC system becomes inoperative. If this occurs, the HPCI system can be used in its place; therefore, the loss of the RCIC system due to the loss of power from panel AD102 will not affect the ability to achieve a cold shutdown condition.

K.

Core spray system instrumentation for Loop A is fed from Division 1 Class 1E power. Loop B instrumentation is fed from Division II. Loss of panel Y101 will cause loss of Loop A flow indication in the control room. Loss of Y102 will cause loss of Loop B flow indication. Loss of either of these panels does not affect the operability of the core spray system; therefore, the ability to achieve a cold shutdown condition is not affected.

L.

Both of the supply panels must be lost in order to lose indication of this parameter.

M.

The RHR system is composed of two redundant loops, each consisting of two pumps and one RHR heat exchanger. The pressure controllers, flow indicators, and pressure indicators for the A loop are fed from separate power panels than those for the B loop. The loss of one bus feeding RHR instrumentation would not affect the operating capability of the RHR system and therefore, would not affect the ability to achieve a cold shutdown.

N.

This system has redundant loops. The instrumentation on each loop is fed from separate buses; therefore, the loss of one loop or panel will not affect the ability to achieve a cold shutdown condition with the remaining loop.

O.

There is more than one instrument in the control room to monitor this parameter and these instruments are fed by two buses (redundant power); Therefore, the loss of one bus will not affect the operators ability to determine the value of this parameter.

LGS UFSAR CHAPTER 08 8.3-116 REV. 13, SEPTEMBER 2006 Table 8.3-31 (Deleted)

LGS UFSAR CHAPTER 08 8.3-117 REV. 13, SEPTEMBER 2006 Table 8.3-32 (The information in this table has been relocated to the TRM)