GTST AP1000-O71-3.3.18, Rev. 1 Date report generated:
Tuesday, May 12, 2015 Page 1 Advanced Passive 1000 (AP1000)
Generic Technical Specification Traveler (GTST)
Title:
Changes Related to LCO 3.3.18, Remote Shutdown Workstation (RSW)
I.
Technical Specifications Task Force (TSTF) Travelers, Approved Since Revision 2 of STS NUREG-1431, and Used to Develop this GTST TSTF Number and
Title:
TSTF-359-A, Rev 9, Increase Flexibility in MODE Restraints STS NUREGs Affected:
TSTF-359-A, Rev 9: NUREGs 1430, 1431, 1432, 1433, and 1434 NRC Approval Date:
TSTF-359-A, Rev 9: 12-May-03 TSTF Classification:
TSTF-359-A, Rev 9: Technical Change
GTST AP1000-O71-3.3.18, Rev. 1 Date report generated:
Tuesday, May 12, 2015 Page 2 II.
Reference Combined License (RCOL) Standard Departures (Std. Dep.), RCOL COL Items, and RCOL Plant-Specific Technical Specifications (PTS) Changes Used to Develop this GTST RCOL Std. Dep. Number and
Title:
There are no Vogtle Electric Generating Plant Units 3 and 4 (Vogtle or VEGP) departures applicable to GTS 3.3.4.
RCOL COL Item Number and
Title:
There are no Vogtle COL items applicable to GTS 3.3.4.
RCOL PTS Change Number and
Title:
The VEGP License Amendment Request (LAR) proposed the following changes to the initial version of the PTS (referred to as the current TS by the VEGP LAR). These changes include Administrative Changes (A), Detail Removed Changes (D), Less Restrictive Changes (L), and More Restrictive Changes (M). These changes are discussed in Sections VI and VII of this GTST.
VEGP LAR DOC A024: Reformat of GTS 3.3.1 into Seven Parts; 3.3.1 through 3.3.7 VEGP LAR DOC A028: Reformat of GTS 3.3.2 into Nine Parts; 3.3.8 through 3.3.16 VEGP LAR DOC A038: Numerous TS surveillances are revised by deletion of word that from the surveillance
GTST AP1000-O71-3.3.18, Rev. 1 Date report generated:
Tuesday, May 12, 2015 Page 3 III.
Comments on Relations Among TSTFs, RCOL Std. Dep., RCOL COL Items, and RCOL PTS Changes This section discusses the considered changes that are: (1) applicable to operating reactor designs, but not to the AP1000 design; (2) already incorporated in the GTS; or (3) superseded by another change.
The justification for TSTF-359 is based on vendor-specific evaluations. For Westinghouse plants, that evaluation is in MUHP-3015, Qualitative Risk Assessment Supporting Increased Flexibility in Mode Restraints, January 2002. This report evaluated the key plant changes that occur during the Mode changes so it is possible to identify the initiating events that can occur and systems available for event detection, actuation, and mitigation. It also considered initiating events and equipment available to mitigate those events. Based on that evaluation, Notes were proposed for several systems to prohibit the use of LCO 3.0.4.b. These Notes were applied to LTOP, ECCS-Shutdown, AFW, and AC Sources - Operating. TSTF-359-A also removed existing Notes from the ISTS and revised SR 3.0.4. There is no technical basis for concluding that the analysis performed in support of TSTF-359-A and the high-risk configurations addressed by the Notes are applicable to AP1000 plants. TSTF-359-A is not implemented by this GTST and is deferred for future consideration.
GTST AP1000-O71-3.3.18, Rev. 1 Date report generated:
Tuesday, May 12, 2015 Page 4 IV.
Additional Changes Proposed as Part of this GTST (modifications proposed by NRC staff and/or clear editorial changes or deviations identified by preparer of GTST)
APOG Recommended Changes to Improve the Bases Throughout the Bases, references to Sections and Chapters of the FSAR do not include the FSAR clarifier. Since these Section and Chapter references are to an external document, it is appropriate to include the FSAR modifier. (DOC A003)
GTST AP1000-O71-3.3.18, Rev. 1 Date report generated:
Tuesday, May 12, 2015 Page 5 V.
Applicability Affected Generic Technical Specifications and Bases:
Subsection 3.3.18, Remote Shutdown Workstation (RSW)
Changes to the Generic Technical Specifications and Bases:
GTS 3.3.1, Reactor Trip System (RTS) Instrumentation, is reformatted by VEGP LAR DOC A024 into seven Specifications; interim A024-modified TS (MTS) 3.3.1 through MTS 3.3.7.
The AP1000 GTS 3.3.2, Engineered Safety Feature Actuation System (ESFAS)
Instrumentation, is reformatted by VEGP LAR DOC A028 into nine Specifications; MTS 3.3.8 through MTS 3.3.16. As a result of the reformatting, GTS 3.3.4, Remote Shutdown Workstation (RSW), is renumbered as MTS 3.3.18. The MTS format is depicted in Section XI of this GTST as the reference case in the markup of the GTST instrumentation requirements for remote shutdown workstation instrumentation.
References 2, 3, and 6 provide details showing the correspondence of GTS 3.3.4 and STS 3.3.18.
MTS SR 3.3.18.2 is revised to remove that from SR description. This is consistent with the guidance provided in the TS Writer's Guide (Reference 4). (DOC A038)
The acronym FSAR is added to modify Section and Chapter in references to the FSAR throughout the Bases. (DOC A003) (APOG Comment)
GTST AP1000-O71-3.3.18, Rev. 1 Date report generated:
Tuesday, May 12, 2015 Page 6 VI.
Traveler Information Description of TSTF changes:
Not Applicable Rationale for TSTF changes:
Not Applicable Description of changes in RCOL Std. Dep., RCOL COL Item(s), and RCOL PTS Changes:
The Vogtle Electric Generating Plant Units 3 and 4 (VEGP) technical specifications upgrade (TSU) License Amendment Request (VEGP TSU LAR) (Reference 2) proposed changes to the initial version of the VEGP PTS (referred to as the current TS by the VEGP TSU LAR). As detailed in VEGP TSU LAR Enclosure 1, administrative change number 24 (DOC A024) reformats PTS 3.3.1 into multiple Specifications as follows:
3.3.1, Reactor Trip System (RTS) Instrumentation; 3.3.2, Reactor Trip System (RTS) Source Range Instrumentation; 3.3.3, Reactor Trip System (RTS) Intermediate Range Instrumentation; 3.3.4, Reactor Trip System (RTS) Engineered Safety Feature Actuation 3.3.5, Reactor Trip System (RTS) Manual Actuation; 3.3.6, Reactor Trip System (RTS) Automatic Trip Logic; and 3.3.7, Reactor Trip System (RTS) Trip Actuation Devices.
As detailed in VEGP TSU LAR Enclosure 1, DOC A028 reformats PTS 3.3.2 into multiple Specifications as follows:
3.3.8, Engineered Safety Feature Actuation System (ESFAS) Instrumentation, 3.3.9, Engineered Safety Feature Actuation System (ESFAS) Manual Initiation, 3.3.10, Engineered Safety Feature Actuation System (ESFAS) Reactor Coolant System (RCS) Hot Leg Level Instrumentation, 3.3.11, Engineered Safety Feature Actuation System (ESFAS) Startup Feedwater Flow Instrumentation, 3.3.12, Engineered Safety Feature Actuation System (ESFAS) Reactor Trip Initiation, 3.3.13, Engineered Safety Feature Actuation System (ESFAS) Control Room Air Supply Radiation Instrumentation, 3.3.14, Engineered Safety Feature Actuation System (ESFAS) Spent Fuel Pool Level Instrumentation, 3.3.15, Engineered Safety Feature Actuation System (ESFAS) Actuation Logic -
Operating, and 3.3.16, Engineered Safety Feature Actuation System (ESFAS) Actuation Logic -
Shutdown.
As a result, GTS 3.3.4 is renumbered as MTS 3.3.18.
VEGP LAR DOC A038 revises MTS SR 3.3.18.2 by deleting that from the surveillance.
GTST AP1000-O71-3.3.18, Rev. 1 Date report generated:
Tuesday, May 12, 2015 Page 7 A more detailed description of the changes by each of the above DOCs can be found in Reference 2, VEGP TSU LAR in Enclosure 1; the NRC staff safety evaluation can be found in Reference 3, VEGP LAR SER. The VEGP TSU LAR was modified in response to NRC staff RAIs (Reference 5) by Southern Nuclear Operating Companys RAI Response in Reference 6.
Rationale for changes in RCOL Std. Dep., RCOL COL Item(s), and RCOL PTS Changes:
The reformatting per VEGP LAR DOCs A024 and A028, except where addressed in other Discussion of Changes, addresses inconsistencies in formatting and approach between PTS 3.3.1 and PTS 3.3.2, respectively. Simplification and clarification are proposed for each Specification. In breaking down each PTS Specification into specific subsets of the Protection and Safety Monitoring System (PMS) function, improved human factored operator usability results.
The editorial change per VEGP LAR DOC A038 is consistent with the guidance provided in the TS Writer's Guide (Reference 4).
Description of additional changes proposed by NRC staff/preparer of GTST:
The acronym FSAR is added to modify Section and Chapter in references to the FSAR throughout the Bases. (DOC A003) (APOG Comment)
Rationale for additional changes proposed by NRC staff/preparer of GTST:
Since Bases references to FSAR Sections and Chapters are to an external document, it is appropriate to include the FSAR modifier.
GTST AP1000-O71-3.3.18, Rev. 1 Date report generated:
Tuesday, May 12, 2015 Page 8 VII. GTST Safety Evaluation Technical Analysis:
The changes are editorial, clarifying, grammatical, or otherwise considered administrative.
These changes do not affect the technical content, but improve the readability, implementation, and understanding of the requirements, and are therefore acceptable.
Having found that this GTSTs proposed changes to the GTS and Bases are acceptable, the NRC staff concludes that AP1000 STS Subsection 3.3.18 is an acceptable model Specification for the AP1000 standard reactor design.
References to Previous NRC Safety Evaluation Reports (SERs):
None
GTST AP1000-O71-3.3.18, Rev. 1 Date report generated:
Tuesday, May 12, 2015 Page 9 VIII. Review Information Evaluator Comments:
None Randy Belles Oak Ridge National Laboratory 865-574-0388 bellesrj@ornl.gov Review Information:
Availability for public review and comment on Revision 0 of this traveler approved by NRC staff on 5/29/2014.
APOG Comments (Ref. 7) and Resolutions:
- 1.
(Internal # 3) Throughout the Bases, references to Sections and Chapters of the FSAR do not include the FSAR clarifier. Since these Section and Chapter references are to an external document, it is appropriate (DOC A003) to include the FSAR modifier. This is resolved by adding the FSAR modifier as appropriate.
- 2.
(Internal # 6) The GTST sections often repeat VEGP LAR DOCs, which reference existing and current requirements. The inclusion in the GTST of references to existing and current, are not always valid in the context of the GTS. Each occurrence of existing and current should be revised to be clear and specific to GTS, MTS, or VEGP COL TS (or other), as appropriate. Noted ambiguities are corrected in the GTST body.
- 3.
(Internal # 7)Section VII, GTST Safety Evaluation, inconsistently completes the subsection References to Previous NRC Safety Evaluation Reports (SERs) by citing the associated SE for VEGP 3&4 COL Amendment 13. It is not clear whether there is a substantive intended difference when omitting the SE citation. This is resolved by removing the SE citation in Section VII of the GTST and ensuring that appropriate references to the consistent citation of this reference in Section X of the GTST are made.
- 4.
(Internal # 11) The GTST incorporates TSTF-359-A, Rev. 9. The justification for TSTF-359 was based on vendor-specific evaluations. For Westinghouse plants, that evaluation was in MUHP-3015, Qualitative Risk Assessment Supporting Increased Flexibility in Mode Restraints, January 2002. This report evaluated the key plant changes that occur during the Mode changes so it is possible to identify the initiating events that can occur and systems available for event detection, actuation, and mitigation. It also considered initiating events and equipment available to mitigate those events. Based on that evaluation, Notes were proposed for several systems to prohibit the use of LCO 3.0.4.b.
These Notes were applied to LTOP, ECCS-Shutdown, AFW, and AC Sources - Operating.
TSTF-359-A also removed existing Notes from the ISTS and revised SR 3.0.4. There is no technical basis for concluding that the analysis performed in support of TSTF-359-A and the high-risk configurations addressed by the Notes are applicable to AP1000 plants. Remove TSTF-359-A from the GTST. Include TSTF-359-A in the reference disposition tables, as TSTF deferred for future consideration
GTST AP1000-O71-3.3.18, Rev. 1 Date report generated:
Tuesday, May 12, 2015 Page 10 Note: also reinstate LCO 3.0.4 not applicable Notes deleted in various Specifications as a result of incorporating TSTF-359. This is resolved by reversing all changes implemented by the initial application of TSTF-359-A to this GTST.
NRC Final Approval Date: 5/12/15 NRC
Contact:
C. Craig Harbuck United States Nuclear Regulatory Commission 301-415-3140 Craig.Harbuck@nrc.gov
GTST AP1000-O71-3.3.18, Rev. 1 Date report generated:
Tuesday, May 12, 2015 Page 11 IX.
Evaluator Comments for Consideration in Finalizing Technical Specifications and Bases None
GTST AP1000-O71-3.3.18, Rev. 1 Date report generated:
Tuesday, May 12, 2015 Page 12 X.
References Used in GTST
- 1.
AP1000 DCD, Revision 19, Section 16, Technical Specifications, June 2011 (ML11171A500).
- 2.
Southern Nuclear Operating Company, Vogtle Electric Generating Plant, Units 3 and 4, Technical Specifications Upgrade License Amendment Request, February 24, 2011 (ML12065A057).
- 3.
NRC Safety Evaluation (SE) for Amendment No. 13 to Combined License (COL) No.
NPF-91 for Vogtle Electric Generating Plant (VEGP) Unit 3, and Amendment No. 13 to COL No. NPF-92 for VEGP Unit 4, September 9, 2013, ADAMS Package Accession No. ML13238A337, which contains:
ML13238A355 Cover Letter - Issuance of License Amendment No. 13 for Vogtle Units 3 and 4 (LAR 12-002).
ML13238A359 - Amendment No. 13 to COL No. NPF-91 ML13239A256 - Amendment No. 13 to COL No. NPF-92 ML13239A284 Enclosure 3 - Revised plant-specific TS pages (Attachment to Amendment No. 13)
ML13239A287 - Safety Evaluation (SE), and Attachment 1 - Acronyms ML13239A288 SE Attachment 2 - Table A - Administrative Changes ML13239A319 SE Attachment 3 - Table M - More Restrictive Changes ML13239A333 SE Attachment 4 - Table R - Relocated Specifications ML13239A331 SE Attachment 5 - Table D - Detail Removed Changes ML13239A316 SE Attachment 6 - Table L - Less Restrictive Changes The following documents were subsequently issued to correct an administrative error in :
ML13277A616 Letter - Correction To The Attachment (Replacement Pages) - Vogtle Electric Generating Plant Units 3 and 4-Issuance of Amendment Re:
Technical Specifications Upgrade (LAR 12-002) (TAC No. RP9402)
ML13277A637 - Revised plant-specific TS pages (Attachment to Amendment No. 13) (corrected)
- 4.
TSTF-GG-05-01, Writer's Guide for Plant-Specific Improved Technical Specifications, June 2005.
- 5.
RAI Letter No. 01 Related to License Amendment Request (LAR)12-002 for the Vogtle Electric Generating Plant Units 3 and 4 Combined Licenses, September 7, 2012 (ML12251A355).
- 6.
Southern Nuclear Operating Company, Vogtle Electric Generating Plant, Units 3 and 4, Response to Request for Additional Information Letter No. 01 Related to License Amendment Request LAR-12-002, ND-12-2015, October 04, 2012 (ML12286A363 and ML12286A360)
GTST AP1000-O71-3.3.18, Rev. 1 Date report generated:
Tuesday, May 12, 2015 Page 13
- 7.
APOG-2014-008, APOG (AP1000 Utilities) Comments on AP1000 Standardized Technical Specifications (STS) Generic Technical Specification Travelers (GTSTs), Docket ID NRC-2014-0147, September 22, 2014 (ML14265A493).
GTST AP1000-O71-3.3.18, Rev. 1 Date report generated:
Tuesday, May 12, 2015 Page 14 XI.
MARKUP of the Applicable GTS Subsection for Preparation of the STS NUREG The entire section of the Specifications and the Bases associated with this GTST is presented next.
Changes to the Specifications and Bases are denoted as follows: Deleted portions are marked in strikethrough red font, and inserted portions in bold blue font.
GTST AP1000-O71-3.3.18, Rev. 1 RSW 3.3.18 AP1000 STS 3.3.18-1 Amendment 0Rev. 0 Revision 19 Date report generated:
Tuesday, May 12, 2015 Page 15 3.3 INSTRUMENTATION 3.3.18 Remote Shutdown Workstation (RSW)
LCO 3.3.18 The RSW shall be OPERABLE:
APPLICABILITY:
MODES 1, 2, and 3.
MODE 4 with Reactor Coolant System (RCS) average temperature (Tavg) 350°F.
ACTIONS
NOTE-----------------------------------------------------------
LCO 3.0.4 is not applicable.
CONDITION REQUIRED ACTION COMPLETION TIME A. RSW inoperable.
A.1 Restore to OPERABLE status.
30 days B. Required Action and associated Completion Time not met.
B.1 Be in MODE 3.
AND 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> B.2 Be in MODE 4 with Tavg
< 350°F.
12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.3.18.1 Verify each required transfer switch is capable of performing the required function.
24 months
GTST AP1000-O71-3.3.18, Rev. 1 RSW 3.3.18 AP1000 STS 3.3.18-2 Amendment 0Rev. 0 Revision 19 Date report generated:
Tuesday, May 12, 2015 Page 16 SURVEILLANCE REQUIREMENTS (continued)
SURVEILLANCE FREQUENCY SR 3.3.18.2 Verify that the RSW communicates indication and controls with Division A, B, C and D of the Protection and Safety Monitoring System (PMS).
24 months SR 3.3.18.3 Verify the OPERABILITY of the RSW hardware and software.
24 months SR 3.3.18.4 Perform TADOT of the reactor trip breaker open/closed indication.
24 months
GTST AP1000-O71-3.3.18, Rev. 1 RSW B 3.3.18 AP1000 STS B 3.3.18-1 Amendment 0Rev. 0 Revision 19 Date report generated:
Tuesday, May 12, 2015 Page 17 B 3.3 INSTRUMENTATION B 3.3.18 Remote Shutdown Workstation (RSW)
BASES BACKGROUND The RSW provides the control room operator with sufficient displays and controls to place and maintain the unit in a safe shutdown condition from a location other than the control room (Ref. 1). This capability is necessary to protect against the possibility that the control room becomes inaccessible. Passive residual heat removal (PRHR), the core makeup tanks (CMTs), and the in-containment refueling water storage tank (IRWST) can be used to remove core decay heat. The use of passive safety systems allows extended operation in MODE 4.
If the control room becomes inaccessible, the operators can establish control at the RSW and place and maintain the unit in MODE 4 with Tavg < 350°F. The unit can be maintained safely in MODE 4 with Tavg < 350°F for an extended period of time.
The OPERABILITY of the remote shutdown control and display functions ensures there is sufficient information available on selected unit parameters to place and maintain the unit in MODE 4 with Tavg < 350°F should the control room become inaccessible.
APPLICABLE SAFETY ANALYSES The RSW is required to provide equipment at appropriate locations outside the control room with a capability to promptly shut down and maintain the unit in a safe condition in MODE 4 with Tavg < 350°F.
The criteria governing the design and the specific system requirements of the RSW are located in 10 CFR 50, Appendix A, GDC 19 (Ref. 2).
Since the passive safety systems alone can establish and maintain safe shutdown conditions for the unit, nonsafety systems are not required for safe shutdown of the unit. Therefore, no credit is taken in the safety analysis for nonsafety systems.
The RSW satisfies Criterion 4 of 10 CFR 50.36(c)(2)(ii).
LCO The RSW LCO provides the OPERABILITY requirements of the displays and controls necessary to place and maintain the unit in MODE 4 from a location other than the control room.
GTST AP1000-O71-3.3.18, Rev. 1 RSW B 3.3.18 AP1000 STS B 3.3.18-2 Amendment 0Rev. 0 Revision 19 Date report generated:
Tuesday, May 12, 2015 Page 18 BASES LCO (continued)
The RSW covered by this LCO does not need to be energized to be considered OPERABLE. This LCO is intended to ensure the RSW will be OPERABLE if unit conditions require that the RSW be placed in operation.
APPLICABILITY The RSW LCO is applicable in MODES 1, 2, and 3 and in MODE 4 with Tavg 350°F. This is required so that the facility can be placed and maintained in MODE 4 for an extended period of time from a location other than the control room.
This LCO is not applicable in MODE 4 with Tavg < 350°F or in MODE 5 or 6. In these MODES, the unit is already subcritical and in a condition of reduced Reactor Coolant System (RCS) energy. Under these conditions, considerable time is available to restore necessary instrument control functions if control room instruments or controls become unavailable.
ACTIONS The Note excludes the MODE change restriction of LCO 3.0.4. This exception allows entry into an applicable MODE while relying on the ACTIONS even though the ACTIONS may eventually require a unit shutdown. This exception is acceptable due to the low probability of an event requiring the RSW and because the equipment can generally be repaired during operation without significant risk of a spurious trip.
A.1 Condition A addresses the situation where the RSW is inoperable. The Required Action is to restore the RSW to OPERABLE status within 30 days. The Completion Time is based on operating experience and the low probability of an event that would require evacuation of the control room.
B.1 and B.2 If the Required Action and associated Completion Time of Condition A is not met, the unit must be brought to a MODE in which the LCO does not apply. To achieve this status, the unit must be brought to at least MODE 3 within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and to MODE 4 with Tavg < 350°F within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />. The allowed Completion Times are reasonable, based on operating experience, to reach the required unit conditions from full power conditions in an orderly manner and without challenging unit systems.
GTST AP1000-O71-3.3.18, Rev. 1 RSW B 3.3.18 AP1000 STS B 3.3.18-3 Amendment 0Rev. 0 Revision 19 Date report generated:
Tuesday, May 12, 2015 Page 19 BASES SURVEILLANCE REQUIREMENTS SR 3.3.18.1 SR 3.3.18.1 verifies that each required RSW transfer switch performs the required functions. This ensures that if the control room becomes inaccessible, the unit can be placed and maintained in MODE 4 with Tavg
< 350°F from the RSW. The 24 month Frequency was developed considering it is prudent that these types of surveillances be performed during a unit outage. However, this surveillance is not required to be performed only during a unit outage. This is due to the unit conditions needed to perform the surveillance and the potential for unplanned transients if the surveillance is performed with the reactor at power.
Operating experience demonstrates that RSW transfer switches usually pass the surveillance test when performed on the 24 month Frequency.
SR 3.3.18.2 This Surveillance verifies that the RSW communicates controls and indications with Divisions A, B, C, and D of the PMS. Communication is accomplished by use of separate multiplexers for each division. The operator can select the controls and indications available through each PMS division.
The Frequency of 24 months is based on the use of the data display capability in the control room as part of the normal unit operation and the availability of multiple video display units at the RSW. The Frequency of 24 months is based upon operating experience and consistency with control room hardware and software.
SR 3.3.18.3 SR 3.3.18.3 verifies the OPERABILITY of the RSW hardware and software by performing diagnostics to show that operator displays are capable of being called up and displayed to an operator at the RSW.
The RSW has several video display units which can be used by the operator. The video display units are identical to that provided in the control room and the operator can display information on the video display units in a manner which is identical to the way the information is displayed in the control room. The operator normally selects an appropriate set of displays based on the particular operational goals being controlled by the operator at the time. Each display consists of static graphical and legend information which is contained within the display processor associated with each video display unit and dynamic data which is updated by the data display system.
GTST AP1000-O71-3.3.18, Rev. 1 RSW B 3.3.18 AP1000 STS B 3.3.18-4 Amendment 0Rev. 0 Revision 19 Date report generated:
Tuesday, May 12, 2015 Page 20 BASES SURVEILLANCE REQUIREMENTS (continued)
The Frequency is based on the known reliability of the Functions and the redundancy available, and has been shown to be acceptable through operating experience.
SR 3.3.18.4 SR 3.3.18.4 is the performance of a TRIP ACTUATING DEVICE OPERATIONAL TEST (TADOT) every 24 months. This test should verify the OPERABILITY of the reactor trip breakers (RTBs) open and closed indication on the RSW by actuating the RTBs. The Frequency of 24 months was chosen because the RTBs may not be exercised while the facility is at power and is based on operating experience and consistency with the refueling outage.
REFERENCES
- 1.
FSAR Section 7.4.1, Safe Shutdown.
- 2.
10 CFR 50, Appendix A, GDC 19.
GTST AP1000-O71-3.3.18, Rev. 1 Date report generated:
Tuesday, May 12, 2015 Page 21 XII. Applicable STS Subsection After Incorporation of this GTSTs Modifications The entire subsection of the Specifications and the Bases associated with this GTST, following incorporation of the modifications, is presented next.
GTST AP1000-O71-3.3.18, Rev. 1 RSW 3.3.18 AP1000 STS 3.3.18-1 Rev. 0 Date report generated:
Tuesday, May 12, 2015 Page 22 3.3 INSTRUMENTATION 3.3.18 Remote Shutdown Workstation (RSW)
LCO 3.3.18 The RSW shall be OPERABLE:
APPLICABILITY:
MODES 1, 2, and 3.
MODE 4 with Reactor Coolant System (RCS) average temperature (Tavg) 350°F.
ACTIONS
NOTE-----------------------------------------------------------
LCO 3.0.4 is not applicable.
CONDITION REQUIRED ACTION COMPLETION TIME A. RSW inoperable.
A.1 Restore to OPERABLE status.
30 days B. Required Action and associated Completion Time not met.
B.1 Be in MODE 3.
AND 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> B.2 Be in MODE 4 with Tavg
< 350°F.
12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.3.18.1 Verify each required transfer switch is capable of performing the required function.
24 months
GTST AP1000-O71-3.3.18, Rev. 1 RSW 3.3.18 AP1000 STS 3.3.18-2 Rev. 0 Date report generated:
Tuesday, May 12, 2015 Page 23 SURVEILLANCE REQUIREMENTS (continued)
SURVEILLANCE FREQUENCY SR 3.3.18.2 Verify the RSW communicates indication and controls with Division A, B, C and D of the Protection and Safety Monitoring System (PMS).
24 months SR 3.3.18.3 Verify the OPERABILITY of the RSW hardware and software.
24 months SR 3.3.18.4 Perform TADOT of the reactor trip breaker open/closed indication.
24 months
GTST AP1000-O71-3.3.18, Rev. 1 RSW B 3.3.18 AP1000 STS B 3.3.18-1 Rev. 0 Date report generated:
Tuesday, May 12, 2015 Page 24 B 3.3 INSTRUMENTATION B 3.3.18 Remote Shutdown Workstation (RSW)
BASES BACKGROUND The RSW provides the control room operator with sufficient displays and controls to place and maintain the unit in a safe shutdown condition from a location other than the control room (Ref. 1). This capability is necessary to protect against the possibility that the control room becomes inaccessible. Passive residual heat removal (PRHR), the core makeup tanks (CMTs), and the in-containment refueling water storage tank (IRWST) can be used to remove core decay heat. The use of passive safety systems allows extended operation in MODE 4.
If the control room becomes inaccessible, the operators can establish control at the RSW and place and maintain the unit in MODE 4 with Tavg < 350°F. The unit can be maintained safely in MODE 4 with Tavg < 350°F for an extended period of time.
The OPERABILITY of the remote shutdown control and display functions ensures there is sufficient information available on selected unit parameters to place and maintain the unit in MODE 4 with Tavg < 350°F should the control room become inaccessible.
APPLICABLE SAFETY ANALYSES The RSW is required to provide equipment at appropriate locations outside the control room with a capability to promptly shut down and maintain the unit in a safe condition in MODE 4 with Tavg < 350°F.
The criteria governing the design and the specific system requirements of the RSW are located in 10 CFR 50, Appendix A, GDC 19 (Ref. 2).
Since the passive safety systems alone can establish and maintain safe shutdown conditions for the unit, nonsafety systems are not required for safe shutdown of the unit. Therefore, no credit is taken in the safety analysis for nonsafety systems.
The RSW satisfies Criterion 4 of 10 CFR 50.36(c)(2)(ii).
LCO The RSW LCO provides the OPERABILITY requirements of the displays and controls necessary to place and maintain the unit in MODE 4 from a location other than the control room.
GTST AP1000-O71-3.3.18, Rev. 1 RSW B 3.3.18 AP1000 STS B 3.3.18-2 Rev. 0 Date report generated:
Tuesday, May 12, 2015 Page 25 BASES LCO (continued)
The RSW covered by this LCO does not need to be energized to be considered OPERABLE. This LCO is intended to ensure the RSW will be OPERABLE if unit conditions require that the RSW be placed in operation.
APPLICABILITY The RSW LCO is applicable in MODES 1, 2, and 3 and in MODE 4 with Tavg 350°F. This is required so that the facility can be placed and maintained in MODE 4 for an extended period of time from a location other than the control room.
This LCO is not applicable in MODE 4 with Tavg < 350°F or in MODE 5 or 6. In these MODES, the unit is already subcritical and in a condition of reduced Reactor Coolant System (RCS) energy. Under these conditions, considerable time is available to restore necessary instrument control functions if control room instruments or controls become unavailable.
ACTIONS The Note excludes the MODE change restriction of LCO 3.0.4. This exception allows entry into an applicable MODE while relying on the ACTIONS even though the ACTIONS may eventually require a unit shutdown. This exception is acceptable due to the low probability of an event requiring the RSW and because the equipment can generally be repaired during operation without significant risk of a spurious trip.
A.1 Condition A addresses the situation where the RSW is inoperable. The Required Action is to restore the RSW to OPERABLE status within 30 days. The Completion Time is based on operating experience and the low probability of an event that would require evacuation of the control room.
B.1 and B.2 If the Required Action and associated Completion Time of Condition A is not met, the unit must be brought to a MODE in which the LCO does not apply. To achieve this status, the unit must be brought to at least MODE 3 within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and to MODE 4 with Tavg < 350°F within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />. The allowed Completion Times are reasonable, based on operating experience, to reach the required unit conditions from full
GTST AP1000-O71-3.3.18, Rev. 1 RSW B 3.3.18 AP1000 STS B 3.3.18-3 Rev. 0 Date report generated:
Tuesday, May 12, 2015 Page 26 BASES ACTIONS (continued) power conditions in an orderly manner and without challenging unit systems.
SURVEILLANCE REQUIREMENTS SR 3.3.18.1 SR 3.3.18.1 verifies that each required RSW transfer switch performs the required functions. This ensures that if the control room becomes inaccessible, the unit can be placed and maintained in MODE 4 with Tavg
< 350°F from the RSW. The 24 month Frequency was developed considering it is prudent that these types of surveillances be performed during a unit outage. However, this surveillance is not required to be performed only during a unit outage. This is due to the unit conditions needed to perform the surveillance and the potential for unplanned transients if the surveillance is performed with the reactor at power.
Operating experience demonstrates that RSW transfer switches usually pass the surveillance test when performed on the 24 month Frequency.
SR 3.3.18.2 This Surveillance verifies that the RSW communicates controls and indications with Divisions A, B, C, and D of the PMS. Communication is accomplished by use of separate multiplexers for each division. The operator can select the controls and indications available through each PMS division.
The Frequency of 24 months is based on the use of the data display capability in the control room as part of the normal unit operation and the availability of multiple video display units at the RSW. The Frequency of 24 months is based upon operating experience and consistency with control room hardware and software.
SR 3.3.18.3 SR 3.3.18.3 verifies the OPERABILITY of the RSW hardware and software by performing diagnostics to show that operator displays are capable of being called up and displayed to an operator at the RSW.
The RSW has several video display units which can be used by the operator. The video display units are identical to that provided in the control room and the operator can display information on the video
GTST AP1000-O71-3.3.18, Rev. 1 RSW B 3.3.18 AP1000 STS B 3.3.18-4 Rev. 0 Date report generated:
Tuesday, May 12, 2015 Page 27 BASES SURVEILLANCE REQUIREMENTS (continued) display units in a manner which is identical to the way the information is displayed in the control room. The operator normally selects an appropriate set of displays based on the particular operational goals being controlled by the operator at the time. Each display consists of static graphical and legend information which is contained within the display processor associated with each video display unit and dynamic data which is updated by the data display system.
The Frequency is based on the known reliability of the Functions and the redundancy available, and has been shown to be acceptable through operating experience.
SR 3.3.18.4 SR 3.3.18.4 is the performance of a TRIP ACTUATING DEVICE OPERATIONAL TEST (TADOT) every 24 months. This test should verify the OPERABILITY of the reactor trip breakers (RTBs) open and closed indication on the RSW by actuating the RTBs. The Frequency of 24 months was chosen because the RTBs may not be exercised while the facility is at power and is based on operating experience and consistency with the refueling outage.
REFERENCES
- 1.
FSAR Section 7.4.1, Safe Shutdown.
- 2.