6 to Updated Final Safety Analysis Report, Figure 7.2-1, Sheet 2 of 36, Drawing 495871, Revision 1, Sheet 1, Functional Logic Diagram Index and Symbols
ML21305A614
Person / Time
Site: Diablo Canyon  
(DPR-080, DPR-082)
Issue date: 10/11/2021
From:
Pacific Gas & Electric Co
To:
Office of Nuclear Reactor Regulation
Shared Package
ML21306A142 List: ... further results
References
DCL-21-074 495871, Rev. 1
Download: ML21305A614 (1)


Text

E FOLD D

C B

l'OLD A

I L8S6t;,

LOGIC SYMBOLS

[ 160, 130] 495871 D. E62 4351 SYMBOL

+

+

t t

/'-.

+

t t 2/3

...-M.R.

L R LOGIC FUNCTION AND NOT OR OFF RETURN MEMORY RETENTIVE MEMORY ADJUSTABLE TIME DELAY ENERGIZING ADJUSTABLE TIME DELAY DE-ENERGIZING COINCIDENCE 12 OUT OF 3 SHOWN!

RETENTIVE MEMORY WITH MANUAL RESET 04-25-91 VAL 2

3 A DEVICE WHICH PRODUCES AN OUTPUT ONLY WHEN EVERY INPUT EXISTS.

A DEVICE v/H I CH PRODUCES AN OUTPUT WHEN THE INPUT DOES NOT EXIST.

A DEVICE WHICH PRODUCES AN OUTPUT WHEN ONE INPUT IOR MORE) EXISTS.

ONLY A DEVICE WHICH RETAINS THE CONDITION OF OUTPUT CORRESPONDING TO THE LAST ENERGIZED INPUT, EXCEPT UPON INTERRUPTION OF POWER IT RETURNS TO THE OFF CONDITION.

A DEVICE WHICH RETAINS THE CONDITION OF OUTPUT CORRESPONDING TO THE LAST ENERGIZED INPUT !ALSO UPON INTERRUPTION OF POWER!.

A DEVICE WHICH PRODUCES AN OUTPUT FOLLOWING DEFINITE INTENTIONAL TIME DELAY AFTER RECEIVING AN INPUT.

A DEVICE WHICH CONTINUES TO PRODUCE AN OUTPUT FOR A DEFINITE INTENTIONAL PERIOD OF TIME AFTER THE INPUT HAS BEEN REMOVED.

A DEVICE WHICH PRODUCES AN OUTPUT WHEN THE PRESCRIBED NUMBER OF INPUTS EXIST (EXAMPLE 2 INPUTS MUST EXIST FOR AN OUTPUT l.

A DEVICE HAVING THE LOGICAL FUNCTION AS INDICATED BY THE DIAGRAM BELOW.

ACTUATING SIGNAL MANUAL RESET (MOMENTARY P.B.l

  • )

4 5

6 7

ADDITIONAL SYMBOLS

_,,-----~NSTRUMENT CHANNEL BISTABLE; A TAG NOTATION OF "*"" INDICATES A

( GENERIC BISTABLE ASSOCIATED WITH A GENERIC OR TYPICAL FUNCTION BLOCK I' PC' BISTABLE

,,,,,--------- INDICATES THAT THE DEVICE OR INSTRUMENT CHANNEL HAS A

/

LOGIC I OUTPUT WHEN:

143 I

I l u PARAMETER MEASURED IS GREATER THAN A PRESET VALUE PARAMETER MEASURED IS LESS THAN A PRESET VALUE PARAMETER MEASURED DEVIATES FROM A PRESET VALUE BY MORE THAN A PRESET AMOUNT.

OR + OR+ SAME AS ABOVE EXCEPT WITH AN AUTOMATICALLY SET VARIABLE VALUE U

OR J OR l SAME AS ABOVE EXCEPT WITH REQUIRED HYSTERESIS BETWEEN TURN ON AND TURN OFF.

_,,..,,..------ NON-INSTRUMENT BISTABLE

/~.----OUTPUT INDICATOR SAME AS EXPLAINED ABOVE

-~

27 1

& 2 0

CD ANALOG INPUT ALARM ANNUNCIATOR I ALARMS ON THE SAME SHEET WITH THE SAME SUBSCRIPT SHARE A COMMON ANNUNCIATOR WINDOW!

REACTOR TRIP FIRST OUT ANNUNCIATOR TURBINE TRIP FIRST OUT ANNUNCIATOR COMPUTER INPUT INDICATOR LAMP T TRIP STATUS LIGHTS P

PERMISSIVE STATUS LIGHTS B BYPASS STATUS LIGHTS A ACTUATION SIGNAL LIGHTS LOGIC INFORMATION TRANSMISSION ANALOG INFORMATION TRANSMISSION; 1--.._

( REAL VARIABLE FOR DIGITAL SYSTEM

}

ANALOG DISPLAY I

ANALOG INDICATOR R

RECORDER R2 RECORDER 2 CHANNEL R3 RECORDER 3 CHANNEL RB RECORDER 8 POINT ANALOG SUMMER CONTROL-0 ANALOG LOGIC GATE INPUT A DEVICE WHICH PERMITS AN ANALOG SIGNAL TO PASS IN AN ISOLATED CIRCUIT IF THE CONTROL LOGIC INPUT EXISTS.

v ANALOG OUTPUT A

B SIGNAL MULTIPLICATION FUNCTION C=A*B LOGIC ACTUATED SWITCHING FUNCTION C=B IF D=I C =A IF D =0 A--> fl xlt:_ ___ B_,_ FUNCTION GENERATOR B ~ fl A l X

I r,:.,,.,,.A f*ro$u REV REGISTERED ENGINEER 8

9 DEVICE FUNCTION LETTERS AND NUMBERS DC FC LC NC PC RC TC 20 27 33 POSITION IDISPLACEMENTI CHANNEL FLOW CHANNEL LEVEL CHANNEL NUCLEAR CHANNEL PRESSURE CHANNEL RADIATION CHANNEL TEMPERATURE CHANNEL ELECTRIC OPERATED VALVE UNDERVOLTAGE RELAY POSITION SWITCH SUFFIX LETTER:

ae, ao, be, bo - LIMIT SWITCH ae, tc bo, to ao be a 10%

b 10%

tc, to,

- TORQUE SWITCH POSITION SWITCH DEVELOPMENTS 0

I I I I - I (VALVE CLOSED)

FULL TRAVEL I

I I

I I

I (VALVE OPEN) 52 AC CIRCUIT BREAKER SUFFIX LETTER:

63 71 80 81 PRESSURE SWITCH LEVEL SWITCH FLOW SWITCH UNDERFREQUENCY RELAY a

b AUXILIARY CONTACT - OPEN WHEN MAIN CONTACTS ARE OPEN AUXILIARY CONTACT - CLOSED WHEN MAIN CONTACTS ARE OPEN NOTES I. EXCEPT WHERE INDICATED OTHERWISE THE FOLLOWING IS TRUE:

ALL LOGIC CIRCUITS ARE REDUNDANT. ALL INSTRUMENT CHANNELS, BISTABLES, ANNUNCIATORS, COMPUTER INPUTS, AND INDICATOR LAMPS ARE NOT REDUNDANT.

MANUAL CONTROL DO NOT HAVE REDUNDANT ACTUATORS, BUT DO HAVE REDUNDANT CONTACTS WHERE LOGIC IS REDUNDANT.

ALL INDICATOR LAMPS, COMPUTER INPUTS & ANNUNCIATORS ARE CONNECTED TO BOTH TRAINS SO THAT A SIGNAL IN EITHER TRAIN WILL ACTUATE.

2. THIS SET OF DRAWINGS IS IDENTICAL FOR UNITS I & 2 EXCEPT FOR THE TAG NUMBERS.

FOR UNIT I, TAG NUMBERS ADD A "I". EXAMPLE; I PC-455E FOR UNIT 2, TAG NUMBERS ADD A "2". EXAMPLE; 2PC-455E

3. WHENEVER A PROCESS SIGNAL IS USED FOR CONTROL AND JS DERIVED FROM A PROTECTION
CHANNEL, ISOLATION MUST BE PROVIDED.
4. THIS DRAWING ILLUSTRATES THE FUNCTIONAL REQUIREMENTS OF THE REACTOR 10 CONTROL AND PROTECTION SYSTEM. THIS DRAWING DOES NOT REPRESENT ACTUAL HARDWARE IMPLEMENTATION. FOR HARDWARE IMPLEMENTATION, REFER TO THE APPLICABLE SCHEMATIC.

f"' 5. SHEET NUMBERS REFER TO THE REFERENCE NUMBERS~

REFERENCES WE DWG PG&E DWG I.

2.
3.
4.
5.
6.
7.
8.
9.

I O

  • I I.

I 2.

I 3.

I 4.

I 5.

I 6.

I 7.

I 8.

I 9.

20.
21.
22.
23.

FUNCTIONAL LOGIC DIAGRAM INDEX AND SYMBOLS ____________________________________ 5653074-l ______ 495871 FUNCTIONAL LOGIC DIAGRAM REACTOR TRIP SIGNALS _________________________________ 5653074-2 ______ 495872 FUNCTIONAL LOGIC DIAGRAM NUCLEAR INSTR AND MANUAL TRIP SIGNALS __________________ 5653074-3 ______ 495873 FUNCTIONAL LOGIC DIAGRAM NUCLEAR INSTR PERMISSIVES AND BLOCKS ___________________ 5653D74-4 ______ 495874 FUNCTIONAL LOGIC DIAGRAM PRIMARY COOLANT SYSTEM TRIP SIGNALS. ___________________ 5653074-5 ______ 495875 DIAGRAM PRESSURIZER TRIP SIGNALS _____________________________ 5653074-6 ______ 495876 DIAGRAM STEAM GENERATOR TRIP SIGNALS __________________________ 5653074-7 ______ 495877 FUNCTIONAL LOGIC FUNCTIONAL LOGIC I

FUNCTIONAL LOGIC DIAGRAM SAFEGUARDS ACTUATION SIGNALS _________________________ 5653074-8 ______ 495878 FUNCTIONAL LOGIC DIAGRAM ROD CONTROLS AND ROD BLOCKS ___________________________ 5653074-9 ______ 495879

\\

FUNCTIONAL LOGIC DIAGRAM STEAM DUMP CONTROL ___________________________________ 5653074-10 _____ 495880 DIAGRAM PRESSURIZER PRESSURE AND LEVEL CONTROL. ________________ 5653074-1 I _____ 495881 DIAGRAM PRESSURIZER HEATER CONTROL ___________________________ 5653074-12 _____ 495882 FUNCTIONAL LOGIC FUNCTIONAL LOGIC I

FUNCTIONAL LOGIC DIAGRAM FEEDWATER CONTROL AND ISOLATION _______________________ 5653074-13 _____ 495883 FUNCTIONAL LOGIC DIAGRAM FEEDWATER CONTROL AND ISOLATION _______________________ 5653074-14 _____ 495884 FUNCTIONAL LOGIC DIAGRAM AUXILIARY FEEDWATER PUMPS STARTUP _____________________ 5653074-15 _____ 495885 FUNCTIONAL LOGIC DIAGRAM TURBINE TRIPS, RUNBACKS & SIGNALS ______________________ 5653074-16 _____ 495886 FUNCTIONAL LOGIC DIAGRAM AMSAC SIGNALS _______________________________________ 5653074-17 _____ 495887 FUNCTIONAL LOGIC DIAGRAM SEISMIC TRIP. ________________________________________ 8759077 ________ 495888 FUNCTIONAL LOGIC DIAGRAM DIGITAL FW CONT SYS INPUT SIGNAL VALIDATION ____________ 5653074-18 _____ 495889 FUNCTIONAL LOGIC DIAGRAM DIGITAL FW CONT SYS FW FLOW CONTROLLER & Cv DEMAND ______ 5653074-19 _____ 495890 FUNCTIONAL LOGIC DIAGRAM DIGITAL FW CONT SYS CONT VCV SEQ & TRACKING LOGIC _______ 5653074-20 _____ 495891 FUNCTIONAL LOGIC DIAGRAM DIGITAL FW CONT SYS SIGNAL SELECTOR LOGIC ______________ 5653074-21 _____ 495892 DRAWING INDEX SOLID STATE PROTECTION SYS INTERCONNECTION & SCHEM. DIAGRAM-------- 108D442-I ----- 458826 DWG DWG TYPE Gl SUBJECT DRAWING TITLE UNIT No.

0 I IINIDIE\\xl IAINIDI lslYIMIBl0ILlsl I I I I I I I I I I 121 RM INDEXED REV _I_

14 15 16 21 16-44 42 44 PROJECT LO::ATION IDI IIAIBIL\\01

.t.5-50 INSTALLATION DIVISION DD MAH TYPE NAME MISC CODE HOURS GADD

[I]

l§l D @}QI I I I I l9 51 52 53

~5 56 57 59 60 DRAW I NG SOURCE

~

70

£ J11'l'J-,r"Jur,illi---_'-----+&CA~~S>Q8c-+:'9~/5:7'c'.'lq'0~1

(/

SJGNA URE CA REO NO, EXF OATE NUCLEAR SAFETY RELATED KEY DWG--SECTION _ 3_

APPROVED GM BY SUPV L HOLLOWAY UNIT 2 FUNCTIONAL LOG[C DIAGRAM INDEX AND SYMBOLS COAST VALLEYS DIVISION MICROFILM BILL OF HATL DWG LIST 1Wf,,;llJTt' DSGN WESTINGHOUSE 1-1---+-------------f---+-l-+-+--+-+--J---+------------+-----l-+--+-+--I---+--'-. ----1--------------+--+---+---l---+-+----F,I=.::-:

DWNW ALBOVIAS I 'r-uCfj 0UFERSeDtPE,? r;w..Ge,31'1~-lo(t)C()*El:'*45&&1 Ml\\ Vin,.,,,

CHKD v ~ "'"'

SUPSDS 663195-18 t-t----t-------------i-----t--t---t--t----t---t--t----t--------------t------1--t----t---t--i-----i--'-r--~. Pl:f< A0 ~1111.:r f rxi

  • E* *-Z '2.'c<_'L-J-+--+--+=:::.c_+---+V"':'*

OK U" I ~

OWN CHKD SUPV "APVD 5Y DATE NO.

DA TE DES CR I PT ION GM/SPEC OWN CHKD SUPV APVD BY NO.

DATE DESCRIPTION GH/SPEC DWt-.1 CHKD SUPV APVD BY NO.

DATE DES CR I PT ION R E V I S I O N S R E V I S I O N S R E V I S I O N S SCALES NONE 2

3 4

5 6

7 DIABLO CANYON DEPARTMENT OF ENGINEERING PAC!F!C GAS AND ELECTRIC COMPANY SAN FRANCISCO, CALIFORNIA SUPSD BY SHEET NO, SHEETS 495871 REV I

UI - 495841 E

FOLD D

B F"OLD A