MONTHYEARML24029A1132024-01-16016 January 2024 Notification of Inspection and Request for Information (Email) ML23207A0762023-07-14014 July 2023 EN 56557 - Update to Part 21 Report Re Potential Defect with Trane External Auto/Stop Emergency Stop Relay Card Pn: XI2650728-06 ML23192A0552023-07-11011 July 2023 Relief Request Later Edition of ASME Code for ISI ML23172A0132023-06-20020 June 2023 Duke Fleet - Correction to June 2, 2023, Request for Additional Information Proposed License Amendment Request to Revise Restrictive Surveillance Requirement Frequencies ML23159A0052023-06-0505 June 2023 56557-EN 56557 - Paragon - Redlined ML23153A1892023-06-0202 June 2023 Duke Fleet - Request for Additional Information Proposed License Amendment Request to Revise Restrictive Surveillance Requirement Frequencies ML23151A3482023-05-30030 May 2023 Duke Fleet - Request for Additional Information Proposed Alternative for Pressurizer Welds in Accordance with 10 CFR 50.55a(z)(1) ML23142A2732023-05-22022 May 2023 Duke Fleet - Request for Additional Information Proposed Alternative for Steam Generator Welds in Accordance with 10 CFR 50.55a(z)(1) ML23124A1212023-05-0404 May 2023 Acceptance of Requested Licensing Action Duke Fleet Proposed Alternative for Pressurizer Welds in Accordance with 10 CFR 50.55a(z)(1) ML23087A0282023-03-27027 March 2023 Acceptance of Requested Licensing Action Amendment TSTF-505 ML23087A2492023-03-27027 March 2023 50.69 Acceptance Email ML23073A2282023-03-13013 March 2023 Duke Fleet- Adoption of TSTF-554, Revision 1, Revise Reactor Coolant Leakage Requirements - Acceptance Review ML23058A0562023-02-27027 February 2023 Acceptance of Amendment to Revise Surveillance Frequencies for RCS Pressure Isolation Valve Operational Leakage Testing and Reactor Trip System Instrumentation ML23048A1512023-02-16016 February 2023 Acceptance Review - Proposed Alternative for Steam Generator Welds (L-2023-LLR-0003) ML23030B9032023-01-30030 January 2023 Formal Release of RAIs for McGuire Unit 1, Relief Request Impractical RPV Rx Coolant System Welds, Due March 1, 2023 (Email) ML23017A2232023-01-13013 January 2023 Request for Additional Information (RAI) Issuance for McGuire Unit 1 Steam Generator Tube Inspection Report (Email) ML22291A4602022-10-17017 October 2022 Relief Request Impractical RPV and Rx Coolant Sys. Welds ML22242A1602022-08-30030 August 2022 Hardship Relief Request Pilot-Operated Relief Valve Acceptance Review Results ML22115A1412022-04-25025 April 2022 NRR E-mail Capture - Duke Common EOF Relocation - Request for Addition Information ML22083A0702022-03-24024 March 2022 NRR E-mail Capture - Catawba Nuclear Station, Units 1 and 2, Shearon Harris Nuclear Power Plant, Unit 1, and McGuire Nuclear Station, Units 1 and 2 - Acceptance Review for TSTF-569 LAR ML22049B0152022-02-17017 February 2022 NRC RP Inspection Document Request Letter ML22038A1572022-02-0707 February 2022 NRR E-mail Capture - Duke Energy Fleet - Acceptance of License Amendment Request Regarding Adoption of TSTF-541, Revision 2 ML22024A3952022-01-24024 January 2022 Acceptance of Requested Licensing Action Amendment McGuire RCS PT Limits Change TS 3.4.3 and EFPY Changes ML22018A0272022-01-18018 January 2022 2022 All RFI Responses - Exercise and Program Inspections - Revl ML21361A0122021-12-23023 December 2021 NRR E-mail Capture - Accepted for Review - Duke Energy Fleet License Amendment Request to Relocate Emergency Operations Facility ML21354A8612021-12-15015 December 2021 NRR E-mail Capture - Request for Additional Information - Duke Fleet Request RA-19-0352 - Alternative for RPV Closure Stud Exams (L-2020-LLR-0156) ML21286A7812021-11-22022 November 2021 Acceptance of Requested Licensing Action Revision to the End of Cycle Moderator Temperature Coefficient Measurement Methodology ML21295A0372021-10-0505 October 2021 NRR E-mail Capture - Accepted for Review - Duke Energy Fleet License Amendment Request to Adopt TSTF-577 Revised Frequencies for Steam Generator Tube Inspections ML21252A0532021-09-0808 September 2021 NRR E-mail Capture - Formal Release of Rais, 30 Day Response, Mcguire Relief Request, Ref: Later Edition Addenda ASME Code, Section XI, 50.55a(g)(4)(iv) ML21195A2022021-07-14014 July 2021 NRR E-mail Capture - McGuire Relief Request Acceptance Review Results; McGuire Unit 1 RR, Later Edition Addenda ASME Code, Section XI, 50.55a(g)(4)(iv) ML21103A0542021-04-13013 April 2021 NRR E-mail Capture - Extension to Request for Additional Information AMS Topical Report AMS-TR-0720R1 ML21096A3002021-04-0606 April 2021 E-mail for Approval of Proprietary Withholding for Duke Energy Exemptions for the Magnastor Storage Cask ML21096A2512021-04-0505 April 2021 NRR E-mail Capture - McGuire Emergency Plan Submittal, Letter Dated March 31 2021 ML21067A6742021-03-0505 March 2021 NRR E-mail Capture - Final Request for Additional Information AMS Topical Report AMS-TR-0720R1 ML21049A2632021-02-0404 February 2021 NRR E-mail Capture - Request for Additional Information - Duke Energy Fleet License Amendment Request to Revise Emergency Plan ML21007A3722021-01-0707 January 2021 NRR E-mail Capture - Acceptance Review - Duke Fleet - RA-19-0352 - Proposed Alternative for Reactor Vessel Close Stud Examinations (L-2020-LLR-0156) ML21006A4302021-01-0606 January 2021 Acceptance Review - Duke Fleet RA-20-0207 Request to Revise the Technical Specification for Engineered Safety Feature Actuation System (ESFAS) Instrumentation ML20346A0212020-12-10010 December 2020 NRR E-mail Capture - Formal Release of RAIs - License Amendment to Change TS 3.8.1 Due Jan. 29, 2021 ML20323A4072020-11-18018 November 2020 NRR E-mail Capture - Request for Additional Information - Brunswick License Exemption Request from 10CFR73 Annual Force on Force Exercise Requirements (EPIC L-2020-LLE-0180) ML20297A3102020-10-13013 October 2020 NRR E-mail Capture - Acceptance Review - Duke Fleet - RA-20-0191 - Request to Use a Provision of a Later Edition of the ASME B&PV Code, Section XI - IWA-5120, IWA-5213, IWA-5241, IWA-5242, and IWA-5250 (L-2020-LLR-0126) ML20297A3082020-10-0707 October 2020 NRR E-mail Capture - Acceptance Review - Duke Fleet - RA-20-0263 - Request to Use a Provision of a Later Edition of the ASME B&PV Code, Section XI for Repair/Replacement (L-2020-LLR-0124) ML20297A3092020-10-0606 October 2020 NRR E-mail Capture - Acceptance Review - Duke Fleet - RA-20-0262 - Request to Use a Provision of a Later Edition of the ASME B&PV Code, Section XI - IWA-4540(b) (L-2020-LLR-0125) ML20216A3512020-08-0303 August 2020 Mcquire U-1 ISI RFI ML20177A3792020-06-23023 June 2020 Email from L. Cox, North Carolina Department of Health and Human Services to NRC Regarding Exemption Request for Duke Energy'S McGuire Nuclear Station ML20140A0852020-05-19019 May 2020 ADAMS 2D ML20101L3132020-04-10010 April 2020 Notification of Inspection and Request for Information ML20071D0962020-03-0505 March 2020 NRR E-mail Capture - Request for Additional Information - McGuire Nuclear Station Unit 1 Delay in Update of the Code of Record for in Service Inspections ML20029E8592020-01-24024 January 2020 NRR E-mail Capture - McGuire Nuclear Station, Unit 1 -Acceptance of Requested Licensing Action Request to the 10-year ISI Interval Update ML20015A3162020-01-14014 January 2020 1/7/2020, E-Mail from M. Coflin to DCR Approval of Exemption Request McGuire Nuclear Facility ML20008D5592020-01-0707 January 2020 Email to Nc Shpo Exemption Request McGuire Nuclear Facility 2024-01-16
[Table view] |
Text
From: Sigmon, Chet Austin <Chet.Sigmon@duke-energy.com>
Sent: Monday, September 27, 2021 2:09 PM To: Klos, John Cc: Zaremba, Arthur H.; Grzeck, Lee
Subject:
[External_Sender] RE: [EXTERNAL] chet, is it possible NRC could also get related pictures, as appropriate, from/related to today's Stm Gen.
discussion?, thanks John K (eom)
Attachments: Primary Separator Curved Arm Stiffener Erosion NRC Presentation.pdf
- John, Attached is a PDF file of the presentation, which also updates some of the wording to reflect erosion as opposed to FAC which was discussed on the call today. Please use this file when updating anything on your end.
Thank you, Chet A. Sigmon, P.E.
Senior Nuclear Engineer Fleet Licensing Duke Energy Office: (704) 382-7269 Cell: (704) 929-3138 From: Sigmon, Chet Austin Sent: Monday, September 27, 2021 1:08 PM To: Klos, John <John.Klos@nrc.gov>
Cc: Zaremba, Arthur H. <Arthur.Zaremba@duke-energy.com>; Grzeck, Lee <Lee.Grzeck@duke-energy.com>
Subject:
RE: [EXTERNAL] chet, is it possible NRC could also get related pictures, as appropriate, from/related to today's Stm Gen. discussion?, thanks John K (eom)
- John, See the presentation attached. The list of attendees is as follows:
Chet Sigmon Art Zaremba Etienne Fonteneau Mitch Hatley Chuck Cauthen Dan Mayes Thank you, Chet A. Sigmon, P.E.
Senior Nuclear Engineer Fleet Licensing Duke Energy Office: (704) 382-7269 Cell: (704) 929-3138
From: Klos, John <John.Klos@nrc.gov>
Sent: Monday, September 27, 2021 11:26 AM To: Sigmon, Chet Austin <Chet.Sigmon@duke-energy.com>
Cc: Klos, John <John.Klos@nrc.gov>
Subject:
[EXTERNAL] chet, is it possible NRC could also get related pictures, as appropriate, from/related to today's Stm Gen. discussion?, thanks John K (eom)
- CAUTION! EXTERNAL SENDER *** STOP. ASSESS. VERIFY!! Were you expecting this email?
Are grammar and spelling correct? Does the content make sense? Can you verify the sender? If suspicious report it, then do not click links, open attachments or enter your ID or password.
Thanks in advance, John Klos DORL Mcguire, Surry Licensing Project Manager U.S. NRC, Office of Nuclear Reactor Regulation (NRR),
Division of Operating Reactor Licensing (DORL),
NRC/NRR/DORL/LPL2-1, MS O9E3 Washington, DC 20555-0001 301.415.5136, John.Klos@NRC.gov
Hearing Identifier: NRR_DRMA Email Number: 1374 Mail Envelope Properties (BYAPR03MB43287D4685569374F6A64BD5A0A79)
Subject:
[External_Sender] RE: [EXTERNAL] chet, is it possible NRC could also get related pictures, as appropriate, from/related to today's Stm Gen. discussion?, thanks John K (eom)
Sent Date: 9/27/2021 2:09:27 PM Received Date: 9/27/2021 2:10:26 PM From: Sigmon, Chet Austin Created By: Chet.Sigmon@duke-energy.com Recipients:
"Zaremba, Arthur H." <Arthur.Zaremba@duke-energy.com>
Tracking Status: None "Grzeck, Lee" <Lee.Grzeck@duke-energy.com>
Tracking Status: None "Klos, John" <John.Klos@nrc.gov>
Tracking Status: None Post Office: BYAPR03MB4328.namprd03.prod.outlook.com Files Size Date & Time MESSAGE 2103 9/27/2021 2:10:26 PM Primary Separator Curved Arm Stiffener Erosion NRC Presentation.pdf 635188 Options Priority: Normal Return Notification: No Reply Requested: No Sensitivity: Normal Expiration Date:
McGuire Unit 2 Steam Drum Inspection Primary Separator Curved Arm Stiffener Erosion
McGuire Steam Drum Inspection Plan
- As part of the McGuire M2R27 Steam Generator Steam Drum inspection, Duke requested an inspection plan from the SG OEM.
- The following was recommended by the OEM
- recommended we follow our normal Steam Drum Inspection plan.
- recommended inspection of a sample of Secondary Separator bottom plate (metrology) and all separator skimmer wall area (visual), where erosion has been found previously McGuire.
- provided additional visual inspection areas based off recent OE.
- recommended that 30 Primary Separators should be visually inspected with particular interest in the following:
- Primary Separator Top Plate
- Inside surface of a sample of the Curved Arms
- ID surface of the Outer Cylinder (Can).
- During the Inspection on Sept 18th, a new to McGuire issue was found. Through wall erosion was found in five Stiffener Plates in two Primary Separator Curved Arm Separators.
- Three Stiffener Plates in the #2 Primary Separator
- Two Stiffener Plates in the #6 Primary Separator
- This erosion has been found within the industry previously (Darlington U3 and Wolsong), however, this was the first time inspection of this region
Steam Drum Arrangement 3
Primary Curved Arm Separator Stiffener Plate Stiffener plate is rounded, but approximately 1.38 X 7.65 curved CS plate that is 0.112 thick. There are two internal stiffener plates per curved arm for a total of 8 plates per Primary Separator.
New Stiffener Plate Erosion in Primary Separator # 2 &
- 6 (max. estimated at 1x4)
==
Conclusion:==
- No Issues were noted in the general inspection.
- No issues noted with Primary Separator Top Plate
- No Issues were noted on the ID of the Separator Outer Cylinder
- Some minor erosion was noted on the inside surface of the curved arms outer wall, but no TW degradation.
- Erosion was found in Five Stiffener Plates in two Primary Separator Curved Arm Separators.
- None of the Stiffener Plates observed were completely eroded
- No Issue with continued operation (OEM)
- Plan is to monitor this erosion in planned future inspections.
- Secondary Separator Skimmer Wall erosion is continuing. 54 separators were found with through wall degradation vs 43 during M2R25 (2018). It appears that portions of the skimmer wall are flaking off and migrating to the bundle area. No degradation was associated with these parts during the ECT/SSI inspections.
- Secondary Separator Bottom Plate erosion is continuing, though none were found with through wall degradation. Worst case erosion was 94.8% TW vs 47.6% as left in M2R25 (2018).