ML21130A236

From kanterella
Jump to navigation Jump to search
0 to Updated Final Safety Analysis Report, Drawing 3009, Sheet 1, One Line Switching Diagram 12.5 Kv Ring Bus System
ML21130A236
Person / Time
Site: Cooper 
Issue date: 04/21/2021
From:
Nebraska Public Power District (NPPD)
To:
Office of Nuclear Reactor Regulation
Shared Package
ML21130A114 List: ... further results
References
NLS2021013
Download: ML21130A236 (1)


Text

'

85-D I NEW STATION WELLS WT-LCP-WEL.LS (SEE DWG. 3187)

TO VERIZON CELL EQUIPMENT (SEE CED 6021162 DWG.E-2) 100A 200A 111*-h 1 1 1 I

f I

l J!J..=.ll ! I OPA-DSC-WELLS STEPDOWN XFMR 12.5 KV/4BOV 75KVA, 3 PHASE TRAILERS OPA-PNL-TRPARK (SEE SH. 9) lit-"', I,

f Y T

I CIC=OPA-XFMR-TRPAAK STEPDOWN XFMR 12.5 KV/20BY-120V 300 KVA. 3 PHASE PAD MOUNT I

TRANSF. NO. 7

~

12/16/20/22.4MVA TO COOPER 161KV SUBSTATION I

Ml-XFMR-1 STEPDOWN XFMR 7200/240-120V SOKVA, 1 PHASE TO 345KV

.!Mi 204

--.,F""i,,,-21~_13D.BKV.6. /12.5KVY LINE NO. 1962 l J.BKV SW'GR SEE DWG. NC43456

~

_,if--

---...____.:,_+> 1 204 02 204 D1 ~ c~~*, ~l~l ~+> ~ I

~

rf"\\

~I 121-;,)D

.2Q1.=.D

~

3-L.(N =

1 3-L/N I

t; P.T.e

-=-

PT's ii

'---------------------------7 SEE SHT.9 FOR MAINTENANCE TRAINING FACILITY ELEC DISTRIBUTION OPA-DSC-WR2 OPA-PNL-MTFYD TO FIRE TRNG AREA TO MI-SW-MET(TRANS)

DWG. 3009 SH.2 OUTSIDE WELDING RECPTL MTF OUTSIDE LIGHTING

,)22=]

pp M=.ll 11, TO COt.tM BLDG OPA-PNL-MW (SEE SH.9)

,,_,u,-;li CIC=OPA-XFMR-MW STEPDOWN XFMR 720D/24D-12DV r-,11 5DKVA. 1 PHASE I '

CIC=OPA-XFMR-MTF STEPDOWN TRANSFORMER 12.5 KV/480-277V Y 300 KVA, 3 PHASE

'-----'-I'--+' PADMOUNT

,-11,

~-'----+, CIC=OPA-XFMR-MTFYD1

\\ ' ' i I T T T ]

STEPDOWN XFMR'S 7.2KV/48CNAC 75 KVA. 3 PHASE

---11, r----11,

~--'--!, CIC=OPA-XFMR-MTFYD2 ~-'----+, CIC=OPA-XFMR-FT

\\

1

.1. i STEPDOWN XFMR

\\ 1.1. i STEPDOWN XFMR T T T 7.2KV/240-12CN 7 2KV/240 120V 50K,A,1PHASE

'].

15 KVA. 1 PHASE 1~

1~

l (POLE TOP) ~:i

~:i

~:i I

>----------------------------------,1 1--1----------------+------------+------------+-------------------------------,

)

.lll=.ll

/.Mill-POWER POLE (TYPICAL)

'l j.42=1!(POLE TOP)

.lQ=ll pp NORTH OVERHEAD LOOP

.ail::lt!

PP NORTH OVERHEAD LOOP PP

~~ PC

.QlltlQ PP pp M=.ll' (POLE TOP)

.a1=1l (POLE TOP)

SEE SHT.9 FOR FAB SHOP ELEC. DISTRIBUTION SEE SHT.9 FOR CHEM. INJECTION ELEC, DISTRIBUTION CIC-EE-SWGR-12.S(NORTH)

NORTH SWGR, SEE DWG B&:V 147604-CAPC-E1001 FOR ISFSI SUPPORT BUILDING ELECTRICAL DISTRIBUTION

~~

(POLE TOP)

.B 111--7.

I

,.1. J CIC EE XFMR FS STEPDOWN TRANSFORMER 12.5Y7.2 KV/480Y277 300 KVA, 3 PHASE STATION pp M=° (POLE TOP)

=

=

(POLE TOP) zo2 I

~

naa/120

= l.!_4,400;120 ~ J

'---------~ ~

OP-A--XFM-R-TS-8 W 202-D2 202-D1 TRANSF. NO. 5 180/240/300 MVA 345KVY/161 KVY/13.BKV.6, SIGN AT Pl ANT ENTRANCE LIGHT POLE AT END Of CNS ENTRANCE ROAD s

SEE SHT.1 0 FOR

~1--< >--+--, ACCESS ROAD CONTROL STAHON DISTRIBUTION r,

STEPDOWN TRANSFORMER 7200/240-120V SEE SHT.9 FOR TSB &: MAIN PARKING LIGHTS STEPDOWN TRANSFORMER 7200/240-12DV 25 KVA, 1 PHASE 67-D (POLE TOP)

OPA-TB-BLDG102 pp

,1~1 (/F

, I,,

/ y y

CIC=OPA-XFMR-TSB1 STEPDOWN XFMR 12,5 KV/480-277V Y 500 KVA, 3 PHASE CIC's=EE-XFMR-SSB1 & EE-XFMR-SSB2 & EE-XFMR-S5B3 3 STEP DOWN TRANSFORMERS, 12.5KV/48CN -

277V Y 1 OOKVA, SINGLE PHASE

___.P._P ___________,_l _______

P.P ___________

l __ = _________ __..,. pp PP

.M 25 KVA, 1 PHASE OPA-XFMR-L1 TECHNICAL SUPPORT BUILDING (SEE CNS-BLDG-409 SHEET 4-1)

,lj M=I) (POLE TOP)

,lj M=.il (POLE TOP)

,lj ~ M=il (POLE TOP)

EAST SWGR CIC=EE-SWGR-12.5 (EAST)

CIC=EE-XFMR-01 OT ~-+--,

STEPDOWN XFMR 12.5 KV/ 208Y-120V 300 KVA, 3 PHASE PADMOUNT l '

I '

' ~-11, i

SEE SHT.9 FOR EE-PNL-01 OT AUTO-TRANSFORMER TRANSFORMER N0.2 345 K\\ff/161 K\\ff/13.8 ',Wt:,,

180/240/300 MVA I

I I

_ __f CIC=EE-XFMR-02 OT ~-+--,

STEPDOWN XFMR 12.5 KV/ 208Y-12CN 150 KVA, 3 PHASE PADMOUNT I

SEE SHT.9 FOR EE-PNL-02 OT 345 KY SUBSTATION J 3,8 KY SWITCHGEAR P.T.'S 3-L/N OPA-XFt.tR-BLDG102 1.

. _L.J 111 STEPDOWN XFMR

~*:¢:::*x-r.*

12470/480-277 (y

y._l.JII 300 KVA, 3 PHASE f7' ACCESS CONTROL BUILDING SEE DWG E0.1 12,5 KY FEEDER SWGRl llf-7,

~.~~.,

CIC=EE-XFMR-NLDC STEPDOWN TRANSFORMER 12.5 KV/4B0-277V Y 1500 KVA, 3 PHASE SEE SHT.2 FOR NORTH LOAD CENTER ELEC. DISTRIBUTION CIC-OPA-SWGR-12.5(TC)

TRAINING CENTER SWGR rn 1-L/L PT 1201~c

µ'\\

,1(

STEPDOWN TRANSFORMER N0.3 13.8 KV.6/12.5 KVY-7.2 KVY 16/20/22.4 MVA, 3 PHASE

.12=°

.llil

  • -----_,,..._+.1,\\..r,---t----,-------------+--v *-~--"---+---..J ACB 110

~---+-+-,c+--'-<,c-,.--.._*

,i>--"C'7C+-t----+---< r+---+..

FUTURE

.llil

\\

J CIC-EE-XFMR-AERIAL1 STEPDOWN TRANSFORMER r r 12.5 KV/24*-12ov

6.

~-+--+~ 100 KVA, 1 PHASE

~

SEE SHT.9 FOR MOBILE SKID A ELEC. DISTRIBUTION rE ll>--1,l,,

I 1/2 CIC=EE-XFMR-FP STEPDOWN TRANSFORMER 12.5 KV/4B0-277V Y 1500.WA, 3 PHASE SEE SHT.4 FOR FIRE PUMP ELEC. DISTRIBUTION I,

f T T

\\

, 1 CIC=EE-XFMR-AERIAL2 A

A STEPDOWN TRANSFORMER r r 12.5 Kv/240-12ov 6.

~-+--+~ 100 KVA, 1 PHASE

~

SEE SHT.9 FOR FLEX BUILDING #1 ELEC. DISTRIBUTION CIC=EE-XFMR-CST STEPDOWN TRANSFORMER 12.5 KV/4B0-277V Y 1500.WA, 3 PHASE l A l

J f T T ]

CIC=EE-XFMR-AERIAl..3 STEPDOWN TRANSFORMER 12.5 KV/240-120¥ 6.

100 KVA, 1 PHASE SEE SHT.9 FOR MOBILE SKID C ELEC. DISTRIBUTION

/=

~

LOAD BREAK ELBOWS CONNECTING TRANSFORMER WITH DISCONNECT 35-D ARE NORMALLY IN THE PARKED POSITION.

CIC=EE-XFMR-MPF1 STEPDOWN TRANSFORMER 12.5 KV/480-277¥ Y 2500 KVA. 3 PHASE

,1f-l,.) E

,1,,

f T T ]

.J,.

CIC=EE-XFMR-MPF2 STEPDOWN TRANSFORMER 12.5 KV/480-277¥ Y 1500 KVA, 3 PHASE

'\\..

3 CT'S 3 CT'S

1 '-,

J, -,-------;:=W~

ll, --I,--------=

1/2 SEE SHT.3 FOR MULTIPURPOSE FACILITY ELECTRJCAL DISTRIBUTION SEE SHT.3 FOR MULTIPURPOSE FACILITY ELECTRJCAL DISTRIBUTION L

STEPDOWN TRANSFORMER 12.5 KV /240-120V 50 KVA, 1 PHASE (POLE TOP)

( f-------+-------,

( C-----C----------j )

86-D 87-D 140T J.

SEE SHT.5 FOR WEST WAREHOUSE ELEC. DISTRIBUTION STEPDOWN TRANSFORMER 7200-120/240 50kVA, 1 PHASE PADMOUNT SEE SHT.10 FOR LLRW ELEC. DISTR[BUTION PARKING LOT 'C' LIGHTS & RECEPTACLES SEE SHT.1 0 FOR ELEC. DISTR[BUTION NOTE:

LOAD BREAK ELBOWS 1 _1}

CONNECTING TRANSFORMER WITH FUSE 99-D ARE i

NORMALLY IN THE PARKED I~

POSITION. -<'--I-Ir-"

r-+---, STEPDOWN TRANSFORMER 1lr 7 7200-120/240 11Lrh-,+---, STEPDOWN TRANSFORMER

'-..A.,

15 KVA,. 1 PHASE 11 I '-A...

12.5 KVA -

480V

.fY"'

OPA-XFMR-LLSP

,1, ~ 750 KVA, 3*

1lr --+-~

11 ClC=OPA-LLRW-XFMR-H1 CIC=OPA-XFMR-WWHSE STEPDOWN TRANSFORMER 12.5 KV/480-277¥ Y 300 KVA, 3 PHASE PERIMETER FENCE JO WEST LIGHTING SEE SHT 10 96-D

.,_J___.,'----..._-1----~

WW1 SWGR CIC=EE -SWGR-12.5(WW1) iii-- \\..A...

STEPDOWN TRANSFORMER

a.

§ z

=>

ii1 ffi "

z

=>

LOAD BREAK ELBOWS CONNECTING

~

) c-TRANSFORMER WllH TECHNICAL SUPPORT BUILDING TRANSFORMER ARE NORMALLY IN THE PARKED POSITION.

CIC=OPA-XFMR-TC 1

1 1 STEPDOWN TRANSFORMER f T T j 12.5 KV/4B0-277V Y

'----t--+' 500 KVA, 3 PHASE

~

SEE SHT.8 FOR TRAINING CENTER ELEC. DISTRIBUTION CIC-EE-SWGR-12.S(SOUTH)

SOUTH SWGR.

18-D

.,_~.... ------1---...

~~D SEE SHT.9 FOR CONDENSATE TANK SWGR. ELEC. DISTRIBUTION CIC=EE-XFMR-08 ilf-"' I I

I '

STEPDOWN TRANSFORMER 12.5 KV/480-277V Y 750 KVA, 3 PHASE

-+-- ~

LOAD BREAK ELBOW (TYP)

E I

CIC=EE-XFMR-SLOC STEPDOWN TRANSFORMER 12.5 KV/480-277V Y 1500 KVA, 3 PHASE TO BOILER HB-1 C 3 CT'S TYPE CM

__ _;;;;;;;;;;;;:;:;;;;;;;;;;;;;;._1--~_:'"r--y:~:i"----___£,.--.._____.,,,.--*

I

~ 26-D 1,

(Y'\\

P.T. 1-L/N TO BOILER HB 1 D 3 CT'S TYPE CM

_ ____;;;;;!;;!;:;;;;;~;;;._--1-~-..:r.:,c:;;'........t,.--.._____.,,,.~_.

I

.21 24-D 1,

(Y'\\

P.T. 1-L/N

~

100-D I (POLE TOP)

~

~

I (POLE TOP) 1.1.=.ll (POLE TOP) I ill-...f'Y' 7.2 KW -

120/240V

--+-~ 10 KVA, 1 PHASE

,lj

.2ll.=.ll (POLE TOP)

FUSE SIZE/TYPE (TYP.), SEE _/---------+-~

SCHEDULE FOR DETAILS SEE SHT.6 FOR ADMINISTRATION BLDG. ELEC. DISTRIBUTION SEE SHT.7 FOR SOUlH LOAD CENTER ELEC. DISTRIBUTION PLANT HEATING BOILER SWITCHGEAR CIC=EE-SWGR-12.5 {BOILER)

SPARE TT TO SEWAGE LAGOON

(

DISCHARGE IRRIGATION PUMP ONLY (SEE DWG. CNS-ST-9)

.,__,, ~---+--' '--+-----'---------'----

59-*

(POLE TOP)

STEPDOWN TRANSFORMER 12.5KV/277-480V Y 45KVA,. 3 PHASE TT

---+-./ t TO SOUTH PERIMITER LIGHTING

.fill=ll (POLE TOP)

SPARE STEPDOWN TRANSFORMER 12.5KV/120-240V 50KVA. 1 PHASE SPARE WEST SWGR CIC=EE-SWGR-12.5(WEST)

WW2 SWGR C[C= EE-SWGR-12.5 WW2)

I WEST WHSE ADDITION J

  • If-1-1 ' 1 y '

c' STEPDOWN TRANSFORMER 12.5 KV/480-277V Y 500 KVA, 3 PHASE CIC=OPA-XFMR-WMPF 12.SKV PMH-12 SWGR SPARE SPARE COMP 3 COMP 4 SMU-20 FUSE 80 AMP COMP 2 COMP 1 SEE SHEET 11 ADHR SUPPLY SWITCHBOARD ELECTRICAL DISTRIBUTION SOUTH UNDERGROUND LOOP I

J I

J I T l

CIC =

EE-XFMR-ADHR 12.SKVt./ 480Vt.

1500KVA, 3 PHASE PADMOUNT UNIT SUBSTATION MARK A

B C

D E

F G

H J

K L

M N

p R

s T

SIZE (AMPS) 2-300 200 BO 25 50 65 200 15 25 40 1/2 30 31 5

30 12 20 FOR PREVIOUS REVISIONS, SEE SUPERSEDED CARDS.

VERSIONS/REVISIONS BY N.P.P.D.

NO.

DESCRIPTION AG 60 DR-2013-0985 AN 61 DR-2013-0807 AO 62 DR 2016 0464 AO 63 DR-2016-0479 AA 64 DR-2017-0001 OFT DATE ENG DLR 12 10 15 DWHELMI DLR 3 30 16 JEDAUEL DJB 30 16 SCSCHUI DLR 9 9 16 SCSCHU DLR 10 18 17 REJENSE VOLTAGE RATING 14.4KV 14.4KV 14.4KV 2.4-14.4KV 2.4-14.4KV 2.4-14.4KV 2.4-14.4KV 15KV 15KV 15KV 14.4KV B.3KV 7.2KV 15KV 15KV 15KV 15KV SIGNIFICANT NUIIIBER GROUP FUSE SCHEDULE SPEED TYPE SLOW SM-5 SLOW SMU-20 SLOW SMU-20 358C10 BAY-0-NET 358C12 BAY-0-NET 35BC14 BAY-0-NET E

ELSP-G7 SLOW T RATED EXPULSION SLOW T RATED EXPULSION SLOW T RATED EXPULSION STANDARD FUS[STOR SLOW ELST-30E VARJABLE 358C10 SLOW SH SLOW T RATED EXPULSION SLOW T

SLOW ELST-20E COOPER ONE LINE 1 2.5 KV NUCLEAR SWITCHING RING BUS MANUFACTURER S&C S&C S&C RTE RTE RTE RTE KEARNEY CORP.

KEARNEY CORP.

KEARNEY CORP.

S&C RTE RTE KEARNEY CORP.

KEARNEY CORP.

CHANCE RTE 4

STATION DIAGRAM SYSTEM

,1f-, (

.ll CIC=EE-XFMR-IONICS STEPDOWN TRANSFORMER 12.5 KV/4B0-277V Y

.300 KVA, 3 PHASE l 1 J. 1 J

( ' '

.J,.

TO DISCONNECT EE-DSC-IONPWR CIC=EE-XfMR-SAWDECK STEPDOWN TRANSFORMER 12.5 KV/480-277V Y 500 KVA, 3 PHASE J

YORK STOCK CODE NO.

( '

' 1 1/2 146-4223 146-4777 146-4764 146-9210 146-9212 146-9214 TO PANEL EE-PNL-SAWDECK NON-STOCK NPPD JOINT USE DRAWING 146-2115 146-2125 146-2129 THIS DRAWING PERTAINS TO MULTIPLE LAB/OFFICES AND D!Rs. UPDATES SHALL BE RECORDED ON THE PRIMARY DIR WITH PRIMARY LAB/OFFICE APPROVAL. THE SECONDARY DIR SHALL THEN BE VERSIONED BY A DOCUMENT MANAGER, NON-STOCK SPLORDER 146-9210 146-1705 146-2127 146-2112 SPLORDER GROUP 1: 930239 GROUP 5: 3510


1 SECONDARY DIR:

49804539 6 DRAWN I DATE TRU 01/06/92 CHEO<ED I DATE D.R.

1-23-92 APPROVED I DATE WCFischer 1-23-92 AS BUILT 454239079 STATUS: Release STATUS DATE: 10/18/2017 OS APPROVED JDWILSO VER: AR REV: 64 SIZE: F BURNS & ROE

<D 0

0 0

~u t----.---~-----------i.

FILMED 3009 SH 1