PUBLIC SUBMISSION As of: 1/7/21 7:27 AM Received: December 18, 2020 Status: Pending_Post Tracking No. kiu-9qwc-w2rx Comments Due: December 31, 2020 Submission Type: Web Docket: NRC-2020-0231 Risk-Informed, Performance-Based Fire Protection for Existing Light-Water Nuclear Power Plants Comment On: NRC-2020-0231-0001 Risk-Informed, Performance-Based Fire Protection for Existing Light-Water Nuclear Power Plants Document: NRC-2020-0231-DRAFT-0003 Comment on FR Doc # 2020-25173 Submitter Information Email: vka@nei.org Organization: Nuclear Energy Institute General Comment Industry Comments on Draft Regulatory Guide (DG) 1360, Risk-Informed, Performance-Based Fire Protection for Existing Light-Water Nuclear Power Plants, 85 FRN 73088-73089; Docket ID NRC-2020-0231e attached file(s)

Attachments 12-18-20_NEI Comments on Draft Regulatory Guide (DG) 1360 85 FRN 73088-73089 Docket ID NRC-2020-0231 Page 1 of 1 01/07/2021 file:///C:/Users/BHB1/Downloads/NRC-2020-0231-DRAFT-0003.html SUNI Review Complete Template=ADM-013 E-RIDS=ADM-03 ADD: Shivani Mehta, Charles Moulton, Michael Eudy, Mary Neely Comment (1)

Publication Date:

11/16/2020 CITATION 85 FR 73088

VICTORIA K. ANDERSON Technical Advisor, Engineering & Risk 1201 F Street, NW, Suite 1100 Washington, DC 20004 P: 202.739.8101 vka@nei.org nei.org December 18, 2020 Jennifer Borges Office of Administration Mail Stop: TWFN-7-A60M U.S. Nuclear Regulatory Commission Washington, DC 20555-0001

Subject:

Industry Comments on Draft Regulatory Guide (DG) 1360, Risk-Informed, Performance-Based Fire Protection for Existing Light-Water Nuclear Power Plants, 85 FRN 73088-73089; Docket ID NRC-2020-0231 Submitted via regulations.gov Project Number: 689

Dear Ms. Jennifer Borges:

The Nuclear Energy Institute (NEI)1, on behalf of its members, submits the following comments on DG-1360, Risk-Informed, Performance-Based Fire Protection for Existing Light-Water Nuclear Power Plants. We are supportive of the effort to revise this regulatory guide to endorse the latest revision of NEI 04-02, Guidance for Implementing a Risk-Informed, Performance-Based Fire Protection Program Under 10 CFR 50.48(c), and appreciate the opportunity to comment on the draft revision. In our review, we noted that the draft revision generally offers improvements in clarity and consistency. We have included detailed comments in an attachment for your use in finalizing this regulatory guide.

We encourage NRC to consider all stakeholder comments prior to finalizing the revision to this regulatory guide. Please contact me at vka@nei.org or (202) 739-8101 with any questions regarding our comments.

Sincerely, Victoria K. Anderson 1 The Nuclear Energy Institute (NEI) is responsible for establishing unified policy on behalf of its members relating to matters affecting the nuclear energy industry, including the regulatory aspects of generic operational and technical issues. NEIs members include entities licensed to operate commercial nuclear power plants in the United States, nuclear plant designers, major architect and engineering firms, fuel cycle facilities, nuclear materials licensees, and other organizations involved in the nuclear energy industry.

Ms. Jennifer Borges July 29, 2020 Page 2 Attachment c:

Mr. Michael Franovich, NRR Mr. Greg Bowman, NRR Mr. Joshua Borromeo, NRR Mr. Shivani Mehta, NRR Mr. Charles Moulton, NRR Mr. Michael Eudy, RES

Attachment:

NEI Detailed Comments on DG-1360, Risk-Informed, Performance-Based Fire Protection for Existing Light-Water Nuclear Power Plants Section Comment Proposed Resolution Section 3, Pages 22-24 Section 3.3 - Fire PRAs utilize processes in NUREG/CR-7150, Volume 2 on hot short-induced spurious operation probability and duration.

In order to acknowledge this and provide clarification in the event of any conflicts with Section 3.3, the following statement is recommended in Section 3.3 (following the paragraph in page 4 on shorting switches):

Guidance for circuit failure mode likelihood and hot short duration for use in Fire PRAs is included in NUREG/CR-7150, Volume 2.

Section 3.1, Page 19 The following statement that is included in most, if not all, license conditions, is not included in Section 3.1. This License Condition does not apply to any demonstration of equivalency under Section 1.7 of NFPA 805.

Recommend including that statement at the end of (1)

Changes to NFPA 805, Chapter 3, Fundamental Fire Protection Program.