Corrected Monthly Operating Rept for Jul 1986,changing Forced Outage to Scheduled Outage
ML20212M033
Person / Time
Site: Callaway Ameren icon.png
Issue date: 07/31/1986
From: Evans S
UNION ELECTRIC CO.
To:
Shared Package
ML20212M003 List:
References
NUDOCS 8701290476
Download: ML20212M033 (5)


Text

,s

  • DOCKET NO.

50-483 UNIT NAME CALLAWAY UNIT 1 DA'II 8/6/86 (Revised 11/7/86)

COMPLETED BY S. R. EVANS TELEP110NE 314/676-8742 PART A OPERATIONS

SUMMARY

Unit operated at 100% power with the following exceptions:

1) 7/25/86 - forced power reduction due to turbine runback en loss of circulating water.
2) 7/26/86 - turbine trip / reactor trip during turbine surveillance testing.

Plant annual RERP drill conducted with satisfactory results reported from the NRC and FEMA.

PART B PORV AND SAFETY VALVE

SUMMARY

None 8701290476 861117 PDR ADOCK 05000403 R

PDR CA-#804 04/10/85 QDP-ZZ-04204 Page 1 of 4

,s

  • Part C AVERACE DAILY UNIT POWER LEVEL DOCKET NO.

50-483 UNIT NAME CALLAWAY UNIT 1 DAIE 8/6/86 (Rev. 11/7/86)

COMPLETED BY S. R. EVANS TELEPHONE 314/676-8742 MONTH:

JULY 1986 AVERAGE DAILY POWER LEVEL AVERAGE DAILY P0kTR LEVEL DAY (MWe-Net)

DAY (MWe-Net) 1 1042.3 17 1087 2

1098.3 18 1089.5 3

1105.6 19 1085.2 4

1094 20 1090.3 5

1071 21 1099.6 6

1092 22 1097.6 7

1094.3 23 1091.8 8

1090.4 24 1088.3 9

1089.6 25 1001.7 i

10 1090.1 26 12.2 11 1096.8 27 0

12 1102.2 28 485 13 1096.2 29 751.6 14 1086.5 30 767.4 15 1072.1 31 1003.5 16 1087.6 CA-#804 04/10/85 i

QDP-ZZ-04204 Page 2 of 4 l

a Part D OPERATING DATA REPORT DOCKET NO.

50-483 UNIT NAME CALLAWAY UNIT 1 DATE 8/6/86(Rev. 11/7/86)

COMPLETED BY S. R. EVANS TELEPHONE 314/676-8742 OPERATING STATUS (YTD CUM )

1.

REPORTING PERIOD: July 1986 GROSS HOURS IN REPORTING PERIOD:

744 (5087 14149.5) 2.

CURRENTLY AUTHORIZED POWER LEVEL (MWt):

3411 MAX. DEPEND. CAPACITY (MWe-Net):

1120 DESIGN ELECTRICAL RATING (MWe-Net):

1171*

  • At stretch power level which is not currently authorized under the Operating License.

3.

POWER LEVEL TO WHICH RESTRICTED (IF ANY) (FMe-Net):

100%

4 REASONS FOR RESTRICTION (IF ANY):

THIS MONTH YR 10 DAIT CUMULATIVE 5.

NUMBER OF 110URS REACTOR WAS CRITICAL...............

718.6 3681.3 12144.8 6.

REACTOR RESERVE SHUTDOWN HOURS.....................

0 0

0 7.

HOURS GENERATOR ON LINE............................

697.9 3510.4 11697.8 8.

UNIT RESERVE SilUTDOWN HOURS........................

0 0

0 9.

GROSS THERMAL ENERGY CENERATED (MWH)...............

2,279,207 10,964,142 36,981,695

10. CROSS ELECTRICAL ENERGY CENERATED (MMI)............

761',723 3,679,B61 12,493,804

11. NET ELECTRICAL ENERGY CENERATED (MWH)..............

723,828 3,490,183 11,858,970

12. REACIOR SERVICE FACTOR.............................

96.6%

72.4%

85.8%

13. REACTOR AVAILABILITY FACTOR........................

96.6%

72.4%

85.8%

14. UNIT SERVICE FACTOR................................

93.8%

69.0%

82.7%

15. UNIT AVAILABILITY FACTOR...........................

93.8%

69.0%

82.7%

16. UNIT CAPACITY FACIOR (Using MDC)...................

86.9%

61.3%

74.8%

17 UNIT CAPACITY FACTOR (Using Design PMe)............

83.1%

58.6%

71.6%

1 18. UN IT IVRCED OUTAGE RATE............................

6.2%

5.2%

5.9%

19. SHUTDOWNS SCIIEDULED OVER NEXT 6 MONTHS (TYPE, DATE, AND DURATION OF EACH): None 20 IF SHUT DOWN AT END OF REPORTING PERIOD, ESTIMATED DATE OF STARTUP:

CA-*804 Ot./10/85 QDP-ZZ-04204 Page 3 of 4

=.,

'9

'e Part E

~~

UNIT SHUTDOWNS AND POWER REDUCTIONS DOCKET NO.

50-483 UNIT NAME CALLAWAY UNIT 1 DATE 8/6/86 (Rev. 11/7/86)

COMPLETED BY S. R. EVANS TELEPHONE 314/676-8742 REPORT MONIH JULY 1986 METHOD OF TYPE SHUTTING DOWN F: FORCED DURATION TIIE REACIOR OR DATE S: SCHEDULED (HOURS)

REASON REDUCING POWER CORRECTIVE ACTIONS /COMENTS I 15.

7/25/86 F

0 A

4 Reduction in power due to turbine runback on trip of "A" circulating water pumip.

16.

7/26/86 F

46.1 A

3 Turbine trip / reactor trip during turbine surveillance testing. LER 86-027-00

/

s f

SUM 4ARY:

(

f -

REASON I,

METHOD A: EQUIPMENT FAILURE (EXPLAIN) la MANUAL B: MAINT. OR TEST 2: MANUAL SCRAM C: REFUELING 3: AUIOMATIC SCRAM D: RECULATORY RESTRICTION 4: OTHER (EXPLAIN) i,,,

E: OPERATOR TRAINING AND LICENSE EXAMINATION F: ADMINISWATIVE C:' OPERATIONAL ERROR (EXPLAIN)

CA-#804 H: OIHER (EXPLAIN) 04/10/85 QDP-ZZ-04204 Page 4 of 4