Text

+

g.

DOCKET NO.

'50-483 UNIT NAME CALLAWAY UNIT 1 DATE 10/6/86 (Revised 11/7/86)'

COMPLETED BY S. R. EVANS TELEPHONE 314/676-8742 f

i f

PART A OPERATIONS SUff8ARY J

Unit operated at 100% power with one exception:

On 9/9/86, a low flow reactor trip occurred during replacement / restoration of a loop flow transmitter.

The plant was returned to operation within three hours.

i 4

1 PART B PORY AND SAFETY VALVE SLMfARY None

}-

i b

1 4

9 i

CA-#804 04/10/85 i-

?"'

8701290479 861117 QDP-ZZ-04204 PDR ADOCK 05000483 R

ppg

)

Page 1 of 4 4

4

4

{

9 Part C AVERACE DAILY UNIT POWER LEVEL DOCKET NO.

50-483 UNIT NAME CALLAWAY UNIT 1 DATE 10/f/86 (Rev.11/7/86)

COMPLETED BY S. R. EVANS TELEPHONE 314/676-8742 MONTH:

SEPTEMBER 1986 AVERACE DAILY POWER LEVEL AVEkAGE DAILY P0kTR LEVEL DAY (MWe-Net)

DAY (MWe-Net) 1 1094 17 1100 2

1093 18 1097 3

1070 19 1087 4

1084 20 1086 5

1106 21 1085 6

1110 22 1086 7

1116 23 1094 8

1116 24 1087 9

648 25 1083 10 713 26 1089 11 1099 27 1092 12 1097 28 1086 13 1106 29 1091 14 1105 30 1099 15 1100 31 16 1103 CA-#804 04/10/85 QDP-ZZ-04204 Page 2 of 4

e s

Part D OPERATING DATA REPORT DOCKET NO.

50-483' UNIT NAME CALLAWAY UNIT 1 DATE 10/6/86 (Rev.11/7/86)

COMPLETED BY S. R. EVANS TELEPHONE 314/676-8742 OPERATING STATUS (YTD CUM )

1.

REPORTING PERIOD: September 1986 GROSS HOURS IN REPORTING PERIOD:

720 (6551 15613.5) 2.

CURRENTLY AUTHORIZED POWER LEVEL (MWt):

3411 MAX. DEPEND. CAPACITY (MWe-Net):

1120 DESIGN ELECTRICAL RATING (MWe-Net):

1171*

  • At stretch power level which is not currently authorized under the Operating License.

3.

POWER LEVEL TO WHICH RESTRICTED (IF ANY) (MWe-Net):

100%

4.

REASONS FOR RESTRICTION (IF ANY):

THIS MONIH YR TO DATE CUMULATIVE 5.

NUMBER OF HOURS REACTOR WAS CRITICAL...............

718.6 5097.6 13561.1 6.

REACTOR RESERVE SHUTDOWN HOURS.....................

0 0

0 7.

HOURS CENERATOR ON LINE............................

717.2 4915.5 13102.9 8.

UNIT RESERVE SHUTDOWN HOURS........................

0 0

0 9.

CROSS THERMAL ENERGY GENERATED (MWH)...............

2,395,748 15,596,462 41,614,015

10. CROSS ELECTRICAL ENERGY GENERATED (MWH)............

807,309 5,235,976 14,049,919

11. NET ELECTRICAL ENERGY GENERATED (MWH)..............

768,584 4,969,478 13,338,265

12. REACTOR SERVICE FACTOR.............................

99.8%

77.8%

86.9%

13. REACTOR AVAILABILITY FACTOR........................

99.8%

77.8%

86.9%

14. UNIT SERVICE FACIOR................................

99.6%

75.a 83.9%

l

15. UNIT AVAILABILITY FACIOR...........................

99.6%

75.0%

83.9%

i l

16. UNIT CAPACITY FACTOR (Using MDC)...................

95.3%

67.7%

76.3%

~

17. UNIT CAPACITY FACTOR (Using Design MWe)............

91.2%

64.8%

73.0%

l 1 18. UNIT IVRCED OUTAGE RATE............................

0.4%

4.8%

5.7%

19. SHUTDOWNS SCHEDULED OVER NEXT 6 MONTHS (TYPE, DATE, AND DURATION OF EACH): None l

20.

IF SHUT DOWN AT END OF REPORTING PERTOD, ESTIMATED DATE OF STARTUP:

l CA-#804 l

04/10/85 l

QDP-ZZ-04204 l

l Page 3 of 4 I

1

. ^

Part E UNIT SHUTDOWNS AND POWER REDUCTIONS DOCKET NO.

50-483 UNIT NAME CALIAWAY UNII 1 DATE 10/6/86 (Rev. 11/7/86)

COMPLETED BY S. R. EVANS TELEPHONE 314/676-8742 REPORT MONTH: SEPTEMBER 1986 METHOD OF TYPE SHUTTING DOWN F: FORCED DURATION THE REACTOR OR NO.

DATE S: SCHEDULED (HOURS)

REASON REDUCING POWER CORRECTIVE ACTIONS / COMMENTS 20.

9/9/86 F

2.8 A

3 Reactor trip on Icv loop 2 RCS flow signal while returning a flow transmitter to service following its replacement.

LER 66-030-00

SUMMARY

REAS(N METHOD A: E(UIPMENT FAILURE (EXPLAIN) 1: MANUAL B: M4 INT. OR TEST 2: MANUAL SCRAM C: RETUELING 3: AUTOMATIC SCRAM D: PlGULATORY RESTRICTION 4: OTHER (EXPLAIN)

E: OTERATOR TRAINING AND LIGNSE EXAMINATION F: AIMINISTRATIVE C: 0:EMTIONAL ERROR (EXPLAIN)

CA-#804 H: O'1IER (EXPLAIN) 04/10/85 QDP-ZZ-04204 Page 4 of 4