Corrected Monthly Operating Rept for June 1986,changing Forced Outage to Scheduled Outage
ML20212M025
Person / Time
Site: Callaway Ameren icon.png
Issue date: 06/30/1986
From: Evans S
UNION ELECTRIC CO.
To:
Shared Package
ML20212M003 List:
References
NUDOCS 8701290473
Download: ML20212M025 (5)


Text

i DOCKET NO.

50-483 UNIT NAME CALLAWAY UNIT 1 DATE 7/14/86 (Revised 8/5/86)(Revised 11/7/86)

COMPLETED BY S. R. EVANS TELEP110NE 314/676-8742 PART A OPERATIONS SUdfARY Plant operated at 100% power with the following exceptions:

1) 6/06/86 - Low pressure reactor trip.
2) 6/21/86 - Reactor trip on S/C lo-lo level.

Reduced power due to the following:

1) 6/13/86 - Scheduled power reduction for maintenance.
2) 6/17/86 - Forced power reduction due to trip of circulating water pump.

PART B PORY AND SAFETY VALVE

SUMMARY

None CA-#804 04/10/85 QDP-ZZ-04204 fogK05000483-3 861117 D

R Page 1 of 4 PDR

,9 Part C AVERAGE DAILY UNIT POWER LEVEL DOCKET NO.

50-483 UNIT NAME CALLAWAY UNIT 1 DATE 7/14/86 (Rev. 8/5/86)

(Rev. 11/7/86)

COMPLETED BY S. R. EVANS TELEPHONE 314/676-6742 MONTH:

JUNE 1986 AVERAGE DAILY POWER LEVEL AVERAGE DAILY POWER LEVEL DAY (MWe-Net)

DAY (MWe-Net) 1 994 17 1030 2

1082 18 1071 3

1077 19 1071 4

1074 20 1073 5

1083 21 183 6

777 22 0

7 265 23 0

8 899 24 0

9 1065 25 80 10 1066 26 424 11 1072 27 1015 12 1074 28 1094 13 1030 29 1095 14 717 30 1093 15 893 31 16 1062 CA-8804 04/10/85 QDP-Z2-04204 Page 2 of 4

,v P rt D OPERATING DATA REPORT DOCKET NO.

50-483 UNIT NAME CALLAWAY UNIT 1 DATE 7/14/86 (Rev. 8/5/86)

(Rev. 11/7/86)

COMPLETED BY S. R. EVANS TELEPHONE 314/676-8742 OPERATING STATUS (Y1D CUM )

1.

REPORTING PERIOD: June 1986 GROSS !!OURS IN REPORTING PERIOD:

720 (4343 13405.5) 2.

CURRENTLY AUT!!ORIZED POWER LEVEL (MWt):

3411 MAX. DEPEND. CAPACITY (We-Net):

1120 DESIGN ELECTRICAL RATING (HWe-Net):

1171*

  • At stretch power level which is not currently authorized under the Operating License.

3.

POWER LEVEL TO WIIICH RESTRICTED (IF ANY) (MWe-Net):

100%

4.

REASONS MR RESTRICTION (IF ANY):

THIF MONTH YR TO DATE CUMULATIVE 5.

NUMBER OF HOURS REACTOR WAS CRITICAL...............

624.8 2962.7 11426.2 6.

REACTOR RESERVE SHUTDOWN HOURS.....................

0 0

0 7.

HOURS GENERATOR ON LINE............................

608 2812.5 10999.9 8.

UNIT RESERVE SHUTDOWN 110URS........................

0 0

0 9.

GROSS THER* AL ENERGY GENERATED (&11)...............

1,891,846 8,684,936 34,702,488 10 CROSS ELECTRICAL ENERGY GENERATED (511)............

620,885 2,918,138 11,732,081

11. NET ELECTRICAL ENERGY CENERATED (MWil)..............

586,973 2,766,355 11,135,142

12. REACTOR SERVICE FACTOR.............................

86.8%

68.2%

E5.2%

13. REACTOR AVAILABILITY FACTOR........................

86.8%

68.2%

85.2%

14. UNIT SERVICE FACTOR................................

84.4%

64.8%

82.1%

1

15. UNIT AVAILABILITY FACTOR...........................

84.4%

64.8%

82.1%

16. UNIT CAPACITY FACTun (Using MDC)...................

72.8%

56.9%

74.2%

17. UNIT CAPACITY FACTOR (Using Design MWe)............

69.6%

$4.4%

70.9%

1 18. UNIT FURCED OUTAGE RATE............................

15.6%

4.9%

5.8%

i 19 SHUTDOWHS SCHEDULED OVER NEXT 6 MONTHS (TYPE, DATE, AND DURATION OF EACH): None i

20.

IF SHUT DOWN AT END OF REPORTING PERIOD, ESTIMAIID DATE OF STARTUP:

CA-8804 04/10/85 QDP ZZ 04204 Page 3 of 4

i Part E UNIT SHUIDOWNS AND POLTR REDUCTIONS DOCKET NO.

50-483 UNIT NAME CALIJLWAY UNIT 1 f

IlhM&)

l CXPfPLETED BY S. R. EVANS I

TELEPHONE 314/676-8742 i

REPORT MONTH: JUhT 1986 l

METHOD OF TYPE SHUITING DOLN F: FDRCED DURATION THE REACTOR OR NO.

DATE S: SCHEDULED (HOURS)

REASON REDUCING POWER CORRECTIVE ACTIONS / COMMENTS l

11.

6/6/86 F

7.5 G

3 Iow pressure reactor trip. LER 86-019-00 12.

6/13/86 S

O E

4 Reduced reactor power to 70% for maintenance on main feedwater pump, circulating water pump and feedwater heater string.

13.

6/17/86 F

0 A

1 Reduced reactor to 75% power due to trip of circulating water pump caused by phase unbalance relay, i

14.

6/21/86 F

104.5 A

3 Reactor trip on S/G lo-lo level due to circuit card failure. LER 86-022-00

SUMMARY

REASON METHOD i

l A: EQUIPMENT FAILURE (EXPLAIN) 1: MAhTAL B: MAINT. OR TEST 2: MANUAL SCRAM C: RETUELING 3: AUTOMATIC SCRAM D: REGUULIORY RESTRICTION 4: OTHER (EXPLAIN)

E: OPERATOR TRAINING AND LICENSE EXAMINATION F: ADMINISTRATIVE G: OPERATIONAL ERROR (EXPIAIN)

CA-#804 H: OTHIR (EXPLAIN) 04/10/85 QDP-ZZ-04204 Page 4 of 4