ML20211J486

From kanterella
Jump to navigation Jump to search

Discusses Completion of Licensing Action for GL 92-08, Thermo-Lag 330-1 Fire Barriers, Dtd 921217,for Plant
ML20211J486
Person / Time
Site: Duane Arnold 
Issue date: 10/02/1997
From: Kelly G
NRC (Affiliation Not Assigned)
To: Leslie Liu
IES UTILITIES INC., (FORMERLY IOWA ELECTRIC LIGHT
References
GL-92-08, GL-92-8, TAC-M82809, TAC-M85547, NUDOCS 9710080147
Download: ML20211J486 (4)


Text

%

(0 - 3 3 e' OCeog t

UNITED STATES 3

j NUCLEAR REGULATORY COMMISSION i

2 WASHINGTON, D.C. 30666 4001

%...../

October 2, 1997 Mr. Lee Liu I

Chairman of the Board and Chief Executive Officer IES Utilities Inc.

P. O. Box 351 Cedar Rapids, IA 52406-0351

SUBJECT:

COMPLETION OF LICENSING ACTION FOR GENERIC LETTER 92-08, "THERMO-LAG 330-1 FIRE BARRIERS," DATED DECEMBER 17,1992, FOR DUANE ARNOLD ENERGY CENTER (TAC NO. M85547)

Dear Mr. Liu:

By letters dated July 15, May 16, and January 3,1997; December 13 and October 17,1996; December 1, September 1, June 30, June 2, March 23, and February 28,1995; December 12, November 22, and February 14,1994; and April 5,1993; IES Utilities Inc., responded to Gerseric Letter (GL) 92-08, 'Thermo-Lag 330-1 Fire Barriers," dated December 17,1992, and follow-up requests for additional information dated October 16, and August 22,1996; February 14,1995; December 23 and September 19,1994; and December 21 and June 16,1993; in regard to Thermo-Lag 330-1 fire carriers installed at the Duane Arnold Energy Center (DAEC).

The U.S. Nuclear Regulatory Commission (NRC) staff has reviewed your letters. Your responses stated that you have performed a safe shutdown reanalysis, rerouted cables, removed and replaced Thermo-Lag from all continuously energized power cable raceways, and eliminated reliance on fire barrier material for all but one enclosure containing continuously energized power cables. This enclosure, containing cables and penetrations, will be protected by Darmatt fire barrier material. On the basis of its review, the staff has determined that you have provided the information requested in GL 92-08 and the actions tracked by TAC No.

M85547 are complete.

However, based on your December 13,1990, response, there remains an open issue involving ampacity derating caused by the use of Darmatt which emerged as a result of the GL 92-08 review. The resolution of this ampacity derating issue is being treated generically and tracked by TAC No. M82809.

Please advise the staff in writing if you change your schedule or the resolution plans described in your submittals, include the bases for any changes in your corrective action plan and a justification for any changes in your schedule. In addition, in accordance with GL 92-08, please advise the staff in writing when the actions described in your submittals have been implemented. GL 92-08 provides the Office of Management and Budget clearance for this

-Ag information request.

w M1

(

t 9710080147 971002 lR ADOCK 0500 1

L.Liu You should retain all documentation related to the resolution of the concerns with Thermo-Lag 330-1 fire barrier systems for future NRC audits or inspections, if you have any questions regarding this mt tier, please contact me at 301-415-3028.

Sincerely, Original signed by:

Glenn B. Kelly, Senior Project Manager Project Directorate 111-3 Division of Reactor Projects Ill/IV Office of Nuclear Reactor Regulation Docket No. 50-331 cc: See next page Distribution:

Docket File PUBLIC PDlll-3 R/F OGC ACRS GMarcus EAdensam (EGA1)

GGrant, Rill G:\\DUANEARN\\GL9208.LTR -

  • SEE PREVIOUS CONCURRENCE OFC LA:PD33 C

PD33 C

SPLB EELB l

PD33:PM C PD33:PMl C NANE CBoyle My DWeaver*

LMarch' JCalvo*

Pray (//g4 GKelly:am DATE 10/,3./97 U 6/10/97 7/29/S7 9/23/97 f(T2J07

/c/ I/97 OFFICIAL RECORD COPY _-

N\\

L Liu,

You should retain all documentation related to the resolution of the concerns with Thermo-Lag 330-1 fire barrier systems for future NRC audits or inspections.

If you have any questions regarding this matter, please contact me at 301-415 3028.

Sincerely, Original signed by:

Glenn B. Kelly, Senior Project Manager Project Directorate lil 3 Division of Reactor Projects ill/IV Office of Nuclear Reactor Regulation Docket No. 50 331 cc: See next page Distribution:

Docket File PUBLIC PDill-3 R/F OGC ACRS GMarcus EAdensam (EGA1)

GGrant, Rill G:\\DUANEARN\\GL9208.LTR

  • SEE PREVIOUS CONCURRENCE OFC LA:PD33 C

PD33 C

SPLB l EELB PD33:PJM C PD33:PM

~

C

, NAtE CBoyle (M DWeaver*

LMarch*

JCalvo*

Pray %dM.

GKelly:am DATE 10/;3 /97 0 6!10/97 7/29/97 9/23/97 f(l'2.J97

/0/ f/97 OFFICIAL RECORD COPY

.s e

Lee Liu Duane Arnold Energy Center IES Utilities Inc.

cc:

Jack Newman, Esquire Kathleen H. Shea, Esquire Morgan, Lewis, & Bocklus 1800 M Street, NW.

Washington, DC 20036 5869 Chairman, Linn County Board of Supervisors Cedar Rapids, IA 52406 IES Utilities Inc.

ATTN: Gary Van Middlesworth l

Plant Superintendent, Nuclear i

3277 DAEC Road Palo, IA 52324 John F. Franz, Jr.

Vice President, Nuclear Duane Arnold Energy Center 3277 DAEC Road Palo, IA 52324 Ken Peveler Manager of Regulatory Performance Duane Arnold Energy Center 3277 DAEC Road Palo,IA 52324 U.S. Nuclear Regulatory Commiselon Resident inspector's Office Rural Route #1 Palo, IA 52324 Regional Administrator, Rlll U.S. Nuclear Regulatory Commission 801 Warrenville Road Lisle, IL 60532-4531 Parween Baig Utilities Division Iowa Department of Commerce Lucas Office Building,5th floor Des Moines, lA 50319