_
6
'+
t DUKE POWER Gom%NY P.O. HOx 33180 CitARLOTTE, N 0. 28242 HAI. H. TUCKER TELEPIIONE vna ressment (704) 373-4tk'M NtCLeAR PWoen'CTEON April 15, 1986 d r. Harold R. Denton, Director Office of Nuclear Reactor Regulation U.S. Nuclear Regulatory Commission Washington, D.C.
20555 Attention:
Mr. B.J. Youngblood, Director PWR Project Directorate No. 4
Subject:
McGuire Nuclear Station Docket Nos. 50-369 and 50-370 Diesel Generator Reliability, Testing, and Surveillance; Supplemental Response
Dear Mr. Denton:
By letter of July 10, 1985 (Attachment I), Duke Power Company submitted proposed changes to the Technical Specifications for its McGuire Nuclear Station. By letter of December 1, 1985, the NRC Staff requested additional information relative to the determination that the changes would not involve a Significant Hazards Consideration, as defined in 10 CFR 50.91.
Attachment II itemizes the changes and provides the basis for the NSHC determination. Note that as a result of discussions with the NRC staff in the intervening period of time, two itens have been slightly revised with respect to the July 10 submittal. First, references to the description of the Additional Reliability Program (Table 4.8-2) have been deleted. This proaram may be subject to revision, as necessary, to reflect increased experience and data base with respect to the diesels. The ARP is essentially a maintenance function that need not be controlled by Tech Specs.
Second, Surveillance requirement 4.8.1.1.2.e.7) has been rewritten to require a restart and load-energizir; test within 5 minutes, rather than while within an operating temperatuwe band. Thus, the test is virtually identical to the existing requirements, except that the test need not be performed following the 24-hour run.
The above changes, and the concomitant changes to the Technical Justification, are included in Attachment I.
8604210251 860415 gO[(
PCR ADOCK 05000369 P
PDR i i
~
O Harold R.Denton April 15, 1986 Page 2 This letter supplements a previous License Amendment request; therefore, no additional fees are required.
Very truly yours, B&/~~
Hal B. Tucker SAG /jgm Attachment xc:
Dr. J. Nelson Grace, Regional Administrator U.S. Nuclear Regulatory Commission - Region II 101 Marietta Street, Suite 2900 Atlanta, Georgia 30323 Mr. W.T.' Orders Senior Resident Inspector McGuire Nuclear Station Mr. Dayne Brown, Chief Radiation Protection Branch Division of Facility Services Department of Human Resources P.O. Box 12200 Raleigh, NC 27605 1
O Harold R. Denton April 15, 1986 Page 3 l
bxc: N.A. Rutherford R.L. Gill R.O. Sharpe J.B. Day G.W. Hallman l
T.A. Ledford l
Joe Lukowski T.L. McConnell E.O. McCraw MC-813.20 I
A s I ACHMENT I o
a DQCE POWER Goxaur P.O. BOX 33189 cxAntorrc. x.c. 28242 HAL B. TUCKER TE LE PH OVE (704) 373 453g Ju!y 10, 1985 1
Mr. Harold R. Denton, Director Office of Nuclear Reactor Regulation U. S. Nuclear Regulatory Commission Washington, D. C. 20555 Attention:
Ms. E. C. Adensam, Chief Licensing Branch No. 4
Subject:
McGuire Nuclear Station Docket Nu=ber 50-369/370 Diesel Generator Reliability. Testing, and Surveillance
Dear Mr. Denton:
Attached are proposed license amend =ents for McGuire Nuclear Station Facility Operating Licenses NPF-9 (Unit 1) and NPF-17 (Unit 2).
The proposed changes to the Technical Specifications concern diesel generator testing and surveillance, and are presented in five areas: A change to separate the required 24-hour run of the Diesel Generator from an immediate test of the Engineered Safeguards Features; changes to Action Statements to be followed in the event of electrical power supplies being inoperable, pursuant to Generic Letter 84-15; Reduction of Required Testing, also pursuant to Generic Letter 84-15; Deletion of an Excessive Surveillance Requirement, pursuant to Generic Letter 83-30; and addition of Alternate Fuel Oil Testing Criteria.
Attachment I contains the proposed Technical Specification changes. Attachment 11 provides a technical Justification and Safety Analysis in support of the proposed changes. Attachment III provides an analysis conforming to the standards contained in 10CFR50.92 as required by 10CFR50.91. This analysis concludes that the proposed amendments would not have adverse safety or environmental impact.
This request involves one application for amendment to the McGuire's Technical Specifications. Accordingly, pursuant to 10CFR170.21, a check for $150.00 is enclosed.
Please feel free to contact us if you require any additional information.
Very truly yours, s/Hal B. Tucker Hal B. Tucker SAG /mj f g,v"
-g a v If Attachments
pg,3 Mr. Harold R. Denton, Director.
July 10, 1985 Page cc:
Dr. J. Nelson Crace, Regional Administrator U. S. Nuclear Regulatory Commission Region II 101 Marietta Street, Suite 3100 Atlanta, Georgia 30323
)
W. T. Orders Senior Resident Inspector McGuire F1 clear Station Mr. Dayne Brown, Chief Radiation Protection Branch l
Division of Facility Services l
Department of Human Resources l
P. O. Box 12200 i
Raleigh, North Carolina 27605 l
bRf Mr. Harold R. Denton, Director July 10, 1985 Page HAL B. TUCKER, being duly sworn, states that he is Vice President of Duke Power Company; that he is authorized on the part of said Company to sign and file with the Nuclear Regulatory Commission this revision to the McGuire Nuclear Station License Nos. NPF-9 and NPF-17 and that all statements and matters set forth therein are true and correct to ;he best of his knowledge.
s/Hal B. Tucker Hal B. Tucker, Vice President Subscribed and sworn to before me this 10 th day of July,1985.
s/ Sue C. Sherrill Notary Public My Co= mission Expires:
September 20, 1989
f+rc 1 Mr. Harold R. Denton, Director July 10. 1985 Page bec:
-K. S. Canady N. A. Rutherford R.-L. Gill P. B. Nardoci W. H. McDowell-J. B. Day R. W. Quelletta.
E. O. McCraw (MNS)
P. M. Abraham M. D. McIntosh T. L. McConnell (MNS)
D. H. Gabriel G. W. Hallman g
-vy
,ne---nn,
,-yw,,c,w,,-m, y -,
..o--7 g,ye-nr.-w.,
wen--
e,-w- - -. - - -, - - - -.
,-r---m.,
f
~*
A Y
l ATTACHMENTS:
I.
- fhe Proposed Changes to Technical Specifications II. Justification and Safety Evaluation III. Analysis of Significant Hazards Consideration
N.
3/4.8 ELECTRICAL POWER SYSTEMS 3/4.8.1 A.C. SOURCES OPERATING LIMITING CONDITION FOR OPERATION
- 3. 8.1.1 As a minimum, the following A.C. electrical power sources shall be OPERABLE:
a.
Two physically independent c rcuits between the offsite transmission i
network and the Onsite Essential Auxiliary Power System, and b.
Two separate and independent diesel generators, each with:
1)
A separate day tank containing a minimum volume of 120 gallons of fuel, 2)
A separate Fuel Storage System containing a minimum volume of 28,000 gallons of fuel, and 3)
A separate fuel transfer pump.
APPLICABILITY:
MODES 1, 2, 3, and 4.
ACTION:
a.
With an offsite circuit of the above required A.C. electrical power sources inoperable, demonstrate the OPERABILITY of the remaining off-site A.C. sources by performing surveillance requirement 4.8.1.1.la.
within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter; demonstrate the operability of two diesel generators by performing surveillance l
requirement 4.8.1.1.2.a.4 within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> unless this surveillance was performed within the previous 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />, or unless the diesel is operating; restore at least two offsite circuits and two diesel I
generators to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUT 00WN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.
b.
With one offsite circuit and one diesel generator of the above re-quired A.C. electrical power sources inoperable *, demcnstrate the OPERABILITY of the remaining offsite A.C. sources by performing surveillance requirement 4.8.1.1.la. within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter; demonstrate the operability of the remaining diesel generator by performing surveillance requirement 4.8.1.1.2a.4 within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> unless this surveillance was performed within the i
previous 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />, or unless the diesel is operating; restore at least one of the inoperable sources to OPERABLE status within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in
- A diesel generator shall be considered to be inoperable from the time of failure until it satisfies the requirements of Surveillance Requirement 4.8.1.1.2a.4 ELECTRIC POWER SYSTEMS.
_ _ _ mgCSUJE - UNITS 1 and 2 3/4 8-1 varrai W
hR ELECTRICAL POWER SYSTEMS SURVEILLANCE REQUIREMENTS (Continued) l ACTION: (Continued)
COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />; with the diesel generator restored to OPERABLE status, follow action statement A; with the offsite circuit restored to OPERABLE, follow action statement C.
c.
With a diesel generator of the above required A.C. electrical power sources inoperable, demonstrate the OPERABILITY of the A.C. offsite sources by performing Surveillance Raquirement 4.8.1.1.la within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter; and unless the inoperability of the die el was due to preplanned testing or maintenance, demonstrate the operability of the remaining diesel generator by performing Surveillance Requirement 4.8.1.1.2a.4 within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />; restore diesel generators to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or be in at least H0T STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SPUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.
^ ^ "
. C-2 p;M m faib u Te, th;
...pM a Maca' i dict:d '
7 6!:
n th; ^.dditic 21 9: lid i'it; ^.:tient p e n d ;d.n Touie '.^ 2 ;nd it; ett: 9 rts.
With one diesel generator inoperable verify in addition to ACTION a.
or b. above, that:
1.
All required systems, subsystems, trains, components, and devices that depend on the remaining OPERABLE diesel generator as a source of emergency power are also OPERABLE, and 2.
When in MODE 1, 2, or 3 with a steam pressure greater than 900 psig, the steam-driven auxiliary feedwater pump is OPERABLE.
If these conditions are not satisfied within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />, d.
With two of the above required offsite A.C. circuits inoperable, cemonstrate the OPERABILITY of two diesel generators by performing surveillance requirement 4.8.1.1.2a.4) within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />, unless the diesel generators are already operating; restore at least one of the inoperable offsite sources to OPERABLE status within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> or be in at least H0T STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in cold shutdown within the following, 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.
With only one offsite source restored, follow action statement a.
e.
With two of the above required diesel generators inoperable, demonst-rate the OPERABILITY of two offsite A.C. circuits by performing Surveillance Requirement 4.8.1.1.la. within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter; restore at least one of the inoperable diesel generators to OPERABLE status within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> or be in at least H0T STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />. With one diesel generator restored, follow action statement c.
MCGUIRE - UNITS 1 and 2 3/4 8-2
k[
ELECTRICAL POWER SYSTEMS SURVEILLANCE REQUIREMENTS (Continued) 4.8.1.1.1 Each of the above required independent circuits between the offsite transmission network and the onsite Essential Auxiliary Power System shall be:
a.
Determined OPERABLE at least once per 7 days by verifying correct breaker alignments, indicated power availability, and b.
Demonstrated OPERABLE at least once per 18 months during shutdown by transferring (manually and automatically) unit power supply from the normal circuit to the alternate circuit.
4.8.1.1.2 Each diesel generator shall be demonstrated OPERABLE:
a.
In accordance with the frequency specified in Table 4.8-1 on a STAGGERED TEST BASIS, by:
1)
Verifying the fuel level in che day tank, 2)
Verifying the fuel level in the fuel storage tank, 3)
Verifying the fuel transfer pump starts and transfers fuel from the storage system to the day tank, 4)
Verifying the diesel starts from ambient condition and accelerates to at least 488 rpm in less than or equal to 11 seconds *.
The generator voltage and frequency shall be at least 4160 volts and 57 Hz within 11 seconds after the start signal.
The diesel generator shall be started for this test by using one of the following signals:
d)
Manual, or b)
Simulated loss-of-offsite power by itself, or c)
Simulated loss-of-offsite power in conjunction with an ESF Actuation test signal, or d)
An ESF Actuation test signal by itself.
5)
Verifying the generator is synchronized, loaded to greater than or equal to 3000 kW in less than or equal to 60 seconds, and to 4000 kW within 10 minutes and operates for at least 60 minutes, and
- The diesel generator start (11 sec) from ambient conditions shall be per-formed at least once per 184 days in these surveillance tests.
All other engine starts for the purpose of this surveillance testing may be preceded by an engine prelube period and/or other warmup procedures recommended by the manufacturer so that mechanical stress and wear on the diesel engine is minimized.
MCGUIRE - UNITS 1 and 2 3/4 8-3
f ELECTRICAL POWER SYSTEMS SURVEILLANCE REQUIREMENTS (Continued) 6)
Verifying the diesel generator is aligned to provide standby power to the associated emergency busses, b.
By removing accumulated water:
1)
From the fuel oil day tank at least once per 31 days and after each occasion when the diesel is operated for greater than 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />, and 2)
Fr u the fuel oil storage tank at least once per 31 days, c.
By sampling new fuel oil in accordance with ASTM D4057-81 prior to addition to the storage tanks and:
1)
By verifying in accordance with the tests specified in ASTM 0975-81 prior to addition to the storage tanks that the sample has:
a)
An API Gravity of within 0.3 degrees at 60 F or a specific gravity of within 0.0016 at 60/60*F, when compared to the supplier's certificate or an absolute specific gravity at 60/60 F of greater than or equal to 0.83 but less than or equal to 0.89 or an API gravity at 60"F of greater than or equal to 27 degrees but less than or equal to 39 degrees.
b)
A Kinematic viscosity at 40'C of greater than or equal to 1.9 centistokes, but less than or ec il to 4.1 centistokes, (alternatively, Saybolt viscosity, SUS at 100 F of greater than or equal to 32.6, but less than or' equal to 40.1), if gravity was not determined by comparison with the supplier's certification.
c)
A flash point equal to or greater than 125 F, and d)
A clear and bright appearance with proper color when tested in accordance with ASTM D4176-82.
2)
By verifying within 31 days of obtaining the sample that the other properties specified in Table 1 of ASTM D975-81 are met when tested in accordance with ASTM D975-81 except that the analysis for sulfur may be performed in accordance with ASTM D1552-79 or ASTM D2622-82.
d.
At least once every 31 days by obtaining a sample of fuel oil from the storage tanks in accordance with ASTM D2276-78, and verifying that total particulate contamination is less than 10 mg/ liter when checked in accordance with ASTM D2276-78, Method A.
At least once per 18 months, during shutdown, by:
e.
MCGUIRE - UNITS 1 and 2 3/4 8-4
ELECTRICAL POWER SYSTEMS SURVEILLANCE REQUIREMENTS (Continued) 1)
Subjecting the diesel to an inspection in accordance with procedures prepared in conjunction with its manufacturer's recommendations for this class of standby service; 2)
Verifying the generator capability to reject a load of greater than or equal to 576 kW while maintaining voltage at 4160 i 420 volts and frequency at 60 1 1.2 Hz; 3)
Verifying the generator capability to reject a load of 4000 kW without tripping.
The generator voltage shall not exceed 4784 volts during and following the load rejection; 4)
Simulating a loss-of-offsite power by itself, and:
a)
Verifying deenergization of the emergency busses and load shedding from the emergency busses, and b)
Verifying the diesel starts on the auto-start signal, energizes the emergency busses with permanently connected loads within 11 seconds, energizes the auto-connected blackout loads through the load sequencer and operates for greater than or equal to 5 minutes while its generator is loaded with the blackout loads.
After energization, the steady-state voltage and frequency of the emergency busses shall be maintained at 4160 1 420 volts and 60 i 1.2 Hz during this test.
5)
Verifying that on an ESF actuation tests signal, without loss-of-offsite power, the diesel generator starts on the auto-start signal and operates on standby for greater than or equal to 5 minutes.
The generator voltage and frequency shall be at least 4160 volts and 57 Hz within 11 seconds after the auto-start signal; the steady-state generator voltage and frequency shall be maintained within 4160 i 420 volts and 60 1 1.2 Hz during this test; 6)
Simulating a loss-of-offsite power in conjunction with an ESF actuation test signal, and a)
Verifying deenergization of the emergency busses and load shedding from the emergency busses; b)
Verifying the diesel starts on the auto-start signal, energizes the emergency busses with permanently connected loads within 11 seconds, energizes the auto-connected emergency (accident) loads through the load sequencer and operates for greater than or equal to 5 minutes while its generator is loaded with the emergency loads.
After energization, the steady-state voltage and frequency of the emergency busses shall be maintained at 4160 t 420 volts and 60 1 1.2 Hz during this test; and MCGUIRE - UNITS 1 and 2 3/4 8-5
ATTACHMENT I ELECTRICAL POWER SYSTEMS SURVEILLANCE REQUIREMENTS (Continued) c)
Verifying that all automatic diesel generator trips, except engine overspeed, lube oil pressure, and generator differential are automatically bypassed upon loss of voltage on the smergency bus concurrent with a safety Injection Actuation signal.
Additionally, all diesel generator breaker trips, except generator time overcurrent, are verified to be automatically bypassed upon concurrent loss of voltage on the emergency bus and a Safety Injection Actuation signal.
-Tr. OPGRfyrtM(o... L vgera =4 until temperature stabilization is i
7) ui=...
achieved.
L i; U.
J.;.,il i.- J tt.:. 2 0"I cf n....J vesc:t N 4 4 Wig OfteNTES i.=o.g., A. m, restart and perform specification 4.8.1.1.2e.6)b).
8)
Verifying the diesel generator operates for at least 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.
During the first 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> of this test, the diesel generator shall be loaded to greater than or equal to 4400 kw and durin~g the remaining 22 hours2.546296e-4 days <br />0.00611 hours <br />3.637566e-5 weeks <br />8.371e-6 months <br /> of this test, the diesel generator shall be loaded to great =c than or equal to 4000 kw.
The generator voltage and frequency shall be at least 4160 volts and 57 Hz within 11 seconds after the start signal.
The steady-state generator voltage and frequency shall be maintained within 4160 1 420 volts and 60 t 1.2 Hz during this test.
M
- 9) Verifying that the auto-connected loads to each diesel generator do not exceed the 2-hour rating of 4400 kw;
- 10) Verifying the diesel generator's capability to:
a)
Synchronize with the offsite power source while the generator is loaded with its emergency loads upon a simulated restoration of offsite power.
b)
Transfer its loads to the offsite power source, and c)
Be restored to its standby status.
- 11) Verifying that with the diesel generator operating in a test mode, connected to its bus, a simulated Safety Injection signal overrides the test mode by:
(1) returning the diasel generator to star.dby operation, and (2) automatically energizing the emergency loads with offsite power; MCGUIRE - UNITS 1 and 2 3/4 8-6
ELECTRICAL POWER SYSTEMS SURVEILLANCE REQUIREMENTS (Continued)
- 12) Verifying that the fuel transfer pump transfers fuel from each fuel storage tank to the day tank of each diesel via the in-stalled cross-connection lines;
- 13) Verifying that the automatic load sequence timer is OPERABLE with the interval bgtween each load block within the tolerances shown in Table 4.8-4; 2
- 14) Verifying that the following diesel generator lockout features
~ prevent diesel generator starting only when required:
a)
Turning gear engaged, and b)
Emergency stop.
- 15) Verifying that with all diesel generator air start receivers pressurized to less than or equal to 220 prig and the compressors secured, the diesel generator starts at least 2 time from ambient conditions and accelerates to at least 488 rpm in less than or equal to 11 seconds.
f.
At least once per 10 years or af ter any modifications which could "
affect diesel generator interdependence by starting both diesel generators simultaneously, during shutdown, and verifying that both diesel generators accelerate to at least 488 rpm in less than or equal to 11 seconds; and g.
At least once per 10 years by:
1)
Draining each fuel oil storage tank, removing the accumulated sediment and cleaning the tank using a sodium hypochlorite solution, and 2)
Performing a pressure test of those portions of the diesel fuel oil system designed to Section III, subsection ND of the ASME Code at a test pressure equal to 110% of the system design pressure.
- 4. 8.1.1. 3 Reports - All diesel generator failures, valid or non-valid, shall be reported to the Commission pursuant to Specification 6.9.1.
Reports of diesel generator failures shall include the information recommended in Regulatory Position C.3.b of Regulatory Guide 1.108, Revision 1, August 1977.
q 4.8.1.1.4 Diesel Generator Batteries - Each diesel generator 125-volt battery bank and charger shall be demonstrated OPERABLE:
a.
At least once per 7 days by verifying that:
1)
The electrolyte level of each battery is above the plates, and MCGUIRE - UNITS 1 and 2 3/4 8-7
4 ELECTRICAL POWER SYSTEMS SURVEILLANCE REQUIREMENTS (Continued) 2)
The overall battery voltage is greater than or equal to 125 volts under a float charge.
b.
At least once per 18 months by verifying that:
1)
The batteries, cell plates and battery racks show no visual indication of physical damage or abnormal detarioration; 2)
The battery-to-battery and terminal connections are clear, tight, free of corrosion and coated with anti-corrosion material; and 3)
The battery capacity is adequate to supply and maintain in OPERABLE status its emergency loads when subjected to a battery service test.
s MCGUIRE - UNITS 1 and 2 3/4 8-8
\\
TABLE 4.8-1 DIESEL GENERATOR TEST SCHEDULE NUMBER OF' FAILURES IN LAST 20 VALID TESTS
- TEST FREQUENCY
<1 At least once per 31 days
>2 At least once per 7 days **
Criteria for determining number of failures and number of valid tests shall be in accordance with Regulatory Position C.2.e of Regulatory Guide 1.108, Revision 1, August 1977, except the last 20 tests are determined on a per Diesel Generator basis.
For the purposes of this test schedule, only valid tests conducted after the OL issuance date shall be included in the comput-ation of the "last 20 valid tests." Entry into this test schedule shall be made at the 31 day test frequency.
Any successful demonstration of 4.8.1.1.2e.4a and b or 4.8.1.1.2e.6a and b whether simulated or actual will be classified as a valid successful test.
- This test frequency shall be maintained until seven consecutive failt.re-free demands have been performed and the number of failures in the last 20 valid demands has been reduced to one or less.
MCGUIRE - UNITS 1 and 2 3/4 8-9
~
TABLE 4.8-2 ADDITIONAL REL:ABILI ACTIONS No. of failu s in last 20 valid tests or 1 valid tes Action 3
Within 14 days prepare and maintain a report for NRC audit describing the diesel generator reliability improvement program implemented at the site.
Minimum equirements for the report are i
cated in Attachment 1 to this tab' 5
11 Declare diesel generator in-operable.
rform a requali-fication test ogram to the affected diesel nerator.
Re-qualification test rogram re-quirements are indic ed in to this t le.
THis TfBLE, Ahlb ITs ATTACHf1EAITS G)!LL A)oT' BE /A/Cujogh hrt 7ps TECH Spgc g.
MCGUIRE - UNITS 1 and 2 3/4 8-10
ATTACHMENT 1 TO TABLE 4.8-2 REPORTING REQUIREMENTS As a mi imum the Reliability Improvement Program report r NRC audit shall include:
a) a suam y of all tests (valid and invalid) that o curred within the time period er which the last 20/100 valid tests we e performed b) analysis o failures and determination of root causes of failures c) evaluation o each of the recommendations of UREG/CR-0660, "Enchancement of Onsite Emer ency Diesel Generator Reliab ity in Operating Reactors,"
with respect to heir application to the P ant d) identification of 11 actions taken or t be taken to 1) correct the root causes of failures fined in b) above d 2) achieve a general improve-ment of diesel gener or reliability e) the schedule for implem tation of e h action from d) above f) an assessment of the exist g reli ility of electric power to engineered-safety-feature equipment, Once a licensee has prepared and mai ained an initial report detailing the diesel generator reliability improv t program at his site, as defined above, the licensee need prepare only a s pl ental report witnin 14 days after each failure during a valid demand for so lon as the affected diesel generator unit continues to violate the er teria (3 0 or 6/100) for the reliability improvement program remedial a ion.
The s plemental report need only update the failure / demand history for the affected
'esel generator unit since the last report for that diesel nerator.
The su lement report shall also pre-sent an analysis of the fai re(s) with a root use determination, if possible, and shall deline te any further procedu 1, hardware or operational changes to be incorporat into the site diesel ge rator improvement program and the schedule for im ementation of those changes.
In addition to the a ve, submit a yearly data report o the diesel generator reliability if the liability improvement program has be initiated.
MCGUIRE - UNITS 1 and 2 3/4 8-11
f) _ -
-f I L U(~
._l ATTACHMENT 2 TO TABLE 4.8-2 DIESEL GENERATOR REQUALIFICATION PROGRAM (1) Perfo seven consecutive successful demands without a ailure within 30 days of he diesel generator being restored to operabl status and fourteen ansecutive successful demands without a fai ure within 75 days of the die el generator being restored to operable s atus.
(2) If a failure occurs during the first seven tests i the requal: ication test program, erformsevensuccessfuldemandswipioutanadditional failure within 0 days of the diesel generator b ng restored to operable status and four en consecutive successful dema s without a failure within 75 days o being restored to operable st tus.
(3)
If a failure occurs during the second seven t ts (tests 8 through 14) of (1) above, perform urteen consecutive succ sful demands without an additional failure wi in 75 days of the fa ure which occurred during the requalification te ing.
(4) Following the second fai re during the r qualification test program, be in at least HOT STANDBY w1 hin the next hours and COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.
(5) During requalification testin the di el generator should not be tested more frequently than at 24-hou inter als.
After a diesel generator has been suc s fully requalified, subsequent re-peated requalification tests will not required for that diesel generator under the following conditions:
(a) The number of failures in the 1 t2 valid demands is less than 5.
(b) The number of failures in the ast 100 alid demands is less than 11.
(c)
In the event that following uccessful re ualification of a diesel generator, the number of f lures is still in excess of the remedial action criteria (a and/or above) the foll ing exception will be allowed until the diesel enerator is no lon r in violation of the remedial action criteri (a and/or b above).
Requalification testing wi not be required provide that after each valid demand the number of fail res in the last 20 and/or 1 valid demands has not increased.
Once th diesel generator is no longer 'n violation of the remedial action criter above the provisions of those c iteria alone will prevail.
1 MCGUIRE - UNITS 1 and 2 3/4 8-12
k[
TABLE 4.8-/
LOAD SEQUENCING TIMES LOAD GROUP SEQUENCE TIME NUMBER (Seconds)
Initiate Timer (T,)
9.7 1 0.3 1 (T )
T, + 0.9 1 0.1 1
2 (T )
T + 5.6 1 0.4 2
o 3 (T )
T, + 9.4 + 0.6 3
4 (T )
T + 14.1 1 0.9 4
o 5 (T )
T + 18.4 1 1.2 S
o 6 (T )
T + 23.1 1 1.4 6
o 7 (T )
T, + 28.3 1 1.7 7
8 (T )
T + 530.0 1 60.0 8
o 9 (T )
T8 + 56.0 1 4.0 g
10 (TIO)
T8 + 112.3 1 7.0 MCGUIRE - UNITS 1 and 2 3/4 8-13
D
! Tl k 3/4.8 ELECTRICAL POWER SYSTEMS BASES 1
3/4.8.1, 3/4.8.2 AND 3/4.8.3 A.C. SOURCES, D.C. SOURCES AND ONSITE POWER DISTRIBUTION SYSTEMS The OPERABILITY of the A.C. and D.C power sources and associated distribution systems during operation ensures that sufficient power will be available to supply the safety-related equipment required for:
(1) the safe shutdown of the facility, and (2) the mitigation and control of accident condi-tions within~the tacility.
The minimum specified independent and redundant A.C. and D.C. power sources and distribution systems satisfy the requirements of General Design Criterion 17 of Appendix A to 10 CFR 50.
The ACTION requirements specified for the levels of degradation of the power sources provide restriction upon continued facility operation commensurate with the level of degradation.
The OPERABILITY of the power sources are consistent with the initial condition assumptions of the safety analyses and are based upon maintaining at least one redundant set of onsite A.C. and D.C.
power sources and associated distribution systems OPERABLE during accident cenditions coincident with an assumed loss-of-offsite power and single failure of the other onsite A.C. source.
The A.C. and D.C. source allowable out-of-service times are based on Regulatory Guide 1.93, " Availability of Electrical" Power Sources", December 1974.
When one diesel generator is inoperable, there is an additional ACTION requirement to verify that all required systems, subsystems, trains, components and devices, that depend on the remaining OPERABLE diesel generator as a source of emergency power, are also OPERABLE, and that the steam-driven auxiliary feedwater pump is OPERABLE.
This require-ment is intended to provide assurance that a loss-of-offsite power event will not result in a complete loss of safety function of critical systems during the period one of the diesel generators is inoperable.
The term verify as used in this context means to administratively check by examining logs or other information to determine if certain components are out-of-service for maintenance or other reasons.
It does not mean to perform the Surveillance Requirements needed to demonstrate the OPERABILITY of the component.
The ACTION requirements for diesel generator testing in the event of the inoperability I
(
of other electric power sources also reflect the potential for degradation of I
the diesel generator due to excessive testing.
This concern has developed, concurrently with increased industry experience with diesel generators, and has been acknowledged by the NRC staff in Generic Letter 84-15.
The OPERABILITY of the minimum specified A.C. and D.C. power sources and associated distribution systems during shutdown and refueling ensures that:
(1) the facility can be maintained in the shutdown or refueling condition for extended time periods, and (2) sufficient instrumentation and control capability is available for monitoring and maintaining the unit status.
The Surveillance Requirements for demonstrating the OPERABILITY of the diesel generators are in accordance with the recommendations of Regulatory Guides 1.9, " Selection of Diesel Generator Set Capacity for Standby Power Supplies," March 10,1971,1.108, " Periodic Testing of Diesel Generator Units Used as Onsite Electric Power Systems at Nuclear Power Plants," Revision 1,
lN j-ELECTRIC POWER SYSTEMS BASES A.C. SOURCES, D.C. SOURCES AND ONSITE POWER DISTRIBUTION SYSTEMS (Continued)
August 1977, and 1.137, " Fuel-Oil Systems for Standby Diesel Generators,"
Revision 1, October 1979; also, Generic Letter 84-15, which modified the testing frequencies specified in Regulatory Guide 1.108.
L-The Surveillance Requirement for demonstrating the OPERABILITY of the station batteries are based on the recommendations of Regulatory Guide 1.129,
" Maintenance Testing and Replacement of Large Lead Storage Batteries for Nuclear P9wer Plants," February 1978, and IEEE Std 450-1980, "IEEE Recommended Practice for Maintenance, Testino, and Replacement of Large Lead Storage Batteries for Generating Stations and Substations."
Verifying average electrolyte temperature above the minimum for which the battery was sized, total battery terminal voltage onfloat charge, connection resistance vs. lues and the performance of battery service and discharge tests ensures the effectiveness of the charging system, the ability to handle high discharge rates and compares the battery capacity at that time with the rated capacity.
Table 4.8-2 specifies the normal limits for each designated pilot cell and each connected cell for electrolyte level, float voltage and specific gravity.
The limits for the designated pilot cells float voltage and specific gravity, greater than 2.13 volts and 0.015 below the manufacturer's full charge specific gravity or a battery charger current that had stabilized at a low value, is characteristic of a charged cell with adequate capacity. The normal limits for each connected cell for float voltage and specific gravity, greater than 2.13 volts and not more than 0.020 below the manufacturer's full charge specific gravity with an average specific gravity of all the connected cells not more than 0.010 below the manufacturer's full charge specific gravity, ensures the OPERABILITY and capability of the battery.
Operation with a battery celi's parameter o.utside the normal limit but within the allowable value specified in Table 4.8-2 is permitted for up to l
7 days.
During this 7-day period:
(1) the allowable values for electrolyte 1
f level ensures no physical damage to the plates with an adequate electron transfer capability; (2) the allowable value for the average specific gravity of all the cells, not more than 0.020 below the manufacturer's recommended full l
charge specific gravity, ensures that the decrease in rating will be less than l
the safety margin provided in sizing; (3) the allowable value for an individual l
cell's specific gravity, ensures that an individual cell's specific gravity will not be more than 0.040 below the manufacturer's fu R charge specific gravity and that the overall capability of the battery will be maintained within an acceptable limit; and (4) the allowable value for an individual i
cell's float voltage, greater than 2.07 volts, ensures the battery's capability to perform its design function.
i
{
(
i t
Arr I
~
ATTACHMENT II JUSTIFICATION AND SAFETY ANALYSIS A.
SEPARATION OF 24-HOUR RUN AND ESF TEST The current Technical Specification 4.8.1.1.2.e.8, concerning the periodic testing of the diesel generators, calls for performing a 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> or longer test run to be followed by a " Hot Restart" within 5 minutes of the previous test.
The " Hot Restart" test is to be conducted in accordance with Specification 4.8.1.1.2.e.7)b. 4;.,I.^,;.. pis... u To. ;h ;.J..;; ;f :.he d.;;; gn: tr r n
irc:1 x 1;;d..Jm.;.i.n 1000 6 iur S
.e.,,
r.h; ding, c.- - ;,,..:2 uw
+ 'p, id!'n;. A., 6 : c,li.d;.
mh;..
.. r...i.u =>.. '
.;; thz '00*i
_ ;nd f'.=n11, th;..,3.... trip. -li. nos
- ui! r
- ti: t: pc-f;.. th: "";;
u....
w+,.+
t et mityn ;.inntoc ste. th; g;;;g g,,,,, a;; 7 ;7;p, n tn S;;-
r.;;;; nry t: :h:tde.,, th u...el gr --=+a- #rrt-- t'r,csu._._..ded i,
+h=
.ui..! ;;ncr;ter ;h.t "?"a p cn i.; te p.,iviin 69 "nuu L;;;rt" t=t 4+hin E
,u-uu_.-
Ano u em potentially mece severe problem with
~
erforming these tests in quick succession is their poter.tial for causing the p' critical path" complications and delays during an outage.
The 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> test run for the diesel generators by itself can be performed even during the "on line" operation of the power plant.
However, the " Hot Restart" test involving a simulated loss-of-offsite power in conjunction with the ESF actuation test-signal can only be performed during outages.
It is that requirement, that both these tests be performed in quick succession, (Tech. Spec. 4.8.1.1.2.e.8) causes the difficulties mentioned above.
It is the intention of Duke Power Company to demonstrate that the 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> test run and the " Hot Restart" tests can be performed separately and independently without any adverse implications for safety or the reliability of the diesel generators.
The Principle Design Criteria for the diesel generators as described in the IEEE standard 387-1977 includes a requirement that the diesel generator be capable of a restart with an initial temperature equal to the continuous rating full load engine temperature (IEEE 387-1977,5.1.2).
In actual practice the testing is done at equilibrium temperature which is defined as within 110 F of the normal operating temperature (IEEE 387-1977,6.3.1.(1)).
The purpose of " Hot Restart" testing is to verify that the diesel generator l
does not have, in anyway, impaired performance following operation at full load l
or equilibrium temperature.
Failure to " Hot Restart" or extended delay in restarting is typically only experienced with small diesel engines which upon being tripped undergo a temperature rise transient.
This temperature rise transient is experienced in small diesel engines which have engine driven l
forced air cooling.
Large diesel generators at McGuire are water cooled and these diesel generators do not experience any significant temperature rise i
transients during operation or upon its termination.
The McGuire diesel generators are normally maintained at " Hot Standby" conditio,n,,s.
The normal i
standby temperature of diesel lube oil and cooling water i, - 155'F whereas the normal operating temperature for lube oil and cooling water is,- 166-173 F.
According to IEEE 387-1977, Section 6.3.1.1, the equilibrium engine temperature
=.
k i
is defined as jacket water and lube oil temperatures with in 110*F of the normal operating temperatures at full load.
The McGuire diesel units are i-maintained close to equilibrium temperatures even during standby conditions and j
consequently are not subject to unreliability traceable to internal temperature transients.
Since the diesel generator equilibrium operating conditions are the same as the conditions following a 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> full load run, Duke Power
-Company submits that the " Hot Restart" testing may be done following'a separ-ate diesel generator run after the diesel generator has attained equilibrium temperature.
It should be pointed out that starting the diesel generators from normal shutdown conditions and accepting the ESF loads would be more a demanding test.
l The proposed amendments of the technical specifications would permit a separate 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> or more test run and a Hot Restart with full ESF load acceptance test.
i The proposed Hot Restart testing is to be carried out under equilibrium operating conditions for the diesel generators and these do not differ from the conditions of current Hot Restart testing, therefore there are no adverse safety implications that can be attributed to the proposed changes.
1 l
B.
CHANGES PURSUANT TO GENERIC LETTER 84-15 l
The changes included under this part were initiated by the NRC staff as part of Generic Letter 84-15, " Proposed Staff Actions to Improve and Maintain Diesel Generator Reliability." The changes are intended to minimize cold fast i
starts and surveillance testing.
The staff has recognized that these items-l contribute to premature diesel degradation, and has recommended that licensees revise their Technical Specifications accordingly.
Included in the generic letter were sample Tech. Spec. revisions to assist in the accomplishment of that end.
In addition, many of the changes which have been incorporated pursuant to generic letter 84-15 reflect similar changes already approved by the NRC staff for use by Virginia Electric & Power Co. (VEPCO) at North Anna Unit 2 1
(reference letter from Mr. L. B. Engle (NRC) to Mr. W. L. Stewart (VEPCO),
i April 25, 1985).
C.
CHANGES PURSUANT TO GENERIC LETTER 83-30 This changes involves the deletion of (previous) surveillance requirement-l 4.8.1.1.2e.6.
The NRC staff has determined that this requirement is not consistent with Regulatory Guide 1.108, General Design Criterion 17, or the appropriate standard review plan.
i The deleted Tech. Spec. required a test involving a simulated loss of the diesel generator with offsite power not available.
The test is not contained in the Catawba Tech. Specs.
D.
FUEL OIL TESTING Page 3/4 8-3a, section C 1 b) of the Technical Specifications specifies "a kinematic viscosity at 40'C of greater than or equal to 1.9 centistokes, but less than or equal to 4.1 centistokes, if gravity was not determined by comparison with the supplier's certification." The basis of the specification i
.,,~-.-.em.w-.-.,
W 4
is ASTM 0975-81.
The Table 1 of ASTM D975 permits determination of viscosity by two equivalent alternate techniques, Kinematic Viscosity, CST at 40 C and Saybolt, SUS at 100'F.
Inclusion of this alternate technique in the specifica-tion will provide flexibility to the stations.
- ~,.. _ - -, -. - -.., -.,,,. _ _,, _.., -. -....,. _ _..,. _,,.
ATT T
~
ATTACHMENT III ANALYSIS OF SIGNIFICANT HAZARDS CONSIDERATIONS Pursuant to requirements of 10CFR50.91, this analysis provides a determination that the proposed modifications of the Technical Specifications do not involve any significant hazards consideration, as defined by 10CFR50.92.
A.
SEPARATION OF 24-HOUR RUN AND ESF TEST The proposed modification of the Technical Specification, would permit testing of the diesel generators for 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> (or more) test run and a Hot Restart with full ESF load acceptance separately and independently.
Currently these tests are carried out in succession.
Separating these two required tests provides the plant operations added flexibility and prevents critical path complications during the outages.
The proposed testing scheme divides the testing requirement 4.8.1.2.e.8 into two-separate tests.
Each test is carried out under conditions which are nearly identical to those prevailing for the current tests.
The proposed testing scheme provides the same degree of assurance regarding the diesel generator readiness and reliability.
B.
CHANGES PURSUANT TO GENERIC LETTER 84-15 These changes recognize that overtesting can result in an overall reduction in safety, by causing premature degradation of the diesel generators. In addition, the changes provide for a reliability improvement program in the event that diesel generator failures become too frequent.
C.
CHANGE PURSUANT TO GENERIC LETTER 83-30 The proposed amendment of the McGuire Technical Specifications would delete the Surveillance Requirement 4.8.1.1.2e.6.
In view of the rigorous testing program of the diesel generators and diesel generator redundancy this require-ment has been determined to be unnecessary as well as in excess of the provisions of GDC17 by NRC.
D.
FUEL OIL TESTING The proposed change provides for an alterna+ive (equivalent) method of testing and will not reduce acceptance criteria.
The proposed amendments would not:
1)
Involve a significant increase in the probability or consequences of an accident previously evaluated; or 2)
Create the possibility of a r.ew or different kind of accident from any accident previously evaluated; or 3)
Involve a significant redu tion in a margin of safety.
D--
I l l i. l '
ATTACHMENT III (cont'd)
/
ANALYSIS OF SIGNIFICANT HAZARDS CONSIDERATIONS Based upon the preceding analysis, Duke Power Company concludes that the proposed amendments do not involve a significant hazard consideration.
ATTACHMENT II SUPPLEMENTAL SAFETY EVALUATION AND NO SIGNIFICANT HAZARDS ANALYSIS The following identifies each of the changes made to Tech Spec 3/4.8.1 by paragraph and provides an analysis of possible significant hazards considerations.
ACTIONS 1.
New ACTION a New ACTION a has been rewritten to eliminate consideration of inoperable diesel generators (D/Gs).
Inoperable diesels are considered separately in new ACTION c.
ACTION a also eliminates the need to start operable D/Gs every 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> while one off-site A.C. source is inoperable. This reduction in required D/G starts is expected to minimize degradation of the D/Gs and thus improve safety benefits associated with the diesels. This change is in keeping with the context and philosophy of Ceneric Letter 84-15.
Due to the post-accident nature of the D/G function, there is no credible occurrence which can result from a reduction in D/G starts which will have a significant impact on the probability of any accident. No margin of safety will be significantly decreased, because the net overall effect of the change is expected to be an increased assurance that the D/Gs will start on demand, thus reducing the consequences of an accident and decreasing the probability of any effect on the health and safety of the public. ACTION a also changes (from I hour to 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />) the amount of time available, with one off-site A.C. source inoperable, to verify operability (i.e., start) of the diesels. This will provide more time to return the off-site source to operability, thus potentially eliminating a start of each of the two diesels. This is also consistent with GL-84-15, and does not present a SHC because the inoperability of an off-site source does not affect the probability that a diesel will be inoperable.
2.
New ACTION b New ACTION b has also been rewritten to eliminate repetitive starts once the operability of the remaining diesel has been verified. The safety analysis and NSHC logic is the same as that for ACTION a above.
3.
New ACTION c ACTION c represents the inoperable D/G part of what was previously.*6CTION a.
The action, like that in ACTION a, consists of verifying the operability (i.e., starting) the remaining D/G one time within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />. The safety analysic and NSHC logic are identical to that in ACTION a above. The new ACTION also recognizes that a D/G may be inoperable due to pre planned testing or maintenance.
In that event, the redundant D/G is not considered to be susceptible to a common-mode inoperability, and therefore is not required to be started. This does not introduce a SHC, because the planned testing and maintenance will not in any way af fect the operability of the other A.C. sources. This item has been previously approved by the NRC staff for the North Anna and Perry facilities.
ATTACHMENT II Page 2 4.
New ACTION d ACTION d, like ACTIONS a, b, and c, reflects the intent of CL-84-15 with respect to the elimination of repetitive D/G starts. The safety analysis and NSHC logic has been discussed in the above paragraphs. The action taken with one off-site source restored references the appropriate ACTION (a) rather than repeating it.
The requirements are unchanged.
5.
ACTION e ACfl0N e is unchanged, except that as in ACTION d the appropriate ACTION (c) is referenced when one D/G is restored to operability.
Surveillance Requirements 1.
Surveillance 4.8.1.1.2C.1.b):
This surveillance is being expanded to allow an alternate, but equivalent, method of viscosity testing. The change is virtually administrative in nature; i.e., the oil itself is maintained within the same viscosity - only the measurement technique has changed. No Significant Hazards Considerations can exist, because the bottom-line product, the oil viscosity, is unchanged. The equivalent method has been approved for use at Catawba and is in use at Perry Nuclear Station.
2.
Old Surveillance Requirement 4.8.1.1.2.e.6)
This surveillance has been deleted on the advice of the NRC staff in Generic Letter 83-30.
According to the staff, the requirement to test for a loss of a D/G with off-site power not available is in excess of Gene al r
Design Criteria (CDC 17) requirements, Regulatory Guide 1.108, and the Standard Review Plan (SRP 8.2 and 8.3.1).
The change will not introduce a significant hazards consideration because:
- 1) The elimination of this overly conservative surveillance requirement will not adversely affect the probability that a diesel will become inoperable, nor will it significantly affect the probability that an inoperable D/G will go undetected; thus assuring that no significant increase in the consequences of any accident will occur; and 2) The inoperability of a D/G, for any credible reason, will not affect the probability of an accident. No margin of safety is affected because the change does not affect the redundancy or operability requirements of the D/Gs or other power sources. This requirement has been deleted from Standard Technical Specifications Draft Revision 5.
3.
Survelliance Requirement 4.8.1.1.2.e.7 This surveillance requirement was originally part of an existing Tech Spec (4.8.1.1.2.e.8), which required that hot restart be performed within 5 minutes after a 24-hour diesel run. This change simply separates the tests, to minimize potential critical path delays in testing during outages. As a result of discussions with NRC staf f subsequent to Duke's original July 10, 1985 submittal, the wording of this change has been revised somewhat, to include the 5-minute time limit on performance of the restart. NSHC are involved, because the testing requirements are virtually ide n t i c.a l.
-