"Yo#o N Gw wt SoMwwe Requ6rement Specincetkm
+
TRie:
Number:
SRS-Process Computer System - Emergency Response Data
- ERDS SRS-1-3
. System (ERDS)- Data Point Library -
Shoot No:- 1 hbithMD Prepared By Ch Effective Date:
Y Reviewed By: bum Approved By:
~
~
// //
/q YV l
LIST OF PAGES
/
SHEET DESCRIPTION REVISION and DATE 1
LIST OF PAGES Revision 3,11/04/97 2
NI POWER RANGE Revision 1, 4/14/92 -
3 NI INTER RANGE Revision 1, 4/14/92 4
NI SOURC RNG Revision 1, 4/14/92 5
REAC VES LEV Revision 1, 4/14/92 6
RCS PRESSURE Revision 2,1/1/93 7
MAIN FD FLOW Revision 1, 4/14/92 9
HPCI FLOW Revision 2,1/1/93 10 RCIC FLOW Revision 1, 4/14/92 11
_ LPCI FLOW Revision 1, 4/14/92 15 CR SPRAY FL Revision 1, 4/14i92 17 DW FD SMP LV Revision 1, 4/14/92 19 EFF GAS RAD Revision 1, 4/14/92 23 EFF LIQ RAD Revision 1, 4/14/92 29 COND A/E RAD Revision 1, 4/14/92 31 DW RAD Revision 1, 4/14/92 33 MN STEAM RAD Revision 1, 4/14/92 34 DW PRESS Revision 1, 4/14/92 35 DW TEMP '
Revision 1, 4/14/92 36 SP TEMP Revision 1, 4/14/92 37 SP LEVEL Revision 1, 4/14/92 38 H2 CONC Revision 1, 4/14/92 42 CST LEVEL Revision 3,11/04/97 l
- 44 WIND SPEED Revision 1, 4/14/92 48 WIND DlR Revision 1, 4/14/92 52 STAB CLASS Revision 1, 4/14/92 56 Contacts Revision 3,11/04/97 l
57 Selection of Data Feeders Revision 1, 4/14/92 58 Data Feeder Information Revision 1, 4/14/92 N! O 3
PJorthern States Power Company Mortcono Nuclear Gerierating Ptent Software Requirement Specineshon Tale-Number; SRS Process Computer System - Emergency Response Data ERDS-SRS-1-3 System (ERDS)- Data Point Library Sheet No: 2 DATA POINT LIBRARY REFERENCE FILE Date:
01/07/92 Reactor Unit:
M01 Data Feeder.
NI POWER RNG Point ID:
C51C4001 Plant Spec Point Desc.:
AVERAGE CONSISTENT APRM REi DING Generic /Cond Desc.;
NUCLEAR INSTRUMENTS, POWER RANGE Analog / Digital A
Engr Units / Dig States:
Engr Units Conversion:
N/A Minimum Instr Range:
0 Maximum Instr Range:
125 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROC or SENS:
P Number of Sensors:
12 How Processed:
AVERAGE OF CONSISTENT APRMS Sensor Location:
APRM UTILIZE 24 LPRMS LOCATED IN CORE Alarm / Trip Set Points:
Hi-HI TRIP =(.58W+62%),W=%RECIRC FLOW NI Detector Power Supply N/A Cut-off Power Leval:
NI Detector Power Supply N/A Tum-on Power Level:
Instrument Failure Mode:
DOWNSCALE(3%),1NOP, BYPASS Temperature Compensation N/A For DP Transmitters:
Level Reference Leg:
N/A Unique System Desc.:
This point consists of either an average of all consistent APRMs or an average of in-range APRMs if there are less than the required number of consistent signals.
APRMS(Average Power Range Monitors) consist of an average of 24 LPRMs (Local Power Range Monitors). Each individual APRM signal will fail on Downscale(3%), inop, or Bypass. Hl H1 trip feed RPS SCRAM for one-out of-three-twice logic. Hi trip (.58W+50%) results in Rod Withdraw Block.
n States Power company -
. Montacello Nuclear Generstww Plant Sonwere Requirement Specifcetion Teo:
Number;.
SRS-Process Computer System - Emergency Response Data ERDS-SRS-1-3
~
System (ERDS)- Data Point Library
~
Sheet No:
3-t DATA POINT LIBRARY REFERENCE FILE Date:
01/07/92 Reactor Unit:
M01 Data Feeder: '
~
NRC ERDS Parameter:
NIINTER RNG Point ID:
Plant Spec Point Dese.:
(not available)-
Generic /Cond Desc.:
NUCLEAR INSTRUMENTS, INTERMEDIATE RANGE
- Analog / Digital Engr Units / Dig States:
Engr Units Conversion:
Minimum instr Range:
Maximum Instr Range:
Zero Point
Reference:
Reference Point Notes:
PROC or SENS:
Number of Sensors:
How Processed:
Sensor Location:
Alarm / Trip Set Points:
NI Detector Power Supply Cut-off Power Level:
NI Detector Power Supply Tum-on Power Level:
Instrument Failure Mode:
Temperature Compensation For DP Transmitters:
Level Reference Leg:
Unique System Dese.:
Not available to Process Computer
- System, t
4 z,_..,,.,,--.,-.;,,,,.
~. _.
lww.n steles Power Company Monucello Nuclear oenerstmo Plant Software Requirement Specification Title; Number:
f SRS-Process Computer Sys'am - Emergency Response Data ERDS-SRS-1-3 System (ERDS)- Data Point Library
- Sheet No: 4 7
DATA POINT LIBRARY REFERENCE FILE -
Date:
- 01/07/92 Reactor Unit:-
M01 Data Feeder.
. NI SOURC RNG Point ID:
Plant Spec Point Desc.:
(not available)
Generic /Cond Dese.:
NUCLEAR INSTRUMENTS, SOURCE RANGE Analog / Digital
- Engr Units / Dig States:
Engr Units Conversion:
. Minimum Instr Range:
' Maximum Instr Range:
Zero Point
Reference:
Reference Point Notes:
PROC or SENS:
Number of Sensors:
How Processed:
Sensor Location:
Alarm / Trip Set Points:
NI Detector Power Supply Cut off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation For DP Transmitters:
Level Reference Leg:
Unique System Desc.;
Not available to Process Computer System.
)
~
s Norttem States Power Company e.
Monteeno Nucteer Generating Pont SoMwere Requirement specifchm Tale.
Number;
-SRS Process Computer System - Emergency Response Data ERDS-SRS-1-3 System (ERDS)- Data Point Library -
Shoot No: 5 DATA POINT LIBRARY REFERENCE FILE Date:
01/07/92 Reactor Unit:
M01 -
Data Feeder:
REAC VES LEV Point ID:
821C0010 Plant Spec Point Dese.:
RPV VALIDATED WATER LEVEL Generic /Cond Desc.:
REACTOR VESSEL WATER LEVEL Analog / Digital A
Engr Units / Dig States:
INCHES Engr Units Conversion:
N/A Minimum Instr Range:
-350 Maximum Instr Range:
350 Zero Point
Reference:
MSSKRT Reference Point Notes:
0" CORRESPONDS TO 126" ABOVE TOP OF FUEL PROC or SENS:
P-Number of Sensors:
28 How Processed:
WEIGHTED AVERAGE OF CONSISTP:7 LEVELS Sensor Location:
LEVEL REF LEGS - 5 HOT (IN DW) & 2 COLD Alarm / Trip Set Points:
-48 =ECCS INIT,9"= SCRAM,48"=HI TRIP NI Detector Power Supply N/A Cut-off Power Level:
NI Detector Power Supply N/A Tum-on Power Level:
Instrument Failure Mode:
+280" TOP OF REACTOR HEAD Temperature Compensation N/A For DP Trsnsmitters:
Level Reference Leg:
WET Unique System Desc.:
This point consists of either a weighted average of all consistent level indicators or an average of in-range level indicators if there are less than the required number of consistent signals. Algorithm performs temperature compensation and evaluates reference leg flashing on 7 level
- signals, Safeguards Levels (-50" to 50") utilize cold reference leg design outside of drywell. ECCS levels ( 335" to 65") are invalidated with recirc pumps running. Other levels include 2 feedwater (0 to 60") and 1 vessel flood (-50" to 350").
teorthern Ss D Power Company Mord4 cello % clear Generating Plant Software Requirement Specircation TRW Number:
SRS Process Computer System - Emergency Response Data ERDS-SRS-1-3 System (ERDS)- Data Point Library Sheet No: 6 DATA POINT LIBRARY REFERENCE FILE Date:
01/19/93 Reactor Unit:
M01 Data Feeder:
RCS PRESSURE Point ID:
B21CO210 Plant Spec Point Desc.:
RFV VALIDATED PRESSURE Generic /Cond Desc.:
REACTOR COOLANT SYSTEM PRESSURE Analog / Digital A
Engr Units / Dig States:
PSIG Engr Units Conversion:
N/A Minimum Instr Range:
0.00 Maximum Instr Range:
1500 Zero Point
Reference:
N/A Reference Point Notes:
N/A l
PF ;C or SENS:
P Numberof Sensors:
3 How Processed:
WEIGHTED AVERAGE OF CONSISTENT LEVELS Sensor Location:
PRESSURE SENSED OFF LEVEL REF LEGS Alarm / Trip Set Points:
1056 PSIG= SCRAM NI Detector Power Supply N/A Cut off Power Level:
NI Detector Power Supply N/A Turn-on Power Level:
Instrument Failure Mode:
Hl/ LOW SENSOR Temperature Compensation N/A For DP Transmitters:
Level Reference Leg:
N/A Unique System Desc.:
This point consists of either a weighted average of all consistent pressure indicators ur an average of in-range pressure levelindicators if there are less than the required number of consistent signals.
}
..,m
)
6=
Normem states Power Company Monhooto Nucieer Generating Plant SoRwere Requirement Specincetion Tee:
Number.
SRS; Process Computor System - Emergency Response Data ERDS-SRS-1-3 System (ERDS)- Data Point Library Sheet No:~7 i
t DATA POINT LIBRARY REFERENCE FILE -
Date:
01/07/92 i
Reactor Unit:
M01
- Data Feeder:
- NRC ERDS Parameter:
MAIN FD FLOW Point ID:
C51C9001 Plant Spec Point Dese.:
SMOOTHED FEEDWATER FLOW LOOP A Generic /Cond Desc.:
FEEDWATER FLOW INTO THE REACTOR SYSTEM Analog / Digital MLB/HR A
Engr Units / Dig States:
Engr Units Conversioni N/A Minimum instr Range:
0 Maximum Instr Range:
4<
-Zero Point
Reference:
N/A Reference Point Notes:
N/A PROC or SENS:.
P Number of Sensors:
4 How Processed:
SMOOTHED FW FLOW CALC FROM A NOZZLE D/P-
)
Sensor Location:
FW NOZZLE IS DOWNSTREAM OF RX FW PUMPS Alarm /Tric Set Points:
N/A NI Detector Power Supply N/A
+
. Cut-off Power Level:
NI Detector Power Supply N/A Tum c3 Power Level:
1
- Instrument Failure Mode:
Hl/ LOW SENSOR
- Temparature Compensation N/A~
For DP Transmitters:
N/A-Level Reference Leg:
N/A Unique System Dese :
SMOOTHED FW FLOW LOOP A is calculated using Feedwater nozzle D/P, Pressure, and temperature.
Smoothing algorithm sums 1/12 current sample + 11/12 of previous smoothed value. Sampling frequency is 5 seconds.
Feedwater nozzles are located downstream of Reactor Feedwater Pumps and ahead of high pressure heaters.
E
.n...
,n.,..
w,-
~ __ _ _ _.
l No@ern salee Poner competir j
4 Montgene Nucteer Genoestre Pterd sonwere Coeuwemord SpecWicate IMC Number:
SRS Process Computer System - Emergency Response Data ERDS SRS.1-3 l
System (ERDS) Data Point Library j
Sheet No: 3 I
DATA POINT LIBRARY REFERENCE FILE Date:
01/07/92 Reactor Unit:
-M01 Data Feeder:
MAIN FD FLOW Point ID:
C51C9002 Plant Spec Point Desc.:
SMOOTHED FEEDWATER FLOW LOOP B Generic /Cond Desc.:
FEEDWATER FLOW INTO THE REACTOR SYSTEM Analog / Digital A
Engr Units / Dig States:
MLB/HR Engr Units Conversion:
N/A Minimum instr Range:
0 Msximum Instr Range:
4 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROC or SENS:
P Number of Sensorr 4
How Processed:
SMOOTHED FW FLOW CALC FROM B NOZZLE D/P Sensor Location:
FW NOZZLE IS DOWNSTREAM OF RX FW PUMPS Alarm / Trip Set Points:
N/A NI Detector Power Supply N/A Cut off Power Level:
NI Detector Power Supply N/A Turn on Power Level:
Instrument Frillure Mode:
Hl/ LOW SENSOR Temperature Compensation N/A For DP Transmitters:
N/A Level Reference Leg:
itA Unique Systern Desc.:
SMOOTHED FW FLOW LOOP B h calculated using Feedwater nozzle D/P, Pressure, and temperature.
Smoothing algorithm sums 1/12 current sample + 11/12 of previous smoothed value. Sampling frequency is 5 seconds.
Feedwster nozzles are located downstream of Reactor Feedwater Pumps and ahead of high pressure heaters.
Northern Stones Poww Company f
Monhecho Nucher Generetna Ple#W software Reggkoment speerfesten iae Numter; SRS Process Computer System - Emergency Response Data ERDS SRS-13 l
System (ERDS)- Data Point Library Sheet No-9 DATA POINT LIBRARY REFERENCE FILE I
Date:
01/19/93 Reactor Unit:
HO1 Data Feeder:
HPCI FLOW Point ID:
HPC100 Plant Spec Point Desc.:
HPCl PUMP DISCHARGE FLOW Generic /Cond Desc.:
HIGH PRESSURE COOLANT INJECTION FLOW Analog / Digital A
~
Engr Units / Dig States:
GPM Engr Units Conversion:
N/A
- Minimum Instr Range:
0 Maximum instr Range:
3500 Zero Dolnt
Reference:
N/A Reference Point Notes:
N/A PROC or SENS:
S Number of Sensors:
1 How Processed:
SIGNAL INPUT FROM FLOW TRANSMITTER Sensor Location:
FLOW ELEMENT ON HPCI PUMP DISHARGE Alarm / Trip Set Points:
N/A NI Detector Power Supply N/A Cut off Power Level:
NI Detector Power Supply N/A Turn on Power Level:
Instrument Failure Mode:
HIGH & LOW SENSOR Temperature Compensation N/A For DP Transmitters:
N/A Level Reference Leg:
N/A Unique System Desc.:
HPCIis a steam turbine driven pump designed to deliver 2700 gpm over reactor pressure range of 1501120 psig, Flow element is located on pump disharge line ahead of the test retum line to the CST tanks and injection line into *B" feedwater line. HPCI injects into feedwater line prior to the line entering containment.
P i
m
~w.
. _ _..,,m.
,,y
1 dweern States Poww Company
[
unuee we,ow m e ws son.we n.a*.mont swee.n T the
- Numter, SRS Process Computer System - Emergency Response Data ERDS SRS 13 System (ERDS) Data Point Library Sheet No:
10 l
l DATA POINT LIBRARY REFERENCE FILE Date:
01/07/g2 Reactor Unit:
M01 i
Data Feeder:
RCIC FLOW Point ID:
RCl100 Plant Spec Point Desc.:
RCIC PUMP DISCHARGE FLOW Generic /Cond Desc.:
REACTOR CORE ISOLATION COOLING Analog / Digital A
Engr Un!ts/ Dig Stves:
GPM Engr Units Convers'on:
N/A Minimum instr Range:
0 Maximum Instr Range:
500 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROC or SENS:
S
- Numberof Sensors:
1 How Procersed:
SIGNAL INPUT FROM FLOW TRANSMITTER Sensor Location:
FLOW ELEMENT ON RCIC PUMP DISHARGE Alarm / Trip Set Points:
N/A NI Detector Power Supply N/A Cut-off Power Level:
NI Detector Power Supply N/A Turn on Power Level:
Instrument Failure Mode:
HIGH & LOW SENSOR Temperature Compensation N/A For DP Transmitters:
N/A Level Reference Leg:
N/A Unique System Desc.:
RCIC is a steam turbine driven pump designed to deliver 400 gpm over reactor pressure range of 1501120 psig. Flow element is located on pump disharge line ahead of the test retum line to the CST tanks and injection line into "A" feedwater line RCIC injects into feedwater line prior to the line entering containment.
t'
- o.
,--..--,,----;,-.-.-,..--.~,......
thorth.rn States Power Company um.no no., o.n.r.= ei.4 son. nnui,.m.,* sr.eu tina u,..
numw.
SRS Process Computer System - Emergency Response Data ERDS SRS-13 System (ERDS)- Data Point Library Sheet No' 1i DATA POINT LIBRARY REFERENCE FILE Date:
01/07/92 Reactor Unit:
M01 Data Feeder:
LPCI FLOW Point ID:
RHR100 Plant Spec Point Desc.:
CONTAINMENT SPRAY / COOLING A LOOP Generic /Cond Desc.:
LOW PRESSURE COOLANT INJECTION FLOW Analog / Digital A
Engr Units / Dig States:
GPM Engr Units Conversion:
N/A Minimum Instr Range:
0 Maximum instr Range:
10000 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROC or SENS:
S Number of Sensors:
1 How Processed:
SIGNAL INPUT FROM FLOW TRANSMITTER Sensor Location:
DISCHARGE OF RHR HEAT EXCHANGERS Alarm / Trip Set Points:
N/A NI Detector Power Supply N/A Cut-off Power Level:
NI Detector Power Supply N/A Turn-on Power Level:
Instrument Failure Mode:
HIGH & LOW SENSOR Temperature Compensation N/A For OP Transmitters:
N/A Level Reference Leg:
N/A Unique System Desc.:
CONTAINMENT SPRAY / COOLING A LOOP flowis the RHR flow to the A loop drywell spray, torus spray and torus cooling.
Each RHR pump is approximately rated at 4000 gpm depending on system head. Two pumps are located in each loop although flow can be cross tied between A and B loops.
I Northem Stateo Power Cortpant Morsch Nuclear oenerat6re Pised softweie Reaukemord specketen 1aw.
- Numter, SRS Process Computer System - Emergency Response Data ERDS SRS 13 System (ERDS) Data Point Library Shoot No:
12 DATA POINT LIBRARY REFERENCE FILE Date:
01/07/92 Reactor Unit:
M01 Data Feeder:
LPCI FLOW Point ID:
RHR101 Plant Spec Point Dese.:
CONTAINMENT SPRAY / COOLING B LOOP Generic /Cond Desc.:
LOW PRESSURE COOLANT INJECTION FLOW Analo0/ Digital A
Engr Units / Dig States:
GPM Engr Units Conversion:
N/A Minimum Instr Range:
0 Maximum instr Range:
10000 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROC or SENS:
S Number of Sensors:
1 How Processed:
SIGNAL INPUT FROM FLOW TRANSMITTER i
Sensor Location:
DISCHARGE OF RHR HEAT EXCHANGERS Alarm / Trip Set Points:
N/A NI Detector Power Supply N/A Cut off Power Level:
NI Detector Power Supply N/A Turn-on Power Level:
Instrument Failure Mode:-
HIGH & LOW SENSOR
- Temperature Compensation -
N/A For DP Transmitters:
N/A Level Reference Leg:
N/A Unique System Desc.:
CONTAINMENT SPRAY / COOLING B LOOP flow is the RHR flow to the B loop drywell spray, torus spray and torus cooling.
Each RHR pump is approximately rated at 4000 gpm depending on system head. Two pumps are located in each i
loop although flow can be cross tied between A and B loops.
,---,--w
-- we m
r-,,rm#-.r,---.,,,te.-.~,--,-1yv
.n.
,,u--
4=
c e-
---,.m-.
-. - -... = - -
-,. ~_. _ _ -.. -... -. _.
$wesen she Poww Compent m *
- w ero.n.re,naews son.. %*.m re sp.cean 1me Numter; SRS Process Computer System - Emergency Response Data ERDS-SRS 13 System (ERDS) Data Point Library Sheet No:
13 i
9 4
t DATA POINT LIBRARY REFERENCE FILE Date:
01/07/92 Reactor Unit:
M01 i
Data Feeder:
LPCI FLOW Point ID:
RHR102 Plant Spec Point Desc.:
RHR LOOP A INJECT FLOW Generic /Cond Dese.:
LOW PRESSURE COOLAWINJECTION FLOW Analog / Digital A
Engr Units / Dig States:
GPM Engr Units Conversion:
N/A Minimum instr Range:
0 Maximum Instr Range:
10000 Zero Point
Reference:
N/A t
Reference Point Notes:
N/A PROC or SENS:
S Number of Sensors:
1 How Processed:
SIGNAL INPUT FROM FLOW TRANSMITTER Sensor Location:
DISCHARGE OF RHR HEAT EXCHANGERS Alarm / Trip Set Points:
N/A NI Detector Power Supply N/A Cut off Power Levol:
NI Detector Power Supply N/A Tum on Power Level:
Instrument Failure Mode:
HIGH & LOW SENSOR Temperature Compensation N/A For DP Transmitters:
N/A Level Reference Leg:
N/A Unique System Dese.:
RHR LOOP A INJECT FLOWis the RHR flow to the A Recire Loop, Reactor Head Cooling, Waste Surge Tank, and cross tie to B Loop. Each RHR pump is rated at about 4000 gpm depending on system head. Two pumps are located in each loop although flow can be cross tied between A and B loops.
e,-
,,.,e-.c,-m-m---
e rr m-m----.,
y,,.
..-r-e v t-
,r.?-+t-.-nt.
w m yw-r
w----r-
4 t
Northem Steles Power Company MxW NW Oenstehna Pierd soRwere Requiremord specdcatkm Tee.
Number.
SRS Process Computer System - Emergency Response Data ERDS SRS-1-3 System (ERDS)- Data Point Library i
Sheet No:
i4 Y
(
i DATA POINT LIBRARY REFERENCE FILE i
Date:
01/07/g2 1
Reactor Unit:
M01 Data Feeder:
LPCI FLOW Point ID:
RHR103 Plant Spec Point Desc.:
i Generic /Cond Desc.:
LOW PRESSURE COOLANT INJECTION FLOW Ana!og/ Digital A-Engr Units / Dig States:
GPM Engr Units Conversion:
N/A 4
. Minimum Instr Range: -
0 Maximum instr Range:
10000 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROC or SENS:
S Number of Sensors:
1 How Processed:
SIGNAL INPUT FROM FLOW TRANSMITTER
- Sensor Location:
DISCHARGE OF RHR HEAT EXCHANGERS-i Alarm / Trip Set Points:
N/A l
NI Detector Power Supply N/A Cut off Power Level:
NI Detector Power Supply N/A Turn-on Power Level:
Instrument Failure Mode:
HIGH & LOW SENSOR Temperature Compensation N/A For DP Transmitters:
N/A Level Reference Leg:
N/A Unique System Desc.:
RHR LOOP B INJECT FLOW is the RHR flow to the B Recirc Loop and cross tia to A Loop. Each RHR pump is rated at about 4000 gpm depending on system head. Two pumps are located in each loop although flow can be cross tied between A and B loops.
P
-, - - -.. -.. - -. -. +. -.. -..,,, -,. -.. -.,, - - - -,,. -. -..... <.. -..,,..,,..
bn states Power Company I
Montecong Nuclear Generstre Plead spReere Requiremord spec 8ficat6on ilho:
Numtier; SRS Process Computer System Emergency Response Data ERDS SRS-1-3 System (ERDS)- Data Point Library Sheet Nr 15 DATA POINT LIBRARY REFERENCE FILE t
Date:
01/07/92 i
Reactor Unit:
M01 Data Feeder:
CR SPRAY FL Point ID:
CSP 100 Plant Spec Point Dese.:
CS LOOP 11 FLOW Generic /Cond Dese.:
Core Spray Cooling System Flow Analog / Digital A
Engr Units / Dig States:
GPM Engr Units Conversion:
N/A Minimum instr Range:
0 Maximum Instr Range:
5000 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROC or SENS:
S Number of Sensors:
1 How Processed:
SIGNAL INPUT FROM FLOW TRANSMITTER Sensor Location:
ON PUMP DISCHARGE LINE Alarmrfrip Set Pc!nts:
NI Detector Power Supply N/A Cut off Power Level:
NI Detector Power Supply N/A Tum-on Power Level:
-Instrument Failure Mode:
HIGH & LOW SENSOR Temperature Compensation N/A For DP Transmitters:
Level Reference Leg:
N/A Unique System Dese.:
Tne loop A Core Spray system consists of one electric driven pump designed to deliver 3020 gpm against a system head corresponding to a reactor pressure of 130 psi above containment pressure, The flow element is located on the pump discharge line just a head of the reactor vesselinjection and test retum lines.
5,ven sw.s Pow.t company u w u.no u m o.n w eina e w s son *w. n.auw.mwe so. cmc.i.on ille..
Nomter; SRS_
Process Computer System - Emergency Response Data ERDS SRS-13 System (ERDS) Data Point Library Sheet No:
16
[
f DATA POINT LIBRARY REFERENCE FILE Date:
01/07/92 Reactor Unit:
M01 Data Feeder:
PCS i
NRC ERDS Parameter:
CR SPRAY FL Point ID:
CSP 101 Plant Spec Point Desc.:
CS LOOP 12 FLOW Generic /Cond Desc.:
CORE SPRAY COOLING SYSTEM FLOW Analog / Digital A --
Engr Units / Dig States:
GPM l
Engr Units Conversion:
N/A Minimum Instr Range:
0 Maximum Instr Range:
5000 Zero Point
Reference:
N/A 7
Reference Point Notes:
N/A PROC or SENS:
S Number of Sensors:
1 How Processed:
SIGNAL INPUT FROM FLOW TRANSMITTER Sensor Location:
ON PUMP DISCHARGE LINE Alarm / Trip Set Points:
NI Detector Power Supply N/A Cut-off Power Level:
NI Detector Power Supply N/A Tum on Power Level:
Instrument Failure Mode:
HIGH & LOW SENSOR Temperature Compensation N/A For DP Transmitters:
Level Reference Leg:
N/A Unique System Desc.:
The loop B Core Spray system consists of one electric driven pump designed to deliver 3020 gpm against a system head corresponding to a reactor pressure of 130 psi above containment pressure. The flow element is located on the pump discharge line just a head of the reactor vessel injection and test return lines.
herth.tn states Pow.t Comp.nr o
un,u.no e4aci.., c.n.r.,no pi.,4 sove.<. n.aui,.m.re sp.cir,e.tu.
in numm SRS Process Computer System - Emergency Response Data ERDS SRS 1-3 System (ERDS)- Data Point Library sn t wo:
17 i
DATA POINT LIBRARY REFERENCE FILE Date:
01/07/92 Reactor Unit:
M01 Data Feeder:
PCT 138 Plant Spec Point Desc.:
DW EQUIP DRAIN SUMP VOL Generic /Cond Desc.:
DRYWELL FLOOR DRAIN SUMP LEVEL Analog / Digital A
Engr Units / Dig States:
GAL Engr Units Conversion:
N/A Minimum Instr Range:
114.4 Maximum Instr Range:
514.8 Zero Point Referenco:
N/A Reference Point Notes:
N/A PROC or SENS:
S Number of Sensors:
1 How Processed:
SIGNAL INPUT FROM LEVEL TRANSMITTER Sensor Location:
DIRECTLY BELOW RX VESSEL IN DRYWELL Alarm / Trip Set Points:
N/A NI Detector Power Supply N/A Cut off Power Level:
NI Detector Power Supply N/A Turn-on Power Level:
Instrument Failure Mode:
HIGH & LOW SENSOR Temperature Compensation N/A For DP Transmitters:
Level Reference Leg:
N/A Unique System Desc.:
This sump collects liquid effluent from valve stem leak offs, Rx Recire Pump and piping maintenance drains, vent cooler drains, reactor well bulkhead and bellows drains, reactor vessel flange leakoff and Drywell Equipment Drain Sump heat exchanger drain. Two 50 GPM pumps discharge the water to the Waste Collector Tank in the Reactor building. Sump is isolated by Group 11 Isolation or manually from control room.
Sump overflows into Drywell Floor Drain Sump at 1090 Gallons.
~
4=v-n mm eo.w comp.ny i
u-*<= woew ones pww son. n
.mwn so.ew.cen isee.
Number.
SRS Process Computer System - Emergency Response Data ERDS-SRS 13 System (ERDS) Data Point Library f
Sh t No:
10 I
r DATA POINT LIBRARY REFERENCE FILE Date:
01/07/92 Reactor Unit:
M01 Data Feeder:
PCT 139 Plant Spec Point Dese.:
DW FLOOR DRAIN SUMP VOL Generic /Cond Desc.:-
DRYWELL FLOOR DRAIN SUMP LEVEL Analog / Digital A
Engr Units / Dig States:
GAL Engr Units Conversion:
N/A Minimum instr Range:
114.4 Maximum Instr Range:
514.8 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROC or SENS:
S Numberof Sensors:
1 How Processed:
SIGNAL INPUT FROM LEVEL TRANSMITTER Sensor Location:
DIRECTLY BELOW RX VESSEL IN DRYWELL Alarm / Trip Set Points:
N/A
=
NI Detector Power Supply N/A Cut off Power Level:
NI Detector Power Supply N/A Tum on Power Level:
Instrument Failure Mode:
HIGH & LOW SENSOR Temperature Compensation N/A For DP Transmitters:
Level Reference Leg:
N/A Unique System Desc.:
This sump collects liquid effluent from Drywell cooler drains, floor drains, control rod drive leakage and drains, closed cooling water piping drains, and piping and equipment maintenance vents. Two 50 GPM pumps discharge the water to the Floor Drain Collector Tank in the Reactor building.
Sump is isolated by Group 11 Isolation or manually from control roum. Sump overflows into Drywell Equipment Drain Sump at 1090 Gallons.
n States Power Company o
Montecono Nucteet Generolina Plant sonwere Requiremeed spec #cetion 1stee Numter; SRS Process Computer System - Emergency Response Data ERDS SRS-1-3 System (ERDS)- Data Point Library Sheet No: 19 DATA POINT LIBRARY REFERENCE FILE Date:
01/07/g2 Reactor Unit:
M01 Data Feeder:
EFF GAS RAD Point ID:
PRM121 i
t Plant Spec Point Desc.:
STACK EFF MONITOR CH A Gesneric/Cond Desc.:
RADIOACTMTY OF RELEASED GASES Analog / Digital:
A Engr Units / Dig States:
uCl/S Engr Units Conversion:
N/A Minimum instr Range:
1 Maximum Instr Range:
10E12 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROC or SENS:
S Number of Sensors:
1 How Processed:
SIGNAL FROM ANALOG OUTPUT OF MONITOR Sensor Location:
FOUR ISOKINETIC PROBES IN OFF GAS STACK Alarm / Trip Set Points:
Hl=3200, HI Hl=90000 NI Detector Power Supply N/A Cut off Power Level:
NI Detector Power Supply N/A Tum on Power Level:
Instrument Failure Mode:
HIGH & LOW SENSOR Temperature Compensation N/A For DP Transmitters:
Level Reference Leg:
N/A Unique System Dese.:
STACK EFF MONITOR CH A is a wide range gas monitor consisting of isokinetic probe assembly, sample conditioning unit, samp;e detection unit, and Control Room panel. The detector assembly consists of low, mid, and high range detectors. Hi Hi and/or INOP from both Channel A & B monitors will close valves to isolate off gas flow to the stack.
7NeYuf,E*E[r%L son.e.n.aus.m.,e sr e r,e. u w..
rumver.
SRS Process Computer System - Emergency Response Data ERDS-SRS-1-3 System (ERDS)- Data Point Library sheet No: 20 DATA POINT LIBRARY REFERENCE FILE Date:
01/07/92 Reactor Unit:
M01 Data Feeder:
EFF GAS RAD Point ID:
PRM122 Plant Spec Point Desc.:
STACK EFF MONITOR CH B Generic /Cond Desc.:
RADIOACTIVITY OF RELEASED GASES Analog / Digital:
A Engr Units / Dig States:
uCl/S Engr Units Conversion:
N/A Minimum Instr Range:
1 Maximum instr Range:
10E12 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROC or SENS:
S Number of Sensors:
1 How Processed:
SIGNAL FROM ANALOG OUTPUT OF MONITOR Sensor Location:
FOUR ISOKINETIC PROBES IN OFF GAS STACK Alarm / Trip Set Points:
Hl=3200, HI Ul=90000 NI Detector Powe Supply N/A Cut off Power Level:
NI Detector Power Supply N/A Turn-on Power Level:
Instrument Failure Mode:
HIGH & LOW SENSOR Temperature Compensation N/A For DP Transmitters:
Level Reference Leg:
N/A Unique System Desc.:
STACK EFF MONITOR CH B is a wide range gas monitor consisting of Isokinetic probe assembly, sample conditioning unit, sample detection unit, and Control Room panel. The detector assembly consists of low, mid, and high range detectors. Hi Hi and/or INOP from both Channel A & B monitors will close valves to isolate off gas flow to the stack.
. _-. ~ -- -
_. - - ~....- - -_-.- --~.- _. _ _ _.,.- _ _
Nwthem steles Power Company u wec no ---
ca_; Piwa sea.w. m.mm mus someramen t
Tale.
Number; SRS_
Process Computer System - Emergency Response Data ERDS SRS-1-3
.j System (ERDS)- Data Point Library
-l snest No: -21 r
i.
DATA POINT LIBRARY REFERENCE FILE 4
Date:
01/07/92 Reactor Unit:
M01 l
Data Feeder:
PCS l
- NRC ERDS Parameter:
EFF GAS RAD Point ID:
PRM123
= Plant Spec Point Desc.:
RBV EFFLUENT MONITOR CH A Gene <c/Cond Desc.:
RADIOACTIVITY OF RELEASED GASES Analog / Digital:
A Engr Units / Dig States:
uCl/S
(
Engr Units Conversion:
N/A Minimum instr Range:-
1 Maximum' instr Range:
10E12 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROC or SENS:
S i
Number of Sensors:
1 How Processed:
SIGNAL FROM ANALOG OUTPUT OF MONITOR Sensor Location:
ISOKINETIC PROBF.S IN EACH RX BLDG VENT Alarm / Trip Set Points:
Hl=400, HI Hl=4500 NI Detector Power Supply N/A Cut off Power Level:
NI Detector Power Supply N/A Turn on Power Level:
Instrument Failure Mode:
HIGH & LOW SENSOR
-Temperature Compensation -
N/A For DP Transmitters:
Level Reference Leg:
N/A Utilgue System Dese.:
Reactor Building Vent Effluem Monitor Channel A is u wide range gas monitor consisting of isokinetic probe assemblies, sample conditioning unit, sample detection unit, and Control Room panel, The detector assembly consists of low, mld, and high range detectors,
't i
i i
bem Sisies Pow.r Company b
we.= Nuci.e o.nwenn ewe son.w. n.aw. ment so.ca.c.i.n ise.
Numter; SRS Process Computer System - Emergency Response Data ERDS SRS 13 System (ERDS) Data Point Library Sheet No: 22 l
DATA POINT LIBRARY REFERENCE FILE --
Date:
01/07/92 Reactor Unit:
M01 Data Feeder:
EFF GAS RAD Point ID:
PRM124 Plant Spec Point Desc.:
RBV EFFLUENT MONITOR CH B Generic /Cond Desc.:
RADIOACTIVITY OF RELEASED GASES Analog / Digital:
A Engr Units / Dig States:
uCl/S Engr Units Conversion:
N/A Minimum Instr Range:
1 Maximum Instr Range:
10E12 Zero Point
Reference:
N/A Reference Point Notes:
N/A
-p PROC or SENS:
S Numberof Sensors:
1 How Processed:
SIGNAL FROM ANALOG OUTPUT OF MONITOR Sensor Location:
ISOKINETIC PROBES IN EACH RX BLDG VENT Alarm / Trip Set Points:
Hl=400, HI Hl=4500 NI Detector Power Supply N/A Cut-off Power Level:
NI Detector Power Supply N/A Tum-on Power Level:
Instrument Failure Mode:
HIGH & LOW SENSOR Temperature Compensation N/A For DP Transmitters:
Level Refarence Leg:
N/A Uniqur. System Desc.:
Reactor Building Vent Effluent Monitor Channel B is a wide range gas monitor consisting of Isokinetic probe assemblies, i
sample constioning unit, sample detection unit, and Control Room panei. The detector assembly consists d low, mld, and high range detectors.
i
- ~...
$wttiern 1,t.tes Dower company a
um.no no., o.n.<.tino n.m son
.e nequi,.m.rw srwu.t.on u.
namw SRS Process Computer System - Emergency Response Data ERDS SRS 1-3 System (ERDS)- Data Point Library Sheet No: 23 DATA POINT LIBRARY REFERENCE FILE Date:
01/07/92 Reactor Unit:
M01 Data Feeder:
EFF LIQ RAD Point ID:
PRM107 Plant Spec Point Dese.:
SERVICE WATER EFFLUENT Generic /Cond Dese..
RADIOACTIVITY OF RELEASED LIQUIDS Analog /Dlgital:
A Engr Units / Dig States:
CPS Engr Units Conversion:
uCl/Ml=((PRM107 in CPS) 5)*(4.3E 7)
Minimum Instr Range:
.1 Maximum Instr Range:
10E6 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROC or SENS:
S Number of Sensors:
1 How Processed:
SIGNAL INPUT FROM MONITOR Sensor Location:
SAMPLES SW PRIOR TO SW LEAVING RX BLDG Alarm / Trip Set Points:
Hi ALARM AS SET BY PLANT CHEMIST NI Detector Power Supply N/A Cut-off Power Level:
NI Detector Power Supply N/A Turn-on Power Level:
In.trument Failure Mode:
DOWNSCALE & UPSCALE Temperature Compensation N/A For DP Transmitters:
Level Reference Leg:
N/A Unique System Desc.:
Gamma radiation emitted by radioactive materials contcined in process ll quid are detected by a scintillation detector housed in shielded sampler. Sidestream sample is used from the service water line prior to leaving the Reactor Build!.ig.
After leaving Reactor Building, line discharges into circ water discharge pipe. Alarm :4etpoints vary with plant operation as determined by plant chemist.
f j
I bem states Power Cornpeny m.re nvoo, oencenna Pwd son we neeseened speew.on IM.e:
Nurreer; SRS Procesc Computer System - Emergency Response Data ERDS-SRE 13 System (ERDS) Data Point Library sheet No: 24
[
t f
DATA POINT LIBRARY REFERENCE FILE Date:
01/07/92 Reactor Unit:
M01 Data Feeder:
PCS i
NRC ERDS Parameter:
EFF LIQ RAD Point ID:
PRM109 Plant Spec Point Dese.:
RADWASTE EFFLUENT Generic /Cond Dese.:
RADIOACTIVITY OF RELEASED LIQUIDS Analog / Digital:
A Engr Units / Dig States:
CPS Engr Units Conversion:
uCl/Ml=((PRM109 in CPS) 7)*(2.5E 6)
Minimum Instr Range:
.1 Maximum instr Range:
10E6 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROC or SENS:
S Number of Sensors:
1 How Processed:
SIGNAL INPUT FROM MONITOR Sensor Location:
SAMPLED PRIOR TO LEAVING RADWASTE BLDG Alarm / Trip Set Points:
HI ALARM AS SET BY PLANT CHEMIST NI D6tector Power Supply N/A Cut off Power Level:
NI Detector Power Supply N/A Tum-on Power Level:
Instrument Failure Mode:
DOWNSCALE & UPSCALE, INOP Temperatura Compensation N/A For DP Transmitters:
Level Reference Leg:
N/A Unique System Dese.:
Gamma radiation emitted by radioactive materials contained in process liquid are detected by a scintillation detector housed in shielded sampler. Liquid is sampled prior to leaving the Radwaste Building. Afterleaving Radweste Building, eine discharges into discharge canal. Although Monticello has permits, Monticello maintains a policy of zero liquid radweste releases into the river. Alarm setpoints vary with plant operation as determined by plant chemist.
l
i I
Nervem states Power Compery i
Menheeto Noriteer Goteretpg Plent
(,34were Reculedmont specdecahon
[
laes Numter; SRS Process Computer System Emergency Response Data ERDS SRS 13 l
System (ERDS)- Data Point Library sheet No: 25
[
L l
t DATA POINT LIBRARY REFERENCE FILE Date:
01/07/92 Reactor Unit:
M01 Data Feeder:
EFF LIQ RAD Folnt 10:
PRM110 Plant Spec Point Dese.'
TB NORMAL WASTE SUMP CH A Generic /Cond Desc.:
RADIOACTIVITY OF RELEASED LlOUIDS Analog / Digital:
A Engr Units / Dig States:
CPM Engr Units Conversion:
uCl/Ml=((PRM110 in CPM)-400)*(3.5E 9)
Minimum instr Range:
10 Maximum Instr Range:
10E6 Zero Point Neference:
N/A Reference Point Notes:
N/A i
PROC or SENS:
S Number of Sensors:
1 How Processed:
SIGNAL INPUT FROM MONITOR Sensor Location:
SAMPLED PRIOR TO LEAVING TURBINE BLDG Alarm / Trip Set Polnts:
HI /.LARM AS SET BY PLANT CHEMIST NI Detector Power Supply N/A Cut off Power Level:
NI Detector Power Supply N/A Turn-on Power Level:
Instrument Failure Mode:
DOWNSCALE & UPSCALE, INOP Temperature Compensation N/A For DP Transmitters:
Level Reference Leg:
N/A Unique System Desc.:
Gamma radiation emitted by radioactive materials contained in process liquid are detected by a scintillation detectors in cry tube in sump. Gampled prior to leaving the Turbine Building.
1 Alarm setpoints vary with plant operation as datormined by
- plant chemist.
h
+ - -, - -
v r
t_,*_r, er----
v.w g~,v--
,m,,,....n--,
.n
.n.
w--
,-..,-.,.~~.n.r,.--,,---
-.. - -. ~ -.
L s
Wn aldes Power Company e
MwM NWCW GenWahna PW s%, ReayW specAcgp l
IRio.
Number:
SRS Process Computer System - Emergency Response Data ERDS SRS 1-3 i
System (ERDS)- Data Point Library shoot No: 26 I
DATA POINT LIBRARY REFERENCE FILE Date:
01/07/92 Reactor Unit:
M01 Data Feeder:
EFF LIQ RAD Point ID:
PRM111 Plant Spec Point Desc.:
TB NORMAL WASTE SUMP CH B Generic /Cond Desc.:
RADIOACTMTY OF RELEASED LIQUIDS Analog /Digibt:
A Engr Units / Dig States:
CPM Engr Units Conversion:
uCl/Ml=((PRM111 in CPM) 400)'(3.5E 9)
Minimum instr Range:
10 Maximum instr Range:
10E6 Zero Point
Reference:
N/A Reference Point Notas:
N/A PROC or SENS:
S Numberof Sensors:
1 How Processed:
SIGNAL INPUT FROM MONITOR Sensor Location:
SAMPLED PRIOR TO LEAVING TURBINE BLDG Alarm / Trip Set Points:
HI ALARM AS SET BY PLANT CHEMIST NI Detector Power Supply N/A Cut off Power Level:
NI Detector Power Supply N/A Turn on Power Level:
Instrument Failure Mode:
DOWNSCALE & UPSCALE, INOP l
- Temperature Compensation N/A For DP Transmitters:
Level Reference Leg:
N/A Unique System Dese.:
Gamma radiation emitted by radioactive materials contained in process liquid are detected by a scintillation detectors in dry tube it' tump. Sampled prior t's leaving the Turbine Building.
- Alarm setpoints vary with pla,st operation as determined by plant chemist.
4 s
wer 4
-w w-ye w
q.
=p,mav 3--
y-w-D t=v rr-
=--
wr'-
y-
.wr--
---y e
y--rq
. ~.
Northem atsles Power Company
)
Mottoedle Nucteer Genenstma Plant Sphere Requkement speelAcetkm Tibe Number; SRS Process Computer System - Emergency Response Data ERDS SRS.13 i
System (ERDS)- Data Point Library anew No: 27 i
DATA POINT LIBRARY REFERENCE FILF.
5 Date:
01/07/92 Reactor Unit:
M01 Data Feeder:
EFF LIO RAD Point ID:
PRM112 Plant Spec Point Desc.:
DISCHARGE CANAL MONITOR A j
Generic /Cond Desc.:
RADIOACTIVITY OF RELEASED LIQUIDS Analog / Digital:
A Engr Units / Dig States:
- Engr Units Conversion:
uCl/Ml=((PRM112 in CPS) 2)*(1.4E 7)
Minimum Instr Range:
.1 Maximum Instr Range:
- 10E6 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROC or SENS:
S Number of Sensors:
1 How Processed:
SIGNAL INPUT FROM MONITOR Sensor Location:
550FT DOWNSTREAM FROM DISCHARGE STRUCTURE Alarm / Trip Set Points:
HI ALARM AS SET BY PLANT CHEMIST NI Detector Power Supply N/A Cut off Power Level:
NI Detector Power Supply N/A Tum on Power Level:
Instrument Failure Mode:
DOWNSCALE & UPSCALE, INOP Temperature Compensation
- N/A-For DP Transmitters:
Level Reference Leg:
N/A Unique System Desc.:
Gamma radiation emitted by radioactive materials contained in process liquid are detected by a scintillation detectors.
Sample is drawn from 4 standpipes in canal 550 feet downstream from the discharge structure. Alarm setpoints vary with plant operation as determined by plant chemist.
I
-wv,
, w -
,-mw r n x-v
,vs wn
-W-v,-,,
,e
,--r--,
-<,e-r
...-. ~. -
Nor#ern States Power Company Monhceno Nuraiset oonorehne PW Scheere Requiremert Specrechen e
T fhe.
Number; SRS Process Computer System. Emergency Response Data ERDS. SRS-1-3 System (ERDS)- Data Point Library Shed No: 2S f
i DATA POINT LIBRARY REFERENCE FILE Date:
01/07/92 Reactor Unit:
M01 Data Feeder:
EFF LlO RAD Point ID:
PRM113 Plant Spec Point Desc.;
DISCHARGE CANAL MONITOR B Generic /Cond Desc.:
RADIOACTIVITY OF RELEASED LIQUIDS Analog / Digital:
A Engr Units / Dig States:
CPS l
Engr Units Converston:
UCL/Ml=((PRM113 in CPS) 2)*(1,4E 7)
Minimum Instr Pange:
.1 Maximum instr Range:
10E6 Zero Point
Reference:
N/A Reference Point Neies:
N/A PROC or SENS:
S Number of Sensors:
1 How Processed:
SIGNAL INPUT FROM MONITOR Sensor Location:
550FT DOWNSTREAM FROM DISCHARGE STRUCTURE Alarm / Trip Set Points:
Hi ALARM AS SET BY PLANT CHEMIST N! Detecter Power Supply N/A
~
Cut-off Power Level:
NI Detector Power Supply N/A
- Tum on Power Level:
Instrument r llure Mode:
DOWNSCALE & UPSCALE, INOP a
Temperature Compensation N/A For DP Transmitters:
' evel Reference Leg:
N/A Unique System Desc.:
Gamma radiation emitted by radioactive materials contained in process liquid are detected by a scintillation detectors.
Sample is drawn from 4 standpipes in canal 550 feet downstream from the oischarge structure. Alarm setpoints vary with plant operation as determined by plant chemist.
w r
-r,
=+r-
-t-
- ene, a,+
-e
.-wat,, -
-,e--1,,---w-
- m r i-
-t-
"e-e-v~tt i**--
2-
bem sestos Power Comparty Mont6ceno N7e ootershne Plant sobere Requirement Specifcohon ilus Number.
SRS Process Computer System Emergency Response Data ERDS-SRS 1-3 i
System (ERDS)- Data Point Library Sheet No: 29 t
DATA POINT LIS9ARY REFERENCE FILE l
Datw:
01/07/92 Reactor Unit:
M01 PCS Data Feeder: _
CND A/E RAD NRC ERDS Parameter:
Point ID:
PRM118 Plant Spec Point Desc.:
OFF GAS CH 1 Generic /Cond Desc.:
CONDENSER AIR EJECTOR RADIOACTIVITY Analog / Digital:
A Engr Units / Dig States:
MR/HR Engr Units Conversion:
N/A i
Minimum Instr Range:
1 Maximum Instr Range:
10E6 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROC or SENS:
S Number of Sensors:
1 How Processed:
SIGNAL OUTPUT FROM MONITOR Sensor L ocation:
SAMPLE DRAWN FROM OFF GAS LINE Alarm / Trip Set Points:
TRIP ON BOTH MONITORS UP,DOWN OR INOP NI Detector Power Supply N/A Cut off Power Level:
NI Detecto: Power Supply
-N/A Tum on Power Level:
Instrument Failure Mode:
LO'N Temperature Compensation N/A For DP Transmitters:
Level Reference Leg:
N/A Unique System Desc.:
OFF GAS CH 1 radiation monitor is positioned adjacent to a vertical sample chamber. A continuous sample is drawn from the off gas lino downstream from the Steam Jet Air Ehetors and ahead of the Recombiner trains. The sample is monitored after a time delay of approximately 2 minutes to permit Nitroger.16 and Oxygen 19 to decay. Alarm setpoints vary with plant operation as determined by plant chemist.
-. -~
e 6.n awn ro.= cwnsev uw e.e N w =w ow w minoe we son. n.aw.mww swumm Ias.
Number:
SRS Process Computer System - Emergency Response Data ERDS SRS 1-3 System (ERDS) Data Point Library shot wo: 30 i
DATA POINT LIBRARY REFERENCE FILE Date:
01/07/g2 Reactor Unit:
M01 C.t. Feeder:
CND A/E RAD 1
Point ID:
PRM119 Plant Spec Point Dese.:
OFF GAS CH 2 Generic /Cond Desc.:
CONDENSER AIR EJECTOR RADIOACTIVITY Analog / Digital:
A Engr Units / Dig States:
MR/HR Engr Units Conversion:
N/A
- Minimum Instr Range:
1 Madmum Instr Range:
10E6 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROC or SENS:
S Number of Sensors:
1 How Processed:
SIGNAL OUTPUT FROM MONITOR l
Sensor Location:
SAMPLE DOWNSTREAM OF STEAM JET AIR EJECT Alann/ Trip Set Points:
TRIP ON BOTH MONITORS UP.DOWN OR INOP NI Detector Power Supply N/A Cut off Power Level:
NI Detector Power Supply N/A Turn on Power Level:
Instrument Failure Mode:
LOW Temperature Compensation N/A For DP Transmitters:
Level Reference Leg:
N/A Unique System Desc.:
OFF GAS CH 2 radiation monitor is positioned adjacent to a vertical sample chamber. A continuous sample is drawn from the off gas line downstream from the Steam Jet Air Ejectors and ahead of the Recombiner trains, The sample is monitored after a time delay of approximately 2 mirutes to permit Nitro,An 16 and Oxygen 19 to decay. Alarm setpoints vary with plant operation as determined by plant chemist.
1 k
___-.m._,--,-_--.~...
... ~,_.---- -
-- _.,. ---. -- _- - -,, _ _ -- -,..,~--.--
_,.m
.. m.m
kules Power compent uneom w m o ansews son ne = :
Tes; Nmbet; SRS R ocess computer System - Emergency Response Data ERDS SRS 1-3 System (ERDS)- Data Point Library -
sh t No: 31 DATA POINT LIBRARY REFERENCE FILE Date:
01/07/92 Reactor Unit:
M01 Data Feeder:
DW RAD Point ID:
PCT 109 Plant Spec Point Desc.:
DRYWELL RADIATION CH A Generic /Cond Dese.:
RADIATION LEVEL IN THE DRYWELL Analog / Digital:
A Engr Units / Dig States:
R/HR Engr Units Conversion:
N/A Minimum instr Range; 1
Maximum Instr Range:
-10E8 Zero Point
Reference:
N/A Reference Point Notes:
b"A PROC or SENS:
S Numberof Sensors:
1 How Processed:
SIGNAL INPUT FROM RADIATION MONITOR Sensor Location:
DRYWELL 180 DEGREE AZIMUTH AT 944' Alarm / Trip Set Points:
Hl=50, HI Hl=1v0 NI Detector Power Supply N/A Cut off Power Level:
NI Detector Power Supply N/A Tum on Power Level:
Instrument Failure Mode:
HIGH SENSOR, INOP Temperature Compensation N/A For DP Transmitters:
Level Reference Leg:
N/A Unique System Desc.:
Purpose is to provide estimate of core damage by measuring drywell gamma radiation fields caused by fission product leakage from the core. Each sensor is an ionization chamber with an intemal U 234 source which gives 1R/HR reading for operation verificatlun. Elevation 944' is just below bottom of reartor vessel (949').
f y-+w-+-y, e-y emnr-=-,
e
=my--
.-.y w
w
--we--
-,srw,m m wr wro-yvvy,---
- ~.
- _..-. - ~ -.
s i
Northern stelee Power Company i
e Montecollo Nucteer Genershon Pient -
soRwere Rooulremord specticeuen l
Tihe'.
Number.
SRS.
Process Computer System - Emergency Response Data ERDS-SRS-1-3 System (ERDS). Data Point Library 1
Shoot No: 32 l
DATA POINT LIBRARY REFERENCE FILE i
Date:
01/07/92 Reactor Unit:
M01 l
Data Feeder:
DW RAD i
Point ID:
PCT 110 Plant Spec Point Desc.:
DRYWELL RADIATION CL' a Generic /Cond Desc.:
RADIATION LEVEL IN T',E DRYWELL Anato0/ Digital:
A Engr Units / Dig States:
R/HR Engr Units Conversion:
N/A Minimt.m Instr Range:
1 Maximum Instr Range:
10E8 Zero Point
Reference:
N/A Referance Point Notes:
N/A PROC or SENS:
S Numberof Sensors:
1 How Processed:
SIGNAL INPUT FROM RADIATION MONITOR Sensor Location:
DRYWELL 0 DEGREE AZIMUTH AT 944' i
Alarm / Trip Set Points:
Hl=50, HI Hl=100 NI Detector Power Supply N/A Cut off Power Level:
NI Detector Power Sply N/A Turn on Power Level:
Instrument Failure Mode:
HiGH SENSOR, INOP Ternperature Compensation N/A For DP Transmitters:
Level Reference Leg:
N/A Unique System Desc.:
Purpose is to provide estimate of core damage by measuring drywell garnma radiation fields caused by fission product leakage from the core. Each sensor is an lonization chamber with an intemal U 234 source which gives 1R/HR reading for operation verification. 8 Elevation 944' is just below bottom of reactor vessel (949').
2
- -_,~.
I
[dorthern $ tales Par N Company uaniano wuew o.n w<e ews son.w.ceas.mww so.esuuan IRte.
Number; SRS Process Computer System - Emergency Response Data ERDS-SRS-1-3 System (ERDS)- Data Point Library Shed No: 33 DATA POINT LIBRARY REFERENCE FILE Date:
S;/07/92 Reactor Unit:
M01 Data Feeder:
MN STEAM RAD Point ID:
- Plant Spec Point Desc.:
(not available)
Generic /Cond Desc.:
RADIATION LEVEL OF THE.'.*,!N STEAM LINE Analog / Digital:
Engr Units / Dig States:
Ena Units Conversion:
Minimum instr Range:
Maximum Instr Range:
Zero Point
Reference:
Reference Point Notes:
PROC or SENS:
Number of Sensors:
How Processet Sensor Loution:
Alarm / Trip Set Points:
NI Detector Power Supply Cut off Power Level:
NI Detector Power Supply Tum on Power Level:
Instrument Failure Mode:
Temperature Comp &sation For DP Transmitters:
Level Reference Leg:
Unique System Desc.:
Not available to Process Computer System.
y
, - r -.. -
,.-n r
~
c,,
,.----,,v---
--a--...,
e-,
i sWo. Power Company uwmo a. wc w oenw e e ews son.w. n.awomcw co.cww.n l
7 80s.
IcJmber; j
SRS Process Computer System Emergency Response Data ERDS SRS 1-3 l
System (ERDS) Drta Point Library sheet No: 34 DATA POINT LIBRARY REFERENCE FILE i
Date:
01/07/g2 Reactor Unit:
M01 Data Feeder:
DW PRESS Point ID:
D23C0010 Plant Spec Po!nl Desc.:
_ VAllDATED DRYWELL PRESSURE Generic /Cond Desc.:
DRYWELL PRESSURE Analog / Digital:
A Engr Units / Dig States:
n%IG
. Engr Units Conversion:
N/A
- Minimum Instr Range:
5 Maximum Instr Range:
250 Zero Point
Reference:
N/A Reference Poht Notes:
N/A PROC or SENS:
P Number of Sensors:
4 How Processed:
WEIGHTED AVERAGE OF CONSISTENT DW PRESS i
Sensor Location:
SENSING LINES FROM DRYWELL Alarm / Trip Set Points:
ALARMS LOW =0.1, HIGH=1.5 4
NI Detector Power Supply N/A Cut-off Power Level:
NI Detector Power Supply N/A l
Turn-on Power Level:
Instrument Failure Mode:
HIGH & LOW SENSOR Temperature Compensation N/A For DP Transmitters:
Level Reference Leg:
N/A Unique System Desc.:
This point consists of either a weighted average of all consistent drywell pressure or an average of in-range drywell pressures if there are less than the required number of consistent singals. Four drywell pressure signals consist of one narrow range ( 2 to 3), one wide range (0 to 80) and two recident ( 5 to 250) ranges. Weighted averages produces average that is weighted based on instrument accuracy.
j Drywellintemal design pressure is 56 PSIG at 281 Degrees F. At 2 PSIG, RPS initiates Reactor SCRAM and Primary Containment isolatlen initiates Group 2 & 3.
++e.--
?
y y'
g-v-.=-
g.-
.g,,.s
-p<ww.ei.m.wsw-t.
v sia.-rr f'
F'
'N*
f'
- 'r
'-*e-*W'-P
i korthern 3Mes Power Company Montecho Nuc4eer Generstr2 PV Software Requirement Spec (cetion j
1me.
Numper; SRS Process Computer System. Emergency Response Data ERDS SRS-1-3 System (ERDS)- Data Point Library Sheet No: 35 DATA POldT LIBRARY REFERENCE FILE Date:
01/07/92 Reactor Unit:
M01 Data Feeder:
DW TEMP Point ID:
D2SCO310 Plant Spec Point Desc.:
VAllDATED DRYWELL TEMPERATURE Generic /Cond Desc.:
DRYWELL TEMPERATURE Analog / Digital:
A Engr Units / Dig States:
DEGF Engr Units Conversion:
N/A Minimum Instr Range:
32 Maximum instr Range:
-400 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROC or SENS:
P Number of Sensors:
10 How Proerssed:
AVERAGE OF CONSISTENT DW TEMPERAURES Sensor Location:
16 SENSORS AT 8 DRYWELL LOCATIONS Alarm / Trip Set Points:
Hl=150 DEGF NI Detector Power Supply N/A Cut off Power Level:
NI Detector Power Supply N/A Tum-on Power Level:
Instrument Failure Mode:
HIGH & LOW SENSOR Temperat'are Compensation N/A For DP Tran'aitters:
Level Reference Leg:
N/A Unique System Desc -
This point consists of either a weighted average bulk temperature of consistent reg!onal temperatures or an unvalidated, non weighted average of allin-range drywell temperatures. Regional weighting factors co npensate for differences in drywell volume at the various elevations Each location utilizes two sensors and are located in Drywell at:
Elev 932'(East & West), Elev 951'(North & South), Elev 970' (East & West), and Elev 994' (North & South),
. ~-..
-.- -_~ ~ - -. - - ~.
Northem Stsies Power Company.
Monticeno Nucteer Generating Pmnt sofhvore Requirement speciflestkm ime:
Number:
SRS-Process Computer System - Emergency Response Data ERDS SRS-1-3 System (ERDS)- Data Point Library sheet No: 3r DATA POINT LIBRARY REFERENCE FILE Date:
01/07/92-Reactor Unit:
M01 Data Feeder:
~
NRC ERDS Parameter:
SPTEV
' Point ID:
D23C04.
Pit.nt Spec Point Desc.:
- VAllDATED TORUS TEMPERATURE Generic /Cond Desc.:
SUPPRESSION POOL TEMPERATURE
.aalog/ Digital:
A
~
Engr Units / Dig States:
CEGF l
Engr Units Conversion:
N/A Minimum Instr Range:
30 Maximum Instr Range:
230 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROC or SENS:
P Numbo. of Sensors:
16 How Processed:
AVERAGE OF 2 SPOTMOS (8 SENSORS EACH)
Sensor Location:
2 SENSORS IN EACH OF 8 TORUS SRV BAYS Alarm / Trip Set Points:
HIGH=90 NI Detector Power Supply N/A Cut off Power Level:
NI Detector Power Supply N/A Tum-or Power Level; instrument Failure Mode:
HIGH & LOW SENSOR, SPOTMOS INOP Temperature Compensation N/A For DP Transmitters:
1 wol Reference Leg:
N/A Uni +o System Desc.:
VALIDATED TORUS TEMPERATURE is the average of the inputs from two Suppression Pool Temperature Monitoring Systems (SPOTMOS), Each system generates an average of eight sensors. Each sensor is located in one of the etaht bays that Safety Relief Valves discharge into.
J 1
J w--
y
horthem States Power Company Monticello Nuclear Generating Plant software Requirement specification idle:
Number:
.SRS Process Computer System - Emergency Response Data ERDS-SRS-1-3 7
System (ERDS)- Data Point Library i
sheet No-37-DATA POINT LIBRARY REFERENCE FILE Date:
0?/07/92 Reactor Unit:
MQ1 Data Feeder:'-
PUS NRC ERDS Parameter; oP LEVEL Point ID:
G43C0015 Plant Spec Point Dese.:
VAllDATED TORUS WATER LEVEL Generic /Cond Dese.:
SUPPRESSION POOL WATER LEVEL
- Analog / Digital:
A Engr Units / Dig States:
INCHES Engr Units Conversion:
N/A Minimum Instr Range:
-96 Maximum Instr Range:
180 Zero Point
Reference:
N/A Reference Point Notes:
0"= ELEVATION 910'= 530,000 GALLONS PROC or SENS:
P Number of Sensors:
4 How Processed:
WEIGHTED AVERAGE OF CONSISTENT LEVELS Sensor Location:
LEVEL TAPS OFF TORUS SHELL Alarm / Trip Set Points:
HIGH=2, LO= 2 NI Detector Power Supply N/A Cut-off Power Level:
NI Detector Power Supply -
N/A Tum-on Power Level:
Instrument Failure Mode:
HIGH & LOW SENSOR Temperature Compensation N/A For DP Transmitters:
Level Reference Leg:
N/A Unique System Desc.:
This point consists of either a weighted aveinge of all consistent torus water levels or an average of in-range torus water levels if there are less than the required number of consistent signals. Four torus water level signals consist of two narrow range (-15 to 15) and two wide range (-96 to 180),
Weighted averages produce an average that is based on
!.istrunn.nt accuracy. HPCI suction transfer occurs at 2". Tech Specs lent greater than -4" and less than 2.9".
~
p Northern States Power Company.
- Monticeno Nucl64r Generating Plant Software Requirernent Specificatum I
Tfi6e:
Nurnber; SRS Process Comouter System - Emergency Responce Data ERDS-SRS-1-3 System (ERDS)- Data Point Library Sheet No: - 38 DATA POINT LIBRARY REFERENCE FILE Reactor Unit:_
01/07/92 Date: _
M01 Data Feeder:
H2 CONC Point ID:
PCT 116 Plant Spec Point Desc.:
PCTMT H2 ANALYZER A
. Generic /Cond Desc.:
DRYWELL OR TORUS HYDROGEN CONCENTRATION Analog / Digital:
A Engr Units / Dig States:
Engr Units Conversion:
N/A
. Minimum Instr Range:
0 Maximum Instr Range:
20 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROC or StiNS:
S Number of Sensors:
1 How Processed:
SIGNAL OUTPUT FROM H2 ANALYZER Sensor Location:
SAMPLE LINES UPPER DW TORUS,CGCS IN & OUT Alarm / Trip Set Points:
N/A NI Detector Power Supply N/A Cut-off Power Level:
NI Detector Power Supply N/A Tum-on Power Level:
Instrument Failure Mode:
HIGH & LOW SENSOR, SYSTEM OFF
- Temperature Compensation N/A For DP Transmitters:
Level Reference Leg:
N/A Unique System Desc.:
Analyzers are normally shutdown and values will usually read less than 0.75% System is capable of analyzing samples from Drywell (elev 994'), Torus and Combustible Gas Control System inlet and outlet. Sample line and sample retum valves close on Group 2 Isolation, t
~
i Northem $teles Power Company
' MonheeNo Nucieer Generstre Plant Software Requirement Specifket on Tale:
Number:
SRS Process Computer System - Emergency Response Data -
ERDS-SRS-1-3 System (ERDS)- Data Point Library sheet No: 39 DATA POINT LIBRARY REFERENCE FILE Date:
01/07/92 Reactor Unit:
M01 Data Feeder.
H2 CONC Point ID:
PCT 117-Plant Spec Point Desc.:
PCTMT H2 ANALYZER B Generic /Cond Desc.:
DRYWELL OR TORUS HYDROGEN CONCENTRATION Analog / Digital:
A-Engr Units / Dig States:
'/o Engr Units Conversion:
N/A
-. Minimum Instr Range:
0 Maximum Instr Range:
20 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROC or SENS:
S Numberof Sensors:
1 How Processed:
SIGNAL OUTPUT FROM H2 ANALYZER Sensor Location:
SAMPLE LINES UPPER DW, TORUS CGCS IN & OUT Alarm / Trip Set Points:
N/A NI Detector Power Supply N/A Cut off Power Level:
NI Detector Power Supply N/A Turn-on Power Level:
Instrument Failure Mode:
HIGH & LOW SENSOR, SYSTEM OFF Temperature Compensation N/A For DP Transmitters:
Level Reference Leg:
N/A Unique System Desc.:
Analyzers are normally shutdown and values will usually read less than 0.75% System is capable of analyzing samples from Drywell (elev 994'), Torus and Combustible Gas Control System inlet and outlet. Sample line and sample retum valves c!ose on Group 2 Isolation.
~_ -.. -.
~
Northom states Power Company r
Winucello Nuclear Generstmo P6 erd Software Requirement som:lfication Tale:
Number:
,SRS
- Process Computer System - Emergency Response Data ERDS-SRS-1-3
_ System (ERDS)- Data Point Library Sheet No: 40 DATA POINT LIBRARY REFERENCE FILE Date:
'01/07/92 Reactor Unit:
M01 Data Feeder.
H2 CONC Point ID:
PCT 118 Plant Spec Point Desc.:
PCTMT O2 ANALYZER A-Generic /Cond Desc.:
DRYWELL OR TORUS HYDROGEN CONCENTRATION Analog / Digital:
A Engr Unitc/ Dig States:
Engr Units Conversion:
N/A Minimum Instr Range:
0 Maximum Instr Range:
25 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROC or SENS:
S Numberof Sensors:
1 How Processed:
SIGNAL OUTPUT FROM O2 ANALYZER Sensor Location:
SAMPLE LINES UPPER DW, TORUS CGCS IN & OUT Alarm / Trip Set Points:
N/A NI Detector Power Supply N/A Cut off Power Level:
NI Detector Power Supply N/A Turn-on Power Level:
Instrument Failure Mode:
HIGH & LOW SENSOh, SYSTEM OFF Temperature Compensation N/A For DP Transmit;ers:
Level Reference Leg:
N/A Unique System Desc.:
Analyzers are normally shutdown and vraues will usually read less than 0.75%. System is capable of analyzing samples from Drywell (elev 994'), Torus and Combustible Gas Control System inlet and outlet.' Sample line and sample retum valves close on Group 2 Isolation. Normal operation concentrations are 2.4 %
i s
r -
w
[Jotthern states Power Company Monticeno Nuclear Generating Plant Software Requirement Specincaten
Title:
Number:
SRS Process Computer System - Emergency Response Data ERDS-SRS-1-3 System (ERDS)- Data Point Library sheet No: 4i DATA POINT LIBRARY REFERENCE FILE Date:
01/07/92 Reactor Unit:
M01 Data Feeder:
PCS l
NRC ERDS Parameter:
H2 CONC Point ID:
PCT 119 Plant Spec Point Desc.:
PCTMT O2 ANALYZER B Generic /Cond Desc.:
DRYWELL OR TORUS HYDROGEN CONCENTRATION Analog / Digital:
A Engr Units / Dig States:
Engr Units Conversion:
N/A Minimum Instr Range:
0 Maximum Instr Range:
25 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROC or SENS:
S Number of Sensors:
1 How Processed:
SIGNAL OUTPUT FROM O2 ANALYZER Sensor Location:
SAMPLE LINES UPPER DW, TORUS,CGCS IN & OUT Alarm / Trip Set Points:
N/A NI Detector Power Supply N/A Cut off Power Level:
NI Detector Power Supply N/A Tum-on Power Level:
Instrument Failure Mode:
HIGH & LOW SENSOR, SYSTEM OFF Temperature Compensation N/A For DP Transmitters:
Level Reference Leg:
N/A Unique System Desc.:
Analyzers are normally shutdown and values will usually read less than 0.75%. System is capable of analyzing samples from Drywell (elev 994'), Torus and Combustible Gas Control System inlet and outlet. Sample line and sample retum valves close on Group 2 Isolation. Normal operation concentrations are 2,4%.
Northern States Power Company Monteoso Nuclear oenerating Plant Software Requirement spectreaHon Tme:
Nurnber; SRS Process Computer System - Emergency Response Data ERDS-SRS-1-3 System (ERDS)- Data Point Library Sheet No: 42 DATA POINT LIBRARY REFERENCE FILE Date:
01/07/92 Reactor Unit:
MO1 Data Feeder:
CST LEVEL Point ID:
CST 100 Plant Spec Point Desc.:
CST TANK LEVEL A Generic /Cond Desc.:
CONDENSATE STORAGE TANK LEVEL Analog / Digital:
A Engr Units / Dig States:
FEET Engr Units Conversion:
N/A Minimum Instr Range:
5 Maximum Instr Range:
25 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROC or SENS:
S Number of Sensors:
1 How Processed:
SIGNAL FROM LEVEL TRANSMITTER Sensor Location:
LEVEL TX ON WATER COLUMN IN RX BLDG Alarm / Trip Set Points:
Hl=24'(225.600 gal) LO=11.5'(108,100 gal)
NI Detector Power Supply N/A Cut off Power Level:
NI Detector Power Supply N/A Tum-on Power Level:
Instrument Failure Mode:
LOW Temperature Compensation N/A For DP Transmitters:
Level Reference Leg:
N/A Unique System Desc.:
Condensete Storage Tank (CST) Level A is the water level in the A CST. Two CSTs exist with a tank capacity of 230,000 gallons each. Makeup condensate water is provided through 3 electric pumps from the CST tanks to various plant systems.
Each tank has suction line for Control Rod Drive, HPCI, Core Spray, RHP,, and RCIC systems. At 7'(65,800 gal) receive CST Low-Low Level alarm and condensate service pumps trip. At 2'8"(25,100 gal) HPCI and RCIC tran.efer to Torus suction.
teorthem States Power Company Montcello Nuck ar Generahna Plant Software Requirement Specircatnon Tiue:
Number:
SRS Process Computer System - Emergency Response Data ERDS-SRS-1-3 System (ERDS)- Data Point Library Sheet No: 43 DATA POINT LIBRARY REFERENCE FILE Date:
01/07/92 Reactor Unit:
MO1 Data Feeder.
CST LEVEL Point ID:
CST 101 Plant Spec Point Desc.:
CST TANK LEVEL B Generic /Cond Desc.:
CONDENSATE STORAGE TANK LEVEL Analog / Digital:
A Engr Units / Dig States:
FEET Engr Units Conversion:
N/A Minimum Instr Range:
5 Maximum instr Range:
25 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROC or SENS:
S Number of Sensors:
1 How Processed:
SIGNAL FROM LEVEL TRANSMITTER Sensor Location:
LEVEL TX ON WATER COLUMN IN RX BLDG Alarm / Trip Set Points:
Hir24'(225,600 gal) LO=11.5'(108,100 gal)
NI Detector Power Supply N/A Cut-off Power Level:
NI Detector Power Supply N/A Turn-on Power Level:
Instrument Failure Mode:
LOW Temperdure Compensation N/A For DP Transmitters:
Level Reference Leg:
N/A Unique System Desc.:
Condensate Storage Tank (CST) Level B is the water level in the B CST. Two CSTs exist with a tank capacity nf 230,000 gallons each. Makeup condensate water is provided through 3 electric pumps from the CST tanks to various plant systems.
Each tank has suction line for Control Rod Drive, HPCI, Core Spray, RHR, and RCIC systems. At 7'(65,800 gal) receive CST Low-Low Level alarm and condensate service pumps trip. At 2'8*(25,100 gal) HPCI and RCIC transfer to Torus suction.
Northern States Power company..
Monticek Nuclear Generating Plant SoRwere Requirement Specifcetion TNW Number:
SRS Process Computer System - Emergency Response Data ERDS-SRS-1-3 System (ERDS)- Data Point Library -
sneet No; 44-DATA POINT LIBRARY REFERENCE FILE Date:
01/07/92 Reactor Unit:
M01 Data Feeder:
WIND SPEED Point ID:
MET 102 Plant Spec Point Desc.:
PRIMARY MET TOWER 43M AVG WIND SPEED A Generic /Cond Dese.:
WIND SPEED AT THE REACTOR SITE Analog / Digital:
-A Engr Units / Dig States:
MPH Engr Units Conversion:
N/A Minimum instr Range:
0 Maximum Instr Range:
100.00 Zero Point
Reference:
N/A Reference Point Notes:
N/A
- PROC or SENS:
P Number of Sensors:
1 How Processed:
15 MINUTE AVERAGE OF 5 SECOND VALUES Sensor Location:
PRIMARY MET TOWER AT 43 METER HEIGHT Alarm / Trip Set Points:
N/A NI Detector Power Supply N/A Cut-off Power Level:
NI Detector Power Supply N/A Turn-on Power Level:
Instrument Failure Mode:
HIGH & LOW SENSOR Temperature Compensation N/A
-For DP Transmitters:
Level Reference Leg:
N/A Unique System Desc.:
Data is collected every five seconds, averaged every 15 minutes, and stored in data files as 15-minute average.
l r-m
i
'6 steles Poner Company software Reauirement spec 4hoshon Manhceno Nucieer Generehna Plert Tsue:-
Number; -
SRS -
- Process Computer System - Emergency Response Data ERDS-SRS-1-3
- System (ERDS) - Data Point Library-Sheet No: 45^
t
- DATA POINT LIBRARY REFERENCE FILE l
Date:
01/07/92 Reactor Unit:
M01 Data Feeder:
WIND SPEED Point ID:
MET 103 Plant Spec Point Desc.:
PRIMARY MET TOWER 43M AVG WIND SPEED B
._ Generic /Cond Desc.:
WIND SPEED AT THE REACTOR SITE
-~ Analog / Digital:
A 4
Engr Units / Dig States:
MPH
- Engr. Units Conversion:
N/A Minimum Instr Range:
0 Maximum Instr Range:
100.00 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROC or SENS:
P Number of Sensors:
1 How Processed:
15 MINUTE AVERAGE OF 5 SECOND VALUES Sensor Location:
PRIMARY MET TOWER AT 43 METER HEIGHT
' Alarm / Trip Set Points:
N/A NI Detector Power Supply N/A Cut off Power Level:
NI Detector Power Supply N/A Tum-on Power Level:
Instrument Failure Mode:
HIGH & LOW SENSOR Temperature Compensation N/A For DP Transmitters:
Level Reference Leg:
N/A Unique System Desc.:
Data is collected every five seconds, averaged every 15 minutes, and stored in data files as 15-minute average.
. ~.
-~.
Northern States Power Company Monicello Nuclear oenerahng Plant Software Requirement Specircaton
Title:
Numbec SRS Process Computer System - Emergency Response Data -
ERDS-SRS-1-3 System (ERDS)- Data Point Library Sheet No: ~46 g
DATA POINT LIBRARY REFERENCE FILE Date:
01/07/92 Reactor Unit:
M01 Data Feeder:
WIND SPEED Point ID:
MET 104 -
Plant Spec Point Dese.:
PRIMARY MET TOWER 100M AVG WIND SPEED A Generic /Cond Desc.:
WIND SPEED AT THE REACTOR SITE Analog / Digital:
A Engr Units / Dig States:
MPH Engr Units Conversion:
N/A Minimum Instr Range:
0-Maximum instr Range:
100.00 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROC or SENS:
P Number of Sensors:
1
.How Processed:
15 MINUTE AVERAGE OF 5 SECOND VALUES Sensor Location:
PRIMARY MET TOWER AT 100 METER HEIGHT Alarm / Trip Set Points:
N/A NI Detector Power Supply N/A Cut off Power Level:
NI Detector Power Supply N/A
- Turn-on Power Level:
Instrument Failure Mode:
HIGH & LOW SENSOR Temperature Compensation N/A For DP Transmitters:
Level Reference Leg:
N/A Unique System Desc.:
Data is collected every five seconds, averaged every 15 minutes, and stored in data files as 15-minute average.
4 F
Jotthern states Power Company Montreflo Nuclear Generatus Plant Software Requiremerd Specifcation Tsue:
Number:
. Process Computer System - Emergency Response Data ERDS SRS-1-3 System GRDS)- Data Point Library Sheet No: 47 DATA POINT LIBRARY REFERENCE FILE Date:
01/07/92 Reactor Unit:
M01 Data Feeder:
WIND SPEED Point ID:
MET 105 Plant Spec Point Dese.:
PRIMARY MET TOW'ER 100M AVG WIND SPEED B Generic /Cond Desc.:
WIND SPEED AT THE REACTOR SITE Analog / Digital:
A Engr Units / Dig States:
MPH Engr Units Conversion:
N/A Minimum Instr Range:
0 Maximum Instr Range:
100.00 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROC or SENS:
P Number of Sensors:
1 How Processed:
15 MINUTE AVERAGE OF 5 SECOND VALUES Sensor Location:
PRIMARY MET TOWER AT 100 METER HEIGHT Alarm / Trip Set Points:
N/A NI Detector Power Supply N/A Cut-off Power Level:
NI Detector Power Supply N/A Turn-on Power Level:
Instrument Failure Mode:
HIGH & LOW SENSOR Temperature Compensation N/A For DP Transmitter::
Level Reference Leg: N/A Unique System Desc.:
Data is collected every five seconds, averaged every 15 minutes, and stored in data files as 15-minute average.
o-_.__
m.
Northem steles Power Company.
+'
' Monhoolio Nucieer Generehna Pterd sonwere Recuirement Specincetion
Title:
- Number, SRS Process Computer System - Emergency Response Data
- ERDS-SRS-1-3 1
System (ERDS)- Data Point Library Sheet No: "48 i
DATA POINT LIBRARY REFERENCE FILE '
+
4
- Date:
601/07/92 Resctor Unit:
M01 Data Feeder.
- NRC ERDS Parameter.
WIND DIR Point ID:
MET 106 Plant Spec Point Desc.:
PRIMARY MET TOWER 43M AVG WIND DIRECT A 4
Generic /Cond Desc.:
. WIND DIRECTION AT THE REACTOR SITE -
Analog / Digital:
A Engr Units / Dig States:
-DEGFR
-Engr Units Conversion:
N/A
- Minimum Instr Range:
0
- Maximum Instr Range:
540,00
'Zero Point
Reference:
.N/A Reference Point Notes:
N/A-PROC or SENS:
P Number of Sensors:
1 How Processed:
15 MINUTE AVERAGE OF 5 SECOND VALUES
- Sensor Locationi PRIMARY MET TOWER AT 43 METER HEIGHT Alarm / Trip Set Points:..
N/A NI Detector Power Supply N/A Cut-off Power Level:
NI Detector Power Supply -
N/A Turn on Power Level:
Instrument Failure Mode:
HIGH & LOW SENSOR Temperature Compensation N/A For DP Transmitters:
Level Reference Leg:
N/A Unique System Desc.:
Data is collected every five seconds, averaged every 15-minutes, and stored in data files as 15-minute average.
m W
M i.-
,e
,.m.s 4
-w,,
,.-~.---,....
-. h.. i
Northern States Power Cornpany e
Montee11o Nuclear Generating Plant Software Requirement Specifcaton, Taio Number:
SRS Process Computer System - Emergency Response Data ERDS-SRS-1-3 System (ERDS)- Data Point Library sheet No: 49 l
DATA POINT LIBRARY REFERENCE FILE Date:
01/07/92 Reactor Unit:
M01 Data Feeder:
WIND DIR Point ID:
MET 107 Plant Spec Point Desc.:
PRIMARY MET TOWER 43M AVG WIND DIRECT B Generic /Cond Desc.:
WIND DIRECTION AT THE REACTOR SITE Analog / Digital:
A Engr Units / Dig States:
DEGFR Engr Units Conversion:
N/A Minimum Instr Range:
0 Maximum instr Range:
540.00 i
Zero Point
Reference:
N/A Reference Point Notes:
N/A PROC or SENS:
P Number of Sensors:
1 How Processed:
15 MINUTE AVERAGE OF 5 SECOND VALUES Sensor Location:
PRIMARY MET TOWER AT 43 METER HEIGHT Alarm / Trip Set Points:
N/A NI Detector Power Supply N/A Cut-off Power Level:
NI Detector Power Supply N/A Tum-on Power Level:
Instrument Failure Mode:
HIGH & LOW SENSOR Temperature Compensation N/A For DP Transmitters:
Level Reference Leg:
N/A Unique System Desc.:
Data is collected every five seconds, averaged every 15 minutes, and stored in data files as 15-minute average.
=...
Northern states Power Company.
Mortcono Nuclear Gerwetana Plant Software Requirement Specifcetion TRie:
Number;
- SRS _
- Process Computer System _- Emergency Response Data ERDS-SRS-1-3 System (ERDS)- Data Point Library Sheet No: 150 I
DATA POINT LIBRARY REFERENCE FILE Date:
01/07/92
- Reactor Unit:
M01 Data Feeder:
WIND DlR Point ID:
MET 108 Plant Spec Point Desc.:
PRIMARY MET TOWER 100M AVG WIND DIRECT A Generic /Cond Desc.:
WIND DIRECTION AT THE REACTOR SITE
. Analog / Digital:-
A
' Engr Units / Dig States:
DEGFR Engr Units Conversion:
N/A Minimum Instr Range:
0 Maximum Instr Range:
540.00 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROC or SENS:
P Number of Sensors:
1 How Processed:
15 MINUTE AVERAGE OF 5 SECOND VALUES Sensor Location:
PRIMARY MET TOWER AT 100 METER HEIGHT Alarm / Trip Set Points:
N/A NI Detector Power Supply N/A Cut off Power Level:
NI Detector Power Supply N/A Tum-on Power Level:
Instrument Failure Mode:
HIGH & LOW SENSOR Temperature Compensation
-N/A For DP Transmitters:
Level Reference Leg:
N/A Unique System Desc.:
Data is collected every five seconds, averaged every 15 minutes, and stored in data files as 15-minute average.
P m
e-
.- ~ -
~ Northem States Power company -
' Monhoebo MM Generating Plant Software Requirement specthcahon Tale:
Number:
- SRS' Process Computer System _- Emergency Response. Data ERDS-SRS-1-3 System (ERDS) Data Point Library
_i
- Sheet No: 51
- i
. DATA POINT LIBRARY REFERENCE FILE -
i
- Date:
01/07/92-Reactor Unit:
. MO1 Data Feeder:
.)
- NRC ERDS Parameter:
- WIND DlR
)
. Point ID:.
MET 109 I
Plant Spec Point Desc.:
PRIMARY MET TOWER 100M AVG WIND DIRECT B
-Generic /Cond Desc.:
WIND DIRECTION AT THE REACTOR SITE Analog / Digital:
A
- Engr Units / Dig States:
DEGFR
- Engr Units Conversion
_N/A Minimum Instr Range:
0 Maximum Instr Range:
540.00 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROC or SENS:
P Number of Sensors:
1-How Processed:
15 MINUTE AVERAGE OF 5 SECOND VALUES Sensor Location:
PRIMARY MET TOWER AT 100 METER HEIGHT
-Alarm / Trip Set Points:
N/A NI Detector Power Supply N/A Cut off Power Level:
NI Detector Power Supply N/A Tum-on Power Level:
Instrunient Failure Mode:
HIGH & LOW SENSOR Temperature Compensation N/A For DP Transmitters:
Level Reference Leg:
N/A Unique System Desc.:
Data is collected every five seconds, averaged every 15 minutes, and stored in data files as 15-minute average.
a w
y me r
m-
,,e.+
.'s.-
m uye 9
+
s 4-t w
, - = - - - - -
Northern Stones Power company Monhooto Nucteer oonorahna Plant sonwere Rooulroment specucahon Tme:
Number:
SRS.
L Process Computer System _- Emergency Response Data -
ERDS-SRS-1-3 i
System (ERDS)- Data Point Library -
Sheet No: :52 DATA POINT LIBRARY REFERENCE FILE w
Date:
01/07/92.
Reactor Unit:
' M01 --
Data Feeder:
STAB CLASS
- PointID:
MET 110 j
Plant Spec Point Dese,:
. PRIMARY MET TOWER 43M AVG DELTA TEMP A -
- Generic /Cond Desc.:
AIR STABILITY AT THE REACTOR SITE -
- Analog / Digital
A Engr Units / Dig States:
- DEGF, Engr Units Conversion:
N/A Minimum Instr Range:
-9.0 Maximum Instr Range:
9.0 N/A Zero Point
Reference:
t Reference Point Notes:
N/A PROC or SENS:
PROC f
Number of Sensors:-
2 How Processed:
AVERAGED DIFFERENTIAL Sensor Location:
PRIMARY MET AT 10 & 43 METER HEIGHT Alarm / Trip Set Points:
N/A NI Detector Power Supply -
N/A Cut off Power Level:
NI Detector Power Supp:.
N/A Turn-on Power Level:
Instrument Failure Mode:
HIGH & LOW SENSOR Temperature Compensation
'N/A For DP Transmitters:
- Level Reference Leg:
N/A-
. Unique System Desc.:
Data is collected every five seconds, averaged every 15 minutes, and stored in data files as 15-minute average. This value represents the difference in temperature in degF/100ft.
-)
l
~
. _ -. - = - - -..
[Northom states Power Company 4
Monleello Nucieer ownereuno Ptent Software Requirement speciflceuon Tsae; Nur eer; SRS Process Computer System - Emergency Response Data ERDS-SRS-1-3 System (ERDS)- Data Point Library sheet No: 53
)
DATA POINT LIBRARY REFERENCE FILE Date:
01/07/92 Reactor Unit:
M01 Data Feeder.
STAB CLASS PointID:
MET 111 Plant Spec Point Desc.;
PRIMARY MET TOWER 43M AVG DELTA TEMP B Generic /Cond Desc.:
AIR STABILITY AT THE REACTOR SITE Analog / Digital:
A Engr Units / Dig States:
DEGF Engr Units Conversion:
N/A Minimum Instr Range:
-9.0 Maximum Instr Range:
9.0 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROC or SENS:-
PROC Number of Sensors:
2 Hew Processed:
AVERAGED DIFFERENTIAL Sensor Location:
PRIMARY MET AT 10 & 43 METER HEIGHT AlamVTrip Set Points:
N/A NI Detector Power Supply N/A Cut-off Power Level:
NI Detector Power Supply N/A Tum-on Power Level:
Instrument Failure Mode:
HIGH & LOW SENSOR Temperature Compensation N/A For DP Transmitters:
Level Reference Leg:
N/A Unique System Dese.:
Data is collected every five seconds, averaged avery 15 minutes, and stored in data files as 15-mirute average. This value represents the difference in temperature in degF/100ft.
f i
1 q
y wen-r--
w
NorttrJrn States Power Company e
Montcebo Nuclear Generating Plant SoRwere Requirement Specircation Title.
Number; SRS Process Computer System - Emergency Response Data ERDS-SRS-1-3
. System (ERDS)- Data Point Library Sheet No: 54 DATA POINT LIBRARY REFERENCE FILE Date:
01/07/92 Reactor Unit:
1 Data Feeder:
S NRC ERDS Paramater:
AB CLASS PointID:
MET 112 Plant Spec Point Desc.:
PRIMARY MET TOWER 100M AVG DELTA TEMP A Generic /Cond Dese.:
AIR STABILITY AT THE REACTOR SITE Analog / Digital:
A
- Engr Units / Dig States:
DEGF Engr Units Conversion:
N/A Minimum Instr Range:
-9.0 Maximum Instr Range:
- 9.0 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROC or SENS:
PROC Number of Sensors:
2 How Processed:
AVERAGED DIFFERE.NTIAL Sensor Location:
PRIMAR( MET AT 10 & 100 METER HEIGHT Alarm / Trip Set Points:
N/A NI Detector Power Supply N/A Cut off Power Level:
NI Detector Power Supply N/A Tum-on Power Level:
Instrument Failure Mode:
HIGH & LOW SENSOR Temperature Compensation N/A For DP Transmitters:
Level Reference Leg:
N/A Unique System Desc.:
Data is collected every five seconds, averaged every 15 minutes, and stored in data files as 15-minute average. This value represents the difference in temperature in degF/100ft.
Northern States Power Company
-e-Monticono Nuclear Generating Plant Sonwere Raoutrement specmcetien -
Tee:
Number:
SRS Process Computer System - Emergency Response Data ERDS-SRS-1-3 System (ERDS).- Data Point Library Shot No; 55 f
DATA POINT LIBRARY REFERENCE FILE Date:
01/07/92 Reactor Unit:
M01 Data Feeder:
STAB CLASS PointID:
MET 113 Plant Spec Point Desc.:
PRIMARY MET TOWER 100M AVG DELTA TEMP B Generic /Cond Desc.:
AIR STABILITY AT THE REACTOR SITF Analog / Digital:
A
. Engr Units / Dig States:
DEGF Engr Units Conversion:
N/A Minimum Instr Range:
-9.0 Maximum instr Range:
9.0 Zero Point
Reference:
N/A Reference Point Notes:
N/A j
PROC or SENS:
PROC Number of Sensors:
2 How Processed:
AVERAGED DIFFERENTIAL Sensor Location:
PRIMARY MET AT 10 & 100 METER HEIGHT Alarm / Trip Set Points:
N/A NI Detector Power Supply N/A Cut off Power Level:
NI Detector Power Supply N/A
-Turn-on Power Level:
Instrument Failure Mode:
HIGH & LOW SENSOR
. Temperature Compensation N/A For DP Transmitters:
Level Reference Leg:
N/A Unique System Desc.:
Data is collected every five seconds averaged every 15 minutes, and stored in data files as 15-minute average. This value represents the difference in temperaturr in degF/100ft.
e tio e r Gener no tant Software Requiremerd Specifeston T R6e.
Number:
SRS Process Computer Systam - Emergency Response Data ERDS-SRS-1-3 System (ERDS)- Data Point Library Sheet No:
56 l.
Contacts Note: Plt ase provide name, title, mailing address and phone number.
A.
Survey Coordinator (i.e. contact for later clarification of questionnaire answers):
Russell E. Van Dell Manager, Computer & Information Systems l
Nor+hern States Power Company Monticello Nuclear Generating Plant 2807 W. Highway 75 Monticello, MN 55362 (612)295-1326 B.
Computer Hardware Specialist (s):
Joe Jirsa Engineer Associate ill Northern States Power Company Monticello Nuclear Generating Plant 2807 W. Highway 75 Monticello, MN 55362 (612)295-1388 C.
Systems Software Specialist (s):
Russell E. Van Dell Manager, Computer & Information Systems Northern States Power Company Monticello Nuclear Generating Plant 2807 W. Highway 75 Monticello, MN 55362 (612)295-1326 D.
Application level Software Specialist (s):
Russell E. Van Dell Manager, Computer & Information Systems Northern States Power Company Monticello Nuclear Generating Plant 2807 W. Highway 75 Monticello, MN 55362 (612)295-1326
bewn sw p, comp.ny c-=2:-m - o.r unaPws' se
- r. R.auir. mere so.cincauon Number.
Tat:
SRS Process Computer Systsm - Emergency Response Data ERDS-SRS-1-3 System (ERDS)- Data Point Library.
Sh.etNo; 57 E.
Telephone Systems Specialist (s):
David Seestrom instrument Engineer Northern States Power Company Monticello Nuclear Generating Plant 2807 W. Highway 75 Monticello, MN 55362 (612)295-1376 f
3
~ ' "
?""*T-
- 9
..e
'Northem States Power Company
+
e Montcello Nuclear Genershno Plard Software Requirement Specifcation Tihe:
Number.
SRS Process Computer System - Emergency Response Data ERDS-SRS-1-3 System (ERDS)- Data Point Library Sheet No: 58
- 11. Selection of Data Feeders A.
How many data feeders are there (six maximum)?
One - Process Computer System B.
Identify the selected data feeders and provide the following for each:
1.
a short description of the categories of data points it will provide (e.g., met, red.
or plant data points, by unit) and 2.
the rationale for selecting it if another system can also provide its categories of data points.
a)
It is planned to provide both plant data points and meteorological information through the single feeder, b)
No other system is capable of providing requested information.
C.
Which data feeder is the site time determining feeder? This should be the feeder which is providing the majority of the data points.
s._
_.m.
-..-_. - ~.-.... _..
,e Northem Stelee Power Company
.c Monticello Nucaser Generehno Plent
' Software Requirement Specificehon J
. Titie:
Number:
SRS Process Computer System - Emergency Response Data ERDS-SRS-1-3 System (ERDS)- Data Point Library Sheet No:- 59 l
Ill. Data Feeder Information i
Note: A new Section IV must be filled out for each feeder system selected.
General Questions A.
Identification of Data Feeder 1.
What is the name in local parlance given to this data feeder (e.g., Emergency Response Information System)? Please give both the acronym and the words forming it.
PCS - Process Computer System 2.
Is this the site time determining feeder?
Yes 3.
How often will this fee:ler transmit an update set to the ERDS (in seconds)?
60 Seconds B.
Hardware / Software Environment 1.
Identify the manufacturer and model number of the data feeder hardware.
Digital Equipment Corporation VAX-8350 2.
Identify the operating system.
-VAX VMS 4.7 a
- 3..
What method of timekeeping is implemented on this feeder system (Daylight Savings, Standard, Greenwich)?
Daylight Savings 4.
In what time zone is this feeder located?
Central Standard Time Zone r
...-v.,.
-,_rr,m.
.- -~
. ~
. ~ _..
,e Northeri States Power Company 4
uore,ceso uucieer o.norsi.no Plent -
- SoRwere Requirement Specification -
Ta*
Number:
SRS-Process Computer System - Emergency Response Data ~
ERDS-SRS-1-3 System (ERDS):- Data Point Library sh.d Nw CO C;
Date Communication Details 1.
Can this data feeder provide asynchronous serial data communication (RS-232-
-.C) with full-modem control?
-Yes 2.
Will this feeder transmit in ASCll or EBCDIC 7 -
ASCil 3.
Can this feeder transmit at a serial baud rate of 2400 bps? If not, at what baud rate can it transmit?
- Yes,2400 bps can be used.
4.
Does the operating syste support XON/XOFF flow control?
Yes-a)_
Are any problems foreseen with the NRC using XON/XOFF to control the transmission of data?
No, however the use of SUSPEND and RESUME to control the transmission of data works better as demonstrated in testing with Haliburton/NUS.
5.
If it is not feasible to recontigure a serial port for the ERDS linkup (i.e., change the baud rate, p irity, etc.), please explain why.
Note Applicable.
- 6. -
Do any ports currently exist for the ERDS linkup?
Yes a)
If not, is it possible to add additional ports?
I Not Applicable.
~
N.=*Ud"o.SE"d.m-son
- r. n.avir.m.ni so.cir.c.iion Tse:
Number:
-SRS Process Computer System - Emergency Response Data
' ERDS-SRS-1-3
- System (ERDS)- Data Point Library Sheet No: 61 b)
If yes, w?! the port be used solely by the ERDS or shared with other non-emergency-time users? Give details.
Port will be dedicated for ERDS.
D.
Data Feeder Physical Environment and Management 1.
Where is the data feeder located in terms of the TSC, EOF, and control room?
Computer Room located in Plant Administrative Building adjacent to Plant Control Room.
2.
Is the data feeder protected from loss of supply of electricity?
Yes, PCS is provided with UPS (batteries with inverter and diesel generator).
3.
Is there a human operator for this data feeder?
Yes a)
If so, how many hours a day is the feedar attended?
It is planned to have the Shift Emergency Communicator (SEC) initiate the ERDS System per Emergency implementing Procedures. An SEC is on duty 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> / day.