ML20198D296

From kanterella
Jump to navigation Jump to search
Semiannual Radioactive Effluent Release Rept,Jan-June 1985
ML20198D296
Person / Time
Site: Farley  
Issue date: 06/30/1985
From:
ALABAMA POWER CO.
To:
Shared Package
ML20198D286 List:
References
NUDOCS 8511120303
Download: ML20198D296 (134)


Text

.

ALABANA POWER COMPANY FARLEY NUCLEAR PLANT UNIT NO. ONE LICENSE NO. NPF-2 AND FARLEY NUCLEAR PLANT UNIT NO. TWO LICENSE NO. NPF-8 SENI-ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT JAN.

1, 1985 THROUGH JUNE 30, 1985 rd""ei$lPMh" P

R

)

TABLE OF CONTENTS SUBJECT PAGE A.

Introduction i

B.

Supplemental Information for E# fluent and Waste Disposal 1.

Regulatory Limits 2

a.

Fission and Activation Gases b.

Iodines and Particulates c.

Liquid Effluents 2.

Maximum Permissible Concentrations 3

a.

Airborne b.

Liquid 3.

Average Energy 3

4.

Measurements and Approximations of Total 3

Activity a.

Fission and Activation Gases b.

Iodines and Particulates c.

Liquid Effluents 5.

Batch Releases 6

a.

Liquid b.

Gasecus 6.

Abnormal" Releases 6

a.

Liquid b.

Gaseous 1

- - - - - - - - - - - - - ----- U

l 1

i l

TABLE OF CONTENTS (con't)

SUBJECT PAGE 7.

Estimate of Total Error 8

8.

Solid Waste 9

9.

Radiological Impact on Man 9

10. Meteorological Data 11
11. Minimam Detectable concentration (MDC) 11
12. Deviations from Liquid Waste Release 11 Program
13. Deviations from Gaseous Waste Release 11 Program
14. Process Control Program 124 e

e b

n 8

11 J

r-i l

LIST OF TABLES TABLE PAGE 1A-1Q1 Gaseous Effluents - Summation of All Releases, 12 Unit 1 - 1st Quarter, 1985 1A-1Q2 Gaseous Effluents - Summation of All Releases, 13 Unit 1 - 2nd Quarter, 1985 1A-2Q1 Gaseous Effluents - Summation of All Releases, 14 Unit 2 - 1st Quarter, 1985 1A-2Q2 Gaseous Effluents - Summation of All Releases, 15 Unit 2 - 2nd Quarter, 1985 15-1Q1 Gaseous Effluents - Elevated Release Unit 1, 16 ist Quarter, 1985 l

15-1Q2 Gaseous Effluents - Elevated Release Unit 1, 17 2nd Quarter, 1985 15-201 Gaseous Effluents - Elevated Release Unit 2, 18 1st Quarter, 1985 l

15-2Q2 Gaseous Effluents - Elevated Release Unit 2, 19 2nd Quarter, 19,85 1C-1QL Gaseous Effluents - Ground Level Release, 20 Unit 1 - 1st Quarter, 1985 1C-1Q2 Geseous Effluents - Ground Level Release, 21 Unit 1 - 2nd Quarter, 1985 1C-2Q1 Gaseous Effluents - Ground Level Release, 22 l

Unit 2 - 1st Quarter, 1985 1C-2Q2 Gaseous Effluents - Ground Level Release, 23 Unit 2 - 2nd Quarter, 1985 2A-1 Liquid Effluents - Summation of All Releases, 24 l

Unit 1 - 1st Half, 1985

~

2A-2 Liquid Effluents - Summation of All Releases, 25 Unit 2 - 1st Half, 1985 25-1B Liquid Effluents - Batch, Unit 1 - 1st Half, 26 1985 25-2B Liquid Effluents - Batch, Unit 2 - 1st Half 27 1985 111 I

\\

.)

r LIST OF TABLES (cont.)

TABLE PAGE 2B-1C Liquid Effluents - Continuous, Unit 1 - 1st Half 28 1985 25-2C Liquid Effluents - Concinuous, Unit 2 - 1st Half 29 1985 3

Solid Waste and Irradiated Fuel Shipments, 30 ist Half, 1985 4A-CQ1 Cumulative Joint Frequency Distribution, 32 Continuous Mode - 1st Quarter, 1985 4A-CQ2 Cumulative Joint Frequency Distribution, 46 Continuous Mode - 2nd Quarter, 1985 4A-1BQL Cumulative Joint Frequency Distribution, 60 Unit 1 Batch Mode - 1st Quarter, 1985 4A-1BQ2 Cumulative Joint Frequency Distribution, 74 Unit i Batch Mode - 2nd Quarter, 1985 4A-25Q1 Cumulative Joint Frequency Distribution, 88 Unit 2 Batch Mode - 1st Quarter, 1985 4A-25Q2 Cumulative Joint Frequency Distribution, 102 Unit 2 Batch Mode - 2nd Quarter, 1985 45 Classification of Atmospheric Stability 116 5

Radioactive Liquid Waste Sampling and Analysis 117 Program, Units 1 & 2 6

Radioactive Gaseous Waste Sampling and Analysis 120 Program, Units 1 & 2 7

Liquid Discharges Not Meeting Specified Detection 123 Limits, Units 1 & 2 - 1st Half, 1985 iv

)

INTRODUCTION This Semi-annual radioactive release report, for the period January 1 through June 30, 1985, is submitted in accordance with Appendix A of License Nos. NPF-2 and NPF-8.

Appendix A will hereinafter be referred to as the Standard Technical Specifications or STS.

A single submittal is made for both units which combines those sections that are common.

Separate tables of releases and release totals are included where separate processing systems exist.

This report includes a summary of hourly meteorological measurements taken during each quarter in the six month reporting period. This data appears as joint frequency distributions of wind direction and wind speed by atmospheric stability class. Hourly meteorological data for batch releases are presented for the periods of actual release. All assessments of radiation doses are performed in accordance with the OFFSITE DOSE CALCULATION MANUAL (ODCM).

e i

.]

B.

SUPPLEMENTAL INFORMATION FOR EFFLUENT AND WASTE DISPOSAL 1.

Regulatory Limits a.

Fission and Activation Gases 1.The dose rate from the site at any time due to noble gases shall be less than or equal to 500 mrem /yr to the total body and 3000 mrem /yr to the skin.

2.The air dose from each reactor unit from the site during any calendar quarter due to noble gases shall be less than or equal to 5 mrad for gamma radiation and 10 mrad for beta radiation.

3.The air dose from each reactor unit from the site during any calendar year due to noble gases shall be less than or equal to 10 mrad for gamma radiation and 20 mrad for beta radiation.

b.

Iodines and Particulates 1.The dose ratefrbmthesite at any time due to iodines, particulates and radionuclides with half-lives greater than 8 days shall be less than or equal to 1500 mrem /yr to any organ.

2.The dose from each reactor unit from the site during any calendar quarter due to iodines, particulates and radionuclides with half-lives greater than 8 days shall be less than or equal-to 7.5 mrem to any organ.

3.The dose from each reactor unit from the site during any calendar year due to iodines, particulates and radionuclides with half-lives greater than 8 days shall be less than or equal to 15 mrem to any organ, c.

Liquid Effluents 1.The concentration of radioactive materials released in liquid effluents to unrestricted areas from all reactors at the site shall not exceed at any time the values specified in 10 CFR Part 20, Appendix B, Table II, Column 2. The concentration of dissolved or en-trained noble gases, released in liquid effluents to unrestricted areas from all reactors at the site, shall not. exceed at any time 2E-4 uCi/ml in water.

2.The' dose or dose commitment due to liquid effluents released from each reactor unit from the site during any calendar quarter shall be less than or equal to 1.5 mrem to the total body and 5 mrem to any organ.

3.The dose or dose commitment due to liquid effluents released from each reactor unit from the site during any calendar year shall be less than or equal to 3 mrem to -he total body and 10 mrem to any organ.

I 2

s b

2.

Maximum Permissible Concentrations a.

Airborne - The maximum permissible concentration of radioactive materials in gaseous effluents is limited by the dose rate restrictions of 10CFR20.

In this case, the maximum permissible concentracions are actually determined by the dose factors in the ODCM.

b.

Liquid - 10 CFR Part 20, Appendix B, Table II, Column 2.*

  • NOTE: The MPC chosen is the most conservative value of either the soluble or insoluble MPC for each isotope.

3.

Average Energy Not applicable for Farley's STS.

4.

Measurements and Approximations of Total Activity The following discussion details the methods used to measure and approximate total activity for the following:

a.

Fission and Activation Gases b.

Iodines and Particulates c.

Liquid Effluents Tables 5 and 6 give sampling frequencies and minimum detectable concentration requirements for the analysis of liquid and gaseous effluent streams, respectively.

Values in the attached tables given as zero do not mean that the nuclides were not present.

A zero indicates that the nuclide was not present at levels greater than the sensitivity requirements shown in Tables 5 and 6.

For some nuclides, lower detection limits than required may be readily achievable; when a nuclide is measured below its stated limit, it is reported.

a.

Fission and Activation Gases The following noble gases are considered in evaluating gaseous airborne discharge:

Kr-87 Xe-133 Kr-88 Xe-135 Xe-133m Xe-138 3

Periodic grab samples from plant effluent streams are analyzed by a computerized pulse height analyzer system utilizing high resolution germanium detectors. (See Table 6 for semplinn and analytical requirements).

Isotopic values thus o*

'T4

're used for release rate calculations as speci' C:0.

s Only those nuclides that are detected are u.ku it

.e computation.

During the period between gran < w.a l e t t6s amount of radioactivity released is based 50 thh ett 4ent monitor readings.

Monitors are assig og a Rh'hbr

>n factor based upon the last isotopic t V2it ay31g tt, following relationship:

CF

=A

/ m, where i

i CF isotopic calibration factor for isotope i.

=

i A

= concentration of isotope in the grab sample, in uCi/ml.

i a

= net monitor reading associated with the effluent stream.

These calibration factors along with the hourly effluent monitor readings are inputs to the laboratory computer where the release rates for individual nuclides are calculated and stored.

To ensure isotopic distributions do not change significantly during major operational occurrences, the frequency of grab sampling is increased to satisfy the requirements of footnotes b & d of STS Table 4.11-2, " Radioactive Gaseous Waste Sampling and Analysis Program".

b.

Iodines and Particulates The radioiodines and radioactive materials in particulate forms to be considered are:

Mn-54 I-131 Fe-59 I-133 Co-58 Cs-134 Co-60 Cs-137 Zn-65 Ce-141 Sr-89 Co-144 Sr-90 H-3 Mo-99 other nuclides with half-lives greater than 8 days which are identified and measured are also considered.

The MDC's will vary and are not required to meet the MDC limits of those isotopes listed specifically.

Tritium is considered in the gaseous or water vapor form.

4 j

Continuous Releases: Continuous sampling is performed on the continuous release points (i.e.

the Plant Vent Stack, Containment Purge and the Turbine Building Vent).

Particulate material is collected by filtration.

Periodically these filters are removed and analyzed on the pulse height analyzer to identify and quantify radioactive materials collected on the filters.

Particulate filters are then analyzed for gross alpha and strontium as required.

Gross alpha determinations are made using a 2 pi gas flow proportional counter. Sr-89 and 90 values are obtained by chemical separation and subsequent analysis using 2 pi gas flow proportional counters.

Batch Releases:

The processing of batch type releases (from Containment or Waste Gas Decay Tanks) is analogous to continuous releases, except that the release is not commenced until grab samples have been obtained and analyzed.

c.

Liquid Effluents The radionuclides listed below are considered when evaluating liquid effluents:

Mn-54 I-131 Fe-59 Cs-134 Co-58 Cs-137 Co-60 Ce-141 Zn-65 Ce-144 Sr-89 Mo-99 Sr-90 Fe-55 H-3 Batch Releases: Representative pre-release grab samples are obtained and analyzed per Table 5.

Isotopic analyses are performed using the computerized pulse height analysis system previously described.

Aliquots of each pre-release sample proportional to the waste volume released are composited in accordance with requirements in Table 5.

Strontium and Iron determinations are made by performing a chemical separation and counting the isotope thus separated using a 2 pi gas flow proportional counter. Gross beta and gross alpha determinations are made using 2 pi gas flow proportional counters.

Tritium concen-trations are determined by using liquid scintillation techniques.

Dissolved gases are datermined employing grab sampling techniques and then counting on the pulse height analyzer.

Continuous Releases: Continuous releases (from the Steam Generator Blowdown) are analogous to that of the batch releases except that they are analyzed on a weekly composite basis per Table S.

5 y.

p; 7

~

UNIT # 1 1985 5.

Batch Release a.

Liquid Quarter 1 Quarter 2 1.

Number of batch releases:

261 130 2.

Total time period for releases:

23613 min.

11026 min.

3.

Maximum time period for a release:

189 min.

170 min.

4.

Average time period for a release:

90 min.

85 min.

5.

Minimum time period for a release:

1 min.

51 min.

6.

Average stream flow during periods of release of effluent into a

  • 1.15E4 cfs
  • 1.15E4 cfs flowing stream:

b.

Gaseous Quarter 1 Quarter 2 1.

Number of releases:

0 12 2.

Total time period for releases:

0 min.

4920 min.

3.

Maximum time period for a release:

0 min.

540 min.

'4.

Average time period for a release:

0 min.

410 min.

5.

Minimum time period for a release:

0 min.

240 min.

6.

Abnormal Releases a.

Liquid (See 12.2) 1.

Number of releases:

1 2.

Total activity released:

5.94E-03 Ci i

b.

Gaseous (See 13.1 and 13.2) 1.

Number of releases:

2 2.

Total activity released:

1.15E 01 Ci

  • Annual Average River Flow Rate.

6 i

i UNIT # 2 1985 5.

Batch ReleasG a.

Liquid Quarter 1 Quarter 2 1.

Number of batch releases:

113 56 2.

Total time period for releases:

9598 min.

4697 min.

3.

Maximum time period for a release:

216 min.

140 min.

4.

Average time period for a release:

85 min.

84 min.

5.

Minimum time period for a release:

54 min.

66 min.

6.

Average stream flow during periods of release of effluent into a

  • 1.15E4 cfs
  • 1.15E4 cfs flowing stream:

b.

Gaseous Quarter 1 Quarter 2 1.

Number of releases:

8 1

2.

Total time period for releases:

4920 min.

960 min.

3.

Maximum time period for a release:

1080 min.

960 min.

4.

Average time period for a release:

615 min.

960 min.

5.

Minimum time period for a release:

180 min.

960 min.

6.

Abnormal Releases a.

Liquid 1.

Number of releases:

None 2.

Total activity released:

N/A l

b.

Gaseous 1.

Number of releases:

None 2.

Total activity released:

N/A

  • Annual Average River Flow Rate.

7

7.

Estimate of Total Error a.

Liquid 1.

The maximum error associated with volume and flow measurements, based upon plant calibration practice is estimated to be + or - 10%.

2.

The average error associated with counting is estimated to be less than + or - 15%.

b.

Gaseous 1.

The maximum errors associated with monitor readings, sample flow, vent flow, sample collection, monitor calibration and laboratory procedure are collectively estimated to be:

Fission and Activation Gases Iodines Particulates Tritium 75%

60%

50%

45%

2.

The average error associated with counting is estimated to be:

Fission and Activation Gases Iodines Particulates Tritium 6%

18%

19%

12%

c.

Solid Radwaste The error involved in determining the contents of solid radwaste shipments is estimated to be less than + or -

15%.

8

[

i

UNIT # 1 1985 8.

Solid Waste See Table 3 9.

Radiological Impact On Man a.

Water Related Exposure Pathways ist Quarter 2nd Quarter Total Body = 4.0E-03 mrem 2.12-03 mrem Bone = 2.2E-03 mrem 1.6E-03 mrem Liver = 6.6E-03 mrem 3.8E-03 mrem Thyroid = 1.7E-03 mrem 1.4E-03 mrem Kidney = 2.5E-03 mrem 1.9E-03 mrem Lungs = 4.9E-03 mrem 3.7E-03 mrem j

GI Tract = 1.3E-02 mrem 2.1E-02 mrem b.

Gaseous Related Exposure Pathways ist Quarter 2nd Quarter Total Body = 2.5E-02 mrem 1.7E-02 mrem Skin = 4.1E-02 mrem 4.4E-02 mrem c.

Particulate and Iodine 1st Quarter 2nd Quarter Organ Dose = 3.4E-02 mrem 9.5E-03 mrem

{

9 l

l r

UNIT # 2 1985 8.

Solid Waste See Table 3 9.

Radiological Impact On Man a.

Water Related Exposure Pathways ist Quarter 2nd Quarter Total Body = 1.8E-02 mrem 1.9E-03 mrem Bone = 2.1E-02 mrem 1.6E-02 mrem Liver = 2.9E-02 mrem 5.7E-03 mrem Thyroid = 1.0E-03 mrem 1.0E-03 mrem Kidney = 8.9E-03 mrem 2.9E-03 mrem Lungs = 4.6E-03 mrem 1.1E-03 mrem GI Tract = 4.6E-03 mrem 1.2E-02 mrem b.

. Gaseous Related Exposure Pathways ist Quarter 2nd Quarter Total Body = 3.5E-03 mrem 8.1E-03 mrem Skin = 5.0E-03 mrem 4.3E-02 mrem c.

Particulate and Iodine 1st Quarter 2nd Quarter Organ Dose = ;l.9E-03 mrem 1.0E-02 mrem i

10

10.

Meteorological Data See Tables, " Cumulative Joint Frequency Distribution".

Continuous Release Mode:

1st Quarter, 1985

4A-CQ1 2nd Quarter, 1985
4A-CQ2 Batch Release Mode (Units 1 & 2) ist Quarter, 1985
4A-1BQ1 & 4A-2BQ1 2nd Quarter, 1985
4A-1BQ2 & 4A-2BQ2 The data for Unit 1 Abnormal Releases is included within Batch Release Mode Tables 4A-1BQ1 & 4A-1BQ2.

11.

Minimum Detectable Concentration (MDC)

Detectable limits for activity analyses are based upon the technical feasibility and on the potential significance in the environment of the quantities released.

However, in practice, when an isotope's a posteriori MDC could not be met due to other nuclides being present in much greater concentrations, the a priori MDC as defined in the STS Table 4.11-1 a.

is relied upon.

12.

Deviations from Liquid Waste Release Program

1. The following liquid update composites were inadvertently poured out prior to final ana}ysis:

Unit 1 Waste Monitor Tank Month 4 Composite.

Unit 1 Waste Monitor Tank Quarter 1 Composite.

Unit 1 Steam Generator Blowdown Quarter 1 Composite.

Unit 2 Waste Monitor Tank Quarter 1 Composite.

A review of all past data was made and the highest recorded value was used in all cases.

2.

An abnormal release occurred on Unit i during Quarter 2 due to leakage from the Component Cooling Water System into the Service Water System. The curies released are included under Abnormal Releases and in Tables 2A-1 &

l 2B-1B.

13.

Deviations from Gaseous Waste Release Program

1. An abnormal release occurred on Unit i during Quarter i due to inadvertent venting of the Hydrogen Recombiner System to the Auxiliary Building. The curies released are included under Abnormal Releases and in Tables 1A-1Q1 &

1C-1Q1.

2. An abnormal release occurred on Unit i during Quarter 2 due to the Residual Heat Removal System Sump Vent exhausting to l

the Component Cooling Water Heat Exchanger Room on Unit i Non-Rad Side. The curies released are included under Abnormal j

Releases and in Tables 1A-1Q2 & 1C-1Q2.

11 e

. * - +

.w----

,,,.+--+--r

,4 f-,-


e

,r q-r

TABLE 1A-1Q1 GASEOUS EFFLUENTS--SUMMATION OF ALL RELEASES Farley Unit 1-1st Quarter, 1985 UNITS QTR 1 Est Error A.

Fission & activation gases:

1. Total release Ci 5.32E 02 2.51E 01
2. Average release rate uCi/sec 6.74e 01 3.

% of Technical Specification 3.74E-03*

6.99E-03**

B.

Iodines 1.

Total iodine-131 Ci 4.79E-03 3.22E-04 2.

Average release rate uCi/sec 6.16E-04 3.

% of Technical Specification 1.88E-06***

C.

Particulates 1.

Particulates with T1/2>8 days C1 2.46E-05 1.03E-05 2.

Average release rate uCi/sec 3.17E-06 3.

% of Technical Specification 9.66E-09***

4.

Gross alpha radioactivity Ci 0.00E 00 D. Tritium

1. Total release Ci 1.81E 01 1.28E-01
2. Average release rate uCi/sec 2.33E 00 3.

4 of Technical Specificatior.

2.15E-07***

  • Whole body limit (<500 mrem /yr)
    • Extrem. limit (<3000 mrem /yr)
      • % of 1500 mrem /yr for all 18 isotopes 12

TABLE 1A-1Q2 GASEOUS EFFLUENTS--SUMMATION OF ALL RELEASES Farley Unit 1 - 2nd Quarter, 1985 UNITS QTR 2 Est Error A. Fission & activation gases:

1. Total release Ci 4.86E 02 1.02E 01
2. Average release rate uCi/sec 6.13e 01 3.

% of Technical Specification 9.24E-04*

2.12E-03**

B.

Iodines

1. Total iodine-131 Ci 7.32E-04 6.71E-05 2.

Average release rate uCi/sec 9.30E-05 3.

t of Technical Specification 2.83E-07***

C.

Particulates 1.

Particulates with T1/2>8 days C1 1.84E-05 4.48E-06 2.

Average release rate uCi/sec 2.34E-06 3.

% of Technical Specification 8.62E-07***

4. Gross alpha radioactivity Ci 0.00E 00 D. Tritium
1. Total release C1 2.40E 01 1.82E-01
2. Average release rate uCi/sec 3.05E 00 3.

% of Technical Specification 2.83E-07***

  • Whole body limit (<500 mrem /yr)
    • Extrem. limit (<3000 mrem /yr)
      • % of 1500 mrem /yr for all 18 isotopes 13

TABLE 1A-2Q1 GASEOUS EFFLUENTS--SUMMATION OF ALL RELEASES Farley Unit 2 - 1st Quarter, 1985 UNITS QTR 1 Est Error A.

Fission & activation gases:

1. Total release Ci 1.08E 02 8.58E 00 2.

Average release rate uCi/sec 1.39E 01 3.

4 of Technical Specification 3.20E-04*

7.20E-04**

B.

Iodines

1. Total iodine-131 Ci 2.49E-04 1.61E-05
2. Average release rate uCi/sec 3.21E-05 3.

% of Technical Specification 9.76E-08***

C.

Particulates 1.

Particulates with T1/2>8 days Ci 8.70E-06 2.03E-06 2.

Average release rate uCi/sec 1.12E-06 3.

% of Technical Specification 1.18E-06***

4. Gross alpha radioactivity Ci 0.00E 00 D. Tritium
1. Total release Ci 4.78E 01 4.83E-01
2. Average release rate uCi/sec 6.15E 00 3.

4 of Technical Specification 5.77E-07***

  • Whole body limit (<500 mrem /yr)

Extrem. limit (<3000 mrem /yr)

      • % of 1500 mrem /yr for all 18 isotopes 14 l.

(

TABLE 1A-2Q2 GASEOUS EFFLUENTS--SUMMATION OF ALL RELEASES Farley Unit 2 - 2nd Quarter, 1985 UNITS QTR 2 Est Error A.

Fission & activation gases:

1. Total release C1 2.28E 02 2.20E 01 2.

Average release rate uCi/sec 2.90E 01 3.

% of Technical Specification 6.57E-03*

1.07E-02**

B.

Iodines 1.

To.tal iodine-131 Ci 7.53E-06 1.64E-06

2. Average release rate uCi/sec 9.58E-07 3.

% of Technical Specification 2.92E-09***

C. Particulates 1.

Particulates with T1/2>8 days C1 1.94E-06 6.54E-07

2. Average release rate uCf/sec 2.47E-07 3.

% of Technical Specification s

2.78E-11***

4. Gross alpha radioactivity Ci 0.00E 00 D. Tritium
1. Total release C1 1.18E 02 3.20E-01 2.

Average release rate uCi/sec 1.89E 01 3.

% of Technical Specification 1..mE-06***

  • Whole body limit (<500 mrem /yr)
    • Extrem. limit (<3000 mrem /yr)
      • % of 1500 mrem /yr for all 18 isotopes 15 l

l

TABLE 1B-1Q1 GASEOUS EFFLUENTS--ELEVATED RELEASE Farley Unit 1-1st Quarter, 1985 CONTINUOUS BATCH Mode Mode Nuclides Released Unit QTR4 1 QTR# 1 1.

Fission gases Ar-41 Ci 2.46E C1 0.00E 00 Xe-135M Ci 4.42E 00 0.00E 00 Xe-138 Ci 2.92E 00 0.00E 00 Kr-87 Ci 3.56E 00 0.00E 00 Kr-85M Ci 4.54E 00 0.00E 00 Xe-135 Ci 1.54E 02 0.00E 00 Xe-133M Ci 0.00E 00 0.00E 00 Kr-88 Ci 6.57E 00 0.00E 00 Xe-133 Ci 3.08E 02 0.00E 00 Total for period Ci 5.08E 02 0.00E 00 2.

Iodines I-133 Ci 9.18E-04 0.00E 00 I-131 Ci 4.49E-03 0.00E 00 Total for period Ci 5.40E-03 0.00E 00 3.

Particulates

  • Mo-99 Ci 0.00E 00 0.00E 00 Co-60 Ci 0.00E 00 0.00E 00 Zn-65 Ci 0.00E 00 0.00E 00 Fe-59 Ci 0.00E 00 0.00E 00 Mn-54 Ci 0.00E 00 0.00E 00 Co-58 Ci 0.00E 00 0.00E 00 Cs-137 Ci 0.00E 00 0.00E 00 Cs-134 Ci 0.00E 00 0.00E 00 I-133 C1 2.89E-03 0.00E 00 I-131 Ci 2.33E-05 0.00E 00 Ce-141 Ci 0.00E 00 0.00E 00 Ce-144 Ci 0.00E 00 0.00E 00 Sr-89 Ci 0.00E 00 0.00E 00 Sr-90 Ci 0.00E 00 0.00E 00 Total for period C1 2.91E-03 0.00E 00 Isotope with half-life less than 8 days 16

,~...

s TABLE 1B-1Q2 GASEOUS EFFLUENTS--ELEVATED RELEASE Farley Unit 1 - 2nd Quarter, 1985 CONTINUOUS BATCH Mode Mode Nuclides Released Unit QTR# 2 QTR# 2 l

1.

Fission gases Ar-41 Ci 1.46E 00 0.00E 00 Xe-135M Ci 2.47E-02 0.00E 00 Kr-85 Ci 0.00E 00 6.96E-01 Xe-138 Ci 0.00E 00 0.00E 00 Kr-87 Ci 3.92E-02 0.00E 00 Kr-85M Ci 0.00E 00 1.39E-02 Xe-135 C1 1.79E 01 1.83E-02 Xe-133M Ci 5.41E 00 2.39E-01 Kr-88 Ci 6.68E-02 3.47E-05 Xe-131M Ci 0.00E 00 8.07E-03 Xe-133 Ci 3.62E 02 7.87E 01 Total for period Ci 3.86E 02 7.97E 01 2.

Iodines I-133 C1 2.54E-04 0.00E 00 I-131 Ci 7.17E-04 6.20E-07 l

Total for period Ci 9.71E-04 6.20E-07 3.

Particulates

  • Mo-99 Ci 0.00E 00 0.00E 00 Co-60 Ci 2.63E-06 6.22E-10 Zn-65 Ci 0.00E 00 0.00E 00 Fe-59 Ci 0.00E 00 0.00E 00 Mn-54 Ci 0.00E 00 0.00E 00 Co-58 Ci 1.28E-06 0.00E 00 l

i Cs-137 Ci 3.02E-06 0.00E 00 Cs-134 Ci 0.00E 00 0.00E 00 I-133 Ci 7.27E-06 0.00E 00 I-131 C1 1.06E-05 6.20E-07 Ce-141 Ci 0.00E 00 0.00E 00 Ce-144 Ci 0.00E 00 0.00E 00 Sr-89 Ci 0.00E 00 1.75E-13 Sr-90 Ci 0.00E 00 6.43E-11 Total for period Ci 2.48E-05 6.21E-07 Isotope with half-life less than 8 days 17 i

4 TABLE 1B-2Q1 i

GASEOUS EFFLUENTS--ELEVATED RELEASE I

Farley Unit 2-1st Quarter, 1985 CONTINUOUS BATCH Mode Mode Nuclides Released Unit QTR# 1 QTR# 1 i

1.

Fission gases Ar-41 Ci 8.71E-01 0.00E 00 i

Xe-135M Ci 4.09E-01 0.00E 00 Kr-85 Ci 0.00E 00 3.35E 00 Xe-138 Ci 0.00E 00 0.00E 00 i

Kr-87 Ci 0.00E 00 0.00E 00 Kr-85M Ci 0.00E 00 3.60E-03 Xe-135 Ci 1.33E 01 2.15E-03 Xe-133M Ci 0.00E 00 7.53E-02 3

Kr-88 Ci 0.00E 00 0.00E 00 Xe-131M C1 1.35E 01 3.76E-01 Xe-133 Ci 3.41E 01 3.55E 01 i

Total for period Ci 6.22E 01 3.93E 01 2.

Iodines I-133 Ci 7.03E-06 1.13E-09 I-131 C1 2.42E-04 1.06E-06 Total for period C1 2.49E-04 1.06E-06 i

3.

Partienlates

  • Mo-99 Ci 0.00E 00 0.00E 00 Co-60 Ci 3.21E-06 0.00E 00 Zn-65 Ci 0.00E 00 0.00E 00 Fe-59 Ci 0.00E 00 0.00E 00 Mn-54 Ci 0.00E 00 0.00E 00 Co-58 C1 2.31E-06 0.00E 00 Cs-137 Ci 0.00E 00 0.00E 00 Cs-134 Ci 0.00E 00 0.00E 00 I-133 Ci 0.00E 00 1.13E-09 i

I-131 C1 1.42E-06 1.05E-06 i

Ce-141 Ci 0.00E 00 0.00E 00 Co-144 Ci 0.00E 00 0.00E 00 I

Sr-89 Ci 0.00E 00 0.00E 00 Sr-90 Ci 0.00E 00 0.00E 00 l

Total for period Ci 6.94E-06 1.06E-06 Isotope with half-life less than 8 days 18 l

I

TABLE 1B-2Q2 GASEOUS EFFLUENTS--ELEVATED RELEASE Farley Unit 2 - 2nd Citarter, 1985 1

i CONTINUOUS BATCH Mode Mode 1

Nuclides Released Unit QTR# 2 QTR# 2

= -----------

t

1. Fission gases i

Ar-41 Ci 1.47E 02 0.00E 00 Xe-137 C1 1.58E 01 0.00E 00 Kr-85 Ci 0.00E 00 9.80E-02 Xe-138 Ci 0.00E 00 0.00E 00 Kr-87 Ci 0.00E 00 0.00E 00 Xe-135 Ci 8.17E 00 0.00E 00 Xe-133M Ci 0.00E 00 0.00E 00 Kr-88 Ci 0.00E 00 0.00E 00 Xe-133 Ci 5.18E 01 3.08E-02 Total for period Ci 2.22E 02 1.29E-01 2.

Iodines I-133 Ci 2.59E-10 0.00E 00 I-131 Ci 6.99E-06 0.00E 00 Total for period Ci 6.99E-06 0.00E 00 3.

Particulates

  • Mo-99 Ci 0.00E 00 0.00E 00 Co-60 Ci 0.00E 00 0.00E 00 2n-65 Ci 0.00E 00 0.00E 00 Fe-59 Ci 0.00E 00 0.00E 00 Mn-54 Ci 0.00E 00 0.00E 00 Co-58 Ci 0.00E 00 0.00E 00 Cs-137 Ci 0.00E 00 0.00E 00 Cs-134 Ci 0.00E 00 0.00E 00 I-133 Ci 0.00E 00 0.00E 00 I-131 Ci 0.00E 00 0.00E 00 Ce-141 Ci 1.89E-06 0.00E 00 Ce-144 Ci 0.00E 00 0.00E 00 Sr-89 Ci 0.00E 00 0.00E 00 Sr-90 Ci 0.00E 00 0.00E 00 i

Total for period C1 1.89E-06 0.00E 00 i

Isotope with half-life less than 8 days 19 m

-m.

,--,.---,--n n~-

-- ~

TABLE 1C-1Q1 GASEOUS EFFLUENTS--GROUND RELEASE Farley Unit 1-1st Quarter, 1985 CONTINUOUS BATCH Mode Mode Nuclides Released Unit QTR# 1 QTR# 1 1.

Fission gases Ar-41 Ci 7.36E-01 1.02E-03 Xe-135M Ci 1.51E-01 0.00E 00 i

Xe-138 Ci 9.29E-02 0.00E 00 Kr-87 Ci 1.14E-01 4.82E-02 Kr-85M Ci 1.42E-01 1.37E-01 Xe-135 Ci 5.20E 00 2.07E 00 Xe-133M Ci 0.00E 00 1.55E-01 Kr-89 Ci 3.94E-03 0.00E 00 Kr-88 Ci 2.11E-01 1.63E-01 Xe-133 Ci 9.32E 00 5.04E 00 Total for period Ci 1.60E 01 7.62E 00 2.

Iodines I-133 Ci 2.43E-05 0.00E 00 I-131 Ci 3.03E-04 0.00E 00 Total for period Ci

'3.27E-04 0.00E 00 3.

Particulates

  • Mo-99 Ci 0.00E 00 0.00E 00 Co-60 Ci 0.00E 00 0.00E 00 Zn-65 Ci 0.00E 00 0.00E 00 Fe-59 Ci 0.00E 00 0.00E 00 Mn-54 Ci 0.00E 00 0.00E 00 Co-58 Ci 0.00E 00 0.00E 00 Cs-137 Ci 0.00E 00 0.00E 00 Cs-134 Ci 0.00E 00 0.00E 00 I-133 Ci 3.38E-04 0.00E 00 I-131 Ci 1.38E-06 0.00E 00

~

Ce-141 Ci 0.00E 00 0.00E 00 Ce-144 Ci 0.00E 00 0.00E 00 Sr-89 Ci 0.00E 00 0.00E 00 Sr-90 Ci 0.00E 00 0.00E 00 Total for period Ci 3.39E-04 0.00E 00 Isotope with half-life less than 8 days 20

TABLE 1C-1Q2 GASEOUS EFFLUENTS--GROUND RELEASE Farley Unit 1 2nd Quarter, 1985 CONTINUOUS BATCH Mode Mode Nuclides Released Unit QTR# 2 QTR# 2

=_

=--------------

1.

Fission gases Ar-41 Ci 4.05E-02 0.00E 00 Xe-135M Ci 1.04E-03 0.00E 00 Kr-85 Ci 0.00E 00 2.26E-02 Xe-138 Ci 0.00E 00 0.00E 00 Kr-87 Ci 1.98E-03 0.00C 00 Kr-85M Ci 0.00E 00 3.94E-03 Xe-135 Ci 5.63E-01 1.19E-01 Xe-133M Ci 1.87E-01 5.10E-02 Kr-88 Ci 3.43E-03 3.17E-08 Xe-131M Ci 0.00E 00 8.15E-04 Xe-133 Ci 1.47E 01 4.34E 00 Total for period C1 1.55E 01 4.54E 00 2.

Iodines I-133 Ci 2.90E-06 0.00E 00 I-131 Ci 1.43E-05 8.27E-09 Total for period Ci 1.72E-05 8.27E-09 3.

Particulates

  • Mo-99 Ci 0.00E 00 0.00E 00 Co-60 Ci 6.01E-08 3.43E-11 Zn-65 Ci 0.00E 00 0.00E 00 Fe-59 Ci 0.00E 00 0.00E 00 Mn-54 Ci 0.00E 00 0.00E 00 Co-58 Ci 1.25E-08 0.00E 00 Cs-137 Ci 3.36E-08 0.00E 00 Cs-134 Ci 0.00E 00 0.00E 00 I-133 Ci 3.65E-07 0.00E 00 I-131 C1 1.40E-07 8.24E-09 Ce-141 Ci 0.00E 00 0.00E 00 Ce-144 Ci 0.00E 00 0.00E 00 Sr-89 Ci 0.00E 00 2.92E-14 Sr-90 Ci 0.00E 00 3.94E-12 Total for period Ci 6.11E-07 8.28E-09 Isotope with half-life less than 8 days 21 t

TABLE 1C-2Q1 GASEOUS EFFLUENTS--GROUND RELEASE Farley Unit 2-1st Quarter, 1985 CONTINUOUS BATCH Mode Mode Nuclides Released Unit QTR# 1 QTR# 1 1.

Fission gases Ar-41 Ci 8.10E-02 0.00E 00 Xe-137 Ci 1.74E-02 0.00E 00 Xe-135M Ci 9.50E-03 0.00E 00 Kr-85 Ci 0.00E 00 1.40E-01 Xe-138 Ci 4.44E-02 0.00E 00 Kr-87 Ci 0.00E 00 0.00E 00 Kr-85M Ci 0.00E 00 2.62E-04 Xe-135 Ci 1.19E 00 1.39E-04 Xe-133M Ci 0.00E 00 3.06E-03 Kr-89 Ci 2.26E-03 0.00E 00 Kr-88 Ci 0.00E 00 0.00E 00 Xe-131M Ci 5.97E-01 2.70E-02 Xe-133 Ci 2.67E 00 1.58E 00 Total for period Ci 4.62E 00 1.75E 00 2.

Iodines I-133 C1 1.88E-09 1.42E-11 I-131 Ci 5.91E-06 1.33E-08 Total for period Ci 5.92E-06 1.33E-08 3.

Particulates

  • Mo-99 Ci 0.00E 00 0.00E 00 Co-60 Ci 4.00E-07 0.00E 00 Zn-65 Ci 0.00E 00 0.00E 00 Fe-59 Ci 0.00E 00 0.00E 00 Mn-54 Ci 0.00E 00 0.00E 00 Co-58 Ci 2.67E-07 0.00E 00 Cs-137 Ci 0.00E 00 0.00E 00 Cs-134 Ci 0.00E 00 0.00E 00 I-133 Ci 0.00E 00 1.45E-11 I-131 Ci 3.01E-08 1.36E-08 Ce-141 Ci 0.00E 00 0.00E 00 Ce-144 Ci 0.00E 00 0.00E 00 Sr-89 Ci 0.00E 00 0.00E 00 Sr-90 Ci 0.00E 00 0.00E 00 Total _for period Ci 6.97E-07 1.36E-08 Isotope with half-life less than 8 days 22

TABLE 1C-2Q2 GASEOUS EFFLUENTS--GROUND RELEASE Farley Unit 2 - 2nd Quarter, 1985 CONTINUOUS BATCH Mode Mode Nuclides Released Unit QTR# 2 QTR# 2 1.

Fission gases Ar-41 Ci 3.01E 00 0.00E 00 Xe-137 Ci 1.23E 00 0.00E 00 Kr-85 Ci 0.00E 00 1.17E-02 Xe-138 Ci 0.00E 00 0.00E 00 Kr-87 Ci 0.00E 00 3.00E 00 Xe-135 Ci 1.70E-01 0.00E 00 Xe-133M Ci 0.00E 00 0.00E 00 Kr-88 Ci 0.00E 00 0.00E 00 Xe-133 C1 1.04E 00 3.66E-03 Total for period Ci 5.45E 00 1.53E-02 2.

Iodines I-133 C1 2.51E-11 0.00E 00 I-131 Ci 5.37E-07 0.00E 00 Total for period Ci 5.37E-07 0.00E 00 3.,Particulates

  • Mo-99 Ci 0.00E 00 0.00E 00 Co-60 Ci 0.00E 00 0.00E 00 Zn-65 Ci 0.00E 00 0.00E 00 Fe-59 Ci 0.00E 00 0.00E 00 Mn-54 Ci 0.00E 00 0.00E 00 Cc-58 Ci 0.00E 00 0.00E 00 Cs-137 Ci 0.00E 00 0.00E 00 Cs-134 Ci 0.00E 00 0.00E 00
  • 'I-133 Ci 0.00E 00 0.00E 00 I-131 Ci 0.00E 00 0.00E 00 Ce-141 Ci 5.27E-08 0.00E 00 Co-144 Ci 0.00E 00 0.00E 00 Sr-89 Ci 0.00E 00 0.00E 00 Sr-90 Ci 0.00E 00 0.00E 00 Total for period Ci 5.27E-08 0.00E 00 1

Isotope with half-life less than 8 days i

23

TABLE 2A-1 LIQUID EFFLUENT--SUMMATION OF ALL RELEASES Farley Unit 1 - 1st Half, 1985 UNIT Qtr 1 Qtr 2 A.

Fission and Activation Products 1.

Total release Note (1)

Ci 4.30E-02 1.69E-02 2.

Average diluted concentration During Period Note (2) uCi/ml 2.45E-09 8.51E-10 3.

Percent of applicable limit During Period Note (2) 2.47E-03 2.45E-03 B.

Tritium 1.

Total release Note (1)

Ci 1.57E 02 2.12E 02 2.

Average diluted concentration During Period Note (2) uCi/ml 8.98E-06 1.07E-05 3.

Percent of applicable limit During Period Note (2) 2.99E-01 3.57E-01 C.

Dissolved and Entrained Gases

1. Total release Note (1)

Ci 3.41E-02 8.55E-03 2.

Average diluted concentration During Period Note (2) uCi/ml 1.94E-09 4.31E-10 3.

Percent of applicable limit During Period Note (2) 9.71E-04 2.16E-04 D.

Gross Alpha Radioactivity 1.

Total release Note (1)

Ci 0.00E 00 2.53E-04 E. Volume of Waste Water Note (3)

1. WMT liters 3.73E 06 1.79E 06
2. SGBD and Turbine Bldg Sumps liters 6.31E 07 7.45E 07
3.. Liquid Radioactive Effluent TOTAL Note (4) liters 3.73E 06 1.79E 06 F. Volume of Dilution Water During Quarter liters 1.75E 10 1.97E 10 NOTE:

(1) Steam Generator Blowdown and Turbine Building Sump release curie amounts and doses were measured and are included in these totals and in table 2B-1C in accordance with TABLE 4.11-1, Footnote E of Joseph M.

Farley Nuclear Plant Unit Number 1 Technical Specifications (Appendix A of License No. NPF-2).

(2) During period of discharge (3) Prior to dilution (4) Steam Generator Blowdown and Turbine Building Sump releases are excluded from Total Liquid Radioactive Effluent in accordance with 10 CFR 20, Appendix B, Note 5.

24

TABLE 2A-2 LIQUID EFFLUENT--SUMMATION OF ALL RELEASES l

Farley Unit 2 - 1st Half, 1985 UNIT Qtr 1 Qtr 2 A.

Fission and Activation Products 1.

Total release Note (1s Ci 1.90E-02 8.68E-03 2.

Average diluted concentration During Period Note (2) uCi/nl 1.19E-09 5.83E-10 3.

Percent of applicable limit During Period Note (2) 1.27E-03 4.05E-03 B.

Tritium

1. Total release Note (1)

Ci 1.09E 02 7.31E 01 2.

Average diluted concentration During Period Note (2) uCi/ml 6.80E-06 4.91E-06

3. Percent of applicable limit During Period Note (2) 2.27E-01 1.64E-01 C. Dissolved and Entrained Gases l
1. Total release Note (1)

Ci 2.54E-02 9.50E-03

2. Average diluted concentration During Period Note (2) uCi/ml 1.59E-09 6.38E-10 3.

Percent of applicable limit During Period Note (2) 7.93E-04 3.19E-04 D. Gross Alpha Radioactivity

1. Total release Note (1)

C1 0.00E 00 0.00E 00 E. Volume of Waste Water Note (3)

1. WMT liters 1.62E 06 8.14E 05
2. SGBD and Turbine Bldg Sumps liters 1.47E 08 4.75E 07 1

3.

Liquid Radioactive Effluent TOTAL Note (4) liters 1.62E 06 8.14E 05 F. Volume of Dilution Water During Quarter liters 1.59E 10 1.48Z 10 NOTE:

(1) Steam Generator Blowdown and Turbine Building Sump release curie amounts and doses were measured and are included in these totals and in table 2B-2C in accordance with TABLE 4.11-1, Footnote E of Joseph M.

Farley Nuclear Plant Unit Number 2 Technical Specifications (Appendix A of License No. NPF-8).

(2) During periods of discharge (3) Prior to dilution (4) Steam Generator Blowdown and Turbine Building Sump releases are excluded from Total Liquid Radioactive Effluent in accordance with 10 CFR 20, Appendix B, Note 5.

25

. _ _ _.. _ _. ~ _ _..

i TABLE 2B-1B LIQUID EFFLUENTS--BATCH j

Farley Unit 1 1st Half, 1985 Nuclides Released Unit Qtr 1 Qtr 2 Sr-89 Ci 0.00E 00 0.00E 00 i

Sr-90 Ci 0.00E 00 0.00E 00 Fe-55 C1 1.56E-02 2.70E-03 4

Co-57 Ci 3.66E-06 0.00E 00 Ce-144 Ci 2.63E-04 1.90E-04 4

Tc-93M C1 1.32E-05 0.00E 00 Ce-141 Ci 0.00E 00 3.83E-05 l

}

Np-239 Ci 0.00E 00 3.74E-04 j

Cr-51 Ci 1.63E-04 1.22E-03 I-131 Ci 3.05E-05 9.90E-07 Ru-103 Ci 0.00E 00 5.30E-04 i

j I-133 Ci 6.95E-05 9.68E-07 Ba-140 C1 1.76E-06 0.00E 00 r

As-76 Ci 2.77E-06 5.84E-06 Cs-134 Ci 1.25E-05 4.24E-06 j

Ru-106 C1 1.87E-04 7.02E-04 I

Cs-137 C1 1.44E-04 1.24E-05

.Mo-99 Ci 4.21E-06 0.00E 00 Zr-95 C1 1.73E-06 1.95E-04 Nb-95 C1 2.07E-04 4.51E-04 I-132 Ci 8.71E-06 2.13E-03 Co-58, Ci 6.07E-04 5.96E-04 j

Cs-136 Ci 1.34E-05 2.55E-05 Mn-54 Ci 1.20E-04 1.19E-06 Ag-110M C1 1.03E-03 8.17E-04 j

Sr-91 Ci 0.00E 00 9.71E-06 Zn-65 Ci 5.43E-06 1.74E-05 I-135 Ci 6.53E-06 0.00E 00 Fe-59 Ci 2.59E-05 1.10E-05 Co-60 Ci 4.76E-03 1.23E-03 I

Na-24 Ci 0.00E 03 0.00E 00 I

La-140 Ci 0.00E 00 7.43E-07 i

Cu-64 C1 1.37E-04 0.00E 00 Sb-124 Ci 3.97E-04 5.05E-06 i

Te-132 Ci 9.33E-06 6.67E-04 Sb-125 Ci 6.43E-03 5.29E-05 l

Zr-97 Ci 0.00E 00 3.84E-06 TOTALS Ci 3.02E-02 1.20E-02 Ee-133 Ci 3.32E-02 8.27E-03 1

Ee-135' Ci 8.15E-04 2.78E-04 TOTALS C1 3.40E-02 8.55E-03 i

H-3 C1 1.56E 02 2.12E 02 i

26

- ~ ~

TABLE 2B-2B J

LIQUID EFFLUENTS--EATCH Farley Unit 2 1st Half, 1985 Nuclides Released Unit Qtr 1 Qtr 2 l

Sr-89 Ci 0.00E 00 0.00E 00 Sr-90 Ci 0.00E 00 0.00E 00 Fe-55 Ci 1.09E-02 3.46E-04 Co-57 Ci 3.89E-07 0.00E 00 Ce-144 Ci 4.81E-05 4.95E-05 Tc-99M Ci 2.46E-06 0.00E 00 Ce-141 Ci 6.58E-07 0.00E 00 Np-239 Ci 3.76E-06 2.93E-04 Cr-51 Ci 1.64E-04 7.99E-05 I-131 Ci 4.71E-07 5.24E-07 Ru-103 Ci 0.00E 00 4.99E-05 I-133 Ci 3.19E-05 0.00E 00 Ba-140 Ci 8.23E-06 0.00E 00 As-76 Ci 1.72E-06 2.31E-07 Cs-134 Ci 6.35E-06 2.85E-06 Ru-106 Ci 0.00E 00 1.19E-04 Cs-137 Ci 4.07E-05 6.30E-06

.Mo-99 Ci 0.00E 00 8.78E-06 Zr-95 C1 1.68E-06 1.17E-05 Nb-95 Ci 6.50E-05 4.84E-05 j

I-132 Ci 0.00E 00 4.35E-03 i

I Co-58 Ci 5.30E-04 3.37E-04 Cs-136 Ci 0.00E 00 0.00E 00 Mn-54 Ci 5.64E-05 0.00E 00 Ag-110M C1 1.71E-04 2.48E-04 Zn-65 Ci 0.00E 00 0.00E 00 I-135 Ci 1.61E-05 1.71E-05 Fe-59 Ci 2.55E-05 0.00E 00 Co-60 Ci 9.05E-04 4.04E-04 Na-24 Ci 0.00E 00 0.00E 00 La-140 Ci 0.00E 00 0.00E 00 Sb-124 Ci 1.42E-04 0.00E 00 Sb-125 Ci 3.78E-03 2.38E-05 Te-132 Ci 0.00E 00 2.11E-03 TOTALS C1 1.69E-02 8.51E-03 Xe-133 C1 2.50E-02 9.34E-03 Xe-135 C1 3.74E-04 1.55E-04 TOTALS Ci 2.54E-02 9.50E-03 H-3 Ci 8.13E 01 7.22E 01 i

27

TABLE 2B-1C LIQUID EFFLUENTS--CONTINUOUS Farley Unit 1 - 1st Half, 1985 Nuclides Released Unit Qtr 1 Qtr 2 Sr-89 Ci 0.00E 00 0.00E 00 Sr-90 Ci 0.00E 00 0.00E 00 Ce-144 Ci 0.00E 00 0.00E 00 Ce-141 Ci 0.00E 00 0.00E 00 Np-239 Ci 0.00E 00 0.00E 00 Cs-134 Ci 0.00E 00 0.00E 00 Cs-137 Ci 0.00E 00 0.00E 00 Mo-99 Ci 0.00E 00 0.00E 00 Co-58 Ci 0.00E 00 0.00E 00 Mn-54 Ci 0.00E 00 0.00E 00 Ag-110M Ci 0.00E 00 0.00E 00 Fe-55 Ci 1.28E-02 3.98E-03 Zn-65 Ci 0.00E 00 0.00E 00 Fe-59 Ci 0.00E 00 0.00E 00 Co-60 Ci 0.00E 00 8.99E-04 Zr-95 Ci 0.00E 00 0.00E 00 TOTALS C1 1.28E-02 4.88E-03 Xe-133 Ci 0.00E 00 0.00E 00 Xe-135 Ci 0.00E 00 0.00E 00 Kr-87 Ci 0.00E 00 0.00E 00 Kr-88 Ci 0.00E 00 0.00E 00 TOTALS Ci 0.00E 00 0.00E 00 H-3 Ci 1.89E 00 0.00E 00 NOTE:

Although Steam Generator Blowdown and Turbine Building Sump releases were excluded from total liquid radioactive effl.ent volume in accordance with 10 CFR 20, Appendix B, Note 5, curie amounts and doses from these releases were measured and are reported here in accordance with Table 4.11-1, Footnote E of Joseph M.

Farley Nuclear Plant Unit Number 1 Technical Specification (Appendix A of License No.

NPF-2).

28 i

TABLE 2B-2C LIQUID EFFLUENTS--CONTINUOUS Farley Unit 2-1st Half, 1985 Nuclides Released Unit Qtr 1 Qtr 2 Sr-89 Ci 0.00E 00 0.00E 00 Sr-90 Ci 0.00E 00 0.00E 00 Ce-144 Ci 0.00E 00 0.00E 00 Ce-141 Ci 0.00E 00 0.00E 00 Cs-134 Ci 5.39E-04 0.00E 00 Cs-137 Ci 8.57E-04 9.50E-05 Mo-99 Ci 0.00E 00 0.00E 00 Zr-95 Ci 0.00E 00 0.00E 00 Nb-95 Ci 0.00E 00 0.00E 00 Co-58 Ci 5.00E-04 8.34E-05 Mn-54 Ci 9.59E-05 0.00E 00 Zn-65 Ci 0.00E 00 0.00E 00 I-135 Ci 0.00E 00 0.00E 00 Fe-59 Ci 0.00E 00 0.00E 00 Co-60 Ci 1.67E-04 0.00E 00 I-131 Ci 0.00E 00 0.00E 00 I-133 Ci 0.00E 00 0.00E 00 Na-24 Ci 0.00E 00 0.00E 00 Fe-55 Ci 0.00E 00 0.00E 00 Ag-110M Ci 0.00E 00 0.00E 00 TOTALS Ci 2.16E-03 1.78E-04 Xe-133 Ci 0.00E 00 0.00E 00 Xe-135 Ci 0.00E 00 0.00E 00 Kr-87 Ci 0.00E 00 0.00E 00 Kr-88 Ci 0.00E 00 0.00E 00 TOTALS Ci 0.00E 00 0.00E 00 H-3 Ci 2.77E 01 8.62E-01 NOTE:

Although Steam Generator Blowdown and Turbine Building Sump releases were excluded from total liquid radioactive effluent volume in accordance with 10 CFR 20, Appendix B, Note 5, curie amounts and doses from these releases were measured and are reported here in accordance with Table 4.11-1, Footnote E of Joseph M.

Farley Nuclear Plant Unit Number 2 Technical Specification (Appendix A of License No.

NPF-8).

29

=

TABLE 3 EFFLUENT AND WASTE DISPOSAL SEMIANNUAL REPORT (1985)

SOLID WASTE AND IRRADIATED FUEL SHIPMENTS SOLID WASIC SHIPPED OFFSITE FOR BURIAL OR DISPOSAL (Not irradiated fuel) 1.

Type of Waste UNITS PERIOD Jan.1-June 30 3

a.

Spent resins, filter sludges, m

3.568E 01 evaporator bottoms, etc.

Ci 2.747E 01 3

b.

Dry compressible waste, m

2.639E 02 contaminated equipment, etc.

Ci 1.272E 01 3

c.

Irradiated components, m

None control rods, etc.

Ci None 3

d.

Other (described) m None Ci None 2.

Estimate of major-nuclide composition ISOTOPES ISOTOPES a.

H-3 4.99 Co-58 2.82, N

Co-60 64.74 '-

Ni-63 19.31 Ce-144' 1.84 g

Mn-54 2.52 I

Cs-137 1.05 C-14 1.50 i

b.

H-3 18.3#

C? 144 3.03 Cr-51 4.E6

.'E - 2 41 2.75 Mn-54 2.7L 3'

Co-58 14.40 1

5. =

Co-60 17.06 Ni-63 34.15 t-Cs-137 2.01

/

30 s

a m

,-m

-.m,

TABLE 3 (con't)

EFFLUENT AND WASTE DISPOSAL SEMIANNUAL REPORT (1985)

SOLID WASTE AND IRRADIATED FUEL SHIPMENTS 3.

Solid Waste Disposition a.

Number of Shipments 15 b.

Mode of Transportation Chem-Nuclear Transport (11)

Hittman Transport (4) c.

Destination Chem-Nuclear Systems, Inc.

Barnwell, South Carolina 4.

Type of Containers a.

( la )

170 cu.ft. steel liners (dewatered resin & charcoal media) 55 cu.ft. High Integrity Containers

( Spent filters )

b.

( lb )

55 gallon steel drum 112 cu.ft. wooden boxes 5.

Solidification Agents a.

( 1a )

No solidifications during this period.

All items (spent resin and charcoal) that are categorized for item la were shipped dewatered.

b.

( lb )

N/A B.

IRRADIATED FUEL SHIPMENTS (Disposition) 1.

Number of Shipments None 2.

Mode of Transportation N/A 3.

Destination N/A 31

Tablo 4A-CQ1 CUMULATIVE JOINT FREQUENCY DISTRIBbTION Farley Nuclear Plant - 1st Quarter, 1985 HOURS AT EACH WIND SPEED AND DIRECTION RELEASE MODE: CONTINUOUS PERIOD OF RECORD:

1 85 )

3-31-85 STABILITY CLASS: A ELEVATION:45.7m Wind Speed (mph) at 45.7m level Wind Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

O 1

10 3

0 0

14 NNE O

1 10 9

0 0

20 NE 1

1 4

0 0

0 6

ENE 1

0 6

0 0

0 7

E O

O 1

1 0

0 2

ESE 1

3 7

0 0

0 11 SE O

4 7

0 0

0 11 SSE O

2 6

2 0

0 10 S

0 0

3 1

0 0

4 SSW 0

1 1

11 0

0 13 SW 0

2 10 9

0 0

21 WSW 0

0 2

1 0

0 3

W 0

4 4

2 0

1 11 WNW 0

0 4

7 2

1 14 NW 1

2 15 7

1 0

26 NNW 0

0 5

1 0

0 6

VARIABLE O

O O

O O

O O

Total 4

21 95 54 3

2 179 Periods of calm (hours):

0 Hours of missing data:

0 32

~

Table 4A-CQ1 CUMULATIVE JOINT FREQUENCY DISTRIBUTION Farley Nuclear Plant - 1st Quarter, 1985 HOURS AT EACH WIND SPEED AND DIRECTION RELEASE MODE: CONTINUOUS PERIOD OF RECORD:

1 85 )

3-31-85 STABILITY CLASS: A ELEVATION:10.0m Wind Speed (mph) at 10.0m level Wind Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

1 6

15 0

0 0

22 NNE O

3 1

0 0

0 4

NE 1

3 2

0 0

0 6

ENE 1

1 4

0 0

0 6

E O

4 3

0 0

0 7

ESE 1

4 6

0 0

0 11 SE 4

1 6

0 0

0 11 SSE O

2 6

0 0

0 8

5 0

0 2

1 0

0 3

SSW 1

3 7

14 0

0 25 4

SW 0

1 7

0 0

0 8

.l WSW 0

5 3

0 0

0 8

W 0

3 6

1 0

1 11 WNW 1

2 8

3 2

1 17 NW 0

7 14 1

0 0

22 NNW 0

3 7

0 0

0 10 VARIABLE O

O O

O O

O O

Total 10 48 97 20 2

2 179 Periods of calm (hours):

0 Hours of missing data:

0 33

Table 4A-CQ1 CUMULATIVE JOINT FREQUENCY DISTRIBUTION Farley Nuclear Plant - 1st Quarter, 1985 HOURS AT EACH WIND SPEED AND DIRECTION RELEASE MODE: CONTINUOUS PERIOD OF RECORD:

1 85 )

3-31-85 STABILITY CLASS: B ELEVATION:45.7m Wind Speed (mph) at 45.7m level Wind Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

O 2

4 2

0 0

8 NNE 3

4 4

0 0

0 11 NE 2

6 1

0 0

0 9

ENE 3

2 4

0 0

0 9

E O

2 2

1 0

0 5

ESE 1

4 1

0 0

0 6

SE O

3 6

0 0

0 9

SSE 2

1 2

2 0

0 7

S 1

2 2

3 0

0 8

SSW 1

0 0

8 0

0 9

SW 0

2 4

0 1

0 7

WSW 0

8 2

0 0

0 10 W

0 2

10 1

0 0

13 WNW 0

2 8

3 0

0 13 NW 2

6 17 3

0 1

29 NNW 2

4 6

1 0

0 13 VARIABLE O

O O

O 0

0 0

Total 17 50 73 24 1

1 166 Periods of calm (hours):

0 Hours of missing data 0

t 34 s

Table 4A-CQ1 CUMULATIVE JOINT FREQUENCY DISTRIBUTION Farley Nuclear Plant - 1st Quarter, 1985 HOURS AT EACH WIND SPEED AND DIRECTION RELEASE MODE: CONTINUOUS PERIOD OF RECORD:

1 85 )

3-31-85 STABILITY CLASS: B ELEVATION:10.0m Wind Speed (mph) at 10.0m level Wind Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

4 9

0 0

0 0

13 NNE O

5 0

0 0

0 5

NE 4

5 2

0 0

0 11 ENE 2

2 2

0 0

0 6

E O

6 2

0 0

0 8

ESE 1

5 0

0 0

0 6

SE 1

2 3

0 0

0 6

SSE 2

1 5

0 0

0 8

S 2

0 3

3 0

0 8

SSW 0

2 4

2 0

0 8

SW 0

7 5

0 0

0 12 WSW 1

4 6

0 0

0 11 W

0 6

5 0

0 0

11 WNW 0

7 9

0 0

0 16 NW 3

14 9

1 0

1 28 NNW 1

3 5

0 0

0 9

VARIABLE O

O O

O O

O O

Total 21 78 60 6

0 1

166 Periods of calm (hours):

0 Hours of missing data:

0 35

/

Tablo 4A-CQ1 CUMULATIVE JOINT FREQUENCY DISTRIBdTION Farley Nuclear Plant - 1st Quarter, 1985 HOURS AT EACH WIND SPEED AND DIRECTION RELEASE MODE: CONTINUOUS PERIOD OF RECORD:

1 85 )

3-31-85 STABILITY CLASS: C ELEVATION:45.7m

=------_--_-----

==-------______-__-----------

Wind Speed (mph) at 45.7m level Wind Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

1 14 10 5

0 0

30 NNE O

7 6

1 0

0 14 NE 3

3 0

0 0

0 6

ENE 1

4 2

0 0

1 8

E 2

9 1

1 0

0 13 ESE 1

5 1

0 0

0 7

SE O

4 0

0 0

0 4

SSE O

O 4

2 0

1 7

S 2

0 2

5 0

0 9

SSW 2

1 1

7 0

0 11 SW 1

4 2

10 3

1 21 WSW 2

1 2

1 0

0 6

W 1

2 8

0 0

0 11 WNW 0

3 9

11 1

1 25 NW 2

11 10 1

1 0

25 NKW 2

6 11 3

0 0

22 VARIABLE O

O O

O O

O O

Total 20 74 69 47 5

4 219 Periods of calm (hours):

0 Hours of missing data:

0 36

1 i

Table 4A-CQ1 CUMULATIVE JOINT FREQUENCY DISTRIBUTION Farley Nuclear Plant - 1st Quarter, 1985 HOURS AT EACH WIND SPEED AND DIRECTION RELEASE MODE: CONTINUOUS PERIOD OF RECORD:

1 85 )

3-31-85 STABILITY CLASS: C ELEVATION:10.0m Wind Speed (mph) at 10.0m level Wind Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL i

N 2

14 0

1 0

0 17 NNE 2

0 1

0 0

0 3

NE 4

4 0

0 0

0 8

ENE 2

5 1

0 0

1 9

E 4

7 1

0 0

0 12 ESE 1

3 1

0 0

0 5

SE 1

3 4

0 0

1 9

SSE 1

4 7

2 0

0 14 S

0 4

7 1

0 0

12 SSW 5

2 4

10 0

0 21 SW 2

5 6

0 2

0 15 WSW 1

5 6

0 0

0 12 W

i 3

9 0

0 0

13 WNW 2

11 7

2 2

0 24 NW 5

11 5

0 0

0 21 NNW 2

15 6

1 0

0 24 VARIABLE O

O O

O O

O O

Total 35 96 65 17' 4

2 219 Periods of calm (hours):

0 Hours of missing data:

0 37

Table 4A-CQ1 CUMULATIVE JOINT FREQUENCY DISTRIBUTION Farley Nuclear Plant - 1st Quarter, 1985 HOURS AT EACH WIND SPEED AND DIRECTION RELEASE MODE: CONTINUOUS PERIOD OF RECORD:

1 85 )

3-31-85 STABILITY CLASS: D ELEVATION:45.7m Wind speed (mph) at 45.7m level Wind Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

4 29 38 16 0

0 87 NNE 1

23 21 2

0 0

47 NE 5

11 9

0 0

0 25 ENE 3

21 13 0

0 0

37 E

1 14 17 2

0 1

35 ESE 1

7 16 2

1 0

27 SE 4

12 13 3

0 1

33 SSE O

4 21 12 1

0 38 5

5 4

8 3

0 0

20 SSW 4

4 6

23 1

0 38 SW 5

6 24 22 8

2 67 WSW 0

16 20 3

0 1

40 W

2 11 16 5

0 0

34 WNW 4

10 23 15 11 0

63 NW 2

11 32 21 3

1 70 NNW 1

27 44 12 1

1 86 VARIABLE O

O O

O O

O O

i Total 42 210 321 141 26 7

747 Periods of calm (hours):

0 Hours of missing data:

0 38

Tcble 4A-CQ1 CUMULATIVE JOINT FREQUENCY DISTRIBbTION Farley Nuclear Plant - 1st Quarter, 1985 HOURS AT EACH WIND SPEED AND DIRECTION RELEASE MO3E: CONTINUOUS PERIOD OF RECORD:

1 85 )

3-31-85 STABILITY CLASS: D ELEVATION:10.0m Wind Speed (mph) at 10.0m level Wind Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

17 23 0

0 0

0 40 NNE 10 17 0

0 0

0 27 NE 10 26 0

0 0

0 36 ENE 4

27 3

0 0

0 34 E

8 15 9

0 0

0 32 ESE 2

22 4

1 0

1 30 SE 3

21 16 1

0 0

41 SSE 3

5 13 3

0 0

24 S

4 5

3 0

0 0

12 SSW 4

9 37 17 1

0 68 SW 9

28 18 3

2 3

63 WSW 7

17 5

0 0

0 29 W

8 17 8

0 0

0 33 WWW 9

31 25 12 3

0 80 NW 11 45 21 3

0 1

81 NNW 15 62 37 3

0 0

117 VARIABLE O

0 0

0 0

0 0

Total 124 370 199 43 6

5 747 Periods of calm (hours):

0 Hours of missing datas 0

39

Tcblo 4A-CQ1 CUMULATIVE JOINT FREQUENCY DISTRIBdTION Farley Nuclear Plant - 1st Quarter, 1985 HOURS AT EACH WIND SPEED AND DIRECTION RELEASE MODE: CONTINUOUS PERIOD OF RECORD:

1 85 )

3-31-85 STABILITY CLASS: E ELEVATION:45.7m Wind Speed (mph) at 45.7m level Wind Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

2 16 11 0

0 0

29 NNE 7

11 5

0 0

0 23 NE 1

4 5

0 0

0 10 ENE 2

7 7

0 0

0 16 E

O 14 12 0

0 0

26 ESE 1

11 22 0

0 1

35 SE

.1 3

16 1

0 0

21 SSE 2

3 22 6

1 0

34 5

1 8

8 2

0 0

19 SSW 1

2 5

11 0

0 19 SW 3

3 26 9

0 0

41 WSW 0

10 19 1

0 0

30 W

2 14 13 3

0 0

32 WNW 0

4 16 4

0 0

24 NW 0

12 31 2

0 0

45 NNW 2

16 24 2

0 0

44 VARIABLE 0

0 0

0 0

0 0

Total 25 138 242 41 1

1 448 Periods of calm (hours):

0 Hours of missing datat 0

40

Tcblo 4A-CQ1 CUMULATIVE JOINT FREQUENCY DISTRIBUTION Farley Nuclear Plant - 1st Quarter, 1985 HOURS AT EACH WIND SPEED AND DIRECTION RELEASE MODE: CONTINUOUS PERIOD OF RECORD:

1 85 )

3-31-85 STABILITY CLASS: E ELEVATION:10.0m Wind Speed (mph) at 10.0m level Wind Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

16 2

0 0

0 0

18 NNE 16 5

0 0

0 0

21 NE 4

3 0

0 0

0 7

ENE 18 7

1 0

0 0

26 E

7 14 5

1 0

0 27 ESE 11 19 1

0 0

0 31 SE 5

23 6

0 0

0 34 SSE 2

10 7

0 1

0 20 i

S 2

1 1

0 0

0 4

SSW 4

11 14 1

0 0

30 SW 8

26 10 0

0 0

44 i

WSW 14 16 2

0 0

0 32 W

9 11 0

0 0

0 20 WNW 8

32 4

0 0

0 44 KW 17 27 2

0 0

0 46 WNW 21 21 2

0 0

0 44 VARIABLE O

O 0

0 0

0 0

Total 162 228 55 2

1 0

448 Periods of calm (hours):

0 1

Hours of missing data 0

41

Tcble 4A-CQ1 CUMULATIVE JOINT FREQUENCY DISTRIBU' TION Farley Nuclear Plant - 1st Quarter, 1985 HOURS AT EACH WIND SPEED AND DIRECTION l

RELEASE MODE: CONTINUOUS PERIOD OF RECORD:

1 85 )

3-31-85 STABILITY CLASS: F ELEVATION:45.7m Wind Speed (mph) at 45.7m level 4

Wind Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

O 5

10 0

0 0

15 NNE 1

4 8

0 0

0 13 NZ 2

5 6

0 0

0 13 ENE 1

5 8

0 0

0 14 E

1 3

4 0

0 0

8 ESE O

7 7

0 0

0 14 SE 1

3 6

0 0

0 10 l

SSE 1

4 11 1

0 0

17 S

0 2

1 1

0 0

4 SSW 0

2 0

0 0

0 2

SW 0

2 9

2 0

0 13 WSW 0

4 3

0 0

0 7

W i

3 5

0 0

0 9

WNW 0

1 14 1

0 0

16 4

NW 0

1 23 1

0 0

25 i

NNW 1

5 13 1

0 0

20 I

I VARIABLE O

0 0

0 0

0 0

Total 9

56 128 7

0 0

200 Periods of calm (hours):

0 Hours of missing datas 0

42

Table 4A-CQ1 CUMULATIVE JOINT FREQUENCY DISTRIBUTION Farley Nuclear Plant - 1st Quarter, 1985 HOUF AT EACH WIND SPEED AND DIRECTION RELEASE MODE: CONTINUOUS PERIOD OF RECORD:

1 85 )

3-31-85 STABILITY CLASS: F ELEVATION:10.0m Wind Speed (mph) at 10.0m level Wind Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

16 0

0 0

0 0

16 NNE 11 0

0 0

0 0

11 NE 6

1 0

0 0

0 7

ENE 6

4 3

0 0

0 13 i

E 7

2 0

0 0

0 9

l ESE 8

2 0

0 0

0 10 SE 4

7 2

0 0

0 13 SSE 1

0 0

0 0

0 1

S 1

0 0

0 0

0 1

i SSW 3

5 0

0 0

0 8

1 SW 5

7 0

0 0

0 12 WSW 7

2 0

0 0

0

-9 W

10 2

0 0

0 0

12 WNW 8

17 0

0 0

0 25 NW 11 13 0

0 0

0 24

(

NNW 20 9

0 0

0 0

29 VARIABLE O

O O

O 0

0 0

Total 124 71 5

0 0

0 200 Periods of calm (hours):

0 Hours of missing datas 0

43

Table 4A-CQ1 CUMULATIVE JOINT FREQUENCY DISTRIBUTION Farley Nuclear Plant 1st Quarter, 1985 HOURS AT EACH WIND SPEED AND DIRECTION RELEASE MODE: CONTINUOUS PERIOD OF RECORD:

1 85 )

3-31-85 STABILITY CLASS: G ELEVATION:45.7m Wind Speed (mph) at 45.7m level Wind Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL i

N 3

8 3

0 0

0 14 NNE 2

11 9

0 0

0 22 NE 2

7 13 0

0 1

23 ENE 4

6 4

0 0

0 14 E

1 12 12 0

0 0

25 ESE 1

9 8

0 0

0 18 3

SE 2

11 4

0 0

0 17 SSE 3

3 8

0 0

0 14 S

0 5

2 0

0 0

7 SSW 2

3 2

0 0

0 7

SW 2

3 2

0 0

0 7

WSW 0

1 2

0 0

0 3

W 2

0 1

0 0

0 3

WNW 2

0 1

0 0

0 3

I NW 3

3 3

0 0

0 9

NNW 2

3 10 0

0 0

15 VARIABLE O

O O

O O

0 0

Total 31 85 84 0

0 1

201 Periods of calm (hours):

0 Hours of missing data:

0 44

I Table 4A-CQ1 CUMULATIVE JOINT FREQUENCY DISTRIBUTION Farley Nuclear Plant - 1st Quarter, 1985 HOURS AT EACH WIND SPEED AND DIRECTION RELEASE MODE: CONTINUOUS PERIOD OF RECORD:

1 85 )

3-31-85 STABILITY CLASS: G ELEVATION:10.0m Wind Speed (mph) at 10.0m level Wind Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL T

N 54 1

0 0

0 0

55 i

NME 14 1

1 0

0 0

16 NE 7

0 0

0 0

0 7

i ENE 5

0 1

0 0

0 6

E 2

0 0

0 0

0 2

ESE 2

1 0

0 0

0 3

j i

a;.

SE 5

1 0

0 0

0 6

SSE 8

0 0

0 0

0 8

5 3

0 0

0 0

0 3

SSW 3

1 0

0 0

0 4

}

l SW 3

0 0

0 0

0 3

WSW 3

1 0

0 0

0 4

i I

W 2

2 0

0 0

0 4

M 2

2 0

0 0

0 4

NW 12 1

0 0

0 0

13 NNW 63 0

0 0

0 0

63 VARIABLE O

O 0

0 0

0 0

f Total 188 11 2

0 0

0 201 d

Periods of calm (hours):

0 l

Hours of missing data:

0 J

l 45 l

i

Tcblo 4A-CQ2 CUMULATIVE JOINT FREQUENCY DISTRIBUTION Farley Nuclear Plant - 2nd Quarter, 1985 HOURS AT EACH WIND SPEED AND DIRECTION RELEASE MODE: CONTINUOUS i

PERIOD OF RECORD:

4 85 6-30-85 STABILITY CLASS: A ELEVATION:45.7m Wind Speed (mph) at 45.7m level Wind Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

2 12 12 3

0 0

29 NNE 1

16 10 2

0 0

29 NE 4

5 2

1 0

0 12 ENE' 7

4 3

2 0

0 16 E

2 15 7

5 0

0 29 ESE 1

14 7

3 0

0 25 SE 5

12 8

4 0

0 29 SSE 1

18 14 0

0 0

33 5

1 3

4 0

0 0

8 SSW 1

0 2

1 3

0 7

SW 1

6 12 11 0

0 30 l

WSW 1

15 16 5

0 0

??

W 5

13 22 0

0 0

40 WNW 1

7 9

0 0

1 18 NW 0

7 11 7

1 0

26 NNW 4

9 11 1

0 1

26 VARIABLE O

0 0

0 0

0 0

' Total 37 156 150 45 4

2 394 Periods of calm (hours):

0 Hours of missing datas 0

46

Tcblo 4A-CQ2 CUMULATIVE JOINT FREQUENCY DISTRIBdTION Farley Nuclear Plant - 2nd Quarter, 1985 HOURS AT EACH WIND SPEED AND DIRECTION RELEASE MODE: CONTINUOUS PERIOD OF RECORD:

4 85 6-30-85 STABILITY CLASS: A ELEVATION:10.0m Wind Speed (mph) at 10.0m level Wind Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

6 21 4

0 0

0 31 NNE 4

10 2

0 0

0 16 NE 5

6 0

0 0

0 11 ENE 10 9

10 1

0 0

30 E

4 14 6

0 0

0 24 ESE 2

18 5

1 0

0 26 SE 7

20 8,

0 0

0 35 SSE 1

12 7

0 1

0 21 S

2 1

0 2

0 0

5 SSW 1

3 2

4 2

0 12 SW 2

10 28 5

2 0

47 WSW 3

20 9

2 1

1 36 W

2 15 7

0 1

0 25 WNW 1

7 6

1 0

1 16 NW 1

6 12 6

0 1

26 NNW 6

17 9

0 0

1 33 VARIABLE O

O O

O O

O O

t*

Total 57 189 115 22 7

4 394 Periods of calm (hours):

0 Hours of missing datat 0

47

Table 4A-CQ2 CUMULATIVE JOINT FREQUENCY DISTRIBUTION I

Farley Nuclear Plant - 2nd Quarter, 1985 HOURS AT EACH WIND SPEED AND DIRECTION RELEASE MODE: CONTINUOUS PERIOD OF RECORD:

4 85 6-30-85 STABILITY CLASS: B ELEVATION:45.7m Wind speed (mph) at 45.7m level Wind i

Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

4 12 2

0 0

0 18 NNE 4

9 4

0 0

0 17 NE 4

5 3

0 0

0 12 ENE O

7 3

0 0

0 10 E

10 8

4 0

0 0

22 ESE 2

9 1

0 0

0 12 SE 5

5 4

0 0

0 14 SSE 1

10 7

0 0

0 18 5

0 5

1 1

0 0

7 SSW 0

1 2

0 1

0 4

SW 0

0 6

0 2

0 8

4 WSW 0

8 4

0 0

0 12 W

0 9

5 0

0 1

15 WWW 0

5 4

1 0

0 10 i

a NW 2

10 6

3 0

0 21 NNW 0

4 1

0 0

0 5

VARIABLE O

0 0

0 0

0 0

j Total 32 107 57 5

3 1

205 Periods of calm (hours):

0 Hours of missing data:

0 48

-... ~.. - _. _. _ _

Table 4A-CQ2 CUMULATIVE JOINT FREQUENCY DISTRIBUTION Farley Nuclear Plant - 2nd Quarter, 1985 HOURS AT EACH WIND SPEED AND DIRECTION RELEASE MODE: CONTINUOUS PERIOD OF RECORD:

4 85 6-30-85 STABILITY CLASS: B ELEVATION:10.0m Wind speed (mph) at 10.0m level Wind Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL l

N 7

13 0

0 0

0 20 NNE 6

7 2

0 0

0 15 NE 3

6 0

0 0

0 9

4 ENE 4

9 4

0 0

0 17 I

E 6

6 0

0 0

0 12 ESE 4

15 0

0 0

0 19 SE 5

14 1

0 0

0 20 SSE 1

3 5

0 0

0 9

S 1

1 0

1 0

0 3

j SSW 0

1 0

1 1

0 3

j SW 0

5 5

2 1

0 13 WSW 1

9 2

0 0

0 12 i

W 2

9 4

0 0

1 16 7

WNW 0

7 5

1 0

0 13 l

NW 2

6 4

0 0

0 12 NNW 2

9 1

0 0

0 12 I

VARIABLE 0

0

'O 0

0 0

0 Total 44 120 33 5

2 1

205 Periods of calm (hours):

0 Hours of missing datas 0

49

Tcble 4A-CQ2 CUMULATIVE JOINT FREQUENCY DISTRIBdTION Farley Nuclear Plant 2nd Quarter, 1985 HOURS AT EACH WIND SPEED AND DIRECTION RELEASE MODE: CONTINUOUS PERIOD OF RECORD:

4 85 6-30-85 STABILITY CLASS: C ELEVATION:45.7m Wind speed (mph) at 45.7m level Wind Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

0 5

2 1

0 0

8 NNE 1

3 1

0 0

0 5

l NE 3

2 1

0 0

0 6

ENE O

8 3

0 0

0 11 E

6 12 0

0 0

0 18 ESE 2

3 4

1 0

0 10 SE O

5 3

0 0

0 8

SSE 1

4 4

0 0

0 9

S 2

2 0

1 0

0 5

SSW 1

0 2

0 1

0 4

SW 0

1 6

7 0

0 14 WSW 0

5 6

1 0

0 12 W

3 3

2 0

0 0

8 WNW 0

7 0

0 0

0 7

~

NW 0

11 2

2 0

0 15 NNW 2

3 6

0 0

0 11 VARIABLE O

O O

O 0

0 0

Total 21 74 42 13 1

0 151 Periods of calm (hours):

0 Hours of missing datas 0

50

Tablo 4A-CQ2 CUMULATIVE JOINT FREQUENCY DISTRIBUTION Farley Nuclear Plant - 2nd Quarter, 1985 HOURS AT EACH WIND SPEED AND DIRECTION RELEASE MODE: CONTINUCUS PERIOD OF RECORD:

4 85 6-30-85 STABILITY CLASS: C FLEVATION:10.0m Wind Speed (mph) at 10.0m level Wind Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

3 3

1 0

0 0

7 i

i NNE 2

2 0

0 0

0 4

NE 3

6 1

0 0

0 10 ENE 5

12 1

0 0

0 18 E

8 3

2 0

0 0

13 ESE 0

7 0

0 0

0 7

SE 3

8 3

0 0

0 14 SSE O

2 0

1 0

0 3

S 2

1 0

0 1

0 4

SSW 0

0 2

1 0

0 3

SW 0

5 10 1

0 0

16 WSW 2

6 5

0 0

0 13 W

0 4

1 0

0 0

5 WNW 1

9 2

0 0

0 12 NW 1

5 5

0 0

0 11 WWW 2

8 1

0 0

0 11 VARIABLE O

O O

O O

O O

Total 32 81 34 3

1 0

151 Periods of calm (hours):

0 Hours of missing datat 0

51

Tcblo 4A-CQ2 4

CUMULATIVE JOINT FREQUENCY DISTRIBUTION Farley Nuclear Plant - 2nd Quarter, 1985 HOURS AT EACH WIND SPEED AND DIRECTION RELEASE MODE: CONTINUOUS PERIOD OF RECORD:

4 85 6-30-85 STABILITY CLASS: D ELEVATION:45.7m

[

Wind Speed (mph) at 45.7m level Wind Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

4 10 5

0 0

0 19 NNE 3

13 7

0 0

0 23 NE 4

11 5

0 0

0 20 ENE 5

13 6

1 0

0 25 E

2 12 9

0 0

0 23 ESE 1

9 9

1 0

0 20 SE 2

6 17 1

0 0

26 SSE 2

10 16 2

0 0

30 S

2 4

10 2

0 0

18 SSW 3

4 4

3 6

0 20 SW 2

11 37 22 4

0 76 WSW 3

34 54 9

1 0

101 W

4 16 7

0 0

0 27 WNW 3

9 6

1 0

0 19 NW 0

5 7

3 0

0 15 NNW 3

12 16 3

0 1

35 VARIABLE O

0 0

0 0

0 0

Total 43 179 215 48 11 1

497 Periods of calm (hours):

0 Hours of missing datas 0

52

Tcblo 4A-CQ2 CUMULATIVE JOINT FREQUENCY DISTRIBdTION Farley Nuclear Plant - 2nd Quarter, 1985 HOURS AT EACH WIND SPEED AND DIRECTION RELEASE MODE: CONTINUOUS PERIOD OF RECORD:

4 85 6-30-85 STABILITY CLASS: D ELEVATION:10.0m Wind Speed (mph) at 10.0m level Wind Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL 4

N 10 5

0 0

0 0

15 NNE 8

9 0

1 0

0 18 NE 13 13 0

0 0

0 26 ENE 7

14 4

0 0

0 25 E

5 18 2

1 0

0 26 i

ESE 4

15 3

0 0

0 22 i

SE 5

21 8

0 0

0 34

^

SSE 2

12 8

0 0

0 22 5

2 3

3 2

0 0

10 I

SSW 4

4 3

4 3

1 19 SW 11 66 45 9

0 0

131 WSW 10 27 11 2

0 0

50 W

11 9

2 0

0 0

22

.i j

WNW 8

6 3

1 0

0 18

~

NW 1

12 11 1

0 0

25 NNW 15 15 4

0 0

0 34 VARIABLE O

O 0

0 0

0 0

Total 116 249 107 21 3

1 497 Periods of calm (hours):

0 Hours of missing datat 0

53

Table 4A-CQ2 CUMULATIVE JOINT FREQUENCY DISTRIBUTION Farley Nuclear Plant - 2nd Quarter, 1985 HOURS AT EACH WIND SPEED AND DIRECTION RELEASE MODE: CONTINUOUS PERIOD OF RECORD:

4 85 6-30-85 STABILITY CLASS: E ELEVATION:45.7m Wind Speed (mph) at 45.7m level Wind Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

1 2

8 0

0 0

11 NNE 3

7 2

0 0

0 12 NE 1

4 2

0 0

1 8

i ENE 3

4 2

0 0

0 9

E O

15 11 0

0 0

26 ESE 3

18 5

0 0

0 26 SE 1

11 11 1

0 0

24 i

SSE 1

5 11 2

0 0

19

]

S 4

4 18 6

0 0

32 SSW 2

3 4

2 0

0 11 SW 6

8 41 13 0

0 68 WSW 3

24 45 4

0 0

76 W

3 33 12 0

0 0

48 WNW 7

12 12 1

0 0

32 NW 6

15 22 3

0 0

46 NNW 2

8 20 1

0 0

31 VARIABLE O

O O

O O

O O

Total 46 173 226 33 0

1 479 Periods of calm (hours):

0 Hours of missing data 0

54

Tcblo 4A-CQ2 CUMULATIVE JOINT FREQUENCY DISTRIBUTION Farley Nuclear Plant - 2nd Quarter, 1985 HOURS AT EACH WIND SPEED AND DIRECTION RELEASE MODE: CONTINUOUS PERIOD OF RECORD:

4 85 6-30-85 STABILITY CLASS: E ELEVATION:10.0m Wind Speed (mph) at 10.0m level Wind Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

16 1

1 2

0 0

20 1

NNE 5

3 0

0 0

0 8

I NE 7

4 0

0 0

0 11 ENE 16 14 0

0 0

0 30 E

12 5

0 0

0 0

17 ESE 16 12 0

0 0

0 28 SE 6

13 5

0 0

0 24 SSE 1

12 9

.0 0

0 22 S

3 2

2 2

0 0

9 SSW 7

7 1

0 0

0 15 SW 26 59 22 0

0 0

107 WSW 20 21 5

0 0

0 46 W

24 6

1 0

0 0

31 WNW 18 18 4

0 0

0 40 i

WW 18 29 1

0 0

0 48 WNW 13 8

0 1

1 0

23 VARIABLE O

O O

O 0

0 0

Total 208 214 51 5

1 0

479 Periods of calm (hours):

0 Hours of missi'ng datat 0

55 i

.~

7

Tcblo 4A-CQ2 CUMULATIVE JOINT FREQUENCY DISTRIBUTION Farley Nuclear Plant - 2nd Quarter, 1985 HOURS AT EACH WIND SPEED AND DIRECTION RELEASE MODE: CONTINUOUS PERIOD OF RECORD:

4 85 6-30-85 STABILITY CLASS: F ELEVATION:45.7m Wind Speed (mph) at 45.7m level Wind' Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

1 8

9 0

0 0

18 NNE 1

6 3

0 0

0 10 NE 3

3 5

0 0

0 11 ENE 2

2 3

0 0

0 7

l E

6 5

8 0

0 0

19 ESE 3

10 6

0 0

0 19 SE 4

9 11 0

0 0

24 SSE 1

5 5

0 0

0 11 5

4 3

2 0

0 0

9 SSW 2

2 0

0 0

0 4

SW 2

6 9

1 0

0 18 WSW 1

11 5

0 0

0 17 W

1 8

3 0

0 0

12 WNW 3

13 8

1 0

0 25 s WW 4

14 14 1

0 0

33 NKW 2

10 16 1

0 0

29 VARIABLE O

0 0

0 0

0 0

Total 40 115 107 4

0 0

266 Periods of calm (hours):

0 Hours of missing datas 0

56

~

Table 4A-CQ2 CUMULATIVE JOINT FREQUENCY DISTRIBUTION Farley Nuclear Plant - 2nd Quarter, 1985 HOURS AT EACH WIND SPEED AND DIRECTION RELEASE MODE: CONTINUOUS PERIOD OF RECORD:

4 85 6-30-85 STABILITY CLASS: F ELEVATION:10.0m

--________------_--_-----_---====_

Wind speed (mph) at 10.cm level Wind j

Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL J'

N 19 0

1 0

0 0

20 NNE 13 1

0 0

0 0

14

.NE 13 1

0 0

0 0

14 ENE 12 0

1 0

0 0

13

-l E

10 3

0 0

0 0

13 ECE 17 3

O O

O O

20 SE 6

6 1

0 0

0 13 I

SSE 7

1 0

0 0

0 8

i S

1 0

1 0

0 0

2 SSW i

0 0

0 0

0 1

SW 9

7 1

0 0

0 17 WSW 5

5 0

0 0

0 10 W

16 7

1 0

0 0

24 WNW 15 16 0

0 0

0 31 8

NW 19 15 1

0 0

0 35 NNW 24 5

2 0

0 0

31 VARIABLE O

O O

O O

O O

Total 187 70 9

0 0

0 266 Periods of calm (hours):

0 Hours of missing data:

0 57 4

.~

..m

Table 4A-CQ2 CUMULATIVE JOINT FREQUENCY DISTRIBUTION Farley Nuclear Plant - 2nd Quarter, 1985 HOURS AT EACH WIND SPEED AND DIRECTION RELEASE MODE: CONTINUOUS PERIOD OF RECORD:

4 85 6-30-85 STABILITY CLASS: G ELEVATION:45.7m Wind Speed (mph) at 45.7m level Wind Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

3 14 4

0 0

0 21 NNE 5

8 6

1 0

0 20 NE 8

9 3

0 0

0 20 ENE 5

11 6

0 0

0 22 E

4 8

7 0

0 0

19 ESE 5

9 1

0 0

0 15 SE 4

10 2

0 0

0 16 SSE 3

3 1

0 0

0 7

S 1

2 0

0 0

0 3

SSW 1

2 0

0 0

0 3

SW 1

3 0

0 0

0 4

WSW 0

4 1

0 0

0 5

W 1

0 1

0 0

0 2

WNW 2

6 2

0 0

0 10 NW 2

3 10 0

0 0

15 NNW 2

3 5

0 0

0 10 VARIABLE O

O O

O O

O O

Total 47 95 49 1

0 0

192 Periods of calm (hours):

0 Hours of missing data:

0 3 58 1

Tcblo 4A-CQ2 CUMULATIVE JOINT FREQUENCY DISTRIBUTION Farley Nuclear Plant - 2nd Quarter, 1985 HOURS AT EACH WIND SPEED AND DIRECTION RELEASE MODE: CONTINUOUS PERIOD OF RECORD:

4 85 6-30-85 STABILITY CLASS: G ELEVATION:10.0m Wind Speed (mph) at 10.0m level Wind Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

54 0

0 0

0 0

54 NNE 20 1

0 0

0 0

21 NE 10 0

0 0

0 0

10 ENE 8

0 0

0 0

0 8

E 1

0 0

0 0

0 1

ESE 5

0 0

0 0

0 5

SE 6

0 0

0 0

0 6

SSE O

O O

O 0

0 0

S 0

0 0

0 0

0 0

SSW 1

0 0

0 0

0 1

SW 1

0 0

0 0

0 1

WSW 1

1 0

0 0

0 2

W 1

1 0

0 0

0 2

WNW 12 2

0 0

0 0

14 NW 23 3

0 0

0 0

26 NNW 40 1

0 0

0 0

41 VARIABLE O

O O

O O

O 0

Total 183 9

0 0

0 0

192 Periods of calm (hours):

0 Hours of missing data:

0 59

TABLE 4A-1BQ1 CUMULATIVE JOINT FREQUENCY DISTRIBUTION Farley Unit 1-1st Quarter, 1985 HOURS AT EACH WIND SPEED AND DIRECTION RELEASE MODE: BATCH PERIOD OF RECORD:

1 85 3-31-85 STABILITY CLASS: A ELEVATION:45.7m Wind Speed (mph) at 45.7m level Wind Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

O O

O O

O O

O NNE O

O O

O O

O O

NE O

O O

O O

O O

ENE O

O O

O O

O O

E O

O O

O O

O O

l ESE O

O O

O O

O O

SE O

O O

O O

O O

SSE O

O 0

0 0

0 0

S 0

0 0

0 0

0 0

SSW 0

0 0

0 0

0 0

SW 0

0 0

0 0

0 0

WSW 0

0 1

0 0

0 1

W 0

0 0

0 0

0 0

WNW 0

0 0

0 0

0 0

NW 0

0 0

0 0

0 0

NNW 0

0 0

0 0

0 0

VARIABLE O

0 0

0 0

0 0

Total 0

0 1

0 0

0 1

Periods of calm (hours):

0 Hours of missing data:

0 60

~

TABLE 4A-1BQ1 CUMULATIVE JOINT FREQUENCY DISTRIBUTION Farley Unit 1 - 1st Quarter, 1985 HOURS AT EACH WIND SPEED AND DIRECTION l

1 RELEASE MODE: BATCH PERIOD OF RECORD:

1 85 3-31-85 STABILITY CLASS: A ELEVATION:10.0m

---____====------------------------------------------------------

Wind Speed (mph) at 10.0m level Wind Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

O O

O O

O O

O NNE O

O O

O O

O O

NE O

O O

O O

O O

ENE O

O O

O O

O O

E O

O O

O O

O O

ESE O

O O

O O

O O

SE O

O O

O O

O O

SSE O

O O

O O

O O

S 0

0 0

0 0

0 0

SSW 0

0 0

0 0

0 0

SW 0

0 1

0 0

0 1

WSW 0

0 0

0 0

0 0

W 0

0 0

0 0

0 0

WNW 0

0 0

0 0

0 0

NW 0

0 0

0 0

0 0

NNW 0

0 0

0 0

0 0

VARIABLE O

O O

O O

O O

Total 0

0 1

0 0

0 1

Periods of calm (hours):

0 Hours of missing data:

0 61

TABLE 4A-1BQ1 CUMULATIVE JOINT FREQUENCY DISTRIBUTION Farley Unit 1-1st Quarter, 1985 HOURS AT EACH WIND SPEED AND DIRECTION RELEASE MODE: BATCH PERIOD OF RECORD:

1 85 3-31-85 STABILITY CLASS: B ELEVATION:45.7m Wind Speed (mph) at 45.7m level Wind Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

O O

O O

O O

O NNE O

O O

O O

O O

NE O

0 0

0 0

0 0

ENE O

O O

O O

O O

E O

O O

O O

O O

ESE O

O O

O 0

0 0

SE O

O O

O O

O O

SSE O

O O

O O

O O

S 0

0 0

0 0

0 0

SSW 0

0 0

0 0

0 0

'SW 0

0 0

0 0

0 0

WSW 0

0 0

0 0

0 0

W 0

0 1

0 0

0 1

WNW 0

0 0

0 0

0 0

NW 0

0 0

0 0

0 0

NNW 0

0 0

0 0

0 0

VARIABLE O

O O

O O

O O

Total 0

0 1

0 0

0 1

Periods of calm (hours):

0 Hours of missing data:

0 62

TABLE 4A-1BQ1 CUMULATIVE JOINT FREQUENCY DISTRIBUTION Farley Unit 1 - 1st Quarter, 1985 HOURS AT EACH WIND SPEED AND DIRECTION RELEASE MODE: BATCH PERIOD OF RECORD:

1 85 3-31-85 STABILITY CLASS: B ELEVATION:10.0m Wind Speed (mph) at 10.0m level Wind Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

O O

O O

O O

O NNE O

0 0

0 0

0 0

NE O

O O

O O

O O

ENE O

O O

O O

O O

E O

O O

O O

O O

ESE O

O O

O O

O O

SE O

O O

O O

O O

SSE O

O 0

0 0

0 0

S 0

0 0

0 0

0.

O SSW 0

0 0

0 0

0 0

SW 0

0 0

0 0

0 0

WSW 0

0 1

0 0

0 1

W 0

0 0

0 0

0 0

WNW 0

0 0

0 0

0 0

i NW 0

0 0

0 0

0 0

NNW 0

0 0

0 0

0 0

i i

VARIABLE O

O O

O O

O O

=-------------

Total' 0

0 1

0 0

0 1

' Periods of' calm (hours):

0 Hours of missing data:

0 I

63

TABLE 4A-1BQ1 CUMULATIVE JOINT FREQUENCY DISTRIBUTION Farley Unit 1-1st Quarter, 1985 HOURS AT EACH WIND SPEED AND DIRECTION RELEASE MODE: BATCH PERIOD OF RECORD:

1 85 3-31-85 STABILITY CLASS: C ELEVATION:45.7m Wind Speed (mph) at 45.7m level Wind Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

O O

O O

O O

O NNE O

O 0

0 0

0 0

NE O

O O

O O

O O

ENE O

O O

O O

O O

E O

O O

O O

O O

ESE O

O O

O O

O O

EE O

0 0

0 0

0 0

SSE 0

0 0

0 0

0 0

S 0

0 0

0 0

0 0

SSW 0

0 0

0 0

0 0

SW 0

0 0

0 0

0 0

WSW 0

0 0

1 0

0 1

W 0

0 3

0 0

0 3

WNW 0

1 0

0 0

0 1

NW 0

0 0

0 0

0 0

NNW 0

0 0

0 0

0 0

VARIABLE O

O 0

0 0

0 0

Total 0-1 3

1 0

0 5

Periods of calm (hours):

0 Hours of missing data:

0 64

TABLE 4A-1BQ1 CUMULATIVE JOINT FREQUENCY DISTRIBUTION Farley Unit 1 1st Quarter, 1985 HOURS AT EACH WIND SPEED AND DIRECTION RELEASE MODE: BATCH PERIOD OF RECORD:

1 85 3-31-85 STABILITY CLASS: C ELEVATION:10.0m Wind Speed (mph) at 10.0m level Wind Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

0 O

O O

O O

O NNE O

O O

O O

O O

NE O

O O

O O

O O

ENE O

O O

O O

O O

E O

O O

O O

O O

ESE O

O O

0 0

0 0

SE O

O O

O O

O O

SSE O

O O

O O

O O

S 0

0 0

0 0

0 0

SSW 0

0 0

0 0

0 0

SW 0

0 0

0 0

0 0

WSW 0

1 3

0 0

0 4

W 0

1 0

0 0

0 1

WNW 0

0 0

0 0

0 0

NW 0

0 0

0 0

0 0

NNW 0

0 0

0 0

0 0

VARIABLE O

O O

O 0

0 0

Total 0

2 3

0 0

0 5

Periods of calm (hocrs):

0 Hours of missing data:

0 65

-.- -.. - -.~.

c--

TABLE 4A-1BQ1 CUMULATIVE JOINT FREQUENCY DISTRIBUTION Farley Unit 1-1st Quarter, 1985 HOURS AT EACH WIND SPEED AND DIRECTION RELEASE MODE: BATCH PERIOD OF RECORD:

1 85 3-31-85 STABILITY CLASS: D ELEVATION:45.7m Wind Speed (mph) at 45.7m level Wind Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

O O

O O

O O

O NNE O

O O

O O

O O

NE O

O O

O O

O O

ENE O

O O

O O

O O

E O

O O

O O

O O

ESE O

O O

O O

O O

SE O

O O

O O

O O

SSE O

O 0

0 0

0 0

S 0

0 0

0 0

0 0

SSW 0

0 0

0 0

0 0

SW 0

0 0

0 0

0 0

WSW 0

0 0

0 0

0 0

W 0

0 0

1 0

0 1

WNW 0

0 0

0 0

0 0

NW 0

0 0

0 0

0 0

NNW 0

0 0

0 0

0 0

VARIABLE O

O O

O O

O 0

Total 0

0 0

1 0

0 1

Periods of calm (hours):

0 Hours of missing data:

0 66

TABLE 4A-1BQ1 CUMULATIVE JOINT FREQUENCY DISTRIBUTION Farley Unit 1 - 1st Quarter, 1985 HOURS AT EACH WIND SPEED AND DIRECTION RELEASE MODE: BATCH PERIOD OF RECORD:

1 85 3-31-85 STABILITY CLASS: D ELEVATION:10.0m


_ ____====-

Wind Speed (mph) at 10.0m level Wind Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

O O

O O

O O

O NNE O

O O

O O

O O

NE O

O O

O O

O O

ENE O

O O

O O

O O

E O

O O

O O

O O

ESE O

O O

O O

O O

SE O

O O

O O

O O

SSE O

0 0

0 0

0 0

S 0

0 0

0 0

0 0

SSW 0

0 0

0 0

0 0

SW 0

0 0

0 0

0~

0 WSW 0

0 0

0 0

0 0

W 0

0 1

0 0

0 1

WNW 0

0 0

0 0

0 0

NW 0

0 0

0 0

0 0

NNW 0

0 0

0 0

0 O

VARIABLE O

O O

O O

O O

Total 0

0 1

0 0

0 1

l l

l Periods of calm (hours):

0 i

Hours of missing data:

O l

l 67

TABLE 4A-1BQ1 CUMULATIVE JOINT FREQUENCY DISTRIBUTION Farley Unit 1-1st Quarter, 1985 HOURS AT EACH WIND SPEED AND DIRECTION RELEASE MODE: BATCH PERIOD OF RECORD:

1 85 3-31-85 STABILITY CLASS: E ELEVATION:45.7m Wind Speed (mph) at 45.7m level Wind Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

O O

O O

O O

O NNE O

O O

O O

O O

NE O

O O

O O

O O

ENE O

O O

O O

O O

E O

O O

O O

O O

ESE O

O O

O 0

0 0

SE O

0 0

0 0

0 0

SSE O

O O

O O

O O

S 0

0 0

0 0

0 0

SSW 0

0 0

0 0

0 0

SW 0

0 0

0 0

0 0

WSW 0

0 1

0 0

0 1

W 0

0 2

0 0

0 2

WNW 0

0 0

0 0

0 0

NW 0

0 0

0 0

0 0

NNW 0

0 0

0 0

0 0

VARIABLE O

O O

O 0

0 0

Total 0

0 3

0 0

0 3

Periods of calm (hours):

O L

Hours of missing data:

0 68

TABLE 4A-1BQ1 CUMULATIVE JOINT FREQUENCY DISTRIBUTION Farley Unit 1-1st Quarter, 1985 HOURS AT EACH WIND SPEED AND DIRECTION RELEASE MODE: BATCH PERIOD OF RECORD:

1 85 3-31-85 STABILITY CLASS: E ELEVATION:10.0m Wind Speed (mph) at 10.0m level Wind Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

O O

O O

O O

O NNE O

O O

O O

O O

NE O

O 0

0 0

0 0

ENE O

0 0

0 0

0 0

E O

O O

O O

O O

i ESE O

O O

O O

O O

SE O

O O

O O

O O

j SSE O

O O

O O

O 0

S 0

0 0

0 0

0 0

I SSW 0

0 0

0 0

0 0

SW 0

0 0

0 0

0 0

WSW 0

3 0

0 0

0 3

W 0

0 0

0 0

0 0

WNW 0

0 0

0 0

0 0

NW 0

0 0

0 0

0 0

NKW 0

0 0

0 0

0 0

VARIABLE O

O O

O O

O 0

Total 0

3 0

0 0

0 3

Periods of calm (hours):

0 Hours of missing data:

0 i

69 I_ -

J

TABLE 4A-1BQ1 CUMULATIVE JOINT FREQUENCY DISTRIBUTION Farley Unit 1 - 1st Quarter, 1985 HOURS AT EACH WIND SPEED AND DIRECTION RELEASE MODE: BATCH PERIOD OF RECORD:

1 85 3-31-85 STABILITY CLASS: F ELEVATION:45.7m Wind Speed (mph) at 45.7m level Wind Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

O O

O O

O O

O NNE O

O O

O O

O O

NE O

O O

O O

O O

ENE O

O O

O O

O O

E O

O O

O O

O O

ESE O

O O

O O

O O

SE O

O O

O O

O O

SSE O

O O

O O

O O

S 0

0 0

0 0

0 0

SSW 0

0 0

0 0

0 0

SW 0

0 0

0 0

0 0

WSW 0

0 0

0 0

0 0

W 0

0 0

0 0

0 0

WNW 0

0 0

0 0

0 0

NW 0

0 0

0 0

0 0

NNW,

0 0

0 0

0 0

0 VARIABLE O

O O

O O

O O

Total 0

0 0

0 0

0 0

Periods of calm (hours):

0 Hours of missing data:

0 70

2-e W

h TABLE 4A-1BQ1 CUMULATIVE JOINT FREQUENCY DISTRIBUTION Farley Unit 1 - 1st Quarter, 1985 HOURS AT EACH WIND SPEED AND DIRECTION RELEASE MODE: BATCH PERIOD OF RECORD:

1 85 3-31-85 STABILITY CLASS: F ELEVATION:10.0m

--====-------

Wind Speed (mph) at 10.0m level Wind Direction 1-3 4-7 8-12 13-18 19-24

> 24 TOTAL N

O O

O O

O O

O NNE O

O O

0 0

0 0

NE O

O O

O O

O O

ENE O

O O

O O

O O

E O

O O

O O

O O

ESE O

O O

O O

O O

SE O

O O

O O

O O

SSE O

O O

O 0

0 0

S 0

0 0

0 0

0 0

SSW 0

0 0

0 0

0 0

SW 0

0 0

0 0

0 0

WSW 0

0 0

0 0

0 0

W 0

0 0

0 0

0 0

WNW 0

0 0

0 0

0 0

NW 0

0 0

0 0

0 0

NNW 0

0 0

0 0

0 0

VARIABLE O

O O

O O

O O

Tota'l 0

0 0

0 0

0 0

i Periods of calm (hours):

0 Hours of missing data:

0 l

71

TABLE 4A-1BQ1 CUMULATIVE JOINT FREQUENCY DISTRIBUTION Farley Unit 1-1st Quarter, 1985 HOURS AT EACH WIND SPEED AND DIRECTION RELEASE MODE: BATCH PERIOD OF RECORD:

1 85 3-31-85 STABILITY CLASS: G ELEVATION:45.7m Wind Speed (mph) at 45.7m level Wind Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

O O

O O

O O

0 NNE O

O O

O O

O O

NE O

O O

O O

O O

ENE O

O O

0 0

0 0

E O

O O

O O

O O

ESE O

O O

O O

O O

SE O

O O

O 0

0 0

SSE O

O O

O O

O O

S 0

0 0

0 0

0 0

SSW 0

0 0

0 0

0 0

SW 0

0 0

0 0

0 0

WSW O

O O

O O

0 0

W 0

0 0

0 0

0 0

WNW 0

0 0

0 0

0 0

NW 0

0 0

0 O

O O

illRf 0

0 0

0 0

0 0

VARIABLE O

O O

O O

0 0

Total 0

0 0

0 0

0 0

Periods of calm (hours):

0 Hours of' missing data:

0 72

.-=.u.

~

~

TABLE 4A-1BQ1 CUMULATIVE JOINT FREQUENCY DISTRIBUTION Farley Unit 1 1st Quarter, 1985 HOURS AT EACH WIND SPEED AND DIRECTION RELEASE MODE: BATCH PERIOD OF RECORD:

1 85 3-31-85 STABILITY CLASS: G ELEVATION 10.0m


==__

==-----=____=-----------------------------------=_

Wind Speed (mph) at 10.0m level Wind Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

O O

O O

O O

O NNE O

O O

O O

O O

NE O

O O

0 0

0 0

4 ENE O

O O

O O

O O

E O

O O

O O

O O

ESE O

O O

O O

O O

SE O

O O

O O

O O

SSE O

O O

O 0

0 0

S 0

0 0

0 0

0 0

SSW 2

0 0

0 0

0 0

SW 0

0 0

0 0

0 0

WSW 0

0 0

0 0

0 0

W 0

0 0

0 0

0 0

WNW 0

0 0

0 0

0 0

MW 0

0 0

0 0

0 0

NNW 0

0 0

0 0

0 0

VARIABLE O

O O

O O

O 0

Total 0

0 0

'O O

O O

Periods of calm (hours):

0 Hours of missing data:

0 73

. - - - ~,... _ _

TABLE 4A-1BQ2 CUMULATIVE JOINT FREQUENCY DISTRIBUTf0N Farley Unit 1 - 2nd Quarter, 1985 HOURS AT EACH WIND SPEED AND DIRECTION RELEASE MODE: BATCH PERIOD OF RECORD:

4 85 6-30-85 STABILITY CLASS: A ELEVATION:45.7m Wind Speed (mph) at 45.7m level Wind Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

0 1

0 0

0 0

1 NNE O

1 1

0 0

0 2

NE 1

0 0

0 0

0 1

ENE 2

1 2

0 0

0 5

E 2

1 1

0 0

0 4

ESE O

5 0

0 0

0 5

SE 2

4 4

0 0

0 10 SSE O

2 0

0 0

0 2

S 1

0 1

0 0

0 2

SSW 0

0 1

0 0

0 1

SW 0

0 0

0 0

0 0

WSW 0

2 1

0 0

0 3

W 0

2 0

0 0

0 2

WNW 0

0 1

0 0

0 1

NW 0

0 0

1 0

0 1

NKW 0

1 0

0 0

0 1

VARIABLE O

O O

O O

O O

Total 8

20 12 1

0 0

41 Periods of calm (hours):

0 Hours of missing data:

0 74

TABLE 4A-1BQ2 CUMULATIVE JOINT FREQUENCY DISTRIBUTION Farley Unit 1 - 2nd Quarter, 1985 HOURS AT EACH WIND SPEED AND DIRECTION RELEASE MODE: BATCH PERIOD OF RECORD:

4 85 6-30-85 STABILITY CLASS: A ELEVATION:10.0m

- - = - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

Wind Speed (mph) at 10.0m level Wind Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL

=

N 1

0 0

0 0

0 1

NNE 1

1 0

0 0

0 2

NE O

2 0

0 0

0 2

ENE 2

2 0

0 0

0 4

E 2

2 0

0 0

0 4

ESE 1

7 0

0 0

0 8

SE 2

6 0

0 0

0 8

SSE O

1 0

0 1

0 2

S 0

0 0

1 0

0 1

SSW 0

0 0

0 1

0 1

SW 0

0 3

0 0

0 3

WSW 0

0 0

0 0

0 0

W 0

0 2

0 0

0 2

WNW 0

0 0

0 0

0 0

NW 0

0 0

1 0

0 1

NNW 0

2 0

0 0

0 2

VARIABLE O

O O

O O

O O

Total 9

23 5

2 2

0 41 Periods of calm (hours):

0 Hours of missing data:

0 75 t

b

TABLE 4A-1BQ2 CUMULATIVE JOINT FREQUENCY DISTRIBUTION Farley Unit 1 - 2nd Quarter, 1985 HOURS AT EACH WIND SPEED AND DIRECTION RELEASE MODE: BATCH PERIOD OF RECORD:

4 85 6-30-85 STABILITY CLASS: B ELEVATION:45.7m Wind Speed (mph) at 45.7m level Wind Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

O 1

0 0

0 0

1 NNE O

O O

O O

O O

NE 1

0 0

0 0

0 1

ENE O

O O

O O

O O

E 5

0 0

0 0

0 5

ESE O

3 1

0 0

0 4

SE 2

0 2

0 0

0 4

SSE O

3 0

0 0

0 3

S 0

0 0

0 0

0 0

SSW 0

0 0

0 0

0 0

SW 0

0 0

0 0

0 0

WSW 0

0 0

0 0

0 0

W 0

0 0

0 0

0 0

WNW 0

0 0

0 0

0 0

NW 0

1 0

1 0

0 2

NNW 0

0 0

0 0

0 0

VARIABLE O

O O

O O

O O

Total 8

8 3

1 0

0 20 Periods of calm (hours):

0 Hours of missing data:

0 f

76 t

TABLE 4A-1BQ2 CUMULATIVE JOINT FREQUENCY DISTRIBUTION Farley Unit 1 - 2nd Quarter, 1985 HOURS AT EACH WIND SPEED AND DIRECTION RELEASE MODE: BATCH PERIOD OF RECORD:

4 85 6-30-85 STABILITY CLASS: B ELEVATION:10.0m Wind Speed (mph) at 10.0m level Wind Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

O 1

0 0

0 0

1 NNE O

O O

O O

O O

NE O

1 0

0 0

0 1

ENE O

1 0

0 0

0 1

E 4

0 0

0 0

0 4

ESE 1

4 0

0 0

0 5

SE 2

2 0

0 0

0 4

SSE O

2 0

0 0

0 2

S 0

0 0

0 0

0 0

SSW 0

0 0

0 0

0 0

SW 0

0 0

0 0

0 0

WSW 0

0 0

0 0

0 0

W 0

0 0

0 0

0 0

WNW 0

1 1

0 0

0 2

NW 0

0 0

0 0

0 0

NNW 0

0 0

0 0

0 0

VARIABLE O

O O

O O

O O

Total 7

12 1

0 0

0 20 Periods of calm (hours):

0 Hours of missing data:

0 l

77 t

TABLE 4A-1BQ2 CUMULATIVE JOINT FREQUENCY DISTRIBUTION Farley Unit 1 - 2nd Quarter, 1985 HOURS AT EACH WIND SPEED AND DIRECTION RELEASE MODE: BATCH PERIOD OF RECORD:

4 85 6-30-85 STABILITY CLASS: C ELEVATION:45.7m Wind Speed (mph) at 45.7m level Wind Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

O O

O O

O O

O NNE O

O O

O O

O O

NE O

O O

O O

O O

l ENE O

2 0

0 0

0 2

E 2

2 0

0 0

0 4

ESE O

O O

O O

O O

SE O

2 1

0 0

0-3 SSE O

1 0

0 0

0 1

S 0

0 0

0 0

0 0

SSW 0

0 0

0 0

0 0

SW 0

0 0

0 0

0 0

WSW 0

1 0

0 0

0 1

W 0

0 0

0 0

0 0

WNW 0

0 0

0 0

0 0

NW 0

0 0

1 0

0 1

NNW 0

0 0

0 0

0 0

VARIABLE O

O O

O O

O O

Total 2

8 1

1 0

0 12 Periods of calm (hours):

0 Hours of missing data:

0 1

78 L-

)

TABLE 4A-1BQ2 CUMULATIVE JOINT FREQUENCY DISTRIBUTION Farley Unit 1 - 2nd Quarter, 1985 l

HOURS AT EACH WIND SPEED AND DIRECTION RELEASE MODE: BATCH PERIOD OF RECORD:

4 85 6-30-85 STABILITY CLASS: C ELEVATION:10.0m t

Wind speed (mph) at 10.0m level Wind Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

O O

O O

O O

0 NNE O

O O

O O

O O

NE O

O O

O O

O O

'ENE 1

3 0

0 0

0 4

1 E

2 0

0 0

0 0

2 i

ESE 0

0 0

0 0

0 0

1 l

SE O

3 1

0 0

0 4

SSE O

O O

O O

O O

4 S

0 0

0 0

0 0

0 SSW 0

0 0

0 0

0 0

i SW 0

0 0

0 0

0 0

i j

WSW 0

0 1

0 0

0 1

W 0

0 0

0 0

0 0

WNW 0

0 0

0 0

0 0

MW 0

0 1

0 0

0 1

l NNW 0

0 0

0 0

0 0

VARIABLE O

O O

0 0

0 0

Total 3

6 3

0 0-0 12 i

Periods of calm (hours):

0 Hours of missing data:

0 79 L

TABLE 4A-1BQ2 CUMULATIVE JOINT FREQUENCY DISTRIBUTION Farley Unit 1 - 2nd Quarter, 1985 HOURS AT EACH WIND SPEED AND DIRECTION RELEASE MODE: BATCH PERIOD OF RECORD:

4 85 6-30-85 STABILITY CLASS: D ELEVATION:45.7m Wind Speed (mph) at 45.7m level Wind Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

0 O

O O

O O

O NNE O

O O

O O

O O

NE' 3

0 0

0 0

0 3

ENE 2

0 0

0 0

0 2

E O

1 0

0 0

0 1

ESE O

1 0

0 0

0 1

SE O

O O

O O

O O

SSE O

1 0

0 0

0 1

S 0

0 0

0 0

0 0

SSW 0

0 0

0 0

0 0

SW 0

0 1

0 0

0 1

WSW 0

3 1

0 0

0 4

W 0

1 0

0 0

0 1

WNW 0

0 0

0 0

0 0

NW 0

0 2

1 0

0 3

NNW 0

0 0

0 0

0 0

VARIABLE O

O O

O 0

0 0

Total 5

7 4

1 0

0 17 Periods of calm (hours):

0 Hours of missing data:

0 80-m

- ~, - -

r-1 TABLE 4A-1BQ2 CUMULATIVE JOINT FREQUENCY DISTRIBUTION Farley Unit 1 - 2nd Quarter, 1985 HOURS AT EACH WIND SPEED AND DIRECTION RELEASE MODE: BATCH PERIOD OF RECORD:

4 85 6-30-85 STABILITY CLASS: D ELEVATION:10.0m


__----__=-

Wir.d Speed (mph) at 10.0m level Wind Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

O O

O O

O O

O NNE 1

0 0

0 0

0 1

NE 1

0 0

0 0

0 1

ENE 2

0 0

0 0

0 2

E 2

0 0

0 0

0 2

ESE 1

0 0

0 0

0 1

SE 1

0 0

0 0

0 1

SSE O

O 0

0 0

0 0

S 0

0 0

0 0

0 0

SSW 0

0 0

0 0

0 0

SW 0

0 4

1 0

0 5

WSW 0

1 0

0 0

0 1

W 0

0 0

0 0

0 0

WNW 0

0 0

0 0

0 0

NW 0

2 1

0 0

0 3

NNW 0

0 0

0 0

0 0

VARIABLE O

0 0

0 0

0 0

Total 8

3 5

1 0

0 17 Periods of calm (hours):

0 Hours of missing data:

0 l

81 E

- m u.-

..m m

TABLE 4A-1BQ2 CUMULATIVE JOINT FREQUENCY DISTRIBUTION Farley Unit 1 - 2nd Quarter, 1985 HOURS AT EACH WIND SPEED AND DIRECTION RELEASE MODE: BATCH PERIOD OF RECORD:

4 85 6-30-85 STABILITY CLASS: E ELEVATION:45.7m Wind Speed (mph) at 45.7m level Wind Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

O O

O O

O O

O NNE O

O O

O O

O O

NE 1

0 0

0 0

0 1

ENE O

O O

O O

O O

E O

4 2

0 0

0 6

ESE 1

2 1

0 0

0 4

SE O

O 4

1 0

0 5

SSE 0

0 0

0 0

0 0

5 0

0 0

0 0

0 0

SSW 0

0 0

0 0

0 0

SW 0

0 0

0 0

0 0

WSW 0

1 3

2 0

0 6

W 0

2 2

0 0

0 4

WNW 0

0 2

0 0

0 2

NW 0

0 4

0 0

0 4

NNW 0

0 2

0 0

0 2

VARIABLE O

O O

O O

O O

Total 2

9 20 3

0 0

34 i

Periods of calm (hours):

0 Hours of missing data:

0 82 L

7 TABLE 4A-1BQ2 CUMULATIVE JOINT FREQUENCY DISTRIBUTION Farley Unit 1 - 2nd Quarter, 1985 HOURS AT EACH WIND SPEED AND DIRECTION RELEASE MODE: BATCH PERIOD OF RECORD:

4 85 6-30-85 STABILITY CLASS: E ELEVATION:10.0m Wind Speed (mph) at 10.0m level Wind Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

3 0

0 0

0 0

3 NNE O

O O

O O

O O

NE O

C 0

0 0

0 0

ENE 3

2 0

0 0

0 5

E 2

0 0

0 0

0 2

ESE 3

3 0

0 0

0 6

SE O

O O

O O

0 0

SSE O

O O

O O

O O

S 0

0 0

0 0

0 0

SSW 0

0 0

0 0

0 0

SW 1

3 1

0 0

0 5

WSW 0

4 1

0 0

0 5

W 0

0 0

0 0

0 0

WNW 0

2 1

0 0

0 3

NW 0

5 0

0 0

0 5

NNW 0

0 0

0 0

0 0

VARIABLE O

O O

O O

O 0

Total 12 19 3

0 0

0 34 Periods of calm (hours):

0 Hours of missing data:

0 t

83

\\.

j

r i.

TABLE 4A-1BQ2 CUMULATIVE JOINT FREQUENCY DISTRIBUTION Farley Unit 1 - 2nd Quarter, 1985 HOURS AT EACH WIND SPEED AND DIRECTION RELEASE MODE: BATCH PERIOD OF RECORD:

4 85 6-30-85 STABILITY CLASS: F ELEVATION:45.7m Wind Speed (mph) at 45.7m level Wind Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

O O

2 0

0 0

2 NNE O

O O

O O

O O

NE 0

0 0

0 0

0 0

ENE 2

1 0

0 0

0 3

E 2

2 2

0 0

0 6

ESE 2

2 0

0 0

0 4

SE 2

2 2

0 0

0 6

SSE O

2 1

0 0

0 3

S 2

0 0

0 0

0 2

SSW 0

0 0

0 0

0 0

SW 0

0 0

0 0

0' O

WSW 0

0 1

0 0

0 1

W 0

1 0

0 0

0 i

WNW 0

0 0

0 0

0 0

NW 0

0 1

0 0

0 1

NNW 0

0 0

0 0

0 0

VARIABLE O

O 0

0 0

0 0

Total 10 10 9

0 0

0 29 Periods of calm (hours):

0 l

Hours of missing data:

0 l

84

-- ms -

7 TABLE 4A-1BQ2 CUMULATIVE JOINT FREQUENCY DISTRIBUTION Farley Unit 1 - 2nd Quarter, 1985 HOURS AT EACH WIND SPEED AND DIRECTION RELEASE MODE: BATCH PERIOD OF RECORD:

4 85 6-30-85 STABILITY CLASS: F ELEVATION:10.0m Wind Speed (mph) at 10.0m level Wind Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

3 0

0 0

0 0

3 NNE 4

0 0

0 0

0 4

NE 5

0 0

0 0

0 5

ENE 1

0 0

0 0

0 1

E 2

0 0

0 0

0 2

ESE 5

0 0

0 0

0 5

SE 1

1 0

0 0

0 2

SSE 2

0 0

0 0

0 2

S 0

0 0

0 0

0 0

SSW 0

0 0

0 0

0 0

SW 0

1 0

0 0

0 1

WSW 0

0 0

0 0

0 0

W 1

0 0

0 0

0 1

WNW 0

0 0

0 0

0 0

NW 1

1 0

0 0

0 2

NNW 1

0 0

0 0

0 i

VARIABLE O

O O

O O

O O

Total 26 3

0 0

0 0

29 Periods of calm (hours):

0 Hours of. missing data:

0 85

24 TOTAL N

O O

O O

O O

O NNE O

O O

O O

O O

NE 2

1 0

0 0

0 3

ENE O

2 ~

1 0

0 0

3 E

O 2

1 0

0 0

3 ESE 5

0 0

0 0

5 SE 4

3 0

0 0

0 7

SSE 0

0 0

0 0

0 0

S 0

0 0

0 0

0 0

SSW 0

0 0

0 0

0 0

SW 0

0 0

j 0

0 0

0 WSW 0

0 0

0 0

0 0

i i

W 0

0 0

0 0

0 0

WNW 0

0 0

0 0

0 0

1 NW 0

0 0

0 0

0 0

NNW 0

0 0

0 0

0 0

VARIABLE O

O O

O O

O O

l

_ _ _ - _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ - _ - - _ - _ _ - - _ _ _ _ _ _ _ _ - _ _ _ - - - _ - - _ - _ _ _ i Total 6

13 2

0 0

0 21 Periods of calm (hours):

0

]

Hours of missing data:

0 I

86

TABLE 4A-1BQ2 CUMULATIVE JOINT FREQUENCY DISTRIBUTION Farley Unit 1 - 2nd Quarter, 1985 HOURS AT EACH WIND SPEED AND DIRECTION RELEASE MODE: BATCH PERIOD OF RECORD:

4 85 6-30-85 STABILITY CLASS: G ELEVATION:10.0m Wind Speed (mph) at 10.0m level Wind Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL J

N 5

0 0

0 0

0 5

NNE 6

0 0

0 0

0 6

NE 5

0 0

0 0

0 5

ENE 1

0 0

0 0

0 1

E O

O O

O O

O O

ESE O

O O

O O

O O

SE 1

0 0

0 0

0 1

SSE 0

0 0

0 0

0 0

S 0

0 0

0 0

0 0

SSW 0

0 0

0 0

0 0

SW 0

0 0

0 0

0 0

WSW 0

0 0

0 0

0 0

W 0

0 0

0 0

0 0

WNW 0

1 0

0 0

0 1

NW 1

0 0

0 0

0 1

NNW 1

0 0

0 0

0 i

VARIABLE O

O O

O O

O O

Total 20 1

0 0

0 0

21 Periods of calm (hours):

0 Hours of missing data:

0 87 u

TABLE 4A-2BQ1 CUMULATIVE JOINT FREQUENCY DISTRIBUTkON Farley Unit 2-1st Quarter, 1985 HOURS AT EACH WIND SPEED AND DIRECTION RELEASE MODE: BATCH PERIOD OF RECORD:

1 85 3-31-85 STABILITY CLASS: A ELEVATION:45.7m Wind Speed Wind (mph) at 45.7m level Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

O O

1 0

0 0

1 NNE O

O O

3 0

0 3

NE O

O O

O O

O O

ENE O

O O

O O

O O

E O

O O

O O

O O

ESE O

2 0

0 0

0 2

SE O

1 2

0 0

0 3

SSE O

O O

O O

O O

S 0

0 0

0 0

0 0

SSW 0

0 0

0 0

0 0

SW 0

0 0

0 0

0 0

WSW 0

0 0

0 0

0 0

W 0

0 1

0 0

0 1

WNW 0

0 0

0 0

0 0

NW 0

0 0

0 0

0 0

NNW 0

0 0

0 0

0 0

VARIABLE O

O O

O O

O O

Total 0

3 4

3 0

0 10 Periods of calm (hours):

0 Hours of missing data:

0 88

TABLE 4A-2BQ1 CUMULATIVE JOINT FREQUENCY DISTRIBUTION Farley Unit 2-1st Quarter, 1985 HOURS AT EACH WIND SPEED AND DIRECTION RELEASE MODE: BATCH PERIOD OF RECORD:

1 85 3-31-85 STABILITY CLASS: A ELEVATION:10.0m

=

Wind Speed (mph) at 10.0m level Wind Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

O O

3 0

0 0

3 NNE O

O 1

0 0

0 1

NE O

O O

O O

O O

ENE O

O O

O O

O O

E O

2 0

0 0

0 2

ESE O

1 1

0 0

0 2

SE 1

0 0

0 0

0 1

SSE O

O O

O O

0 0

S 0

0 0

0 0

0 0

SSW 0

0 0

0 0

0 0

SW 0

0 0

0 0

0 0

WSW 0

1 0

0 0

0 1

W 0

0 0

0 0

0 0

WWW 0

0 0

0 0

0 0

MW 0

0 0

0 0

0 0

NNW 0

0 0

0 0

0 0

VARIABLE O

O O

O O

O O

Total 1

4 5

0 0

0 10 Periods of calm (hours):

0 Hours of missing data:

0 89 L

3 TABLE 4A-2B91 i

CUMULATIVE JOINT FREQUENCY DISTRIBUTION Farley Unit 2 - 1st Quarter, 1985 HOURS AT EACH WIND SPEED AND DIRECTION RELEASE MODE: BATCH PERIOD OF RECORD:

1 85 3-31-85 STABILITY CLASS: B ELEVATION:45.7m

--==


==____-----------------

Wind Speed (mph) at 45.7m level Wind Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

0 0

0 0

0 0

0 NME O

O O

O O

'O O

NE O

O O

O O

O O

ENE O

O O

O O

O O

E O

O O

O O

O O

ESE O

0 0

0 0

0 0

SE O

O 2

0 0

0 2

SSE O

O O

O O

O O

S 0

0 0

0 0

0 0

SSW 0

0 0

0 0

0 0

SW 0

0 0

0 0

0 0

WSW 0

0 0

0 0

0 0

W 0

0 2

0 0

0 2

WNW 0

0 2

0 0

0 2

NW 0

1 3

0 0

0 4

NNW 0

0 0

0 0

0 0

VARIABLE O

O O

0 0

0 0

Total 0

1 9

0 0

0 10 Periods of calm (hours):

0 Hours of missing data:

0 90 L.

TABLE 4A-2BQ1 CUMULATIVE JOINT FREQUENCY DISTRIBUTION Farley Unit 2-1st Quarter, 1985 i

HOURS AT EACH WIND SPEED AND DIRECTION RELEASE MODE: BATCH PERIOD OF RECORD:

1 85 3-31-85 STABILITY CLASS: B ELEVATION:10.0m Wind Speed (mph) at 10.0m level Wind Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

O O

O O

O O

O NNE O

O O

O O

O O

NE O

O O

O O

O O

ENE O

O O

O O

O O

E O

O O

O O

O O

ESE O

O O

O O

O O

SE O

1 1

0 0

0 2

SSE O

O O

O O

O O

S 0

0 0

0 0

0 0

SSW 0

0 0

0 0

0 0

SW 0

0 0

0 0

0 0

WSW 0

0 1

0 0

0 1

W 0

2 0

0 0

0 2

WNW 0

3 1

0 0

0 4

NW 0

0 1

0 0

0 1

NNW 0

0 0

0 0

0 0

VARIABLE O

O O

O O

O O

Total 0

6 4

0 0

0 10 Periods of calm (hours):

0 Hours of missing data:

0 91 L

l

TABLE 4A-2BQ1 CUMULATIVE JOINT FREQUENCY DISTRIBUTION Farley Unit 2 - 1st Quarter, 1985 HOURS AT EACH WIND SPEED AND DIRECTION RELEASE MODE: BATCH PERIOD OF RECORD:

1 85 3-31-85 STABILITY CLASS: C ELEVATION:45.7m Wind speed (mph) at 45.7m level Wind Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

O O

1 0

0 0

1 NNE O

O O

O O

O O

NE O

O O

O O

O O

ENE O

O O

O O

O O

E O

O O

O O

O O

ESE O

O O

O O

O O

SE 0

0 0

0 0

0 0

SSE O

O O

O O

O O

S 1

0 0

0 0

0 1

SSW 0

0 0

0 0

0 0

SW 0

0 0

0 0

0 0

WSW 0

0 2

0 0

0 2

W 0

0 2

0 0

0 2

WNW 0

1 0

0 0

0 1

NW 0

0 0

0 0

0 0

NNW 0

0 0

0 0

0 0

VARIABLE O

O O

O O

0 0

Total 1

1 5

0 0

0-7 Periods of calm (hours):

0 Hours of missing data:

0 92

TABLE 4A-2BQ1 j

i CUMULATIVE JOINT FREQUENCY DISTRIBUTION i

i Farley Unit 2 - 1st Quarter, 1985 HOURS AT EACH WIND SPEUD AND DIRECTION RELEASE MODE: BATCH PERIOD OF RECORD; 1 85 3-31-85 STABILITY CLASS: C ELEVATION:10.0m

==_____________________________________

Wind Speed (mph) at 10.0m level Wind Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

O O

0 0

0 0

0 HNE O

0 0

0 0

0 0

NE O

O O

O O

O O

ENE 0

0 0

0 0

0 0

E O

O O

O O

O O

ESE O

O O

O O

O O

SE 1

0 0

0 0

0 1

SSE O

O O

O O

O O

S 0

0 0

0 0

0 0

SSW 0

0 0

0 0

0 0

SW 0

0 1

0 0

0 1

WSW 0

2 1

0 0

0 3

W 0

1 0

0 0

0 1

WNW 0

0 0

0 0

0 0

NW 0

0 0

0 0

0 0

NNW 0

1 0

0 0

0 1

VARIABLE O

O 0

0 0

0 0

Total 1

4 2

0 0

0 7

Periods of calm (hours):

0 Hours of' missing data:

0 93

TABLE 4A-2BQ1 CUMULATIVE JOINT FREQUENCY DISTRIBUTION Farley Unit 2-1st Quarter, 1985 HOURS AT EACH WIND SPEED AND DIRECTION RELEASE MODE: BATCH PERIOD OF RECORD:

1 85 3-31-85 STABILITY CLASS: D ELEVATION:45.7m

_ _ _ _ - - _ _ _ _ _ - - - - = = - - - -

Wind speed (mph) at 45.7m level Wind Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

0 O

4 2

0 0

6 NNE O

O O

O O

O O

NE O

O O

O O

O O

ENE O

O 0

0 0

0 0

E O

O O

O O

O O

ESE O

O 1

0 0

0 1

SE O

2 0

0 0

0 2

SSE O

O O

O O

O O

S 0

0 0

0 0

0 0

SSW 0

0 0

0 0

0 0

SW 0

0 0

0 0

0 0

l WSW 0

1 0

0 0

0 1

I W

1 1

0 0

0 0

2 WNW 3

0 2

0 0

0 5

NW 0

0 6

1 0

0 7

NNW 0

0 1

3 0

0 4

VARIABLE O

O O

O 0

0 0

Total 4

4 14 6

0 0

28 Periods of calm (hours):

0 Hours of missing data:

0 94 i

1 TABLE 4A-2BQ1 CUMULATIVE JOINT FREQUENCY DISTRIBUTION Farley Unit 2 - 1st Quarter, 1985 HOURS AT EACH WIND SPEED AND DIRECTION RELEASE MODE: BATCH PERIOD OF RECORD:

1 85 3-31-85 STABILITY CLASS: D ELEVATION:10.0m Wind Speed (mph) at 10.0m level Wind Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

O O

O O

O O

O NNE O

O O

O O

O O

NE O

O O

O O

O O

ENE O

O O

O O

O O

E 1

0 0

0 0

0 1

ESE O

O O

O O

O O

SE O

2 0

0 0

0 2

SSE O

O O

O O

O O

S 0

0 0

0 0

0 0

SSW 0

0 0

0 0

0 0

SW 1

0 0

0 0

0 1

WSW 0

1 0

0 0

0 1

W 2

1 0

0

'O O

3 WWW 2

1 4

0 0

0 7

NW 0

3 0

0 0

0 3

NNW 0

3 6

1 0

0 10 VARIABLE O

O O

O O

O O

Total 6

11 10 1

0 0

28 Periods of calm (hours):

0 Hours of missing data:

0 95

TABLE 4A-2BQ1 CUMULATIVE JOINT FREQUENCY DISTRIBUTION Farley Unit 2 - 1st Quarter, 1985 HOURS AT EACH WIND SPEED AND DIRECTION RELEASE MODE: BATCH PERIOD OF RECORD:

1 85 3-31-85 STABILITY CLASS: E ELEVATION:45.7m Wind Speed (mph) at 45.7m level Wind Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

O O

O O

O O

O NNE O

0 0

0 0

0 0

NE O

O O

O O

O O

ENE O

O O

O O

O O

E O

O O

O O

O O

ESE 0

0 0

0 0

0 0

SE O

1 0

0 0

0 1

SSE 0

0 0

0 0

0 0

S 0

0 0

0 0

0 0

SSW 0

0 0

0 0

0 0

SW 0

0 0

0 0

0 0

WSW 0

1 1

0 0

0 2

W 0

1 0

1 0

0 2

WNW 0

0 0

0 0

0 0

NW 0

3 5

0 0

0 8

NNW 0

0 0

0 0

0 3

VARIABLE O

O O

O O

O O

Total 0

6 6

1 0

0 13 Periods of calm (hours):

0 Hours of missing data:

0 96 h4 ume

,J-4-

TABLE 4A-2BQ1 CUMULATIVE JOINT FREQUENCY DISTRIBUTION Farley Unit 2 - 1st Quarter, 1985 HOURS AT EACH WIND SPEED AND DIRECTION RELEASE MODE: BATCH PERIOD OF RECORD:

1 85 3-31-85 STABILITY CLASS: E ELEVATION:10.0m Wind Speed (mph) at 10.0m level Wind Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

0 0

0 0

0 0

0 NNE O

O O

O O

O O

NE O

O O

O O

O O

ENE O

O O

O O

O O

E O

O O

O O

O O

ESE O

1 0

0 0

0 1

SE O

0 0

0 0

0 0

SSE O

O O

O O

O O

S 0

0 0

0 0

0 0

SSW 1

0 0

0 0

0 1

SW 0

0 0

0 0

0 0

WSW 2

2 0

0 0

0 4

W 1

0 0

0 0

0 1

1 WNW 1

2 0

0 0

0 3

NW 1

2 0

0 0

0 3

NNW 0

0 0

0 0

0 0

VARIABLE 0

0 0

0 0

0 0

Total 6

7 0

0 0

0 13 Periods of calm (hours):

0 Hours of missing data:

0 97

TABLE 4A-2BQ1 CUMULATIVE JOINT FREQUENCY DISTRIBUTION Farley Unit 2-1st Quarter, 1985 HOURS AT EACH WIND SPEED AND DIRECTION RELEASE MODE: BATCH PERIOD OF RECORD:

1 85 3-31-85 STABILITY CLASS: F ELEVATION:45.7m Wind Speed (mph) at 45.7m level Wind Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

O O

O O

O O

O NNE O

O O

O O

O O

NE O

O O

O O

O O

ENE O

O O

O O

O O

E 0

0 0

0 0

0 0

ESE O

O O

O O

O O

SE 0

0 1

0 0

0 1

SSE O

O O

O O

O O

S 0

0 0

0 0

0 0

SSW 0

1 0

0 0

0 1

SW 0

0 1

1 0

0 2

WSW 0

0 1

0 0

0 1

W L

0 0

0 0

0 i

WNW 0

0 0

0 0

0 0

NW 0

0 0

0 0

0 0

NNW L

i 1

0 0

0 3

VARIABLE O

O O

0 0

0 0

Total 2

2 4

1 0

0 9

Periods of calm (hours):

0 Hours of missing datat 0

I 98

TABLE 4A-2BQ1 CUMULATIVE JOINT FREQUENCY DISTRIBUTION Farley Unit 2-1st Quarter, 1985 HOURS AT EACH WIND SPEED AND DIRECTION RELEASE MODE: BATCH PERIOD OF RECORD:

1 85 3-31-85 STABILITY CLASS: F ELEVATION:10.0m Wind speed (mph) at 10.0m level Wind Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

O O

O O

O O

O NNE 2

0 0

0 0

0 2

NE 0

0 0

0 0

0 0

ENE O

O O

O O

O O

E O

O O

O O

O O

ESE 1

0 0

0 0

0 1

SE O

O O

O O

O O

SSE O

O O

O O

O O

S 0

0 0

0 0

0 0

SSW 0

0 0

0 0

0 O

SW 0

2 0

0 0

0 2

WSW 2

0 0

0 0

0 2

W 0

0 0

0 0

0 0

WNW 0

0 0

0 0

0 0

NW 1

1 0

0 0

0 2

NNW 0

0 0

0 0

0 0

VARIABLE O

O O

0 0

0 0

Total 6

3 0

0 0

0 9

Periods of calm (hours):

0 l

Hours of missing datas 0

99

TABLE 4A-2BQ1' CUMULATIVE JOINT FREQUENCY DISTRIBUTION Farley Unit 2-1st Quarter, 1985 HOURS AT EACH WINP, SPEED AND DIRECTION RELEASE MODE: BATCH PERIOD OF RECORD:

1 85 3-31-85 STABILITY CLASS: G ELEVATION:45.7m Wind Speed (mph) at 45.7m level Wind Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

1 2

1 0

0 0

4 NNE O

1 0

0 0

0 1

NE O

O O

O O

O O

ENE O

O O

O 0

0 0

E O

O 3

0 0

0 3

ESE O

O O

O O

O O

SE O

O 1

0 0

0 1

SSE O

O O

O O

O O

S 0

0 0

0 0

0 0

SSW 0

0 0

0 0

0 0

SW 0

0 0

0 0

0 0

WSW 0

0 0

0 0

0 0

W 0

0 0

0 0

0 0

WNW 0

0 0

0 0

0 0

NW 0

0 0

0 0

0 0

NNW 0

2 0

0 0

0 2

VARIABLE O

O O

O O

O O

I Total 1

5 5

0 0

0 11 Periods of calm (hours):

0 Hours of missing datas 0

100 J

TABLE 4A-2BQ1 CUMULATIVE JOINT FR?QUENCY DISTRIBUTION Farley Unit 2 - 1st Quarter, 1985 HOURS AT EACH WIND SPEED AND DIRECTION RELEASE MODE: BATCH PERIOD OF RECORD:

1 85 3-31-85 STABILITY CLASS: G ELEVATION:10.0m Wind Speed (mph) at 10.0m level Wind

' Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

3 0

0 0

0 0

3 NNE 2

1 0

0 0

0 3

NE O

0 0

0 0

0 0

ENE 1

0 0

0 0

0 1

E O

0 0

0 0

0 0

ESE O

O O

O O

O O

SE O

O O

O O

O O

SSE O

O O

O O

O O

S 0

0 0

0 0

0 0

SSW 0

0 0

0 0

0 0

SW 0

0 0

0 0

0 0

WSW 0

0 0

0 0

0 0

W 0

1 0

0 0

0 1

WNW 0

0 0

0 0

0 0

NW 1

0 0

0 0

0 1

NNW 2

0 0

0 0

0 2

VARIABLE O

0 0

0 0

0 0

Total 9

2 0

0 0

0 11 Periods of calm (hours):

0 Hours of missing datas 0

101

TABLE 4A-2BQ2 CUMULATIVE JOINT FREQUENCY DISTRIBUTION Farley Unit 2 - 2nd Quarter, 1985 HOURS AT EACH WIND SPEED AND DIRECTION RELEASE MODE: BATCH PERIOD OF RECORD:

4 85 6-30-85 STABILITY CLASS: A ELEVATION:45.7m Wind Speed (mph) at 45.7m level Wind Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

0 0

0 0

0 0

0 NNE O

O O

O O

O O

NE 0

0 0

0 0

0 0

ENE O

O O

O O

O O

E 0

0 0

0 0

0 0

ESE O

O O

O O

O O

SE O

O 0

0 0

0 0

SSE 0

0 0

0 0

0 0

S 0

0 0

0 0

0 0

SSW 0

0 0

0 0

0 0

SW 0

0 0

0 0

0 0

WSW 0

0 0

0 0

0 0

W 0

0 0

0 0

0 0

WWW 0

0 0

0 0

0 0

NW 0

0 1

1 0

0 2

NNW 0

0 0

0 0

0 0

VARIABLE O

O O

0 0

0 0

Total 0

0 1

1 0

0 2

Periods of calm (hours):

0 Hours of missing datas 0

102

TABLE 4A-2BQ2 CUMULATIVE JOINT FREQUENCY DISTRIBUTION Farley Unit 2 - 2nd Quarter, 1985 HOURS AT EACH WIND SPEED AND DIRECTION RELEASE MODE: BATCH PERIOD OF RECORD:

4 85 6-30-85 STABILITY CLASS: A ELEVATION:10.0m Wind Speed (mph) at 10.0m level Wind Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

0 v

0 0

0 0

0 NNE O

O O

O 0

0 0

NE O

0 0

0 0

0 0

ENE 0

0 0

0 0

0 0

E O

O O

0 0

0 0

ESE O

0 0

0 0

0 0

SE 0

0 0

0 0

0 0

SSE O

0 0

0 0

0 0

S 0

0 0

0 0

0 0

SSW 0

0 0

0 0

0 0

SW 0

0 0

0 0

0 0

WSW 0

0 0

0 0

0 0

W 0

0 0

0 0

0 0

WWW 0

0 0

0 0

0 0

NW 0

0 2

0 0

0 2

NNW 0

0 0

0 0

0 0

VARIABLE O

0 0

0 0

0 0

Total 0

0 2

0 0

0 2

Periods of calm (hours):

0 Hours of missing datas 0

5 103

=-..-. a _ ;..

~

TABLE 4A-2BQ2 CUMULATIVE JOINT FREQUENCY DISTRIBUTION Farley Unit 2 - 2nd Quarter, 1985 HOURS AT EACH WIND SPEED AND DIRECTION 4

RELEASE MODE: BATCH PERIOD OF RECORD:

4 85 6-30-85 STABILITY CLASS: B ELEVATION:45.7m Wind Speed (mph) at 45.7m level Wind Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

O O

O O

O O

O NNE O

0 0

0 0

0 0

NE O

O O

O O

O O

ENE O

O O

O 0,

0 0

E O

0 0

0 0

0 0

ESE O

O O

O 0

0 0

SE 0

0 0

0 0

0 0

SSE O

O O

O 0

0 0

S 0

0 0

0 0

0 0

SSW 0

0 0

0 0

0 0

SW 0

0 0

0 0

0 0

WSW 0

0 0

0 0

0 0

W 0

0 0

0 0

0 0

WWW 0

0 0

0 0

0 0

NW 0

0 0

0 0

0 0

NNW 0

0 0

0 0

0 0

VARIABLE O

0 0

0 0

0 0

Total 0

0 0

0 0

0 0

i Periods of calm (hours):

0 Hours of missing datas 0

104

..___._...-m.

,~. _-

TABLE 4A-2BQ2

' CUMULATIVE JOINT FREQUENCY DISTRIBUTkON Farley Unit 2 - 2nd Quarter, 1985 HOURS AT EACH WIND SPEED AND DIRECTION S

RELEASE MODE: BATCH 1

PERIOD OF RECORD:

4 85 6-30-85 i

i STABILITY CLASS: B ELEVATION:10.0m Wind Speed (mph) at 10.0m level 1

Wind Direction-1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

O O

0 0

0 0

0 NNE O

0 0

0 0

0 0

NE 0

0 0

0 0

O O

ENE O

0 0

0 0

0 0

E O

O O

O O

O O

1 ESE 0

0 0

0 0

0 0

4 SE O

O O

O O

O O

SSE 0

0 0

0 0

0 0

S 0

0 0

0 0

0 0

i~

SSW 0

0 0

0 0

0 0

i SW 0

0 0

0 0

0 0

i WSW 0

0 0

0 0

0 0

W 0

0 0

0 0

0 0

WNW 0

0 0

0 0

0 0

i NW 0

0 0

0 0

0 0

NNW 0

0 0

0 0

0 0

VARIABLE O

O 0

0 0

0 0

Total 0

0 0

0 0

0 0

Periods of calm (hours):

0 Hours of missing datas 0

105

TABLE 4A-2BQ2 CUMULATIVE JOINT FREQUENCY DISTRIBUTION Farley Unit 2 - 2nd Quarter, 1985 HOURS AT EACH WIND SPEED AND DIRECTION RELEASE MODE: BATCH PERIOD OF RECORD:

4 85 6-30-85 STABILITY CLASS: C ELEVATION:45.7m Wind Speed (mph) at 45.7m level Wind Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

0 0

0 0

0 0

0 NNE O

O O

O O

O O

NE O

O O

O O

0 0

ENE O

O O

O 0

0 0

E O

O O

O O

O O

ESE 0

0 0

0 0

0 0

SE O

O O

O 0

0 0

SSE O

O O

O O

O O

S 0

0 0

0 0

0 0

SSW 0

0 0

0 0

0 0

SW 0

0 0

0 0

0 0

WSW 0

0 0

0 0

0 0

W.

0 0

0 0

0 0

0 WNW 0

0 0

0 0

0 0

NW 0

0 1

0 0

0 1

NNW 0

0 0

0 0

0 0

VARIABLE O

O 0

0

'O O

O Total 0

0 1

0 0

0 1

Periods of calm (hours):

0 Hours of missing data:

0

}

106

TABLE 4A-2BQ2 CUMULATIVE JOINT FREQUENCY DISTRIBUTION Farley Unit 2 - 2nd Quarter, 1985 HOURS AT EACH WIND SPEED AND DIRECTION RELEASE MODE: BATCH PERIOD OF RECORD:

4 85 6-30-85 STABILITY CLASS: C ELEVATION:10.0m Wind Speed (mph) at 10.0m level Wind Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

O O

O O

O O

O NNE O

0 0

0 0

0 0

NE O

O 3

0 0

0 0

ENE O

O O

O O

O O

E O

O 0

0 0

0 0

ESE 0

0 0

0 0

0 0

SE O

O O

O O

O O

SSE 0

0 0

0 0

0 0

S 0

0 0

0 0

0 0

SSW 0

0 0

0 0

0 0

SW 0

0 0

0 0

0 0

WSW 0

0 0

0 0

0 0

W 0

0 0

0 0

0 0

-WNW 0

0 0

0 0

0 0

NW 0

0 1

0 0

0 1

NNW 0

0 0

0 0

0 0

VARIABLE 0

0 0

0 0

0 0

Total 0

0 1

0 0

0 1

Periods of calm (hours):

0 Hours of missing datas 0

107

TABLE 4A-2BQ2 CUMULATIVE JOINT FREQUENCY DISTRIBUTkON Farley Unit 2 - 2nd Quarter, 1985 HOURS AT EACH WIND SPEED AND DIRECTION RELEASE MODE: BATCH PERIOD OF RECORD:

4 85 6-30-85 STABILITY CLASS: D ELEVATION:45.7m Wind Speed (mph) at 45.7m level Wind Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

0 0

0 0

0 0

0 NNE 0

0 0

0 0

0 0

NE O

0 0

0 0

0 0

ENE O

O 0

0 0

0 0

E O

O O

O O

O O

ESE O

O 0

0 0

0 0

SE 0

0 0

0 0

0 0

SSE O

O O

O 0

0 0

S 0

0 0

0 0

0 0

SSW 0

0 0

0 0

0 0

SW 0

0 0

0 0

0 0

WSW 0

0 0

0 0

0 0

W 0

0 0

0 0

0 0

WWW 0

0 0

0 0

0 0

NW 0

0 0

0 0

0 0

NNW 0

0 1

0 0

0 1

VARIABLE 0

0 0

0 0

0 0

Total 0

0 1

0 0

0 1

Periods of calm (hours):

0 Hours of missing datas 0

108 L

TABLE 4A-2BQ2 CUMULATIVEJOINTFREQUENCYDISTRIBUTkON Farley Unit 2 - 2nd Quarter, 1985 HOURS AT EACH WIND SPEED AND DIRECTION RELEASE MODE: BATCH PERIOD OF RECORD:

4 85 6-30-85 STABILITY CLASS: D ELEVATION:10.0m Wind Speed (mph) at 10.0m level Wind Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

0 0

0 0

0 0

0 NNE 0

0 0

0 0

0 0

NE O

O 0

0 0

0 0

ENE O

0 0

0 0

0 0

E 0

0 0

0 0

0.

0 ESE O

O O

0 0

0 0

i SE O

O 0

0 0

0 0

SSE 0

0 0

0 0

0 0

S 0

0 0

0 0

0 0

i SSW 0

0 0

0 0

0 0

SW 0

0 0

0 0

0 0

WSW 0

0 0

0 0

0 0

W 0

0 0

0 0

0 0

WWW 0

0 0

0 0

0 0

NW 0

0 1

0 0

0 1

NNW 0

0 0

0 0

0 0

VARIABLE 0

0 0

0 0

0 0

Total 0

0 1

0 0

0 1

Periods of calm (hours):

0 Hours of missing datas 0

109

..g p

.s n-_,

a TABLE 4A-2BQ2 i

CUMULATIVE JOINT FREQUENCY DISTRIBUTION Farley Unit 2 - 2nd Quarter, 1985 1

i HOURS AT EACH WIND SPEED AND DIRECTION i

l RELEASE MODE: BATCH j

PERIOD OF RECORD:

4 85 6-30-85 i

STABILITY CLASS: E l

ELEVATION:45.7m Wind Speed (mph) at 45.7m level Wind Direction 1-3 4-7 8-12 13-18 19-24

> 24 TOTAL i

N 0

0 0

0 0

0 0

NME 0

0 0

0 0

0 0

l NE 0

0 0

0 0

0 0

ENE 0

0 0

0 0

0 0

i E

O O

O 0

0 0

0 ESE 0

0 0

0 0

0 0

SE 0

0 0

0 0

0 0

SSE O

O O

O O

0 0

S 0

0 0

0 0

0 0

4 SSW 0

0 0

0 0

0 0

+

1 SW 0

0 0

0 0

0 0

l WW 0

0 0

0 0

0 0

i W

0 0

0 0

0 0

0 WNW 0

0 0

0 0

0 0

NW 0

0 1

1-0 0

2 l

NNW 0

0 0

0 0

0 0

1 VARIABLE 0

0 0

0 0

0 0

l Total o

0 1

1 0

0 2

Periods of calm (hours):

0 i

Nours of missing datat 0

110

. ~.. - -.. - - -.... - - -.

TABLE 4A-2BQ2 CUMULATIVEJOINTFREQUENCYDISTRIBUTkON Farley Unit 2 - 2nd Quarter, 1985 HOURS AT EACH WIND SPEED AND DIRECTION RELEASE HODE: BATCH PERIOD OF RECORD:

4 85 6-30-85 STABILITY CLASS: E ELEVATION:10.0m Wind Speed (mph) at 10.0m level Wind Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

O O

O O

O O

O NNE O

O 0

0 0

0 0

NE O

O O

O O

O O

ENE O

O 0

0 0

0 0

E O

0 0

0 0

0 0

ESE O

0 0

0 0

0 0

SE O

O 0

0 0

0 0

SSE 0

0 0

0 0

0 0

S 0

0 0

0 0

0 0

SSW 0

0 0

0 0

0 0

SW 0

0 0

0 0

0 0

WSW 0

0 0

0 0

0 0

W 0

0 0

0 0

0 0

WNW 0

2 0

0 0

0 2

NW 0

0 0

0 0

0 0

NNW 0

0 0

0 0

0 0

VARIABLE 0

0 0

0 0

0 0

Total 0

2 0

0 0

0 2

Periods of calm (hours):

0 Hours of missing datas 0

111

.... -. - _ - - ~ - - - -.

TABLE 4A-2BQ2 CUMULATIVE JOINT FREQUENCY DISTRIBUTION Farley Unit 2 - 2nd Quarter, 1985 HOURS AT EACH WIND SPEED AND DIRECTION 1

RELEASE MODE: BATCH j

PERIOD OF RECORD:

4 85 6-30-85 STABILITY CLASS: F 4

i ELEVATION:45.7m l

Wind Speed (mph) at 45.7m level Wind l

Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

0 0

0 0

0 0

0 I

j NME O

0 0

0 0

0 0

i NE 0

0 0

0 0

0 0

i ENE 0

0 0

0 0

0 0

l I

l E

O O

O 0

0 0

0

)

j ESE 0

0 0

0 0

0 0

SE 0

0 0

0 0

0 0

SSE O

0 0

0 0

0 0

S 0

0 0

0 0

0 0

SSW 0

0 0

0 0

0 0'

SW 0

0 0

0 0

0 0

WSW 0

0 0

0 0

0 0

W 0

0 0

0 0

0 0

WWW 0

0 2

1 0

0 3

NW 0

0 2

0 0

0 2

s.

NNW 0

0 0

0 0

0 0

VARIABLE o

0 0

0 0

0 0

i Total 0

0 4

1 0

0 5

Periods of calm (hours):

0 Nours of missing datas 0

112 I

.2.

TABLE 4A-2BQ2 CUMULATIVE JOINT FREQUENCY DISTRIBUTION Farley Unit 2 - 2nd Quarter, 1985 i

HOURS AT EACH WIND SPEED AND DIRECTION RELEASE MODE: BATCH PERIOD OF RECORD:

4 85 6-30-85 STABILITY CLASS: F ELEVATION:10.0m Wind Speed (mph) at 10.0m level Wind Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

O O

O O

O O

O l

NNE O

O O

O O

O O

4 NE O

O O

O O

0 0

4 ENE O

0 0

0 0

0 0

a E

O O

O O

O O

O ESE O

O O

O O

O O

SE O

O O

O 0

0 0

SSE O

0 0

0 0

0 0

I S

0 0

0 0

0 0

0 1

SSW 0

0 0

0 0

0 0

i SW 0

0 0

0 0

0 0

WSW 0

0 0

0 0

0 0

W' i

1 0

C 0

0 2

WNW 0

2 0

0 0

0 2

I NW 0

1 0

0 0

0 i

f NNW 0

0 0

0 0

0 0

VARIABLE 0

0 0

0 0

0 0

4 Total 1

4 0

0 0

0 5

Periods of calm (hours):

0 4

l Hours of missing datas 0

).

113

~

+ - - - ~ -.,

, - ~

.-.r

~ ~

TABLE 4A-2BQ2 CUMULATIVE JOINT FREQUENCY DISTRIBUTkON Farley Unit 2 - 2nd Quarter, 1985 HOURS AT EACH WIND SPEED AND DIRECTION s

RELEASE MODE: BATCH PERIOD OF RECORD:

4 85 6-30-85 STABILITY CLASS: G ELEVATION:45.7m Wind Speed (mph) at 45.7m level Wind Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

O O

O 0

0 0

0 NNE O

0 0

0 0

0 0

NE O

O 0

0 0

0 0

ENE O

O O

O O

O O

E O

O O

O O

O O

ESE O

O O

O O

O O

SE O

O O

O O

O O

SSE O

O O

O O

O O

S 0

0 0

0 0

0 0

SSW 0

0 0

0 0

0 0

SW 0

0 0

0 0

0 0

WSW 0

0 0

0 0

0 0

W 0

0, 0

0 0

0 0

WNW 0

1 2

0 0

0 3

NW 0

0 3

0 0

0 3

r, NNW 0

0 0

0 0

0 0

VARIABLE O

O O

O O

O O

Total.

0

'l 5

0 0

0 6

Periods of calm (hours):

0 Hours of missing data:

0 114

TABLE 4A-2BQ2 CUMULATIVE JOINT FREQUENCY DISTRIBUTION Farley Unit 2 - 2nd Quarter, 1985 HOURS AT EACH WIND SPEED AND DIRECTION RELEASE MODE: BATCH PERIOD OF RECORD:

4 85 6-30-85 STABILITY CLASS: G ELEVATION:10.0m Wind Speed (mph) at 10.0m level 4

Wind Direction 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

O O

O O

O O

0 NNE O

O O

O O

O O

NE O

O 0

0 0

0 0

ENE O

O 0

0 0

0 0

E O

O O

O O

O 0

ESE O

O O

O O

O O

SE 0

0 0

0 0

0 0

SSE 0

0 0

0 0

0 0

S 0

0 0

0 0

0 0

SSW 0

0 0

0 0

0 0

SW 0

0 0

0 0

0 0

WSW 0

0 0

0 0

0 0

W 0

0 0

0 0

0 0

WNW 3

0 0

0 0

0 3

NW 0

1 0

0 0

0 1

NNW 2

0 0

0 0

0 2

VARIABLE O

O 0

0 0

0 0

Total 5

1 0

0 0

0 6

Periods of calm (hours):

0 Hours of missing data:

0 115

TABLE 4B CLASSIFICATION OF ATMOSPHERIC STABILITY a

Stability Pasquill e9 Temperature channel Classification Categories (dagrees) with height (OF/Sim)

Extremely unstable A

25.0

<-1.74 Moderately unstable B

20.0

-1.74 to -1.56 Slightly unstable C

15.0

-1.56 to -1.38 Neutral D

10.0

-1.38 to -0.46 Slightly stable E

5.0

-0.46 to 1.38 Moderately stable F

2.5 1.38 to 3.6 Extremely stable G

1.7

>3.6 a

Standard deviations of horizontal wind direction fluctuation over a period of 15 minutes to i hour.

The values shown are averages for each stability classification, 116

l TABLE 5

\\

RADIOACTIVE LIQUID WASTE SAMPLING AND ANALYSIS PROGRAM I

FARLEY NUCLEAR PLANT - UNITS 1 &2

&s9 Minimum Type of Minimum Liquid Release Sampling Analysis Activity Detectable Type Frequency Frequency Analysis Concentration (MDC)(uCi/ml) c P

P e

A.

Batch Waste Each Each Principal Release Batch Batch Gamma SE-07 Tanks Emitters I-131 1E-06 One Batch /M M

Dissolved &

Entrained Gases 1E-05 (Gamma Emitters)

P Each b

Batch M

H-3 1E-05 Composite Gross Alpha 1E-07 P

Each b

Batch Q

Sr-89, Sr-90 SE-08 Composite Fe-55 1E-06 d,f D

b e

B.

Continuous Grab W

Principal Releases Sample Composite Gamma SE-07 Emitters I-131 1E M 1.

Steam Grab M

Dissolved &

Generator Sample Entrained Gases 1E-05 Blowdown (Gamma Emitters)

D b

Grab M

H-3 1E-05 Sample Composite Gross Alpha 1E-07 D

b Grab Q

Sr-89, Sr-90 SE-08 Sample composite Fe-55 1E-06 P

b e

2. Turbine Grab W

Principle 5E-07 Building Sample Compo=ite Gamma Sump

-Emitters H-3 1E-05 117

. _ ~, - _, _

TABLE 5 (Continued)

TABLE NOTATION a.

The MDC is the smallest concentration of radioactive material in a sample that will be detected with 95% probability with 5%.

probability of falsely concluding that a blank observation represents a "real" signal.

For a particular measurement system (which may include radiochemical separation):

6 4.66 s

/

E

  • V
  • 2.22X10
  • Y
  • exp (-hat)

MDC

=

b where:

MDC is the "a priori" lower limit of detection as defined above (as microcurie per unit mass or volume),

s is the standard deviation of the background counting rate b

or of the counting rate of a blank sample as appropriate (as counts per minute),

E is the counting efficiency (as counts per transformation),

V is the sample size (in units mass or volume),

6 2.22x10 is the number of transformations per minute per microcurie, Y is the fractional radiochemical yield (when applicable),

h is the radioactive decay constant for the particular radionuclide, and at is the elapsed time between midpoint of sample collection and time of counting (Jor plant effluents, not environmental samples).

The value of s used in the calculation of the MDC for a b

detection system shall be based on the actual observed variance of the background counting rate or of the counting rate of the blank samples (as appropriate) rather than on an unverified theoretically predicted variance.

Typical values of E, V, Y, and At shall be used in the calculation.

118 l

1

TABLE 5 (Continued)

TABLE NOTATION b.

A composite sample is one in which the quantity of liquid sampled is proportional to the quantity of liquid waste discharged and in which the method of sampling employed results in a specimen which is representative of the liquids released.

c.

A batch release is the discharge of liquid wastes of a discrete volume.

Prior to sampling for analyses, each batch shall be isolated, and then thoroughly mixed, by a method described in the ODCM, to assure representative sampling.

d.

A continuous release is the discharge of liquid wastes of a nondiscrete volume; e.g.,

from a volume of system that has an input flow during the effluent release.

e.

The principal gamma emitters for which the MDC specification applies exclusively are the following radionuclides: Mn-54, Fe-59, Co-58, Co-60, 2n-65, Mo-99, Cs-134, Cs-137, Co-141, and Ce-144.

This list does not mean that only these nuclides are to be detected and reported.

Other peaks which are measurable and identifiable, together with the above nuclides, shall also be identified and reported.

f.

Sampling will be performed only if the effluent will be discharged to the environment.

g.

Deviation from the MDC requirements of Table 4.11-1 shall be reported per Specification 6.9.1.8 in lieu of any other report.

119

TABLE 6 RADIOACTIVE GASEOUS WASTE SAMPLING AND ANALTSIS PROGRAM FARLEY NUCLEAR PLANT - UNITS 1 & 2 a,h Gaseous Release Sampling Minimum Type of Minimum Type Frequency Analysis Activity Detectable Frequency Analysis Concentration (MDC)(uCi/ml) g,h A. Waste Gas Each Tank Each Tank Principle 1E-04 Storage Tank Grab b

Gamma Sample P P

Emitters 9sj B. Containment Each Purge Each Purge Principle 1E-04 Purge Grab b

Grab b

Gamma Emitters Sample P

Sample P

H-3 1E-06 9s)

C. Condenser M-b,c,e b

Principle Steam Jet Air Grab M

Gamma Emitters 1E-04 Ejector Plant Sample Vent Stack H-3 1E-06 f

D. Plant Vent Continuous Charcoal I-131 1E-12 Stack Charcoal Sample d

Containment W

I-133 1E-10 Purge f

g Continuous Particulate Principle Sample d

Gamma Emitters 1E-11 W

(I-131, others) f Continuous W

i Composite Gross Alpha 1E-11 Particulate Sample f

continuous Q

i Composite Particulate Sr-89, Sr-90 1E-11 Sample f

Continuous Noble Gas Noble Gases Gross 1E-06 Monitor Beta & Gamma 120

TABLE 6 (Continusd)

TABLE NOTATION

a. The MDC is the smallest concentration of radioactive material in a sample thac will be detected with 95% probability with 5%

probability of falsely concluding that a blank observation represents a real" signal.

For a particular measurement system (which may include radiochemical separation):

6 4.66 s

/

E*V* 2.22X10

  • Y
  • exp (-hat)

MDC

=

b where:

MDC is the "a priori" lower limit of detection as defined above (as microcurie per unit mass or volume),

s is the standard deviation of the background counting rate b

or of the counting rate of a blank sample as appropriate (as counts per minute),

E is the counting efficiency (as counts per transformation),

V is the sample size (in units mass or volume),

6 2.22x10 is the number of transformations per minute per microcurie, Y is the fractional radiochemical yield (when applicable),

A is the radioactive decay constant for the particular radionuclide, and At is the elapsed time between midpoint of sample collection and time of counting (for plant effluents, not environmental samples).

The value of s used in the calculation of the MDC for a b

detection system shall be based on the actual observed variance of the background counting rate or of the counting rate of the blank samples (as appropriate) rather than on an unverified theoretically predicted variance.

Typical values of E, V, Y, and at shall be used in the calculation.

121

--e

,-we...-.-%4aw

  • ee. *-

TABLE 6 (Continued)

~

TABLE NOTATION b.

Analyses shall also be performed following shutdown from > or =

15% RATED THERMAL POWER, startup to > or = 15% RATED THERMAL l

i POWER or a THERMAL POWER change exceeding 15% of the RATED THERMAL POWER within a one hour period.

j c.

Tritium grab samples shall be taken from the plant vent stack l

at least once per 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> when the refueling canal is flooded.

d.

Samples shall be changed at least once per 7 days and analyses shall be completed within 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> after changing (or after removal from sampler).

Sampling shall also be performed at least once per 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> for at least 2 days following each shutdown from > or = 15% RATED THERMAL POWER, startup to > or =

i 15% RATED THERMAL POWER or THERMAL POWER change exceeding 15%

of RATED THERMAL POWER in one hour and analyses shall be completed within 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> of changing.

When samples collected for 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> are analyzed, the corresponding MDC may be increased by a factor of 10.

Tritium grab samples shall be taken at least once per 7 days e.

from the ventilation exhaust from the spent fuel pool area, whenever spent fuel is in the spent fuel pool.

f.

The ratio of the sample flow rate to the sampled stream flow rate shall be known for the time period covered by each dose or dose rate calculation made in accordance with Specifications 3.11.2.1, 3.11.2.2 and 3.11.2.3.

g.

The principle gamma emitters for which the MDC specification applies exclusively are the following radionuclides:

Mn-54, Fe-59, Co-58, Co-60, Zn-65, Mo-99, Cs-134, Cs-137, Ce-141 and Ce-144 for particulate emissions.

This list does not mean that only these nuclides are to be detected and reported. Other which are measurable and identifiable, together with the 4bove nuclides, shall also be identified and reported.

h.

Deviations from MDC requirements of Table 4.11-2 shall be reported per Specification 6.9.1.8 in lieu of any other report, i.

A composite particulate sample is one in which the quantity of air sampled is proportional to the quantity of air discharged.

Either a specimen which is representative of the air discharged may be accumulated and analyzed or the individual samples may be analyzed and weighted in proportion to their respective volume discharged.

j.

.The principal gamma emitters for which the MDC specification applies-exclusively are the following radionuclides: Kr-87,.

Kr-88, Xe-133, Xe-133m, Xe-135, and Xe-138 for gaseous emissions. This does not mean that only these nuclides are to be detected and reported.

Other peaks which are measurable and identifiable together with the above nuclides, shall also be identified and reported.

122

-w ms

-_a-----.-.p.-i

,y vr*-.---r-.--

y e ww -y y w ym g.

9y.--g.w.-

+

n p.

ap. g.w, cym,,m._..w.

ucea.u--mm.-ms-.se m erus.

w e--s. caw mss

    • es---swwww--w---

.=

TABLE 7 LIQUID DISCHARGES NOT MEETING SPECIFIED DETECTION LIMITS Farley Units 1 & 2-1st half, 1985 Batch #

N/A*

Date N/A Count Time in Seconds N/A Volume Discharged in Gallons N/A Dilution Water in Gallons N/A Total Isotopic Activity (uCi/ml)

N/A Isotope of Interest N/A MDC Measured N/A

% of Total Isotopic Activity N/A

% of Total Dose N/A

  • No liquid discharges made that did not meet specified detection limits.

123

14.

Process Control Program Changes to the Process Control Program (PCP) during the first semi-annual period of 1985 are submitted per STS section 6.13.2.

Documentation that the changes were reviewed and found acceptable by the Plant Operations Review Committee is also submitted in the following section of this report.

124 l

L

PROCEDURE REQUEST FORM FNP-0-AP-1 1.

Procedure Number FNP-0-M-030 Revision Number 1

-(

Procedure Title process control Prnernm R

Safety Related O

Non-Safety Related O

New Procedure Request Q-Procedure Revision, New Revision Number 2

O Temporary Procedure Change, Effective until next permanent change, TCN C

Temporary Procedure Change, Req'd. by Plant Conditions, TCN O

Temporary Procedure Change, One Time Use, TCN O

Delete procedure 2.

Change Summary.

2.1 Procedure Page Numbers Affected by Change See attached list of effective pages that reflect FNP revision two

_2.2 Description of Changes All changes submitted by vendor.

Westinghouse Hittman Nuclear Incoroorated 2.3 Reason for Change vendor undate of nroceanro<:

1

')

/

3.

Prepared By non., / ~ O 'b

\\<,

n

~

SignKure N

Title Date yD$h//hf/M,

unauner ; an,ar.,4.,,,. l l l f 0 5 '

4.

Reviev' Signatufe Title Date

\\

5.

Cross-Disciplinary /PORC Review Sianlature/

Grou Title Date 4 L 46 tfA l nab

/)M 7-/,9/ W ge -

6.

Temporary Change Approval (Signature /Date)

C Member Group Staff

/

0 Shift Foreman

/

O Senior Reactor Operator

/

C Plant Manager

/

7.

Final Approval (Signature /Date, required within 60 days of temporary approval)

Group Supervisor 4

/

/ $

V Plant Superintendent T KC444 '/d-44R[

, fc]

C MSAER

/

i([L 0

Vice President -

3

'- v Nuclear Generation

/

c

/

O Plant Manager

/

1 Figure 1 Gen. Rev. 13

[

FARLEY NUCLEAR PIJLNT NUCLEAR SAFETY EVALUATION CECK LIST 10 CFR 50.59 1

(1) UNIT io (2) CHECK LIST APPLICABLE TO: FNP-0-M-030 Revision i

TCN (3) SAFETY EVALUATION - PART A

)

The procedure, procedure change or modification to which this evaluation is applicable represents:

(3.1) Yes No x

A change to the plant as described in the FSAR?

(3.2) Yes No y

A change to procedures as described in the FSAR7 (3.3) Yes No y

A test or experiment not described in the FSAR?

(3.4) Yes No y

A change to the Technical Specifications or Operating License?

If the answer to question 3.1, 3.2 or 3.3 is "YES," complete Ites (4) and 4

attach a 10 CFR 50.59 evaluation.

If the answer to all of the above is "No," omit Item (4) and Item (9). If the answer to question 3.4 is "Yes,"

comolete a 10 CFR 50.92 check list.

(4) SAFETY EVALUATION - PART 3 (4.1) Yes No Will the probability of an accident previously evaluated in the FSAR be increased?

(4.2) Yes No

.O Will the consequences of an accident previously

!' M ~

evaluated in the FSAR be increased?

~

(4.3) Yes No May the possibility of an accident which is different than any already evaluated in the FSAR be created?

(4.4) Yes No Will the probability of a malfunction of l

equipment important to safety previously i

evaluated on the FSAR be increased?

(4.5) Yes No Will the consequences of a malfunction of equipment important to safety different than any already evaluated in the FSAR be incrersed?

(4.6) Yes No May the possibility of a malfunction of l

equipment important to safety different than t

any.already evaluated in the FSAR be created?

't (4.7) Yes No Will the margin of safety as defined in the

l basis to any Technical Specification be reduced?

'i

l If the answer to any of the above questions is "Yes," an unreviewed safety

)

question is involved. Explain the basis for each answer provided in Section 4 f

(5) REMARKS:- (Attach additional pages if necessary) b &e. E

  1. _a_n@ h d
  • AA u,= h nauu Ae enyilar & - a
  1. 1 %d J m
  • JG uan=4.

4

.R.= w % AMlstal = eA ES=E

  • _

A-d FA saw (4Ee l

y l

(6) PREPARED Mo hhf2g,v

/

__DATE 6 //J//f r (7) REVIEk Y: WM /J J wy

__ DATE ///7/he

}

(8) PORC. VIEW:' J'Qlf T /Gf af ~

DATE

'fG/f-Yf

J (9) NORB. ' _W
/ / P ~

DATE 1+

l[l Distributio'n Original: Document Control File A216226

'i Figure 3 Gen. Rev. 13 L

J FNP-0-M-030 January 17, 1985 Revision 2 f

,3,,?g ye vtes W PJ * *E " "

.u= = :NOllOYD IdOD GrnO'd1NODNn i

ALABAMA POWER COMPANY i

1 JOSEPH M. FARLEY NUCLEAR PLANT UNITS 1 AND 2 i

UNCONTROLLED COPY S

^

CAUTION:

F nucms, m * ~

E Gmet. Do not una in n &fstr Ec.L'w! Ace o*

T PROCESS CONTROL PROGRAM

's R

L A

T E

D l

I Approved:

[ 0.

l Technical Superintendent Date Issued:

2-l9 -87 O

MISC #4 g

L

  • FNP-0-M-030 Revision 2

(')1 m.

List of Effective Page WHNI Number of FNP Section A Dewatering Revision Pages Revision STD-P-03-003 RADLOCK " Manway Lid Closure and 6

4 0

E Sealing Procedure D

STD-P-03-004 Closure of HITTMAN RADLOK High Integrity 5

4 1

Container Fill Port STD-P-03-005 Dewatering Bead I g Exchange Resin 4

5 0

in HITTMAN RADLOK Containers with Flexable Underdrains to Less Than 1% Drainable Liquid STD-P-03-006 Inspection of Completed HNDC Liners 1

9 1

D STD-D-03-008 A Users Manual for the HITTMAN RADLOCK -55 5 5

1 STD-P-03-008 Transfer &DewgeringPewderedResinin Hittman RADLOK -100 or -200 Containers with a Flexible Underdrain Assembly to Less than 1% Drainable Liquid 4

6 1

p QSTD-D-03-009 A User g anual for the gTTMAN 6

6 1

RADLOK -100 and RADLOK -200 High Integrity Containers STD-P-03-010 Transfer &DewgeringBeadResinin 5

11 1

Hittman RADLOK -100 or -200 Containers with Single Layer Underdrain Assembly to Less Than 1% Drainable Liquid STD-P-03-020 Radlok Inspection Procedure 2

5 1

STD-P-04-002 P.C.P. for Dewatering Ion Exchange 3

6 1

Resin & Activated Charcoal Filter Media to \\% Drainable Liquid S ction B Solidification STD-P-05-002 P.C.P. for Incontainer Solidification 3

12 1

of Oily Waste STD-P-05-003 P.C.P. for Incontainer Solidification 3

12 2

of 4 to 20 Weight Percent Boric Acid STD-P-05-004 P.C.P. for Incontainer Solidification 5

16 2

of Bead Resin v

)

I

1 WHNI Number of FNP Revision Pages Revision STD-P-05-011 Process Control Program for Incontainer

(]b Solidification of Granular Activated Carbon (12-40 MESH) 2 12 2

STD-P-05-021 P.C.P. for Incontainer Solidification of Decanted Diatomaceous Earth Filter Sludge 0

12 0

STD-P-05-022 Calcium Hydroxide Addition Procedure 0

5 0

STD-P-05-023 Incontainer Solidification System (ICSS)

Operational Inspection Procedure Sections A and B) 0 22 1

STD-P-05-027 Full Scale Test Solidification Procedure for Class B or C Bead Resin 0

11 1

STD-P-05-034 PCP for Incontainer Solidification of Class A Stable, Class B and C. Bead Resin at Maximum Packaging Efficiency 0

13 2

F434-P-005 P.C.P. for Incontainer Solidification of Dilute Filter Sludge 1

10 0

Section C Equipment Information STD-D-01-001 Operation & Maintenance Manual

-OT Standard Dewatering Pump Skid 1

18 0

%)

STD-P-04-001 Final Dewatering Pump Skid Operating Instructions 1

8 0

STD-D-05-001 Standard Dewatering Pump Skid

System Description

0 2

0 Section D Reports STD-R-03-001 Report on Dewatering of Bead Ion Exchange Resin and Activated Carbon 0

17 1

STD-R-03-002 Report on-Dewatering of Bead Ion Exchange Resin a ctivated Carbon in HITTMAN RADLO High Integrity Containers 1

17 1

STD-R-03-005 SummaryRep9gtofPowderedResinDewatering In a RADLOK Container 0

24 1

STD-R-03-006 Powdered Resin Dewatering in a Flat Botton Container Using the Hittman Layered Underdrain System 0

6 1

(JSTD-R-05-007 Topical Report Cement Solidified Waste y

To Meet The Stability Requirements of 10CFR61 1

32 2

L