Pcg3 1 of 2 FOR INFORMATl0N ONLY EVALUATION RESEARCH CORPORATION COMANCHE PEAK RESPONSE TEAM QUALITY INSTRUCTION FOR ISSUE-SPECIFIC ACTION PLAN VII.c CHANGE NOTICE: 001 INSTRUCTIOM No. : QI-53 REVISION:
2 ISSUE DATE: 09-22-87 REINSPECTION OF CATECORY I CONDUIT SUPPORTS / I-S-COSP
- j. a
\\
Prepared by:
w-
< ~ ~
Date: "h 16 27 I
A. Rabfmsg h,
Date: 7 -/0 - S 2 Approved by:
~
- L I sue Coordinator
/pproved by:
Date:
-//-h OnJSite QA p resentative Approved by:
bY
/
Date: 6 /Y ((
Q
(
Review Team Leader
'/
/
G804260253 880415 PDR ADOCK 05000445 QI-5*:,/ j t A
P:g; 2 cf 2 1.
Change Section 5.1.0 to read:
"Verify that the orientation of the conduit and/or junction box with respect to the support is in accordance v'th the generic / design drawing."
2.
Add the following to Section 5.3.1.c:
"k' hen the conduit size is not indicated on the sketch (capacity / span sketch) verification of conduit size is not required."
3.
Change Section 5.3.le to read:
"Any additional items attached to the support."
4.
Add the following to NOTE 3 of Section 5.3.1:
"The fittings identified in NOTE 35 of drawing 2323-S-0910 Sh.
G-le (identified in Attachment 6.19 pg. 5 of 31 in the QI) do not require identification or inspection by the inspector."
5.
Change the first sentence in Section 5.3.2 NOTE 2 as follows:
"For junction box supports not requiring load verification (via verification of conduit span length or total weight on support), the number of conduits entering / exiting'the junction box may be noted in writing by the responsible QA/QC Inspector on Attachment 6.13 "Supplemental Remarks."
6, Add the following note after Section 5.3.2ft NOTE 3 : Sub-attributes of Section 5.3.1 and 5.3.2 which are redundant (i.e. the verification of items in one sub-attribute is also reviewed in another sub-attribute) with another sub-attribute which is accepted or rejected by the inspector may be marked NA (not applicable) in the checklist.
QI-53/jt
(
,