05000289/LER-1997-006, Forwards LER 97-006-00,resulting from Violation of TS 3.3 & Declaring Reactor Bldg fans,AH-E-1B & C,Inoperable on 970424

From kanterella
(Redirected from ML20148E562)
Jump to navigation Jump to search
Forwards LER 97-006-00,resulting from Violation of TS 3.3 & Declaring Reactor Bldg fans,AH-E-1B & C,Inoperable on 970424
ML20148E562
Person / Time
Site: Crane 
Issue date: 05/23/1997
From: Langenbach J
GENERAL PUBLIC UTILITIES CORP.
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
Shared Package
ML20148E566 List:
References
6710-97-2198, NUDOCS 9706030156
Download: ML20148E562 (1)


LER-1997-006, Forwards LER 97-006-00,resulting from Violation of TS 3.3 & Declaring Reactor Bldg fans,AH-E-1B & C,Inoperable on 970424
Event date:
Report date:
2891997006R00 - NRC Website

text

..- _ - _

t e

{

GPU Nuclear,Inc.

A Route 441 South NUCLEAg Post Office Box 480 Middletown, PA 17057-0480 Tel 717-944-7621 May 23,1997 6710-97-2198 U. S. Nuclear Regulatory Commission Attn.: Document Control Desk Washington, D.C. 20555 i

Gentlemen:

l Subject: Three Mile Island Nuclear Station, Unit I (TMI-1)

Operating License No. DPR-50 Docket No. 50-289 LER 97-006-00 This letter transmits Licensee Event Report (LER) number 97-006-00 that resulted from the violation of Technical Specification 3.3 and declaring the Reactor Building fans, AH-E-1B & C, j

inoperable on April 24,1997. The inoperability declaration resulted following the observation of installed conditions and the conclusion of a review of the environmental qualification of the connector configurations at the AH-E-1B & C fan motors. The connection, as configured, was not sealed and would have been exposed to post-LOCA Reactor Building atmospheric conditions. AH-E-1B & C were restored to operability on April 25,1997.

Public health and safety were unafrected by this event.

l This LER is being submitted pursuant to 10 CFR 50.73, using the required NRC forms (attached).

NRC Form 366 contains an abstract which provides a brief description of the event. For a complete understanding of the event, refer to the text of the report provided on Form 366A.

I Sincerely, 9706030156 970523

~

l i

DR ADOCK 0500 9

James W. Langenbach 4 gy9, i

{

U r. O u o

Vice President and Director, TMI WGH Attachments cc: Administrator, Region I TMI Senior Resident Inspector I

Senior Project Manager g