ML20140J045

From kanterella
Jump to navigation Jump to search
Forwards Press Release 84-52 Re NRC Proposed Fine Against Util for Alleged Safety Violations,Including Failure to Follow Approved Procedures During Operation of Startup Feedwater Pump
ML20140J045
Person / Time
Site: Davis Besse, 05000000
Issue date: 12/03/1984
From: Kammerer C
NRC OFFICE OF CONGRESSIONAL AFFAIRS (OCA)
To: Glenn, Latta, Markey, Metzenbaum, Ottinger R, Simpson, Udall
HOUSE OF REP., HOUSE OF REP., ENERGY & COMMERCE, SENATE
Shared Package
ML20140C961 List: ... further results
References
FOIA-85-478 NUDOCS 8510230274
Download: ML20140J045 (2)


Text

.

UO>1CECp4%

/*~

^4 UNITED STATES NUCLEAR REGULATORY COMMISSION n

h, WASHINGTO N, D. C. 20555 (Lsj>

i

.. j

%, N'.....#

December 3, 1984 The Honorable Richard L. Ottinger, Chairman Subcommittee on Edergy Conservation and Power Committee on Energy and Commerce United States House of Representatives Washington, DC 20515

Dear Mr. Chairman:

Enclosed for your information is an announcement that the Nuclear Regulatory Conraission staff proposes a $20,000 fine against Toledo Edison Company for alleged safety violations at the Davis Besse plant.

It is planned to mail this information to the news media today, December 3, 1984.

I Sin r q

l i

V rw Cr lto. ;a V, Direi: tor

.fice of Congressional Affairs

Enclosure:

As stated cc: Rep. Carlos Moorhead l

IDENTICAL LETTER SENT T0:

l Sen. Simpson/cc: Sen. Hart Rep. Udall/cc: Rep. Lujan Rep. Markey/cc: Rep. Marlenee Sen. Glenn Sen. Metzenbaum l

Rep. Latta 8510230274 851004 PDR FOIA JACOBS85-478 PDR s

F.

~

f""%

UNITED STATES fpg }

NUCLEAR REGULATORY COMMISSION

[

OFFICE OF PUBLIC AFFAIRS. REGION lli 799 Roosevelt Road. Glen Ellyn. Illinois 60137

.c NEWS ANNOUNCEMENT:

84-S2 CONTACT:

Jan Strasma 312/790-5674 Russ Marabito 312/790-5667

~

NRC STAFF PROPOSES $90,000 FINE AGAINST TOLEDO EDISON COMPANY FOR ALLEGED SAFETY VIOLATIONS AT DAVIS BESSE PLANT The Nuclear Regulatory Commission staff has proposed a $90,000 fine against the Toledo Edison Company for five alleged violations of NRC requirements involving the operability of safety-related equipment at the Davis-Besse Nuclear Power Station near Port Clinton, Ohio.

Two of the alleged violations account for $50,000 of the proposed fine.

An NRC inspection in June-July 1984 determined that one violation involved the inadvertant shutdown of part of the plant's Control Room.

Emergency Ventilation System for a 14-day period.

This system maintains the habitability of the control Room during an emergency through air filtration and temperature control.

Two control switches which affect the cooling function of the system were found to be in the "off" position from April 23 to May 7, 1984, a violation of NRC requirements.

Neither Toledo Edison nor the NRC could determine why the two switches were turned off.

(The emergency ventilation system was never called upon during this time period.)

The second violation involved the utility's failure to follow NRC-approved procedures during the operation of a "startup feedwater pump."

(This pump is used to pump water through a steam generator when the reactor is starting up.

Steam generators remove heat from the reactor.)

Three other violations, with a proposed cumulative fine of $40,000, were:

(1).

On November 1, 1983, the licensee removed one of two Emergency Diesel Generator Ventilation supply fans from service without preparing a

. written safety evaluation and without realizing that this action represented a change in approved procedures.

Two ventilation supply fans are required to ventilate each room containing a diesel generator.

(Diesel generators supply power to safety-related systems in the event of the loss of off-site power.)

(2).

The licensee failed to prepare a written safety evaluation when it opened a suction valve on the startup feedwater pump during power opera-In the event of a pipe break, water could flow through the open valve tion.

into the auxiliary feedwater room, j eopardizing the operability of auxiliary pumps which provide emergency water to the steam generators.

(3).

On March 8 and May 4, 1984, lead shielding was hung on piping by licensee personnel without preparing a written safety evaluation.

It was later determined that the piping could withstand the extra load.

Toledo Edison has until December 21, 1984, to either pay the fine or protest it.

If the fine is protested and subsequently imposed formally by the NRC staff, the utility may request a hearing.

l###

November 27, 1984