Reviews Proposed Tech Spec Change Re Reduction in Cold Fast Start Surveillance Testing of Diesel Generators.Proposed Changes Acceptable
ML20127B131
Person / Time
Site: 05000000, LaSalle
Issue date: 12/09/1983
From: Rubenstein L
Office of Nuclear Reactor Regulation
To: Novak T
Office of Nuclear Reactor Regulation
Shared Package
ML082410334 List:
References
FOIA-85-243 NUDOCS 8401120110
Download: ML20127B131 (2)


Text

'

., {

g.p carg\\

UNITED STATES 7 ~.

/

Q NUCLEAR REGULATORY COMMISSION I.2 f d

-M E

WASHINGTON, D. C. 20555 DEC 9 1983 MEMORANDUM FOR: Thomas M. Novak, Assistant Director for Licensing, DL FROM:

L. S. Rubenstein, Assistant Director for Core and Plant Systems. DSI

SUBJECT:

REVIEW OF THE PROPOSED TECHNICAL SPECIFICATION CHANGE FOR LASALLE UNITS 1 & 2 REGARDING REDUCTION IN COLD FAST START SURVEILLANCE TESTING OF DIESEL GENERATORS In accordance with your request of Deceinber 8,1983, the Power Systems Branch has reviewed the Commonwealth Edison Company's submittal regarding proposed revisions to Unit 1 and 2 Technical Specifications. The Technical Specification changes involve reduction in the number of required fast cold start surveillance tests of diesel generators. All surveillance testing not required to be a fast cold start will be preceded by an engine prelube period and/or other warmup procedures recommended by the diesel generator manufacturer. We find the proposed Technical Specification change to be acceptable based on the following justification.

The DSI staff has for sometime had under review and assessment the method of diesel generator testing. The present method of testing does not take

'into consideration those manufacturer recommended preparatory actions such as prelubrication of all moving parts and warmup procedures which are necessary to reduce engine wear, extend life and improve availability. The existing standard technical specifications require cold fast starts for surveillance testing which in many engine designs and operating practices subject the diesel engine to undue wear and stress on engine parts.

Nuclear industry related groups such as INPO and knerican Nuclear Insurers have expressed concern based on operating experience that cold fast start testing results in incremental degradation of diesel engines and that, if proper procedures covering warmup prelubrication, loading / unloading etc. were taken, an improvement in reliability and availability would be gained.

While the recairements for cold fast starts is based on the EDG's functional requirements in response to a LOCA coincident with a loss of offsite power preliminary analysis indicates that two (2) fast starts per year is a sufficient number to assure the required DG reliability under design basis conditions. Thus, it is the staff's technical judgement that an overall improvement in diesel engine reliability and availability can be gained by perfonning diesel generator starts for surveillance testing using engine prelube and other manufacturer recommended procedures to reduce engine stress and wear.

Contact:

Om Chopra, x2352E q

t uWeb #

Ij g

~

~

1 050 E 23I I Thomas M. Novak We, therefore, recommend that the Commonwealth Edison Company be given the opportunity to institute technical specifications for LaSalle Units 1 and 2 for surveillance testing which permit diesel engine prelube and other manufacturer recommended procedures. The technical specifications should retain the demonstration of fast start testing on a 184 days basis.

This is consistent with the proposed staff resolution of the fast cold start issue. The number and period of surveillance tests specified in the Standard Technical Specifications remain unchanged. Though unlikely, should final resolution of this issue result in changes.to this position with respect to diesel generator surveillance testing, we will so inform the licensee.

This action is being taken'on a plant. specific interim basis pending fina,1 approval of Generic Issue B-56, dealing with surveillance testing of diesel generators.

It is our conclusion that the health and safety of the public will be improved by these improved testing methods and, therefore, are acceptable.

i i

~u_

r 2

L. S. Rubenstein, Assistant Director for Core and Plant Systems Division of Systems Integration cc:

R. Mattson D. Eisenhut R. Purple F. Schroeder A. Thadani M. Srinivasan C. Thomas J. E. Knight A. Ungaro D. Hoffman