Informs of Fourth Insp of Safety Injection & Refueling Water (Sirw) Tank Support on 840211.Util Will Continue to Monitor Sirw Tank Support,Per 840206 Commitment
ML20117M935
Person / Time
Site: 05000000, Palisades
Issue date: 02/14/1984
From: Paul Klein
CONSUMERS ENERGY CO. (FORMERLY CONSUMERS POWER CO.)
To: Keating D
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
Shared Package
ML20114G054 List:
References
FOIA-84-616 PJK-07-84, PJK-7-84, NUDOCS 8505170303
Download: ML20117M935 (1)


Text

LV

\\

~

Consumers

~

.t[j Power Company General offices: 1945 West Parnait Road, Jackson, MI 49201 * (517) 788-0550 February 14, 1984 PJK 07-84 Mr Dale Keating NRC Region III 799 Roosevelt Road Glenn Ellyn, IL 60137

SUBJECT:

PALISADES SIRW TANK SUPPORT STRUCTURES A fourth inspection of the Palisades SIRW tank support was performed on February 11, 1984. The inspection program includes measurement of width of selected concrete beam cracks and elevation measurements of the support structure.

The inspection was conducted with the tank filled to 94% of capacity and compared with the inspection on January 31, 1984 with the tank 94% full. The results of the inspection on February 11, 1984 confirms the results of the inspection on January 31, 1984, which indicate the support structure has generally settled up to a maximum of 1/8 inch at its center as compared with the inspection on August 8, 1983 with the tank 98% full.

Therefore, Consumers Power Company will continue to monitor the SIRW tank support as planned in the previous letter sent to you on February 6, 1984.

[O TM v

Paul J 1 n Senior Engineer Consumers Power Company 1945 West Parnall Road, P-24-114 Jackson, MI 49201 (517) 788-5808 CC: Bruce Jorgenson, NRC DJVandeWalle, P-24-614B BDJohnson, P-24-606 ERCooper, P-24-306 KKChao, P-24-304 DCC 950/00211/01400/L B505170303 840914 PDR FDIA BARFIEL84-616 PDR N

OC0284-0070A-NS06

~

(

FEB27 1984

/

Docket No. 50-373 Docket No. 50-374 Commonwealth Edison Company ATTN:

Mr. Cordell Reed Vice President Post Office Box 767 Chicago, IL 60690 Gentlesco:

Thank you for your letters dated January 20 and February 9,1984, informing us of the steps you have taken to correct the noncompliance which we brought to your attention in Inspection Reports No. 50-373/83-41(DE); 50-374/83-42(DE) forwarded by our letter dated December 7,1983. The described corrective actions and the corrective actions taken and confirmed in the Confirmatory Action Letter, dated November 28, 1983, to prevent the future use of materials of indeterminate quality in safety-related applications will be examined during a subsequent inspection.

Your cooperation with us is appreciated.

Sincerely, c;;!n:1 0'ac.:s -i -'. F. Strc'ater" J. F. Streeter, Chief Engineering Branch I cc:

D. L. Farrar, Director of Nuclear Licensing G. J. Diederich, Station Superintendent R. H. Holyoak, Project Manager cc w/1tr dtd 01/20 & 02/09/84:

DMB/ Document Control Desk (RIDS)

Resident Inspector, RIII Phyllis Dunton, Attorney General's Office, Environmental Control Division RIII RII:' -

RII II RI RIII d

Td O-

@ p/" QKkpp Hunter lier Streeter Choules/sv ish Eb1 sw8awa w

.