EIJ!CTRICAL POER SYSTTMS SURVEILIANCE PsmIRBGNIS f

'4.8.1.1.1

_ Each of the above required independent circuits E between _the offsite tranmission network and the onsite Class lE. distribution system -

.shall be:

a.

. Determined ' OPERABIE at least once per 7 days by verifying correct l

breaker alignsents and indicated power availability, and '

b.

Deonstrated OPERABIE at least once per 18 monthsiduring ' shutdown by transferring, manually and automatically, unit power supply from the normal circuit to the alternate circuit.

4.8.1.1.2 Each diesel generator shall be demonstrated OPERABIE:

a.

In accordance with the frequency specified in Taole 4.8.1.1.2-1 on a STAGGERED TEST BASIS by:

m.

1.

Verifying the fuel level in the day fuel tanks..

2.

Verifying the fuel level in r.he plant fuel storage tank.

3.

Verifying the fuel transfer pap can be started and ' transfers fuel fra the storage systs to the day tank.

4.

Verifying the diesel starts fra ambient condition and accelerates to synchronous speed in (12' seconds, is loaded

) 2764 kw for diesel generator 2A, ) 2360 kw for diesel generator 1B, and ) 2742 kw for diesel generator 2L ing 5 minutes, and operators for ) 60 minutc thereafter.

t 5.

Verifying the diesel generator is aligned to nrovide standby power to the associated mergency busses.

6.

Verifying the pressure in both diesel air stact recuers to be > 225 peig.

b.

At least once per 92 days by verifying that a saple of diesel tuel from the fuel storage

tank, obtained in accordance with AS1M-D270-65, 'is within the acceptable limi) wified in Table 1 of AS1M D975-74 when checked for viscosity, we c and sediment.

I I

1 e

HAto!

IMIT-2 3/4 8-3 l

.