NOV 2 8 378 MDORANDUM FOR:

R. W. Reid. Chief. Operating Reactors Branch d4 i

Division of Operating Reactors t

FROH:

T. S.-Noonan. Chief. Engineering Branch Division of Operating Reactors SUSJECT:

THREE MILE ISUWe UNIT NO.1 - REACTOR COOLANT BUILDING - AING GIRDER SURVEILUUCE TESTS AND INSPECTION - TECHNICAL SPECIFICATION CHANGE REQUEST #77 (TACS #10793)

Plant Name: Three Mile Island Unit No.1 Licensing Stage: Operating Plant Docket No: 50-289 Documents Reviewed:

a.

Metropolitan Edison Co. - Letter to Director of NRA (Atta:

R. W. Reid) dated August 30 1973 requesting Tech. Spec. change #77 t

i b.

Three Mile Island Nuclear Station Unit 1 -

Reactor Containment Building Ring Girder i

i surveillance Test Three Years After S.I.T.,

l June 17.1977 i

c. Additional information provided by Licensee l

in letter to R. W. Reid, dated August 26, 1977 Branch and Project Manager Requesting Assistance: ORB-4 G. Zwetztg.

R. Reid l

Requested Completion Date: 12/1/78 l

Operating Reactors Branches Involved: Engineering Branch Description of Request: TACS #10793

{

Review Status: Complete The Engineering Branch. Division of Operating Reactors has reviewed the structural and material aspects of the taformation sehmitted by the Metropolitan Edissa Compaar in the docaests listad above detailing the reacter building ring girder surveillance program. This is in accordance with TMI-1 Technical Specificattoa 4.4.2.2 (original forsu-j-

1ation). The licensee requests that 4.4.2.2 be changed as indicated i

in document (a) Ifsted above introducing the final periodic inspection l

._ re rting schedules.

l 781205 032, 3

A ct:,I.A. Gluckmann

/

49-28060 I

[

s

..__4._______

see seem m p.m secu sees -

e

.c

..= -

I

+rw

C V 2 8 G78 i.

l R. W. Refd I Discussion i

I In our previous evaluation-(letter to Itcensee dated December 29, 1977) we concurred with the licensee's suggestions but added in substance the following reconmendations:

i 1.

We insist again that the repairs should be perfomed as planned and not later than the and of the refueling outage of 1978.

i l

2.

Section 4.4.2.2A of the Technical Speciffcattons for Three Mile j

Inland Unit No.1 (TMI-1) requires four inspections of the l

containment ring girder at various times after the Structural Integrity Test. It also states that the requirement for further i

inspection will be detemined following review of the report of i

the fourth inspection.

The Itcensee indicates that, since the six month, one year, two j

years, and three years surveillance inspections have not uncovered any significant structural problem, Metropolitan Edison Company, in accordance with Technical Specification 4.4.2.2A does not plan to conduct further ring girder surveillance tests.

On the bests of our previous evaluations and the new information provided by the licensee in the report cited above, we concur with I

the licensae's decision. This recoseednation is contingent upon the perfomance of planned repairs in accordance with our recom-mandation (1) above.

3.

We also recommend that during further service surveillance pro-cedures perfomed in accordance with the reconnendations of the Regulatory Guide 1.35 a visual inspection of the. ring girder be performed by the licensee and its results reported to the NRC as a

provided in R.G. 1.35.

i Our review of the submissions by the Itcensee (including submission (1)) listed above found that it conforms with our suggastions and recommendations.

Conclusf ons.

1 i

We therefore concur with the licensee's request for the Tech. Spec.

Change 77.

Origioel:igned Wi Vincent S. Noonan, Chief Engineering Branch Division of Operating Reactors next page

.O cc:

(B:00R d EB100R R;.QQR....

4

.m...

1 e

AGluckmann:mb B.RLiA,

_.yS.No.ogan 11/IeHA__

1.1/ >'H8._

_1.1L;na._

.n.

i see au m w.m nacu==

  • -..--..m.....--

l

. s R. *d. Reid D IS I978 r

cc:

V. Stello, Jr.

R. I'.attson J. Knf ght O. Eisenhut B.' Grimes S. D. Llaw A. Gluckmann G. Zwetzig K. Herring D. Ziemann i

i

r e

1 1

1 l

i i

4 3

l l

.......e.

..n o.

r une ronu ne <,.sn uncu n.e

  • e.....n...,...~~.. e,... en - ~

l