Text

NRC MONTHLY OPERATING REPORT DOCKET N0. 50-361 UNIT NAME SONGS - 2 DATE 10/17/84 (as revised 3/15/84)

COMPLETED BY C. A. Morris TELEPHONE (714) 492-7700 Ext. 56264 OPERATING STATUS 1.

Unit Name: San Onofre Nuclear Generating Station, Unit 2 2.

Reporting Period:

1 September 1983 through 30 September 1983 3.

Licensed Thermal Power (MWt):

3,390 4.

Nameplate Rating (Gross MWe):

1,127 5.

Design Electrical Rating (Net MWe):

1,070 6.

Maximum Dependable Capacity (Gross MWe):

1,127 7.

Maximum Dependable Capacity (Net MWe):

1,070_ _

8.

If Changes Occur In Capacity Ratings (Items Number 3 Through 7)

Since Last Report, Give Reasons:

NA 9.

Power Level To Which Restricted, If Any (Net MWe):

NA 10.

Reasons For Restrictions, If Any:

NA This Month Yr.-to-Date Cumulative l

11. Hours In Reporting Period 720 1296 1296 4

12.

Number Of Hours Reactor Was Critical 690.5 1266.5 1266.5 13.

Reactor Reserve Shutdown Hours 0

0 0

14.

Hours Generator On-Line 683.9 1259.9 1259.9 l

15.

Unit Reserve Shutdown Hours 0

0 0

16. Gross Thermal Energy Generated (MWH) 2,298,632-

,_4_,003,841 4,203,841

17. Gross Electrical Energy Generated (MWH) 792,200 1,451,958 1,451,958
18. Net Electrical Energy Generated (MWH) 755,500 1,397,128 1,397,128
19. Unit Service Factor 95.0 97.2 97.2
20. Unit Availability Factor 95.0 97.2 97.2
21. Unit Capacity Factor (Using MDC Net) 98.1 100.8 100.8 22.

Unit Capacity Factor (Using CER Net) 98.1 100.8 _

100.8

23. Unit Forced Outage Rate 5.0 2.8 2.8 24.

Shutdowns Scheduled Over Next 6 Months (Type, Date, and Duration of Each):

18-month surveillance outage, November 15, 1983, 1-month duration.

25.

If Shut Down At End Of Report Period, Estimated Date of Startup:

26.

Units In Test Status (Prior To Commercial Operation):

Forecast Achieved INITIAL CRITICALITY NA NA INITIAL ELECTRICITY NA NA COMMERCIAL OPERATION NA NA R

AVERAGE DAILY UNIT POWER LEVEL DOCKET NO.

50-361 UNIT SONGS - 2 DATE 10/17/83 (as revised 3/15/83)

COMPLETED BY C. A. Morris TELEPHONE-(714) 492-7700 Ext. 56264=

MONTH: September 1983 DAY AVERAGE DAILY POWER LEVEL DAY AVERAGE DAILY POWER LEVEL.

(MWe-Net)

.(MWe-Net) 1 1136.67 17 1112.54 2

896.44 18 1113.33 3

0 19 1105.15 4

495.65 20 1120.00 5

1124.48 21 1107.42 6

1118.75 22 1110.00 7

1127.56 23 1090.42 8

1121.27 24 1119.06 9

1103.46 25 1131.25 10 1124.58 26 1107.81 11 1176.5?

27 1115.83 12 1114.79 28 1117.50 13 1125.42 29 1110.42 14 1115.00 30 ___

1116.88 15 1121.67 31 16 1088.02 0565u

UNIT SHUTDOWNS AND POWER REDUCTIONS DOCKET NO. 50-361 UNIT NAME SONGS - 2 REPORT MONTH SEPTEMBER, 1983

. DATE 10/17/83 f a s revised 3/15/84)

COMPLETED BY C,_Am _Mo r r i s TELEPHONE (714) 492-7700 Ext. 56264 Method of Shutting Du ra t ion Down LER System Component Cause & Corrective 1

2 3

4 5

Action to No.

Date

. Type (Hours)

Reason Reactor No.

Code Code Prevent Recurrence 22

.830902 F

36.1 H

3 NA HA INSTRU-Unit tripped when all of the governor valvos closed while the computers which ca lculate the position of the high pressure turbine governor va lves were being synch ron i zed.

As currectfve action, outputs of the three computing channels were monitored with simulated inputs, and the channel synchronization operation was tested prior to 55% reactor power.

O 1

2 3

4 F-Fo rced Reason:

Method:

Exhibit F - Instructions S-Scheduled A-Equipment Fa ilure ( Expla in) 1-Manual for Preparation of Data B-Maintenance or Test 2-Manua l Scram.

Entry Sheets for Licensee

.C-Refueling 3-Automatic Scram.

Event Report (LER) File

' D-Regulatory Restriction

. 4-Continuation f rom (NUREG 0161)

- E-Operator Training & License Examination Previous Month F-Adm i n i st ra t ive 5-Reduction of 20%

5 G-Ope ra t iona l Er ro r. ( Exp l a in) or greater in the Exhibit H-Same Source H-Other ( Expla in) past 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> 6-Other (Explain) 0565u.

__