Proposed Tech Spec Changes to Table 15.3.5-1,Item 10 Re Voltage Settings & Time Delay Settings
ML20052C230
Person / Time
Site: Point Beach  
Issue date: 04/27/1982
From:
WISCONSIN ELECTRIC POWER CO.
To:
Shared Package
ML20052C216 List:
References
TAC-48375, TAC-48376, NUDOCS 8205040518
Download: ML20052C230 (1)


Text

T

, 95100 OPJ i

23 0 3

y$

TABLE 15.3.5-1 (Continued)

(Page 2 of 2) 3

K rc)

OutD Q

NO.

FUNCTIONAL UNIT CHANNEL SETTING LIMIT Ob

'. 'hk$

9.

Degraded Voltage (4.16 KV)

Disconnection of affected

> 3762 volts +2%

bus from offsite power Time delay:,less than 30 sec at 0-100% of voltage setting **

10.

Loss of Voltage a.

4.16 KV Disconnection of affected a.

2450 volts +3%

bus from offsite power Time delay:

5,0.4 sec. +10%

Start Diesel at 0 volts 5,1.2 sec. +20% at 90% of voltage setting b.

480 V Load shedding b.

256 volts +3%

Time delay:

<0.75 sec. +10%

.l at 0 volts i

<3.5 sec. +20 at 90% of voltage setting

    • Within 6 months of the effective date of this amendment (January 11, 1982) the licensee will submit further justification for this voltage setpoint and time delay or a proposed Technical Specification change for Units 1 and 2.

The January 11, 1982 effective date is for Unit 1 only. For Unit 2 this limit is effective upon installation of the associated relays but in no case later than upon return to power from the spring 1982 refueling outage.