ML20052C230
Person / Time
Site: Point Beach  NextEra Energy icon.png
Issue date: 04/27/1982
From:
WISCONSIN ELECTRIC POWER CO.
To:
Shared Package
ML20052C216 List:
References
TAC-48375, TAC-48376, NUDOCS 8205040518
Download: ML20052C230 (1)


Text

T

, 95100 OPJ -

i 23 0 y$ TABLE 15.3.5-1 (Continued)

  • 3 (Page 2 of 2) 3
K r c)

O utD Q

Ob NO. FUNCTIONAL UNIT CHANNEL SETTING LIMIT

9. Degraded Voltage (4.16 KV) Disconnection of affected > 3762 volts +2%

'. 'hk$

& bus from offsite power Time delay: ,less than 30 sec at 0-100% of voltage setting **

10. Loss of Voltage
a. 4.16 KV Disconnection of affected a. 2450 volts +3%

bus from offsite power Time delay: 5,0.4 sec. +10%

Start Diesel at 0 volts 5,1.2 sec. +20% at 90% of voltage setting

b. 480 V Load shedding b. 256 volts +3%

Time delay: <0.75 sec. +10% .l at 0 volts i

<3.5 sec. +20 at 90% of voltage setting

    • Within 6 months of the effective date of this amendment (January 11, 1982) the licensee will submit further justification for this voltage setpoint and time delay or a proposed Technical Specification change for Units 1 and 2. The January 11, 1982 effective date is for Unit 1 only. For Unit 2 this limit is effective upon installation of the associated relays but in no case later than upon return to power from the spring 1982 refueling outage.