Request for: Approved, Closed | |
Questions Answers Results Other: 05000266/LER-1982-009-03, /03L-0:on 820408,4.16-kV Safeguards Undervoltage Relays Did Not Meet 0-volt Time Delay Spec.Caused by Manufacturer Characteristic Curves.Relays Not Capable of Less than 0.38-s.Tech Spec Change Requested on 820427, 05000301/LER-1982-003, Forwards LER 82-003/03L-0, 05000301/LER-1982-003-03, /03L-0:on 820510,during Periodic Testing of Safeguards Protective relays,4 Kv Undervoltage Relays Were Outside Tech Spec Limits.Caused by Limitations of Relays. Relays Adjusted, ML20052C230, ML20078R173, ML20100J065 | |
| From | |
MONTHYEARML20052C2301982-04-27027 April 1982
[table view]Proposed Tech Spec Changes to Table 15.3.5-1,Item 10 Re Voltage Settings & Time Delay Settings ML20052C2151982-04-27027 April 1982 Application for Amend to Licenses DPR-24 & DPR-27, Incorporating Changes to Tech Specs Re Voltage Settings & Time Delay Settings 05000266/LER-1982-009-03, /03L-0:on 820408,4.16-kV Safeguards Undervoltage Relays Did Not Meet 0-volt Time Delay Spec.Caused by Manufacturer Characteristic Curves.Relays Not Capable of Less than 0.38-s.Tech Spec Change Requested on 8204271982-05-0707 May 1982 /03L-0:on 820408,4.16-kV Safeguards Undervoltage Relays Did Not Meet 0-volt Time Delay Spec.Caused by Manufacturer Characteristic Curves.Relays Not Capable of Less than 0.38-s.Tech Spec Change Requested on 820427 05000301/LER-1982-003, Forwards LER 82-003/03L-01982-06-0808 June 1982 Forwards LER 82-003/03L-0 05000301/LER-1982-003-03, /03L-0:on 820510,during Periodic Testing of Safeguards Protective relays,4 Kv Undervoltage Relays Were Outside Tech Spec Limits.Caused by Limitations of Relays. Relays Adjusted1982-06-0808 June 1982 /03L-0:on 820510,during Periodic Testing of Safeguards Protective relays,4 Kv Undervoltage Relays Were Outside Tech Spec Limits.Caused by Limitations of Relays. Relays Adjusted ML20072J6891983-03-23023 March 1983 Application for Amend to Licenses DPR-24 & DPR-27,modifying 820427 Tech Spec Change Request 77 Re Loss of Voltage Protective Relays ML20078R2291983-10-31031 October 1983 Safety Evaluation Supporting Amends 78 & 82 to Licenses DPR-24 & DPR-27,respectively ML20078R1731983-10-31031 October 1983 Amends 78 & 82 to Licenses DPR-24 & DPR-27,revising Tech Specs Re Loss of Voltage Relay Setpoints & Associated Time Delays ML20100J0651984-12-0404 December 1984 Responds to 831031 Amends 78 & 82 to Licenses DPR-24 & DPR-27,respectively,re Installation of New 4,160-volt Loss of Voltage Relays.Installation Completed During Steam Generator Replacement & Refueling Outage 1982-06-08 | |
Retrieved from "https://kanterella.com/w/index.php?title=TAC:48375&oldid=5496446"