05000317/LER-1982-084-03, /03L-0:on 821223,sequencer Initiated Alarm Failed to Clear When Diesel Generator 12 Shut Down.Caused by Failure of Breaker Lever to Operate Auxiliary Switch in Cubicle Due to Displaced Assembly.New Assembly Installed

From kanterella
(Redirected from ML20028F439)
Jump to navigation Jump to search
/03L-0:on 821223,sequencer Initiated Alarm Failed to Clear When Diesel Generator 12 Shut Down.Caused by Failure of Breaker Lever to Operate Auxiliary Switch in Cubicle Due to Displaced Assembly.New Assembly Installed
ML20028F439
Person / Time
Site: Calvert Cliffs 
Issue date: 01/21/1983
From: Basso L, Junge M
BALTIMORE GAS & ELECTRIC CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
Shared Package
ML20028F433 List:
References
LER-82-084-03L, LER-82-84-3L, NUDOCS 8302010354
Download: ML20028F439 (2)


LER-1982-084, /03L-0:on 821223,sequencer Initiated Alarm Failed to Clear When Diesel Generator 12 Shut Down.Caused by Failure of Breaker Lever to Operate Auxiliary Switch in Cubicle Due to Displaced Assembly.New Assembly Installed
Event date:
Report date:
3171982084R03 - NRC Website

text

NRC FORM 366 U. S. NUCLEAR RE!UL ATORY COMMISSION (7 71).

  • 1CENSEE EVENT REPORT CONTROL BLOCK: l l

l l

l l

lh (PLEASE PRINT CR TYPE ALL REQUIRED INFtRMATILN) 1 6

l M l D l C l C l te l 1 l@[0_d0 l-l 0 l 0 l 0 l 0 l 0 l-l 0 l 0 l@l 4 l 1 l 1 l 1 l L]@i l

I@

0 1 i 7 8 9 LICENSEE CODE 14 15 LICENSE NUM8ER

?S 26 LICENSE TYPE _ JO 57 CAT 58 CON'T 10111 3$n"c' l L @l 0 l 5 l 0 l 0 l 013 l 1 l 7 l@l 1 l 212 l 3 l 812 l@l011 l 2 l 1 18 l 3 l@

?

8 60 61 DOCKET NUMBER 68 69 EVENT DATE 74 75 REPORT DME 80 EVENT DESCRIPTION AND PROB ABLE CONSEQUENCES h o 2 l At 1815 during normal operation. f.Le seauencer initiated alarm did not-l J

IO I3 l l clear when 12 diesel generator (DG) was shut down (T.S. 3.8.1.1). With j

l0 l4 l l 11 DG out of service for maintenance, 12 DG aligned to 11 4KV bus.. 11 l

l0l5l l Control Roon. Air Conditioner (CRAC) was without an emergency power l

10 le l I source (T.S. 3.0.5).

At 1855, 12 DG was aligned to 14 4KV bus and I

{7_l l raturned to service. At 2130, 11 DG was returned to service ord 11 CRAC l

l O la J l was declared operable. Similar events: None.

I 80 7

8 9 DE CODE S BC DE COMPONENT CODE SUSC D'E S

E l TIT,I l E-l E lh lE lh lB lh l Cl Kl Tl Bl Rl Klh Wh W h 7

8 9

D) 11 12 13 18 19 20 SEQUENTIAL OCCURRENCE REPORT HEVISION LE R !Ro EVENT YE AR REPORT NO.

CODE TYPE N O.

6 0ug l218l 2l

[-j l 0l 8l 4l y

l0l3l [L_j

[--J

.J t

22 23 24 26 27 M

M-30 31 32 AK N AC O O PL NT M

HOURS 22 S8 I FOR 8.

SUPPL 1 R MANUF CTURER l AlgJ@ J@

J@

(0l0l0l1l W@

W@

W@

l Gl 0l 8l 0l@

J3 34 35 36 3r 40 41 42 43 44 47 CAUSE DESCRIPTION AND CORRECTIVE ACTIONS 27 li l0 l l Investigation found the " Sequencer Initiated" alarm hanging due to fail-l i i l

ure of a lever on the breaker (General Electric MC-4.76) to operate an 1

3 i ; l auxiliary switch in the cubicle. A retaining ring holding a cam & link-l [i l3l l age assembly Q place hac slipped off, displacing the assemtly. A new l

li l4 l l assembly was installed. No further action is planned et this time.

l 7

8 9 80 ST S

% POWE R OTH ER STATUS IS O SISCOVERY DESCRIPTION 3 W W @ l1l0l0l@l NA l

W @l Operator Jbservation l

A TlVITY CO TENT RELEASED OF RELEASE M90UNT OF ACTIVITY LOCATION OF RELEASE NA l

l NA l

M [Jf_] h l_Z_l @ l 7

8 9 10

1 44 d5 80 PERSONNEL EXPOdVRES l 0 l 0 l 0 lhl Z lhlDESCRtPTION NUMBER TYPE NA l

1 7 7

PERSONNE L INJU IES NUMBER

DESCRIPTION

NA l

l0l0l0lhl i a 7

8 9 11 12 80 LOSS OF OR DAMAGE TO FACILITY TYPE

DESCRIPTION

NA l

lzl@l i 9 7

8 9 10 80 PUBLICITY 8302010354 830121 NRC USE ONLY DESCRIPTION,

PDR ADOCK 05000317 ISSUED [N_jhl S

PDR l

lllllllllllll$

2 O 7

8 9 10 68 69 80 5 301-269-4969/4933,

{

NAME OF PREPAREHy. A. Angen. F. Basso PHONE:

+.

LER NO.

82-84 DOCKET NO.59-317 LICENSE NO.

DPR-53 EVENT DATE 12/23/82 REPORT DATE 01/21/83 ATTACIMENT'

EVENT DESCRIPTION

At 1815 during norrsl operation, upon ecuptation of testing #12 i

diesel tenerator (DG) on #17. 4KV bus, the "Sequencet Initiated" alarm

~

j did not clear when the diesel output breaker was opened.

,i2 DG was i

i declared; inoperable (T.S. 3.8.'1.1) when investigation revealed the sequencer would not initiate as designed. With 12 DG aligned to #11 i

4KV bus, and #11 DG out of service for maintenance, #11 Control Room Air Conditioner was left without an emergency power source.

(T.S.3.0.5 and T.S. 3.7.6.1).

At 1855, #12 DG was returned to service when it waar aligned to #14 4KV bus.; AcL2015, action was initiated to place the reactor in Mode 3 as per T.S. 3.0.5.

At 2130 #11 vG was returned to service,.

  1. 11 CRAC was declared ope.*able and the reactor returned to 100% power.

j

Similar events

None.

i 9

t CAUSE DESCRIPTION Investigation found that clearance of the "Sequ4ncer Initiated" alarm was prohibited by failure of a, lever on the breaker (General Electric

?

MC-4.76) to operate an auxiliary switch. mounted in the switch-gear cuolcle. A retaining ring that holds the auxiliary switch operating cams and linkag+ assembly in place had slipped off, dislocating the i

assenbly. The assembly was replaced with_a spare. No cause has been

~

l founi.for the failure of the retaining ring.

Sin <2 this is the tirst such failure, no further preventive action is deemed necer,8ary 1