LER-1981-046, Forwards LER 81-046/03L-0.Detailed Event Analysis Encl |
| Event date: |
|
|---|
| Report date: |
|
|---|
| 2191981046R00 - NRC Website |
|
text
3
//A' OYSTER CREEK i
NUCLEAR GENERATING STATION d
ShlW97
T.{.,.~
(609)693-6000 P O BOX 388
- 08731 October 21, 1981 Mr. Ponald Haynes, Director Office of Inspection and Enforement negion I United States Nuclear Pegulatory Comnission 631 Park Avenue King of Prussia, Pennsylvania 19406
Dear Mr. Haynes:
SUBJDCT: Oyster Creek Nuclear Generating Station Docket No. 50-219 Licensee Event Report Reportable Occurrence No. 50-219/81-46/3L This letter forwards three copies of a Licensee Event Report to report Report.21e Occurrence No. 50-219/81-46/3L in capliance with paragraph 6.9.2.r.2 of the 'Ibchnical Specifications.
Very truly yours,
- - f
$b8A<
J. T. Carroll, Jr Acting Director ster Creek JIC:dh v
J.\\ g s.' ' 'Dl f U
Enclosures (h[N V cc: Director (40 copies) s Office of Inspection and Enforcement
.C NLlJJ [
N United States Nuclear Regulatory Cm mission 2
NOVO 2193jw 4 Washington, D.C.
20555 N9', v.s. m a m a g/
j
^
Director (3)
Office of Managment Information I,
<[
and Program Control
,' gr-t [7,- '
< d' United States Nuclear Regulatory Coninission Washington, D. C. 20555 NRC Resident Inspector (1)
Oyster Cicek Nuclear Generating Station Forked River, N. J.
ohoch$f9 g$
O PDR
'/
-(
~
t*
^
OYSTEP CREEK NUCLEAR GENERATING STATICH Forked River, New Jersey 08731 Licensee Event Report.
Reportable Occurrence No. 50-219/81-46/3L U'
Report Date 4
October 21, 1981 i
Cecurrence Date Septenber 20, 1981 and Septenbo.r 25, 1981 s
, x s
Identification of Occurrence N
During the functional testing of hydraulic snubbers, three'(3) cnubbers 'in the f
^
Shutdown Cooling Systen were found with drag loads outside of acceptable limit.3,'.% s and one of the three also failed in the canpression mode. 'Ihis condition is '
N permitted per Technical Specifications section 3.5.A.8 as a limitincycondition -
for operati.on.
1#
s This event is considered to be a reportable occurrence as defined in the Tschnical.
Specifications, paragraph 6.9.2.b.2.
/
s 4
Oonditions Prior to Occurrence
,'.m 3
u e y
The plant was in the cold shutdown condition.
\\\\
__s Descriptinja 0: cur g c;
.g.(
On Seputnbor 20 at 1600 hours0.0185 days <br />0.444 hours <br />0.00265 weeks <br />6.088e-4 months <br />, hydraulic snubber #51/18 (serial #477253) locatal -
in Shuuown Cooling Systen Icop B, failed its functional test in the ccanpression mode and also could not obtain drag lmd within acceptable linits. Also, snubber
- 51/17 (cerial #487438) in Shutdown Cooling Systen Icop C failed to obtain drag load within acceptable limits. On Septanber 25 at 1600 hours0.0185 days <br />0.444 hours <br />0.00265 weeks <br />6.088e-4 months <br />, snubber #51/19
~
(serial #F93502) in Shutdown Cooling Systen Icop A could not. cbtain drag load within acceptable limits. All snubbers were disassenbled and inspected to determino failure mechanisms.
~~
g ent Cause of Occurrence An inspection of snubber 51/18 revealed rust on the piston head, dirty oil, ard -
a crack in a brass ring on the head cover. Snubber 51/17 was found with a faulty 0-ring, dirty oil, and a scored piston cylinder. Snubber 51/19 was foand to have oil lerJeage around the piston at the top seal assa;bly.
Analysis of Ocmrrence Hydraulic snubbers are installed to limit piping movetent durjng seismic events -
and during transient conditions. Another function is the ability of the piston to move freely during normal operation to ccurpensate for thermal expansion or contraction. All 3 snubbers are nounted in the same manner for each loop; all are perpendicular to the piping and are mounted frcun r.he floor to the piping r
,a
~
v n-c.
....3 J
' (*
.. }
a yO b Page 2 Report 21e Occurrence
),,
s Report No. 30-219/81-4y/36,m.'(,
f
- +
. r
'g.s
. ' p. 1 i.T alnost hcdsontally." Tnb.pihing lines are the liistarge lihes frm the Shutdown Jtich rxi horizontally for approximately 20 feet and Cooling heat exchaire.rs] )M!.pdO. feet to a carmon outlet header.
then verticaiWighto'xim
'Ihere is a
- ~
saniter on each vert.ical lincEdvistreai of the failed snubtors and a pipe supgcrt upstream of the failed snubbers.
I Considering theffact that the plant was in onld shutdown and the Shutdown Cooling
. )n-Systs was ont of service'ior maintenance work, the safety significance of the C
Mont is censidept mininni.s If the plant, had beea shutdown with the Shutdown Cooling Syste'a in operatica), sthe safety significar.a would have been rdnimal
,. ' f' 4 because the piping novemmt, oue to thermal expansion /codtraction would have been in a direction widch would not be affected by the failure of the snnWrs.
In a
"D the event of "a sftatic event, the safety significance would be minimal because the snubbers would have acted as a rigid sap'jort and would properly restrict
'g,.' piping movment.
m n "7 )
$, C,orrective Actinn f-j+g s.
\\
(
},
,[
k j.
1,', All' 3 anubbers uure replacud withl'.perti,14 sptr(s. !'fhe present' number of snubber V-t' "ailures require.1 1000 testing of snubbers in.adoccxiance with the Technical
' Specifications.- Present plans are tq ccmplete testing of the rernaining snubbers, or replace thm with ncVunits, by DeWr. 15; 1981^.',)\\
L Yf
~';
'y
!(,
'O Y
?
I-:
y
- Q Manufacturer - Bergen4stterson Pipempyr1 CLrp.
Podel 1 HSSA-10 (max.10,600"1bs force) s. k-
"s f
j'*
g g
wg ;,
8 y
i y
l
}s.,
(
z',
E,V
\\
s I
I
's 7'/
I l'
V
!s
/,
s
}
,\\
g i1 ' i,,.
_it V
'y,, t s,
W i 3,
6 4
L t
.c a
/.
i
+
g g
h a'
g 1
},'
.f
.i q.
s
+
e i
h y
i f,.
s w%
A 4,=
4 T
\\
4
_ _. _ -. _.. - _. _ - - _ _ _. _ _ _ _ -.. - _ _ -.. - _ _, -. _ _ _. _ _ _ - - -. - - - - - - _ _ _ -. _ _ _. _ _ ~. _ _ _ _ _ _ -. -.. _ _ _ _ -. _ _ _ _ _ _ _. _ _. -. - - _ - _ _ -.. _.... _ _.
|
|---|
|
|
| | | Reporting criterion |
|---|
| 05000219/LER-1981-001-03, /03L-0:on 810102,containment Spray Sys High Drywell Pressure Indicating Switch IP-15C Tripped Above Tech Spec Limits.Caused by Instrument Repeatability.Switch Reset & Study Examining Causes of Repeatability Undertaken | /03L-0:on 810102,containment Spray Sys High Drywell Pressure Indicating Switch IP-15C Tripped Above Tech Spec Limits.Caused by Instrument Repeatability.Switch Reset & Study Examining Causes of Repeatability Undertaken | | | 05000219/LER-1981-001, Forwards LER 81-001/03L-0 | Forwards LER 81-001/03L-0 | | | 05000219/LER-1981-002, Forwards LER 81-002/03L-0 | Forwards LER 81-002/03L-0 | | | 05000219/LER-1981-002-03, /03L-0:on 810102,gaseous Releases to Stack Found Not Continuously Monitored as Required by Tech Spec.Caused by Tripping of Stack Gas Sample Pump Due to Normal Wear.Pump Replaced W/Spare | /03L-0:on 810102,gaseous Releases to Stack Found Not Continuously Monitored as Required by Tech Spec.Caused by Tripping of Stack Gas Sample Pump Due to Normal Wear.Pump Replaced W/Spare | | | 05000219/LER-1981-003-03, /03L-0:on 810112,during Visual Insp of Fire Hydrants,Hydrant 2 Found to Contain Frozen Water in Barrel, Rendering Hydrant Inoperable.Caused by Water Leaking from Hydrant Valve & Freezing in Barrel.Hydrant Thawed | /03L-0:on 810112,during Visual Insp of Fire Hydrants,Hydrant 2 Found to Contain Frozen Water in Barrel, Rendering Hydrant Inoperable.Caused by Water Leaking from Hydrant Valve & Freezing in Barrel.Hydrant Thawed | | | 05000219/LER-1981-003, Forwards LER 81-003/03L-0 | Forwards LER 81-003/03L-0 | | | 05000219/LER-1981-004, Forwards LER 81-004/01T-0 | Forwards LER 81-004/01T-0 | | | 05000219/LER-1981-004-01, /01T-0:on 810116,studies Indicated That Emergency Diesel Generators May Exceed Load Rating During Accident Conditions.Caused by Using Different & More Conservative Methods to Calculate Load.Actions to Reduce Load Underway | /01T-0:on 810116,studies Indicated That Emergency Diesel Generators May Exceed Load Rating During Accident Conditions.Caused by Using Different & More Conservative Methods to Calculate Load.Actions to Reduce Load Underway | | | 05000219/LER-1981-005-03, /03L-0:on 810106,emergency Svc Water Pump 52B Current & Discharge Pressure Found Outside Tech Spec. Probably Caused by Clogged Pump Suction Strainer.Strainer Cleared | /03L-0:on 810106,emergency Svc Water Pump 52B Current & Discharge Pressure Found Outside Tech Spec. Probably Caused by Clogged Pump Suction Strainer.Strainer Cleared | | | 05000219/LER-1981-005, Forwards LER 81-005/03L-0 | Forwards LER 81-005/03L-0 | | | 05000219/LER-1981-006-03, /03L-0:on 810115,during Surveillance Testing, Reactor Triple Low Water Level Indicator Switch RE-18B Tripped at Monometer Reading Higher than Allowed by Tech Spec Table 3.1.1.Caused by Instrument Drift.Switch Reset | /03L-0:on 810115,during Surveillance Testing, Reactor Triple Low Water Level Indicator Switch RE-18B Tripped at Monometer Reading Higher than Allowed by Tech Spec Table 3.1.1.Caused by Instrument Drift.Switch Reset | | | 05000219/LER-1981-006, Forwards LER 81-006/03L-0 | Forwards LER 81-006/03L-0 | | | 05000219/LER-1981-007-03, /03L-0:on 810202,water-tight Door to Containment Spray Sys I Compartment Not Closed & Verification of Closed Door Not Performed.Caused by Personnel Error & Lack of Controls to Ensure Doors Are Closed After Passage | /03L-0:on 810202,water-tight Door to Containment Spray Sys I Compartment Not Closed & Verification of Closed Door Not Performed.Caused by Personnel Error & Lack of Controls to Ensure Doors Are Closed After Passage | | | 05000219/LER-1981-007, Forwards LER 81-007/03L-0 | Forwards LER 81-007/03L-0 | | | 05000219/LER-1981-008, Forwards LER 81-008/03L-0 | Forwards LER 81-008/03L-0 | | | 05000219/LER-1981-008-03, /03L-0:on 810210,water Seepage Observed Along West Wall of Nrw Bldg.Direct Survey Showed Detectable Ground Contamination Only within 6 Inches of Wall.Caused by High Levels in Tank Vaults.Herculite Secured & Sealed to Wall | /03L-0:on 810210,water Seepage Observed Along West Wall of Nrw Bldg.Direct Survey Showed Detectable Ground Contamination Only within 6 Inches of Wall.Caused by High Levels in Tank Vaults.Herculite Secured & Sealed to Wall | | | 05000219/LER-1981-009, Forwards LER 81-009/03L-0.Detailed Event Analysis Submitted | Forwards LER 81-009/03L-0.Detailed Event Analysis Submitted | | | 05000219/LER-1981-009-03, /03L-0:on 810213,snubber 23/3 Found W/Very Low Oil Level & Oil Discovered on Floor at Base Connection During NRC walk-around Insp.Caused by Failure of Inner Shaft Seal Due to Deterioration.Snubber Replaced W/Operable Spare | /03L-0:on 810213,snubber 23/3 Found W/Very Low Oil Level & Oil Discovered on Floor at Base Connection During NRC walk-around Insp.Caused by Failure of Inner Shaft Seal Due to Deterioration.Snubber Replaced W/Operable Spare | | | 05000219/LER-1981-010, Forwards LER 81-010/03L-0 | Forwards LER 81-010/03L-0 | | | 05000219/LER-1981-010-03, /03L-0:on 810202,during Routine Surveillance Testing,Main Steamline High Radiation Monitor RN-06B Tripped at Value Higher That Tech Spec Limits.Caused by Failure to Revise Trip Settings.Trip Settings Lowered | /03L-0:on 810202,during Routine Surveillance Testing,Main Steamline High Radiation Monitor RN-06B Tripped at Value Higher That Tech Spec Limits.Caused by Failure to Revise Trip Settings.Trip Settings Lowered | | | 05000219/LER-1981-011, Forwards LER 81-011/03L-0.Detailed Event Analysis Encl | Forwards LER 81-011/03L-0.Detailed Event Analysis Encl | | | 05000219/LER-1981-011-03, /03L-0:on 810309,isolation Condenser Condensate Return Line Pipe Break Sensor IB11B2 Found to Trip at Value Greater than That Specified in Tech Specs.Caused by Instrument Repeatability.Replacement Recommended | /03L-0:on 810309,isolation Condenser Condensate Return Line Pipe Break Sensor IB11B2 Found to Trip at Value Greater than That Specified in Tech Specs.Caused by Instrument Repeatability.Replacement Recommended | | | 05000219/LER-1981-012-03, /03L-0:on 810313,electromatic Relief Valve High Pressure Actuation Switches 1A83C & 1A83E Tripped Higher than Limit Specified in Tech Spec.Caused by Instrument Repeatability.Pressure Sensors Reset to Trip within Limits | /03L-0:on 810313,electromatic Relief Valve High Pressure Actuation Switches 1A83C & 1A83E Tripped Higher than Limit Specified in Tech Spec.Caused by Instrument Repeatability.Pressure Sensors Reset to Trip within Limits | | | 05000219/LER-1981-012, Forwards LER 81-012/03L-0.Detailed Event Analysis Encl | Forwards LER 81-012/03L-0.Detailed Event Analysis Encl | | | 05000219/LER-1981-013-03, /03L-0:on 810319,core Spray Hi Drywell Pressure Switch RV46B Tripped in Excess of 2 Psi Tech Spec.Caused by Sensor Repeatability.Sensor Recalibr.Replacement of Sensors Recommended by PORC | /03L-0:on 810319,core Spray Hi Drywell Pressure Switch RV46B Tripped in Excess of 2 Psi Tech Spec.Caused by Sensor Repeatability.Sensor Recalibr.Replacement of Sensors Recommended by PORC | | | 05000219/LER-1981-013, Forwards LER 81-013/03L-0.Detailed Event Analysis Encl | Forwards LER 81-013/03L-0.Detailed Event Analysis Encl | | | 05000219/LER-1981-014, Forwards LER 81-014/01T-0.Detailed Event Analysis Encl | Forwards LER 81-014/01T-0.Detailed Event Analysis Encl | | | 05000219/LER-1981-014-01, /01T-0:on 810401,containment Oxygen Concentration Was Not Reduced to Less than 5% within 24-h After Placing Reactor Mode Switch in Run.Caused by Inerting at Significantly Reduced Rates | /01T-0:on 810401,containment Oxygen Concentration Was Not Reduced to Less than 5% within 24-h After Placing Reactor Mode Switch in Run.Caused by Inerting at Significantly Reduced Rates | | | 05000219/LER-1981-015-03, /03L-0:on 810324,main Steam Line High Flow Sensors Tripped at Values Greater than Tech Specs Limit.Caused by Instrument Repeatability.Both Sensors Reset | /03L-0:on 810324,main Steam Line High Flow Sensors Tripped at Values Greater than Tech Specs Limit.Caused by Instrument Repeatability.Both Sensors Reset | | | 05000219/LER-1981-015, Forwards LER 81-015/03L-0.Detailed Event Analysis Encl | Forwards LER 81-015/03L-0.Detailed Event Analysis Encl | | | 05000219/LER-1981-016-03, /03L-0:on 810421,approx 10,000 Gallons of Leakage from Condensate Transfer Pump Bldg Was Discovered on North & South Sides of Bldg.Caused by Loss of Valve Packing on V-2-88.Leakage Was Diked & Valve Repacked | /03L-0:on 810421,approx 10,000 Gallons of Leakage from Condensate Transfer Pump Bldg Was Discovered on North & South Sides of Bldg.Caused by Loss of Valve Packing on V-2-88.Leakage Was Diked & Valve Repacked | | | 05000219/LER-1981-016, Forwards LER 81-016/03L-0 | Forwards LER 81-016/03L-0 | | | 05000219/LER-1981-017, Forwards LER 81-017/03L-0.Detailed Event Analysis Encl | Forwards LER 81-017/03L-0.Detailed Event Analysis Encl | | | 05000219/LER-1981-017-03, /03L-0:on 810415,one Containment Spray Sys Loop Considered Inoperable During Normal Operation.Caused by Large Amount of Sea Lettuce in Intake Canal,Overwhelming Trash Removal Sys.Circulating Water Pump Stopped | /03L-0:on 810415,one Containment Spray Sys Loop Considered Inoperable During Normal Operation.Caused by Large Amount of Sea Lettuce in Intake Canal,Overwhelming Trash Removal Sys.Circulating Water Pump Stopped | | | 05000219/LER-1981-018, Forwards LER 81-018/01T-0.Detailed Event Analysis Encl | Forwards LER 81-018/01T-0.Detailed Event Analysis Encl | | | 05000219/LER-1981-018-01, /01T-0:on 810417,equipment Operator Found Valves Were Blocked from Fully Opening by Scaffolding Placed by Contractor Personnel.Caused by Personnel Error.Scaffolding Repositioned | /01T-0:on 810417,equipment Operator Found Valves Were Blocked from Fully Opening by Scaffolding Placed by Contractor Personnel.Caused by Personnel Error.Scaffolding Repositioned | | | 05000219/LER-1981-019-03, /03L-0:on 810328,during Normal Shutdown Sequence, IRM Calibr Was Not Performed as Required by Tech Specs. Caused by Procedural Inadequacy.Procedures Will Be Revised | /03L-0:on 810328,during Normal Shutdown Sequence, IRM Calibr Was Not Performed as Required by Tech Specs. Caused by Procedural Inadequacy.Procedures Will Be Revised | | | 05000219/LER-1981-019, Forwards LER 81-019/03L-0 | Forwards LER 81-019/03L-0 | | | 05000219/LER-1981-020-03, /03L-0:on 810501,isolation Condenser Shell Level Instrument IGO6B Found Reading High During Annual Calibr. Caused by Evaporation of Instrument Ref Column.Column Backfilled W/Water to Normal Operating Level | /03L-0:on 810501,isolation Condenser Shell Level Instrument IGO6B Found Reading High During Annual Calibr. Caused by Evaporation of Instrument Ref Column.Column Backfilled W/Water to Normal Operating Level | | | 05000219/LER-1981-020, Forwards LER 81-020/03L-0.Detailed Event Analysis Encl | Forwards LER 81-020/03L-0.Detailed Event Analysis Encl | | | 05000219/LER-1981-021, Forwards LER 81-021/03L-0.Detailed Event Analysis Encl | Forwards LER 81-021/03L-0.Detailed Event Analysis Encl | | | 05000219/LER-1981-021-03, /03L-0:on 810603,high Pressure Sensor Switches RE03B, C & D Were Found Tripping within 8 Lb of Setpoint. Caused by Sensor Repeatability.Switches Reset.Switches Will Be Replaced During Next Refueling Outage | /03L-0:on 810603,high Pressure Sensor Switches RE03B, C & D Were Found Tripping within 8 Lb of Setpoint. Caused by Sensor Repeatability.Switches Reset.Switches Will Be Replaced During Next Refueling Outage | | | 05000219/LER-1981-022-01, /01T-0:on 810520,secondary Containment Integrity Not Maintained Due to Personnel Access Airlock Doors Ajar. Caused by Personnel Error & Loosened Striker Plate on Inside Door.Outside Door Closed & Striker Plate Repaired | /01T-0:on 810520,secondary Containment Integrity Not Maintained Due to Personnel Access Airlock Doors Ajar. Caused by Personnel Error & Loosened Striker Plate on Inside Door.Outside Door Closed & Striker Plate Repaired | | | 05000219/LER-1981-022, Forwards LER 81-022/01T-0 | Forwards LER 81-022/01T-0 | | | 05000219/LER-1981-023-03, /03L-0:on 810603,drywell Vented to Reduce Drywell Torus Differential Pressure.Caused by Moisture Buildup in Sensing Line Resulting in Erroneous Indication of Increased Oxygen Concentration.Procedures Will Be Reviewed | /03L-0:on 810603,drywell Vented to Reduce Drywell Torus Differential Pressure.Caused by Moisture Buildup in Sensing Line Resulting in Erroneous Indication of Increased Oxygen Concentration.Procedures Will Be Reviewed | | | 05000219/LER-1981-023, Forwards LER 81-023/03L-0.Detailed Event Analysis Encl | Forwards LER 81-023/03L-0.Detailed Event Analysis Encl | | | 05000219/LER-1981-024-03, /03L-0:on 810608,while Operating in Degraded Mode, Two Emergency Water Pumps Found Inoperable.Caused by Faulty Ammeter,Clogged Pump Suction Bells & Inadequate Administrative Controls.Ammeter Replaced & Bells Cleaned | /03L-0:on 810608,while Operating in Degraded Mode, Two Emergency Water Pumps Found Inoperable.Caused by Faulty Ammeter,Clogged Pump Suction Bells & Inadequate Administrative Controls.Ammeter Replaced & Bells Cleaned | | | 05000219/LER-1981-024, Forwards LER 81-024/03L-0.Detailed Event Analysis Encl | Forwards LER 81-024/03L-0.Detailed Event Analysis Encl | | | 05000219/LER-1981-025-01, /01T-0:on 810617,secondary Containment Was Broken When Both Reactor Bldg Railroad Airlock Doors Were Opened Together.Caused by Failure of Top Inner Door Latch & Operator Error.Operators Will Be Reinstructed | /01T-0:on 810617,secondary Containment Was Broken When Both Reactor Bldg Railroad Airlock Doors Were Opened Together.Caused by Failure of Top Inner Door Latch & Operator Error.Operators Will Be Reinstructed | | | 05000219/LER-1981-025, Forwards LER 81-025/01T-0.Detailed Event Analysis Encl | Forwards LER 81-025/01T-0.Detailed Event Analysis Encl | |
|