05000321/LER-1981-045-03, /03L-0:on 810526,vacuum Relief Valves T48-F310 & F328A Found Leaking Excessively During Local Leak Rate Test. Caused by Leaking o-ring & t-ring.Rings Replaced,Valves Reassembled & Retested

From kanterella
(Redirected from ML20004F799)
Jump to navigation Jump to search
/03L-0:on 810526,vacuum Relief Valves T48-F310 & F328A Found Leaking Excessively During Local Leak Rate Test. Caused by Leaking o-ring & t-ring.Rings Replaced,Valves Reassembled & Retested
ML20004F799
Person / Time
Site: Hatch 
Issue date: 06/16/1981
From: Coggin C
GEORGIA POWER CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
Shared Package
ML20004F798 List:
References
LER-81-045-03L-01, LER-81-45-3L-1, NUDOCS 8106220409
Download: ML20004F799 (2)


LER-1981-045, /03L-0:on 810526,vacuum Relief Valves T48-F310 & F328A Found Leaking Excessively During Local Leak Rate Test. Caused by Leaking o-ring & t-ring.Rings Replaced,Valves Reassembled & Retested
Event date:
Report date:
3211981045R03 - NRC Website

text

M rrin n 3r,s U. S. NiJCLEAR RECULATORY COMMIS310N

- LICENSE 5 EVENT REPOR'T CON 1 Hot DLoCK: l _ l -l l

l l lh (PLEASE PRINT On TYPE ALL HEOUlHED INFORMAllON) l Gl Al El Il 11l 1l@l 0 l 0 l -l 0 l O l 0 l 01 O l - 101 O l@l 4 l 1 l 1 l I l l l@l l

l@

o 1 7

8 9

' LICL NME CODE 14 lb LICENSL NUMulH

?>

24, LICLNSE TYPL JO b7 LAI bat CoTT-

. S$ $ LIJ@l 0151 OI 0101312111GI 01__5121618111@l0 I 611 16 -1811 l@

0 1 i

8-00 GI DOCK Ei NUMBEH u

uJ EVLN T DATL 14 7b HEPOH1 DAlt t<0 EVENT DESCHIPTioN AND PHoDADLE CONSEQUENCES h o 2 10n 5-25-81, with Unit 1 shutdown for a refueling / torus modification out-l l age LLRTs of the vacuum relief valves T48-F310 and F328A were performed.l o 3 lo.141~10n 5-26-81, the LLRT coordinator reviewed the data sheets, ' and it was I

idetermined that the valves were leaking such that it would cause the l

o s o o 1.60 La overall allowable limit of Tech Specs 4.7. A.2.G to be exceeded.

I lo l71 IThis is a repetitive occurrence - refer to LER 50 321/1981-038.

There l

101s 1 faern no effects on public health or safety due to this event.

l S0 7

8 9

  • SII"
  • ^"o'c' s08EOoE susSEE SuSE'oe

^'

C CO COMPONtNT COoE ITIT]

lS lE l@ l_Ej@ l X l@ l V l A l L-l V l E l X l@ LC_j@ [C_l @

7 3

9 10 11 12 13 18 19 20 SEQUENTIAL OCCURRENCE REP 0RT REVISION LE R EVENT YE AR HEPOHT NO.

CODE TYPE N O.

. O",yj,g/HO18111 l-l 1014151 LdJ 10 13 I ILi 1-1 LOJ

_ 21 22 2J 24 26 27 28 M

30 31 32 KEt A Tl ON L 1 A1 T4 HOURS S B IT D FO A huD.

PLI k MAN IA T fen 1 A l@[2 j@

[Zj@

LZ_j@

l 01010 l 0 I l Yl@

l Y l@

l til@

l Fl 1131 Ol@

33 34 3b 3G 37 40 41 42 43 44 47 CAUSE DESCRIPTION AND CORRECTIVE ACTIONS h 11101 l An investigation conducted determined that the "0"

ring on the T48-F328Al 1 121 l valve and the "T"

rino on the T48-F310 valve were leakina.

These were I

i 121 l replaced.

Both valves were reassembled, retested, and left at a leakagel lil3l l of 400 accm.

The unit is now in full compliance with the requirements 04 l Tech Specs 4.7.A.2.G, and no further reporting is required.

I i 4 7

C 9 80 A S

% POWER OTHER STATUS IS V F DISCOVEHY DESCRIPTION W LcJO I 01 01 O l@l NA I

I cl @ l Performed LLRT l

  • AC%vivY Co'e a Nr d'

R( LE ASE D Ol' Id tt ASE AMOUNT Or ACTIVITY LOCAllON OF HELE ASE LZj @ [Zj@l NA l

l NA l

i o 7

8 9 10 tt 44 4b 80 PE f t%ONNEL TxPOSuttES Nut kit n TYPt DESCHIPilON 1010l Ol@LZJ@l NA l

i 2

,i nsONn. i',~,U,in S NUMHl H DESCHIPitON b' j l 01 01 Ol@l NA I

g l7 8 3 Il 12 CO LOSS OF Ost taAMAtit IO FACILITY 3)Pf LIL 5CittP f TON

. [ZJ@l NA l

l i 9 o,

o I

lttP f lON twOdt t@l NA l

llllllllllll1; L,t 2 o is

,o Ln v,

wu l-p1062g001 FHf I'Atti H b b._(099 kUdMP1. Pl k *.N9

  • bOEY
  • l'H ON E -

01?~ 3ra-7IC

4 LER #:

50-321/1981-045 Licensec:

Georgia' Power Company Facility Name:

Edwin I. Ilatch

. Docket #:

50-321 4

Narrative

Report for LER 50-321/1981-045 On 5-25-81, with Unit i shutdown ~ for a. refueling / torus modif-ication ' outage LLRTs of the vacuum relief valves T48-F310 and F328A were performed per'l!NP-1-3952, Primary Containment Peri-odic Type ' B and Type C Leakage Tests.

On 5-26-81, the data sheets were reviewed by the LLRT coordinator, and it was determined that the valves were 1 caking such that it would

cause

the.60 La_overall allowabic leakage limit of Tech Specs 4.7.A.2.G to be exceeded (as found leakage:

test volume would not pressurize).

This is is a repetitive occurrence - refer to-LER 50 321/1981-038.

There were no effects on public health or safety due to this event.

An investigation was conducted to determine the cause of -the valves leaking.

The "0" ring on T48-F328A had worn and so had the "T"

rings on T48-F310.

These "0"

and "T"

rings were replaced and valves were reassembled.

The valves were then successfully. rctested (as 1cft:

400 accm).

The unit is now in full compliance with the requirements of Tech Specs 4.7.A.2.G, and no further reporting is required.

1 4