ML20003E665
| ML20003E665 | |
| Person / Time | |
|---|---|
| Site: | Pilgrim |
| Issue date: | 03/30/1981 |
| From: | Novak T Office of Nuclear Reactor Regulation |
| To: | Morisi A BOSTON EDISON CO. |
| References | |
| NUDOCS 8104080091 | |
| Download: ML20003E665 (44) | |
Text
._
$2
[
)c, UNITED STATES
{j NUCLEAR REGULATORY COTAMISSION y
e NM[/* "'*-4/_
E WASHINGTON, D. C. 20555 March 30,1981 Oceket No. 50 293 P '$
APR'OGgggg_h T
Mr. A. Victor Morisi 9 -
84 8 Boston Edison Company Il
~
M/C NUCLEAR 200 Boylston Street q
/
Boston, Massachusetts 02199 4
to Cear Mr. Morist -
SUEJECT: ENVIRONMENTAL QUALIFICATION OF SAFETY-RELATED ELECTRICAL EQUIPMENT RE:
PILGRIM NUCLEAR POWER STATION - License No. DPR-35
- eference:
Order for Modification of License Concerning the Environmental Qualification of Safety-Related Electrical Eqaipment, October 24, 1980.
nis letter transmits the preliminary results of our review of environmental
- ualifications of safety-related electrical equipment at your facility.
f s evaluation was based on your submittals received over the past mont9s.
n
- e 'acility license was modified by the referenced Order of October 24, 1980, o require that all safety-related electrical equipment be cualified to s:ecified requirements not later than June 30,19c2.
In addition, the Order sted that a licensee is obligated to modify or replace inadequate equipment
- -c ;tly.
The staff's review vi your submittals has resulted in our identifying a ru oer of potential equipment deficiencies involving a' lack of proper
- cumentation, inadequate justification of assumed environmental conditiens
'r'1: wing an accident, and/or inadequate envirennental testing of equipment, s;ch that conformance to the 00R guidelines, as required by the Order,
- 3 /:ot be demonstrated.
You are requested to review our identified deft-
- iencies, and their ramifications, and provide us your overall finding egarding continued safe operation of your facility.
Accordingly, in order
- determine whether your license should be modified or suspended, you are recuired pursuant-to 10 CFR 50.54(f), to provide within 10 days of receipt cf this letter, a. written statement, signed under oath or affirmation sup-
- 3rting the-safe operation.of your facility, that takes into account the V.
staff's preliminary list of deficiencies.
J
.4
.8104h80$It
sf s
The purpose of this statement is to provide the NRC with needed assurance, by the licensee, regarding the continued safety of the facility until you can provide an item-by-item reevaluation in a detailed documented manner at a later date. A negative finding on your part concerning the safety of continued operation would result in a unit shutdown, and should be reported
'as a Licensee Event Report (LER) within twenty-four (24) hours of the deter-mination to the aopropriate NRC Regional Office.
Include in the LER the actions you have taken for the immediate resolution of the matter. A copy of any such LER should be sent to the Director, Division of Licensing, Office of Nuclear Reactor Regulation.
Please submit a copy of ycur reply to us via telecopy.
Sincerely, b
+
Thomas M. Novak, Assistant Director for Operating Reactors Division of Licensing
Enclosure:
Evaluation Report cc W/ enclosure:
See next page a.
e o
e d-
a v
M. A. Victor Morisi 5:ston Edison Company c::
M. 2.ithard D. Machon -
U. ';. Environmental Protection F-Igri, Station Manager Agency 5:st:n Edison Company Region ' Office F.9 =1, Rocky Hill Road ATTN:
EIS COORDINATOR F'/: outh, Massachusetts 02360 JFK Federal Building Boston, Massachusetts 02203 E argy Facilities Siting Council 12:h. Flour 0 a Asburton Place,.
B::t:n, Massachusetts 02108 Etwf Merrnann, Esquire Missachusetts Wildlife Federation lii Tre:.cnt Street 5:ston,. Massachusetts 02111 F*g u h Public Library N:-t, Street F'; :uth, Massachusetts '02360 Mi_S ac'.us ett: Department of Public Health-I'. : Comissioner of Public Health 6*: Washington Street 5::t:n, Passachusetts 02111 Wi e - 'uality & Environmental Co=issioner Et:a-t e-t of Environmental Quality In;ir,eering 1:C 'a-bridge Street E:It:n, Passachusetts 02202
' F. David F. Tarantino C lic.in, Ecard of Selectmen l' Lin:o'.n Street P';- :uth, Massachusetts 02360 0' e:::r, Criteria and Standards
- 1.'f :f c n.
Cf'f ee of Radiation Programs (ANR-460)
U. S. Environmental Protection Agency Wt:h'n; ten. D. C.
20460
.RE:idert Inspector
- c. : '.. S. NRC P. O. Eox S67..
F'. :d-h, l'assachusetts 02360 h
pQQR truu,m;
PmTIAr_Paviu EQUIPMENT EVALUATION REPORT BY THE OFFICE OF NUCLEAR REACTOR REGULATION FOR BOSTON EDISON COMPANY PILGRIM UNIT 1 DOCKET NO. 50-293 3 STAFF EQUIPMENT EVALUATION The staff evaluation of the licarsee's respense included an onsite inspection of selec'.ed Class IE equipment and an examination of the licensee's report for completeness and acceptability.
The criteria described in the 00R guidelines and in NUREG-0588, in part, were used as a basis for the staff evaluation of the adequacy of the licensee's qualification program.
The NRC Office of Inspection and Enforcement performed (1) a preliminary evaluation of the licensee's response, documented in a technical evaluation report (TER) and (2) an onsite verification inspection (April 9 and 10, 1980) s l
of selected safety related electrical equipment.
The automatic depressuriza-tion system (ADS) was inspected to verify proper installation of equipment, t
overall interface integrity, and manufacturers' nameplate data.
The manufac-
' l turer's name and model number.from the nameplate data were compared to infor-i mation given in the Component Evaluation Work Sheets (CES) of the licensee's
~!
report. The site inspection is documented in report IE 50-293/80-24.
No deficiencies were noted.
For this review, the document referenced above has j
been factored into the overall staff evaluation.
- 3.1 Comoleteness of Safetv-Related Ecuiement 1
In accordance with IEB 79-018, the licensee was directed to (1) establish a list cf systems and equipment that are required to mitigate a LOCA and an HELB and.(2) identiff components needed to perform the function of safety related display information, post-accident sampling and monitoring, and radiation
. monitoring.
The staff developed a generic master list based upon a review of plant safety analyses-and emergency procedures. The instrumentation selected includes parameters to monitor overall plant performance as well as to monitor the per-formance of the systems on the list.
The systems list was established on the basis of tne functions that must be performed for accident mitigation (without regarc to location of equipment relative te hostile environments).
The list of safety related systems pre "ed by the licensee was reviewed against the staff-developed master list.
Based upon information in the licensee's submittal,. the staff has concluded that the information en safety-related systems included in the licensee's submittals is insufficient to verify that those systems are all the systems required to achieve or support:
(1) emergency reactor shutdown, (2) contain-ment isolation, (3)-reactor. core cooling, (4) containment heat removal, (5) core residual heat removal, and (6) preventien of significant release of radioactive material to the' environment..The staff acknowledges the licensee's
. effort to include only those safety-related systems located in a potentially
Parsh environment.
However, this review requires the listing of all safety-related systems, both inside and outside potentially harsh environments.
The list of safety-related systems submitted by the licensee is included in A;pendix D.
Display in-trumentation which provides information for the reactor operators t: aid them in the safe handling of the plant was not specifically identified by the licensee.
A complete list of all display instrumentation mentioned in the LOCA and HELS emergency procedures trust be provided.
Equipment qualifi-cation information in the form of summary sheets should be provided for all ccmponents of the display instrumentation exposed to heesh environments.
Ir.strumentation whicts is not considered to be safety related but which is mentioned in the emergency procedure should appear on the list.
For these irstruments, (1) justification should be provided for not considering the ir.strument safety related and (2) assurance should be provided that its sub-sequent failure will not mislead the operator or adversely affect the mitiga-tion of the consequences of the accident.
The environmental qualification of p st-accident sampling and monitoring and radiation monitoring equipment is closely related to the review of the TMI Lessons-Learned modifications and will be performed in conjunction with that review.
Tre licensee identified 536 items of equipment which were assessed by the staff.
3.2 Service Conditions Ccmmission Memorandum and Order CLI-80-21 requires that the 00R guidelines and
- e "For Comment" NUREG-0588 are to be used as the criteria for establishing tre adequacy of the safety-related electrical equipment environmental quali-fication program.
These documents provide the option of establishing a bounding oressure and temperature condition based on plant specific analysis identified ir. tne licensee's Final Safety Analysis 'eport (FSAR) or hased on generic profiles using the methods identified in these documents.
3r this basis, the staff has assumed, unless otherwise noted, that the analysis I
fcr developing the envirom. ental envelopes for Pilgrim Unit 1, relative to the te perature, pressure, and the containment spray caustics, has been performed ir. accordance with the requirements stated above. The staff has reviewed the i
l qualification documentation to ensure that the qualification specifications erselope the conditions established by the licensee.
3.3 Temoerature. Pressure. and Humidity Conditions Inside Containment Tre licensee has provided the results of accident analyses as follows:
Max Tem:; (*F)
Max Press (osic)
Humidity (%)
.C:A 290 44 100 v.i _3 320 24 100
~.e staff has concluded that the minimum temperature profile for equipment r
Outif fication purposes should include a margin to account for analytical
.r:ertainties in the calculsted tenperature profiles for postulated accidents.
A margin of 20 F above saturation is considered to be appropriate for either a postulated LOCA or MSLB, whichever is controlling, as +o potential adverse environmental effects (o equipment.
The licensee's specifiec temperature profiles for qualification parposes enveloped both the MSLB &nd LOCA temperature profiles and includes a margin at least as large as would result from the staff's recommendation.
Therefore, we conclude that the specified temperature profile is acceptable.
3.4 Temperature, Pressure, and Humidity Conditions Outside Containment The licensee has provided the temperature, pressure, humidity, and applicable environment associated with an HELB outside containment.
The following areas outside containment have been addressed:
(1) RHR and core spray pumps room "A" (2) RHR and core spray pumps room "B" (3) HPCI pump panel and valve room (4) RCIC pump room (5) RCIC pump room mezzanine (6) CRD pump room mezzanine (7) CRD modules area east (8) CRD modules area - west (9) RHR piping room (10) Orywell access room (11) RCIC piping room (12) RHR/HPCI piping room (13) Open area - east half (14) Open area - west half (15) Fuel pool heat exchanger area (16) Open area - north half (17) Standby liquid control area (18) Clothing change and storage area
/19) Standby gas treatment filter rooms (20) Steam tunnel between turbine building and drywell (21)_ Compartment surrounding torus The staff'has verified that the parameters identified by the licensee for the MSLB are acceptable.
3.5 Submeroence The licensee has stated that Pilgrim Unit 1 is a Mark I BWR with the potential i
area for submerged equipment being the interior of'the torus.
No safety-related i
electrical equipment has been identified in or below this area, i
j 3.6 Chemical Soray I
The licensee has not_ identified containment spray as a safety-related system, j
- and credit has not been taken.in the analysis.
The system is manually operated L
t k.
1b
ar5usesdemineralizedwater.
Because spray is available and could be used, ary equipment upon which it impinges must be qualified for the spray parameter.
The licensee should provide additional information to resolve this concern.
3.7 @
5ection 7 of the DOR guidelines does not require a qualified life to be established for all safety-related electrical equipment.
However, the fcilowing actions are required:
(1) Make a detailed comparison of existing equipment and the materials identified in Appendix C of the DOR guidelines.
The first supplement to IEB-79-013 requires licensees to utilize the table in Appendix C and identify any additional materials as the result of their effort.
(2)
Establish an ongoing program to review surveillance and maintenance records to identify potential age-related degradations.
(3)
Establish component maintenance and replacement schedules which include considerations of aging characteristics of the installed components.
For this review, the staff requires that the licensee submit supplemental information to identify and verify the degree of conformance to the above equirements.
The response should include all the equipment identified as e;uired to maintain functional operability in harsh environments.
The staff will review the licensee's response when it is submitted and discuss its evaluation in a supplemental report.
l 3.3 Radiation (In>ide and Outside Containment) he licensee has provided values for the radiation levels postulated to exist
'ollowing a LOCA.
The application and methodology employed to determine those calues were presented to the licensee as part of the NRC criteria contained in the 00R guidelines, in NUREG-0588, and in the guidance provided in IEB-79-01B, Su:plement 2.
Therefore, for this review, the staff has assumed that, unless ot erwise noted, the values provided have been determined in accordance with the prescribed criteria.
The staff review determined that the values to which eg;ipment was qualified envelope the requirements identified.by.the licensee.
he radiation value required by the licensee inside containment is an integrated
- ose of 1.8 x 107 rads.
The radiation service condition provided by the
~
.i:ensee is lower than that given in the 00R guidelines for gamma and beta a:iation. The licensee is requested to either provide justification for
_s'ng the lower service condition or. use the service condition provided in the COR guidelines for both. gamma and beta radiation.
If the former option is
- h:sen, the analysis--including the basis,~ assumptions, and a sample calculation--
shall be provided.
% recuired value outside containment of 6.2 x 105 rads has been used by the
'icensee to specify limiting radiation levels within the RHR and core spray u p room of the reactor building. This value does not appear to consider the ~
radiation levels influenced by the source term methodology associated with post-LOCA recirculation fluid lines.
The licensee must correct this along with*the associated equipment summary sheets.
4 QUALIFICATION OF EQUIPMENT The following subsections present the staff's assescaent, based on the licensee's submittal, of the qualification status of safety-related electrical equipment.
The staff has separated the safety-related equipment into three categories:
(1) equipment requiring immediate corrective action, (2) equipment requiring additional qualification information and/or corrective action, and (3) equip-ment considered acceptable if the staff's concern identified in Section 3.7 is satisfactorily resolved.
In its assessment of the licensee's submittal, the NRC staff did not review the methodology employed to determine the values established by the licensee.
However, in reviewing the data sheets, the staff made a determination as to the stated conditions presented by the licensee.
Additionally, the staff has not completed its review of supporting documentation referenced by the licen-see (for example, test reports).
It is expected that when the review of test reports is complete, the environmental qualification data bank established by the staff will provide the means to cross reference each supporting document to the referencing licensee.
If supporting documents are found to be unacceptable, the licensee will be required to take additional corrective actions to either establish qualifi-cation or replace the item (s) of concern.
This effort will begin in early 1981.
.An appendix for each subsection of this report provides a list of equipment for which additional information and/or corrective action is required. Where app.*opriate, a reference is provided in the appendices to identify deficiencies.
It should be noted, as in the Commission Memorandum and Order, that the deficien-cies identified do not necessarily mean that equipment is unqualified.
- However, they are cause for. concern and may require further case-by-case evaluation.
4.1 Ecuicment Recuirina Immediate Corrective Action INTENTIONALLYELANK
.4.2 Eouicment Recuiring Additional Information and/or Corrective Action Appendix B identifies equipment in this categcry, including a tabulation of deficiencies.
The deficiencies are noted by a letter relating to the legend (identified below), indicating that the information provided is not sufficient for the qualification parameter or condition. w.
Lecend R
- radiation T
- temperature QT qualification, time RT required time P
pressure H
- humidity CS - chemical spray A
- material-aging evaluation; replacement schedule; ongoing equipment surveillance 5
- se'omergence M
- ma gin
.)
I
- HElB evaluation outside containment not completed
.[
QM qualification method
![.
RPN equipment relocation or replacement; adequate schedule not provided i
EXN exempted equipment justification inadequate
-5EN separate-effects qualification justification inadequate i
QI qualification information bein; developed RPS equipment relocation or replactment schedule provided As noted in Section 4, these deficiencies do not necessarily mean that the l
ecuiprent is unqualified.
However, the deficiencies are cause for concern and 5
require further case-by-case evaluation. The staff has determined that an a:ce3 table basis to exempt equipment from qualification, in whole or part, can be established provided the following can be established and verified by the i't licensee:
(1)
Equipment does not perform essential safety functions ;n the harsh environ-rent, and equipment failure in the harsh environment will not impact safety-related functions or mislead an operator.
(2a) Equipment performs its function before its exposure to the harsh environ-rent, and the adequacy for the time margin provided-is adequately justified, and (23) Subsequer.t failure of the equipment as a result of the harsh environment does not degrade other safety functions or mislead the operator.
(3) -The safety-related function can be accomplished by some other designated equipment that has been adequately qualified and satisfies the single-failure criterion.
(4)
Equipment will not be subjected to a-harsh environment as a result of the postulated accident.
The licensee is, therefore,-required to supplerent the information presented oy paaviding resolutions to.the deficiencies i;entified; these resolutions srouid include a description of the correctiv'.. action, schedules for its
- pletion (as applicable), and so forth. The staff will review the licensee's response,-when it is submitted, and discuss the resolution in a supplemental reoc rt.
6-T
The licensee is, therefore, required to supplement the information presented by p.oviding resolutions to the deficiencies identified; these resolutions should include a description of the corrective action, schedules for its completion (as applicable), and so forth. The staff will review the licensee's response, when it is submitted, and discuss the resolution in a supplemental report.
r It should be noted that in.:ases whue testing is being conducted, a condition may arise which results in a determination by the licensee that the equipment does not satisfy the qualification test requirements.
For that equipment, the
[
licensee will be required to provide the proposed corrective action, on a timely basis, to ensure that qualification can be established by June 30, 1982.
L i
4.3 Equipment Considered Acceptable or Conditionally Acceptable f
Based on the staff review of the licensee's submittal, %e staff identified t
the equipment in Appendix C a- (1) acceptable on the basis that the qualifi-
[
cation program adequately enveloped the specific environmental plant parameters, or (2) conditionally acceptable subject to the satisfactory resolution of the staff concern identified in Section 3.7.
For the equipment identified as conditionally acceptable, the staff determined
}
that the licensee did not clearly (1) state that an equipment material evaluation was conducted to ensure that no known materials susceptible to degradation because of aging have been j
- used, l
(2) establish an ongoing program to review the plant surveillance and main-I tenance records in order to identify equipment degradation which may be age related, and/or (3) propose a maintenance program and replacement schedule for equipment i
identified in iten 1 or equipment that is qualified for less than the
'i life of the plant.
t The licensee is, therefore, required to supplement the information presented s
for equipm' d, in this category before full acceptance of this equipment can be I
established.
The staff will review the licensee's response when it is sub-
- [
mitted and discuss the resolution in a supplemental report.
5 DEFERRED REQUIREMENTS 1 !'
IEB 79-018, Supplement 3 has relaxed the time constraints for the submission i
of the information associated with cold shutdown equipment and TMI lessons-t-
learned modifications.
The staff has required that this information be provided by February 1, 1981.
The staff will provide a supplemental safety evaluation addressing these concerns.
i aq-q 4 1 3
APPENDIX B Equipment Requiring Additional Information and/or Corrective Action (Category 4.2)
LEGEND:
R - Radiation T - Temperature QT - Qualification time RT - Required time
['
P - Pressure H - Humidity
?
CS '- Chemical spray A - Material aging evaluation, replacement schedule, ongoing equipment i
surveillance S - Submergence M - Margin I - HELB evaluation outside containment not completed i
(4 - Qualification method R N - Equipment relocation or replacement, adequate schedule not provided E).N - Exempted equipment justification inadequate SEN - Separate effects qualification justification inadequate QI - Qualification information being developed RPS - Equipment relocation or replacement schedule provided Ecuipment Description Manufacturer Component No.
Deficiency 600 V Power and Okonite 112 R, H, A, M, QT, RT C:ntrol Cable 600 V Power and Okonite 212 R, H, A, M, QT, RT C:ntrol Cable 6C'] V Power and Okonite 312 R, H, A, M, QT, RT Centrol Cable 6C3 V Power and Okonite 412 R, H, A, M, QT, RT C:ntrol Cable SC3 V Power and Okonite 512 R, H, A, M, QT, RT Centrol Cable l
SCO V Power and Okonita 712 R, H, A, M, QT, RT Ccatrol Cable B-1 4
APPENDIX B (Continued)
Equipment Description Manufacturer Cceconent No.
Deficiency 600 V Power and Kerite 112 A, RT, QT, QI Control Cable 600 V Power and Kerite 212 A,RT,QT,QI Control.able 600 V Power and Kerite 312 A, RT, QT, QI Control Cable 600 V Power and Kerite 412 A, RT, QT, QI i
Control Cable 600 V Power and Kerite 512 A, RT, QT, QI Control Cable 600 V Power and Kerite 712 A, RT, QT, QI Control Cable l
l 600 V Power and Kerite 912 A,RT,QT,QI Control Cable q
Isolation Valve Air
- Various, A0203-1A A, R, QT, RT, Operator and Valve AVCO/Namco, QM,SEN,QI Control System (SOV)/(LIM SW)
Isolation Valve Air
- Various, A0203-1B A. R, QT, RT, Operator and Valve AVC0/Namco, QM, SEN, QI Control System (SOV)/(LIM SW)
Isolation Valve Air
- Various, A0203-1C A, R, QT, RT, Operator and Valve AVCO/Namco, QM, SEN, QI Control System (SOV)/(LIM SW) ll Isolation Valve Air
- Various, A0203-ID A, R, QT, RT, Operator and Valve AVCO/Namco, QM,SEN,QI r
Control System (SOV)/(LIM SW) 1.j Globe Valve Air Namco A0220-44 A, R, QT, RT, QI Operator Limit Switch l
600 V Power and Kerite B6 KERITE A, RT, QT, QI
.I' Control Cable i
600 V Power and Kerite B7 KERITE A, RT, QT, QI i
Control Cable t-i
?
B-2 L
i V
APPENDIX B (Continued)
E;uipment Ciscription Manufacturer Cerconent Nc.
Deficiency L' cit Switch Buchanan /
J.nction Box Hoffman Limit Switch Buchanan /
J209 A, RT, QT J.nction Box Hoffman Limit Switch Buchanan /
J210 A, RT, QT J.nction Box Hoffman L'mit Switch Buchanan /
J211 A,RT,QT J.nction Box Hoffman L'mit Switch Buchanan /
J212 A, RT, QT J.nction Box Hoffman Limit Switch Buchanan /
J213 A, RT, QT J.nction Box Hoffman L'mit Switch Buenanan/
J214 A, RT, QT J.nction Box Hoffman L'mit Switch Buchanan /
J215 A, RT, QT J.nction Box Hoffman J.nction Box and Buchanan J216 A,RT,QT,QM Terrinal Block J.nction Box and Buchanan J43 A,RT,QT,QM Tercinal Block J.nction Box and Buchanan J44 A, RT, QT, QM Terrinal Block J.nction Box and Buchanan J55 A, RT, QT, QM Te-cinal Block J.nction Box and Buchanan J56 A,RT,QT,QM Terrinal Block M:ter Opera'.or Limitorque M01001-50 A, RT, QT M:ter Operator Limitorque M01001-63 A, RT, QT M:ter Operattr Limitorque M01201-63 A, RT, QT V:tcr Operator Limitorque M01201-2 A,RT,QT i
i B-3 P00R CRIBld
APPENDIX B (Continued)
Equipment Description Manufacturer Ceeponent No.
Deficiency Motor Operator Limitorque M01301-16 A, RT, QT Motor Operator Limitorque M02301-4 A, RT, QT Motor Operator Limitorque M0261-1 A, RT, QT Motor Operator Limitorque M0202-5A A, R, QT RT,QI Motor Operator Limitorque M0202-5B A. R, QT RT, QI J
Containment GE Q100A QI, A, QT, RT Electrical Penetration r
lP
~. '
Electrical I
- {
Containment GE Q100C QI, A, QT, RT
~
Electrical Penetration i
Containment GE Q1000 QI, A, QT, RT Electrical Penetration Containment GE Q100E QI, A, QT, RT Electrical Penetration Containment Physical Q101A QM, H, R, A, QT, Electrical Science RT Penetration Containment Physical Q101C QM, H, R, A, QT, Electrical Science RT Penetration 1
Containment GE Q101B QM, QI, A, QT, Electrical RT I
Penetration Containment GE j
Electrical
'Q102A QM, QT, A, QT, RT Penetration f
t B-4
- }..
y
APPENDIX B (continued)
I r
E;uipment Cascriotion Manufacturer Conconent No.
Deficiency j
Containment GE Q1028 QM, QI, A, QT, l
Electrical RT
(
Containment GE Q103A QM, QI, A, QT, Electrical RT Penetration
}-
Electrical QI Containment GE Q103B A, QM, QT, RT, Penetration Containment GE Q104A A, QM, QT, RT, Electrical QI l
Containment GE Q104B A, QM, QT, RT, Electrical QI Penetration i
Containment GE Q104C A, QM, QT, RT, Electrical QI J
Penetration C:ntainment GE Q104D A, QM, QT, RT, Electrical QI Penetration Centainment GE Q104E A, QM, QT, RT, Electrical QI Penetration Centainment GE Q104F A, QM, QT, RT, E;ectrical QI Penetration Centainment GE Q104G A, QM, QT, RT, Electrical QI Penetration C:ntainment GE Q104H A, QM, QT, RT, Electrical QI Fenetration
[
Centainment GE Q104J A, QM, QT, RT,
~g.
Electrical QI Fenetration B-5 a
APPENDIX B (Continued)
Equipment Description Manufacturer Component No.
Deficiency Containment GE Q105A A, QM, QT, RT, Electrical QI Penetration
!(
Containment GE Q105B A, QM, QT, RT,
.l Electrical QI Penetration
'[
Containment GE Q106B A,QM,QT,RT, Electrical QI Penetration Containment Conax Q202A A, QM, QT, RT Electrical Penetration Torus Containment Conax Q2028 A, QM, QT, RT Electrical Penetration Torus Switchboard Wire GE SI57275 A, QT, RT Switchboard Wire GE SI57279 A,QT,RT Cable Splices Raychem SPLICE (600V A, QT, RT PENETRATION)
Cable Splices Raychem SPLICE (50V)
A, QT, RT Solenoid Valve ASCO SV1001-95A A, QT, RT Solenoid Valve ASCO SV1001-958 A, QT, RT Solenoid Valve ASCO SV1400-51A
-A, QT, RT Solenoid Valve ASCO SV1400-51B A, QT, RT Relief Valve Target Rock SVi CA A, QT, RT Solenoid Valve Relief Valve
- Target Rock SV203B A, QT, RT Solenoid Valve
-Relief Valve-Target Rock SV203C.
A, QT, RT Solenoid Valve
?
I B-6
}
P t
APPENDIX B (Continued)
E:uipment
- sscription Manufacturer Cocoonent Nc.
Deficiency Relief Valve Target Rock SV203D A, QT, RT 5:lenoid Valve Scienoid Valve ASCO SV220-44 A, QT, RT fcr A0 220-44 Terminations, Various Terminations EXN Cc:pression Type (Less Than 4 kV)
Hydrogen Analyzer Delphi C118 A, RPS Hydrogen Analyzer Delphi C119 A, RPS
. 5 Instrument Rack Various C129A QM, QI Instrument Rack Various C1298 QM, QI Statdcwn Panel Various:
C152 QM, QI Switches-Electroswitch j
Lights-GE
]
Terminal Blocks-GE 5hatcown Panel Various:
C153 QM,QI j
Switches-Electroswitch j
Lights-GE Terminal Blocks-GE
\\
5hatdown Panel Various:
C154 QM,QI
]
Switches-h Electroswitch ll Lignts-GE a
Terminal L
Blocks-GE Sh:tdc n Panel Various:
C155 GM, QI a
Switches-l Electroswitch
. Lights-GE Terminal Blocks-GE B-7 0
4 APPENDIX B (Continued)
Equipment Description Manufacturer Component No.
Deficiency Shutdown Panel Various:
C156 QM,QI Switches-Electroswitch Lights-GE Terminal Blocks-GE Shutdown Panel Various:
C157 QM, QI Switches-Electroswitch
'l Lights-GE 1
Terminal Blocks-GE Shutdown Panel Various:
C158 QM,QI Switches-Electroswitch Lights-GE Terminal
!l Blocks-GE Shutdown Panel Varicus:
C159 QM, QI Switches-Electroswitch Lights-GE Terminal Blocks-GE Shutdown Panel Various:
C163 QM,QI Switches-Electroswitch Lights-GE Terminal Blocks-GE Instrument Rack Various C2201 QM, QI Instrument Rack Various C2205 QM, QI Instrument Rack Various C2206 QM, QI Instrument Rack Various~
C2207 QM, QI Instrument Rack Various C2250 QM, QI Instrument Rack Various C2251 QM, QI a
Instrument Rack Various C2256 QM, QI B-8
APfENDIX B (Continued)
Eculprent Descriotion Manufacturer Cc.oonent No.
Deficiency Ir.strument Rack various C2257A QM, QI Instrument Rack Various C2257B QM, QI i
i Instrument Rack Various C2260 QM, QI Enclosures and Various C2303 QM,QI Terr.inal Blocks Scram 50L Fuse Panel GE CS13AH QM, QI Centrol Panel, Various C61A QM, QI Reactor Bldg H&V Centrol Panel, Various C61B QM, QI Reacter Bldg H&V Star.dby Gas Treatment Various C68 RPS Filter Unit Panel Stardby Gas Treatment Various C68A RPS Filter Unit Panel Standby Gas Treatment Various C68B RPS Filter Unit Panel Stardby Gas Treatment Various C69 RPS Filter Unit Panel Stardby Gas Treatment Various C69A RPS Filter Unit Panel Stardby Gas Treatment Various C698 RPS Filter Unit Panel Ccntrol Valva Atkomatic CV2301-32 T, P, H, A, QI Sciencid Valve Atkematic CV9068A T, P, H, A. QI Sciencid Valve Attomatic CV90638 T, P, H, A, QI DC Fotor Cutler 07 T, P, H, A, QI Centrol Center Hammer DC Fotor Cutler 08 T, P, H, A, QI Centrol Center Ham.mer B-9
APPENDIX B (Continued) l Equipment Description Manufacturer Component No.
Deficiency I
DC Motor Cutler D9 T, P, H, A, QI
+
I Control Center Hammer
}
Differential Press.
Barton DPIS2301-2352 T, P, QT, A, QI Ind. Switch i
f Differential Press.
Barton DPIS2301-2353 T, P, QT, A, QI Ind. Switch Differential Press.
Barton DPIS261-2A T, P, H, QT, A Switch Differential Press.
Barton DPIS261-2B T, P, H, QT, A Switch Differential Press.
Barton DPIS261-2C T, P, H, QT, A Switch Differential Press.
Barton DPIS261-20 T, P, H, QT, A Switch Differential Press.
Barton DPIS261-2E T, P, H, QT, A Switch Differential Press.
Barton DPIS261-2F T, P, H, QT, A Switch Differential Press.
Barton DPIS261-2G T, P, H, QT, A Switch Differential Press.
Barton DPIS261-2H T, P, H, QT, A Switch Differential Press.
Barton DPIS261-21 T, P, H, QT, A Switch Differential Press.
Barton DPIS261-2J T, P, H QT, A Switch Differential Press.
Barton DP!b:5).-2K T, P, H, QT, A Switch N-Differential Press.
Barton N: '/61-2L T, P, H, QT, A Switch a
Differential Press.
Barton DPIS261-2M T, P, H, QT, A J
Switch 4
- t B-10 t
i
APPENDIX B (Continued)
Eau".p ent Cescriotion Manufacturer Comconent No.
Deficiency Cifferential Press.
Barton DPIS261-2N T, P, H, QT, A Switch
.t V
Cifferential Press.
Barton DPIS261-20 T, P, H, OT, A g
S-itch i
Cifferential Press.
Barton DPIS261-2P T, P, H, QT, A Saitch k
Cifferential Press.
Barton DPIS261-2Q T, P, H, QT, A Ssitch Differential Press.
Barton DPIS261-2R T, P, H, Q'.~,
A Ssitch r
l Cifferential Press.
Barton DPIS261-25 T, P, H, QT, A Switch r:ow Transmitter GE FT1461A T, QT, R, A, QI I
l F:ow Transmittci-GE FT1461B T, QT, R, A, QI F:ow Transmitter GE FT2358 A, R, QI E2M Centrol Box Woodward HPCI Turbine A, R, QI Control E2R Actuator Woodward HPCI Turbine A, R, QI Arembly Control 1 D ocping Pesistor Woodward HPCI Turbine A, R, QI Assembly Control 2 i
L:w-speed Woodward HPCI Turbine A, R, QI
?:tentiometer Control 3
. 1 5:eed Signal Woodward HPCI Turbine A, R, QI C:nserter Control 4 Migretic Pick up Woodward HPCI Turbine A, R, QI Control 5
)
E2R and Magnetic Woodward HPCI Turbine A, R, QI P'ck-up Cable Control 6 Assemblies Rs cte-trip SOV Skinner HPCI Turbine A, R, QI Control 7 I
B-11 L_
APPENDIX B (Continued)
Equipment Descriotion Manufacturer Cemconent No.
Deficiency Pressure Switch Square D HPCI Turbine A, R, QI Centrol 8 Stop VV Limit Switch Namco HPCI Turbine A, R, QI Control 9 Level Ind. Switch Yarway LIS263-57A A, QT, P i
Level Ind. Switch Yarway LIS263-578 A, QT, P Level Ind. Switch Yarway LIS263-58A A, QT, P
[
Level Inc. Switch Yarway LIS263-563 A, QT, P i
i Level Ind. Switch Yarway LIS263-72A A, QT, P Level Ind. Switch Yarway LIS263-723 A, QT, P Level Ind. Switch Yarway.
LIS263-72C A, QT, P Level Ind. Switch Yarway LIS263-720 A, QT, P Level Trans. Switch Yarway LITS 263-59A A, QT, T, P, H, QM, QI l
Level Trans. Switch Yarway LITS 263-59B A, QT, T, P, H, QM, QI Level Ind. Trans.
LITS 263-72A A, T, QT, P Switch l
Level Ind. T ans.
LITS 263-73B A, T, QT, P i
Switch Level _ Transmitter Foxboro LT5038 RPS I
Level Transmitter Foxboro LT5049 RPS I
Level Transmitter GE LT646A A, P, QI Level Transmitter GE LT6463 A, P, QI L
Motor Operttor Limitorque M01001-16A A,T,P,H Motor Operator Limitorque M01001-16B A,T,P,H i
Motor Operator Limitorque M01001-18A A,T,P,H B-12 h
8 L
m
w.. -
- - - - - -. z. -
5 APPENDIX B (Continued)
Ec;ipment Jescription Manufacturer Component No.
Deficiency Mc:or roerator Limitorque M01001-18B A,T,P,H Mctor ;perator Limitorque M01001-21 A,T,P,H Mctor Operator Limitorque M01001-23A A, R, H, QI Mc or Operator Limitorque M01001-23B A, R, H, QI Motor Operator Limitorque M01001-25A A, R, H, QI Motor Operator Limitroque M01001-26B A, R, H, QI Motor Operator Limitorque M01001-28A A, H Motor Operator Limitorque M01001-29A A, H Motor Operator Limitorque M01001-28B A,T,P,H Motor Operator Limitorque M01001-29B A,T,P,H Mc:nr Operator Limitorque M01001-34A A,T,P,H Mo or Operator Limitorque M01001-34B A,T,P,H Mc or Operator Limitorqu?
M01001-36A A,T,P,H Fotor Operator Limitorque M01001-368
~A,T,P,H Motor Operator Limitorque M01001-37A A,T,P,H Mo or Operator Limitorque M01001-37B A,T,P,H l
Motor Operator Limitorque M01001-43A A,T,P,H Fo or Operator Limitorque M01001-43B A,T,P,H Fo or Operator.
Limitorque M01001-43C A,T,P,H l
Fo or Operator Limitorque
_M01001-43D A,T,P,H i
v tor Operator Limitorque M01001-32 A,T,P,H o
Po or Operator
-Limitorque M01001-47 A, R, QI l
o or Operator Limitorque M01001-7A A,T,P,H w
1 B-13
1 APPENDIX B (Continued) i I
Equipment j
Description Manufacturer Component No.
Deficiency Motor Operator Limitorque M01001-78 A,T,P,H L
Motor Operator Limitorque M01001-7C A,T,P,H E
Motor Operator Limitorque M01001-70 A,T,P,H L
g Motor Operator Limitorque M01201-5 A, H Motor Operator Limitorque M01400-24A A, R, H, QI Motor Operator Limitorque M01400-248 A, R, H, QI Motor Operator Limitorque M01400-25A A, R, H, QI Motor Operator Limitorque P41400-25B A, R, H, QI Motor Operator Limitorque M01400-3A A,T,H Motor Operator Limitorque M01400-3B A,T,H Motor Operator Limitorque M01400-4A A,T,H Motor Operator Limitorque M01400-4B A,T,H Motor Operator Limitorque M02301-14 A, R, QI Motor Operator Limitorque M02301-5 A,P,H Motor Operator Limitorque M02301-8 A,T,H Motor Operator Limitorque M0261-2 A,T,P Motor Operator Limitorque M0220-2 A,T,P Outlet Damper Honeywell MON 109 A, R, RPS Outlet Damper Honeywell MON 113 A, R, RPS Shutdown Panel Various N550 A, T, QM, R, QI RHR Pump GE P203A A,T,P,H,R, 4
QT, RT, QM 1'
RHR Pump GE P203B A,T,P,H,R, f
QT, RT, QM 1
B-14 5
l i
i
)
APPENDIX B (Continued) i I
t Equipment l
Cescription Manufacturer Component No.
Deficiency l
[
QT, RT, QM RHR Pump GE P203D A,T,P,H,R, h
QT, RT, QM
'I
?
?
A,T,P,H,R, QT,RT,QM Core Spray Pump GE P21SB A,T,P,H,R, QT, RT, QM Pressure Switch Static PS1001-104A A, T, P, QI Ring Pressure Switch Static PS1001-104B A, T, P, QI Ring Pressure Switch Static PS1001-104C A, T, P, QI Ring Pressure Switch Static PS1001-104D A, T, P, QI Ring Pressure Switch Static PS1001-89A A, P Ring Pressure Switch Static PS1001-89B A, P Ring Pressure Switch Static PS1001-89C A, P Ring Pressure Switch Static PS1001-89D A, P Ring Pressure Switch Static PS1001-90A A, P Ring P essure Switch Static PS1001-908 A, P Ring Fressure Switch Static PS1001-90C A, P
}
Ring i'
Pressure Switch Static PS1001-900 A, P j
Ring j
B-15 i
i
\\
APPENDIX 3 (Continued)
Equip ent Descriction Manufacturer Cc.rcenent No.
Deficiency Pressure Switch Static PS1001-93A A, T, P, QI Ring Pressure Switch Static PS1001-938 A, T, P, QI Ring Pressure Switch Static PS1001-93C A, T, P, QI p
Ring Pressure Switch Static PS1001-930 A, T, P, QI Ring Pressure Switch Static PS1360-SA A, T, P, H, QI Ring Pressure Switch Static PS1350-93 A, T, P, H, QI Ring Pressure Switch Static PS1350-90 A, T, P, H, QI Ring Pressure. Switch Static PS1360-90 A, T, P, H, QI Ring Pressure Switch Static PS1451A A, T, P, QI Ring Pressure Switch Static PS14518 A, T, P, QI Ring Pressure-Switch Static PS1464A A, T, P, QI
-Ring Pressure Switch
- Static-O-PS14643 A, T, ?, QI Ring Pressure Switch Barksdale PS251-23A A, T, H, P, QI i
1 Pressure Switch Barksdale~
.PS251-23B' A, T, H, P, QI 1
Pressure Switch Barksdale PS253-51A
- A, T, P, H, QT 3
1 4-Pressure Switch Barksdale.
PS263-513 A, T, P, H, QT l-Pressure Switch Earksdale PS253-51C A, T, P, H, QT
.5' Pressure Switch Earksdale PS263-510 A, T, P, H, QT
'd J
Tj; S-16 r.
- [-
APPENDIX B (Continued)
Equipment Descriotion Manufacturer Component No.
De'iciency Pressure Switch Barksdale PS263-52A A,T,P,H,Qi Pressure Switch Barksdale PS263-53A A, T, H, P, QI Pressure Switch Barksdale PS263-53B A, T, P, H, QT Pressure Switch Barksdale PS263-55A A, T, P, H, QT Pressure Switch Barksdale PS263-55B A, T, P, H, QT
- t Pressure Switch Barksdale PS263-55C A, T, P, H, QT
'k
.{
Pressure Switch Barksdale PS263-55D A, T, P, H, QT a
Pressure Switch Mercoid PS8135 RPS Pressure Switch Mercoid PS8136 RPS Pressure Transmitter
.GE PT647A A, T, P, QM, QI
-1;)
Pressure Transmitter _
GE PT6478 A, T, P, QM, QI l
l Pressure Transmitter GE PT9016 RPS l
Pressure Transmitter GE PT9017 RPS I "
Pressure Transmitter GE PT9046 A, T, P, QM, QI 2/C #15 Twisted Various 51 A, T, P, QM Shielded Pair 3/C #16 Shielded Boston 53 A, T, P, QT, QM, QI Insulated Wire Scienoid Valve ASCO S0117 A, T, P, QM, QI Sciencid Valve ASCO S0118 A, T, P, QM, QI Scienoid Valve ASCO
.SV1301-12 RPS Scienoid Valve ASCO SV1301-13 RPS Scienoid Valve ASCO SV1301-34 RPS o
Scienoid Valve ASCO SV1301-35 RPS il g
B-17 N
f.+
APPENDIX B (Continued)
Equipment Description Manufacturer Component No.
Deficiency Solenoid Valve ASCO SV1301-71 RPS Solenoid Valve ASCO SV2301-30 RPS Solenoid Valve ASCO SV2301-31 RPS Solenoid Valve
'ASCO SV2301-32 RPS Solenoid Valve ASCO SV2301-65 RPS f
Solenoid Valve ASCO SV2301-29 RPS f
Solenoid Valve ASCO SV2301-64 RPS
?
l Solenoid Valve ASCO SV2301-94 A, R, RPS Solenoid Valve ASCO SV302-19A QM, A, R, QI i
j-Solenoid Valve ASCO SV302-198 QM, A, R, QI Solenoid Valve ASCO SV302-20A T, P, A, QM, 9
QI Solenoid Valve ASCO SV302-208 T,P,A,QM,
[
QI Solenoid Valve ASCO SV4044A RPS Solenoid Valve ASCO SV4044B RPS Solenoid Valve ASCO SV9007 RPS k'
Solenoid Valve ASCO SV9008 RPS Solenoid Valve SVL43 RPS Solenoid Valve-SVL44 RPS Solenoid Valve SVL45 RPS h
Solenoid Valve SVL46 RPS Solenoid Valve SVL47 RPS Solenoid Valve SVL48 RPS B-18 4
APPE;iDIX B (Continued)
Ecuiptent Osscription Manufacturer Component No.
Deficiency Scienoid Valve SVL49 RPS i-Scienoid Valve SVL50 RPS Scienoid Valve SVL51 RPS Scienoid Valve SVL52 RPS jg Scienoid Valve SVL53 RPS Scienoid Valve SVL54 RPS Scienoid Valve SVLS5 RPS Scienoid Valve SVL56 RPS
-Scienoid Valve SVL57 RPS Scienoid Valve SVL58 RPS Scienoid Valve SVL60 RPS Scienoid Valve-SVL62 RPS Scienoid Valve SVL67 RPS Scienoid Valve SVL70 RPS Selenoid Valve SVL71 RPS Scienoid Valve SVL72 RPS Scienoid Valve SVL73 RPS Scler.oid Valve SVL74 RPS Scienoid Valve SVL77 RPS Scie.moid Valve
-SVL78 RPS Scie..oid Valve SVL79 RPS psrature Electric TE5047 RPS e
Element Thermometer-Te perature Electric TE5048 RPS Element Ther=cmeter-B-19 L
APPENDIX B (Continued)
Equipment Description Manufacturer Component No.
De ficiency Temperature Switch Fenwal TS1291-14C A, QT Temperature Switch Fenwal TS1291-14D A, QT Temperature Switch Fenwal TS1291-14E A, QT 2
Temperature switch Fenwal TS1291-14F A,QT Temperature Switch Fenwal TS1291-14G A,QT Temperature Switch Fenwal TS1291-14H A,QT Temperature Switch Fenwal TS1291-14J A,QT I
Temperature Switch Fenwal TS1291-14K A, QT
~
Temperature Switch Fenwal TS1360-14C A,QT Temperature Switch Fenwal TS1360-14D A, QT Temperature Switch Fenwal TS1360-15A A, QT
= !
Temperature Switch Fenwal TS1360-15B A,QT Temperature Switch Fenwal TS1360-15C A,QT Temperature Switch Fenwal TS1360-15D A,QT Temperature Switch Fenwal TS1360-16C A, QT l
Temperature Switch Fenwal TS1360-16D A, QT Temperature Switch Fenwal TS1360-17A A,QT Temperature Switch Fenwal TS1360-17B A, QT l
Temperature Switch Fenwal TS1360-17C A, QT Temperature Ewitch Ferwal TS1360-170 A, QT Temperature Switch Fenwal TS2370C A, QT.
. Temperature Switch Fenwal TS23700 A, QT Temperature Switch Fenwal TS2371A A,QT Temperature Switch Fenwal TS2371B A, QT ll B-20
- 1
. I L
APPENDIX B (Continued)
E:;uiptent Descriotion Manufacturer Co:Donent No.
Deficiency l
Temperature Switch Fenwal TS2371C A, QT I
Temperature Switch Fenwal TS23710 A, QT 1
Temperature Switch Fenwal TS2371B A, QT Te. perature Switch Fenwal TS2372C A,QT l-Temperature Switch Fenwal TS2372D A, QT Te:perature Switch Fenwal TS2373A A, QT Te:perature Switch Fenwal TS2373B A, QT Temperature Switch Fenwal TS2373C A, QT Te perature Switch Fenwal TS23730 A,QT Te:perature Switch Fenwal TS261-15A A, QT Te perature Switch Fenwal TS261-15B A, QT Te:perature Switch Fenwal TS261-15C A, QT Te perature Switch Fenwal TS261-150 A, QT Te perature Switch Fenwal TS261-16A A, QT Te perature Switch Fenwal TS261-16B A, QT Te perature Switch Fenwal TS261-16C A,QT
~l..
Te. perature Switch Fenwal TS261-16D A, QT Thereestat Johnson TSD-41 RPS g
Control tarecstat-Johnson TSD-42 RPS
~i.
Control
-nsrr: stat Johnsen TSD-43 RPS Contrcl ns- : stat Johnson TSD-44 RPS Control s- : stat' Jennsen TSC-45 RPS Centr:1 5-21
APPENDIX 8 (Continued)
Equipment Description Manufacturer Component No.
Deficiency Thermostat Johnson TSD-46 RPS Control Thermostat Johnson TSD-47 RPS Control Thermostat Johnson TSD-48 RPS Control I
RHR Unit Cooler Louis-Allis VAC 204A A, QT, QM, R, Co.
QI RHR Unit Cooler Louis-Allis VAC 204B A, QT, QM, R, Co.
QI RHR Unit Cooler Louis-Allis VAC 204C A, QT, QM, R, Co.
QI RF.< Unit Cooler Louis-Allis VAC 204D A, QT, QM, R, j
Co.
QI Exhaust Fan GE VEX 210A A, R, RPS Exhaust Fan GE VEX 2108 A, R, RPS Filter Unit Farr Co.
VGTF201A A, R, RPS Filter Unit Farr Co.
VGTF201B A, R, RPS AC Motor Control Nelson B17 QM, QI Center AC Motor Control Nelson B18 QM,QI Center
. AC Motor Control Nelson B20 QM, QI Center
. Differential Pressure Barton DPIS261-2A T, P, H, QT, A
-Indicator Switch Differential Pressure Barton DPIS261-28 T, P, H,'QT, A Indicator Switch Differential Pressure Barton DPIS261-2C T, P, H, QT, A g
Indicator Switch i
4 l
B-22 r
1L
- i
-l APPENDIX B (Continued)
Ecuipment j
Descriotion Manufacturer Component No.
Deficiency D'fferential Pressure Barton DPIS26.'-20 T, P, H, QT, A j
Indicator Switch Differentia! Pressure Barton DPIS261-2E T.P,H,O!,A Ir.dicator Switch l
Differential Pressure Barton DPIS261-2F T, P, H, QT, A Indicator Switch
'I Differential Pressure Barton DPIS261-2G T, P, H, QT, A Indicator Switch Differential Pressure Barton DPIS261-2H T, P, H, QT, A Indicatur Switch Differential Pressure Barton DPIS261-2I T, P, H, QT, A Indicator Switch Differenti l Pressure Barton DPIS261-2J T, P, H, QT, A a
Indicator Switch Jifferential Pressure Barton DPIS261-2K T, F, H, QT, A Indicator Switch
-3*fferential Pressure Barton DPIS261-2L T, P, H, QT, A Irdicator Switch Differential Pressure Barton DPIS261-2M T, P, H, QT, A Indicator Switch Jifferential Pressure Barton DPIS261-2N T, P,'H, QT, A Indicator Switch Jifferential Pressure Barton D/IS261-20 T, P, H, QT, A Irdicator Switch 1
.]ifferential Pressure Barton DPIS261-2P T, P, H, QT, A Indicator Switch Jifferential Pressure Barton DPIS261-2Q T, P, H, QT, A j
_ Indicator Switch Jifferential Pressure Barton DPIS261-2R T, P, H, QT, A Irdicator Switch r
(?
Jifferential Pressure Barton DPIS261-2S T, P, H, QT, A Irdicator. Switch B-23 J
APPENDIX B (Continued)
Equip.nent Description Manufacturer Comconent No.
Deficiency Solenoid Valse ASCO SV2301-30 RPS Solenoid Valve ASCO SV2301-31 RPS Solenoid Valve ASCO SV2301-32 RPS Solenoid Valve
.,ASCO SV2301-65 RPS 2
t I
i 2-24
APPENDIX C Equipment Considered Acceptable or Ccnditionally Acceptable (Category 4.3)
LEGEND:
E
't R - Radiation i
T - Temperature QT - Qualification time ET - Required time P - Pressure H - Humidity l
CS - Chemical spray I
A - Material aging evaluation, replacement schedule, ongoing equipment surveillance S - Submergence M - Margin I - HELB evaluation outside containment not completed (M - Qualification method RFN - Equipment relocation or replacement, adequate schedule not provided EXN - Exempted equipment justification inadequate SEN - Separate effects qualification justification inadequate QI - Qualification information being developed RPS - Equipment relocation or replacemer.t schedule provided Ecuipment Descriotion Manufacturer Component No.
Deficiency SCO V Power and Kerite 210 KERITE A
Centrol Cable 6CO V Power and Kerite 410 KERITE A
Centrol Cable 6CO V Power and Kerite C12 KERITE A
Centrol Cable 5 kV Cable Kerite Al KERITE A
5 kV Cable Kerite A2 KERITE A
'I 5 kV Cable Kerite A3 KERITE A
i 5 kV Cable Kerite A4 KERITE A
Ii 5 kV Cable Okonite A1 OKONITE A
3 C-1 i
li
i j
.[.
APPENDIX C (Concinued)
Equipmer.t
}
Description Manufacturer Comoonent No.
Deficiency i
5 kV Cable Okonite A2 OKONITE A
Isolation Valve Air
- Various, A0203-2A d
Operator and Valve AVCO/Namco Control System (SOV)/(LIM SW)
Isolation Valve Air
- Various, A0203-28 A
Operator and Valve AVCO/Namco Control System (SOV)/(LIM SW)
Isolation Valve Air
- Various, A0203-2C A
Operator and Valve AVCO/Namco Control System (SOV)/(LIM SW)
Isolation Valve Air
- Various, A0203-2D A
Operator and Valve AVC0/Namco Control System (SOV)/(LIM SW) 600 V Power Cable Kerite B1 KERITE A
S00 V Power Cable Kerite 32 KERITE A
600 V Power Cable Kerite B3 KERITE A
l 600 V Power Cable Kerite B4 KERITE~
A 600 V Power Cable Kerite B5 KERITE A
I 600 V Power and Okonite B65 OKONITE A
Control Cable Differential Barton OPIS1001-19A A
Pressure Switch Differential Barton DPIS1001-798 A
Pressure Switch Differentia 1' Pressure Barton.
OPIS1360-1A A
Indicator Switch Differential Pressure Barton DPIS1360-1B A
Indicator Switch
-Differential Pressure Barton DPIS1459A A
Indicator Switch-C-2
APPENDIX C (Continued) icai;.ent
~
Descriotion Manufacturer Comoonent No.
Deficiency Differential Pressure Barton DPIS1459B A
Ir.dicator Switch Differential Pressure Barton DPIS261-12A A
Indicator Switch Differential Pressure Barton DPIS261-12B A
^
Indicator Switch
.i
.I 3ifferential Pressure Barton DPIS261-12C A
}
Indicator Switch Differential Pressure Barton DPIS261-120 A
Indicator Switch i
Differential Pressure Carton DPIS261-36A A
Indicator Switch i
Differential Pressure Barton DPIS261-36B A
-l Indicator Switch Jifferential Pressure Barton DPIS261-37A A
Indicator Switch Jifferential Pressure Barton DPIS261-37B A
' Indicator Switch Jifferentisl Pressure Barton DPIS261-38A A
Ihdicator Switch Jifferential Pressure Barton DPIS261-3SB A
Indicator Switch n
3ifferential Pressure Barton DPIS261-39A A
Ir.dicator Switch Differential Pressure-Barton DPIS261 398 A
Indicator Switch Differeatial Barton DPIS5040A A
3ressure Switch Jifferential Barton.
DPIS504DB A
3ressure Switch
- low Switch Barton FS2301-2354 A
C-3
APr'ENDIX C (Continued)
Equipment Description
. Manufacturer Cc=aonent No.
Defic.iency Level Switch Robert Shaw LS2301-2351A A
Level Switch Robert Shaw LS2301-2351B A
Level Switch Robert Shaw LS2301-2.65 A
s Level Switch Robert Shaw LS2301-2369 A
Level Switch Robert Shaw LS302-82A A
Level Switch Robert Shaw LS302-828 A
Level Switch Robert Shaw LS302-82C A
Level Switch Robert Shaw LS302-82D A
~
~
Level Switch McDonnell &
LS8020 A
Miller Level Switch McDonnell &
LS8021 A
Miller Level Switch Robert Shaw LS9068 A
Motor Operator Limitorque M01001-60 A
Motor Operator Limitorque M01201-80 A
Motor Operator Limitorque M01301-17 A
Motor Operator Limitorque M01301-25 A
Motor Operator Limitorque M01301-26 A
Motor Operator Limitorque-M01301 A Motor Operator Limitorque M02301-10 A
Motor Operato-Limitorque M02301-3 A
Motor Operator Limitorcue M02301-35 A
Motor Operator Limitorque M02301-36 A
Motor Operator-Limitorque M02301-9 A
C-4
APPENDIX C (Continued)
EquiccEnt Description Manufacturer Cocoonent No.
Deficiency i
Motor Operator Limitorque M04002 A
.I j
Motor Operator Limitorque M04010A A
Motor Operator Limitorque M04010B A
+
1 Motor Operator Limitorque M04060A A
Mctor Operator L,imitorque M04060B A
Pressure Switch Static PS1001-83A A
Ring Pressure Switch Static PS1001-83B A
Ring Pressure Switch Static PS1001-83C A
Ring Pressure Switch Static PS1001-830 A
Ring Pressure Switch Mercoid PS2301-2368A A
?ressure Switch Mercoid PS2301-2368B A
3ressure. Switch Barksdale PS2301-2389A A
i Pressure Switch Barksdale PS2301-2389B A
Pressure Switch Barksdale PS2301-2389C A
Fressure Switch Barksdale PS2301-2389D A
Pressure Switch Barksdale PS2360-1 A
?ressure Switch Barksdale.
PS263-49A A
Pressure Switch Barksdale PS263-49B A
i
?ressure Switch
-Barksdale PS263-50A A
1
[
?ressure Switch Barksdale PS263-50B A
?ressure Switch Barksdale PS503A A
C-5
~_.
0 i
APPESDIX C (Continued) 1 I
l Equipment i
Description Manufacturer Ccmoonent No.
,na'iciency Pressure Switch Barksdale PS503B A
{
Pressure Switch Barksdale PS503C A
Pressure Switch Barksdale PS503D A
f Pressure Switch Barksdale PS504A A
I
[
Pressure Switch Barksdale PS504B A
Pressure Switch
'sarksdale PS504C A
Pressure Switch Barksdale PS504D A
Pressure Switch Static PS512A A
Ring Pressure Switch Static PS512B A
Ring Pressure Switch Static PSS12C A
Ring Pressure Switch Static PS5120 A
l Ring Solenoid Valve ASCO SV220-45 A
Solenoid Valve ASCO SV2301-9311 A
i Solenoid Valve ASCO SV2301-9313 A
Solenoid Valve ASCO SV5033A A
Solenoid Valve ASCO SV5033B A
Solenoid Valve ASCO SV5033C A
Solenoid Valve ASCO SV5040A A
Solenoid Valve ASCO SV5040B A
Solenoid Valve ASCO SV5041A A
Solenoid Valve ASCO SV5041B A
!d C-6
)
- a9
APPENDIX C (Continued)
Scaipment Description Manufacturer Component No.
Deficiency Scienoid Valve ASCO SV5043A A
l Scienoid Valve ASCO SV50438 A
I Solenoid Valve ASCO SV5035A A
i Scienoid Valve ASCO SV5035B A
Scienoid Valve ASCO SV5036A A
Scienoid Valve ASCO SV5036B A
Scienoid Valve ASCO SV5042A A
Selenoid Valve ASCO SV50428 A
Scienoid Valve ASCO SV5044A A
Scienoid Valve ASCO SV5044B A
1 Scienoid Valve ASCO SV5065-10 A
Scienoid Valve ASCO SV5065-11 A
Scienoid Valve A5CO SV5065-12 A
5clenoid Valve ASCO SV5065-13 A
Selenoid Valve ASCO SV5035-14 A
Scienoid Valve ASCO SV5065-15 5clenoid Vaive ASCO SV5065-16 A
Selenoid Valve ASCO SV5065-17 A
Selenoid Valve ASCO SV5065-18 A
Scienoid Valve ASCO SV5065-19 A
Scienoid Valve ASCO SV5065-20 A
5clenoid Valve-ASCO SV5065-21 A
,i '
Scienoid Valve ASCO SV5065-22 A
t'
'Scienoid Valve ASCO SV5065-23 A
.C-7
?
la e
i APPENDIX C (Continued)
Equipment Description Manufacturer Component No.
Deficiency Solenoid Valve ASCO SV5065-24 A
Solenoid Valve ASCO SV5065-25 A
I Solenoid Valve ASCO SV5065-26 A
Solenoid Valve ASCO SV5065-27 A
.i Solenoid Valve ASCO SV5055-31 A
t "n
Solenoid Valve ASCO SV5055-32 A
I 1
{1 Solenoid Valve ASCO SV5065-33 A
L
- n Solenoid Valve ASCO SV5065-34 A
Solenoid Valve ASCO SV5065-35 A
. s,
!h Solenoid Valve ASCO SV5065-36 A
h
- Solenoid Valve ASCO SV5065-37 A
Solenoid Valve ASCO SV5065-38 A
Control Valve Valcor-SV5081A A
Control Valve Valcor SV50818 A
Control Valve
~
Valcor SV5082A A
Control Valve Valcor SV5082B A
Control Valve Valcor SV5083A A
- I' Control Valve salcor SV50838 A
l Control Valve Valcor SV5084A A
d Control Valve Valcor SV50848 A
Q Control Valve Valcor SV5085A A
Control Valve Valcor SV50858 A
Control Valve Valcor SV5086A A
i 1, --
C-8 i
~~
APPENDIX C (Continued)
E:uipment Osscriotion Manufacturer Comoonent No.
Deficiency C:ntrol Valve Valcor SV5086B A
C:ntrol Valve Valcor SV5087A A
f Centrol Valve Valcor SV50878 A
Centrol Valve Valcor 5V5088A A
Centrol Valve Vsicor SV50888 A
S lenoid Valve ASCO SV7011A A
Scienoid Valve ASCO SV70118 A
S:lenoid Valve ASCO SV7017A A
Selenoid Valve ASCO SV70178 A
4 kV-Cable Splices
_ Kerite TERMINATIONS A
and Motor (4 kV)
Ter=inations HFCI Unit Cooler GE VAC201A A
HF:I Unit Cooler GE VAC2015 A
1
.o i
l C-9 o
.h~
t'
Iw APPENDIX 0 Safety-Related Systems List 1 8
5l Main Steam Line Isolation Valves
- - iil Control Rod Drive System
'l
{
RHRS (LPCI mode)
!I.
RHRS (torus cooling mode)
HPCIS 5
Automatic Depressurization System Core Spray System g
Primary Containment and Reactor Vessel Isolation Standby AC Power System DC Power System Standby Gas. Treatment System 6
Incident' Detection Circuitry Reactor Building Closed Cooling Water Salt Service. Water Main Control Room. Environmental Control
. Reactor Building Isolation Cont'rol
. Torus Water Temperature and Level Indication
~ Equipment Area Cooling System
'As submitted by the licensee.
l!.
h[
u o.{
D-1 N b'