LER-1981-001, /01T-0:on 810114,discovered That FT-236 Changing Header Flow Lacks Complete Info to Qualify for Harsh Radiation Svc Required by IE Bulletin 79-01B.Caused by Incomplete Matls List.Transmitter Will Be Replaced |
| Event date: |
|
|---|
| Report date: |
|
|---|
| 2851981001R01 - NRC Website |
|
text
NRC FOHM 3b6 U. b. NUCLk AH HkUULA10HY COMMihSION (7-77)
LICENSEE EVENT REPORT CONTROL BLOCX: l l
l l
l l
l (PLEASE PRINT OR TYPE ALL REQUIRED INFORMATION) b l E l F l C l S l 1 l@l O l 0 l 0 l 0 l 0 l 0 l 0 l 0 l 0 l 0 l 0 l@l 4 l 1 l 1 l 1 l 1 l@l l
l@
?
8 9 LICENSEE CODE 14 15 LICENSE NUMBER 25 26 LICENSE TYPE JO 57 LAT 68 COvT l0l1I ER]lLl@l0l5l0l0l0l2l8l5 @l0l1l1l4l8l1l@l0l1l1l5l8l1l@
7 8
60 61 DOCKET NUMBER 68 69 EVENT DATE 74 75 REPORT DATE 80 EVENT DESCRIPTION AND PROBABLE CONSEQUENCES h 1012 I I As required bv I.E.
Bulletin 79-OlB. FT-236,charnine header flow lacks Cocolete l
iOl3l 1 information to qualify it for the harsh radiation service intended. The transmitter l I o 14 l l is used for long term core cooling flow to the auxiliary pressurizer sprav.
If the l 10 I s l I transmitter should fail in a post accident situation, charging header pressure, i
10 l6 l l High Pressure Injection Flow, and pump curves can be used to determine flow.
I 10171 I l
l O la I i
__]
80 7
8 9 DE CODE SUBC E COMPONENT CODE St,8 DE S
DE l0l9l l Il D lh Wh l A lh l Il NlS lT lR lU lh W h W h 7
8 9
10 11 12 13 18 19 20 SEQUE NTI AL OCCURRENCE REPORT REVISION LER EVENT YEAR REPORT NO.
CODE S * *E N O.
O ag g'AO la Il l l-l l0 10 11 I l/l I oll I U
L--J Lo_l s
_ 21 22 23 24 26 27 28 29 er T
32 AKEN AC ON ON PLANT MET HOURS 22 S8 IT D FOR ts
)
L1 MANUFACTURER l X l@l C l@
l Z l@
lZ l@
l 0]0 l0 l0 l lYl@
lN lQ lc {$
lF l1 l 8l 0l@
33 34 35 36 37 40 di 42 43 44 47 CAUSE DESCRIPTION AND CORRECTIVE ACTIONS h l1 toll A connlete materials list is not avniinhin en dornr, inn vndineinn dnso l
11 11 ] l limits or qualified life. Although the transmitter is not expected to fail.
l l i l :7 l l it will be replaced with a qualified transmitter by the end of the 1981 l
l1 l 31 l refueling outage.
l 11 141 l l
7 8 9 80 STA 3
% POWER OTHER STATUS DtS OV RY DISCOVERY DESCRIPTION l_M l [jijh l0 l 7 l5 lhl NA l
lC lhl Review for IEB 79-01B l
'S
'JTIVITv CO TENT RELE ASED OF RELE ASE AMOUNT OF ACTIV'TY LOCATION OF RELEASE l
li 16 I L2J @ 12J@l NA I
I NA 7
8 9 10 11 44 45 80 PERSONNEL EXPOSURES NUMBER TYPE
DESCRIPTION
li l 71 1010101@l 7. l@l NA PERSON ~Et'IN;ubs DESCRIPTION @
~ uMe E R I
li la l l 0 l 0101@l NA 7
8 9 11 12 80 LOG 3 or OR DAMAGE TO F ACILITY Q TYPE utSCRIPTION
%,/
l.LI.2.I L7J@l Na l
7 8 9 10 80 ISSUE @ DESCRIPTION l_zj ln I
l 1 I I 1 l l l 11 I lj i 2 O 8101800 Q.l
LER No.81-001 4
Omaha Public Power District j
Fort Calhoun Station Unit No.1 Docket No. 05000285 ATTACHMENT NO. 1
Safety Analysis
The subject transmitter, FT-236, is a Foxboro M-637 and is used to indicate high pressure safety injection pump flow through the auxi-liary pressurizer spray system during long term core cooling operations.
The transmitter provides indication only.
The transmitter is being reported as lacking qualification due to the fact that a complete materials list is not available to determine the radiation qualification and qualified life. However, based on the limited materials list available and transmitter construction, the Dis-trict would expect the transmitter to withstand the post accident high radiation environment.
Should FT-236 fail, the qualified high pressure loop injection flow transmitters, the charging pump header pressures transmitter-located in a " normal" room environment, and HPSI pump flow curve could be used to determine the flow to the pressurizer sprays. Since flow indication will not be required until about 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> following an accident, the proposed measures will be adequate to insure a safe shutdown.
1 5
A
.)1
~....
LER No.81-001 Omaha Public Power District Fort Calhoun Station Unit No.1 Docket No. 05000285 ATTACHMENT N0. 2
Corrective Action
The transmitter will be replaced with a qualified transmitter by the end of the 1981 refueling outage.
LER No.81-001 Omaha Public Power District Fort Calhoun Station Unit No.1 Docket No. 05000285 ATTACHMENT NO. 3 Failure Data This is the first report of an unqualified Foxboro M-637 flow transmitter.
T A
|
|---|
|
|
| | | Reporting criterion |
|---|
| 05000285/LER-1981-001, Forwards LER 81-001/01T-0 | Forwards LER 81-001/01T-0 | | | 05000285/LER-1981-001-01, /01T-0:on 810114,discovered That FT-236 Changing Header Flow Lacks Complete Info to Qualify for Harsh Radiation Svc Required by IE Bulletin 79-01B.Caused by Incomplete Matls List.Transmitter Will Be Replaced | /01T-0:on 810114,discovered That FT-236 Changing Header Flow Lacks Complete Info to Qualify for Harsh Radiation Svc Required by IE Bulletin 79-01B.Caused by Incomplete Matls List.Transmitter Will Be Replaced | | | 05000285/LER-1981-002, Forwards LER 81-002/01T-0 | Forwards LER 81-002/01T-0 | | | 05000285/LER-1981-002-01, /01T-0:on 810413,during Normal Operation at 65% Power,Notification Received of Defect in Certain Foxboro Transmitters.Transmitters Have Capacitor Amplifier Which May Fail Due to Heat During Operation or After LOCA | /01T-0:on 810413,during Normal Operation at 65% Power,Notification Received of Defect in Certain Foxboro Transmitters.Transmitters Have Capacitor Amplifier Which May Fail Due to Heat During Operation or After LOCA | | | 05000285/LER-1981-003, Forwards LER 81-003/01T-0 | Forwards LER 81-003/01T-0 | | | 05000285/LER-1981-003-01, /01T-0:on 810428,MSIVs HCV-1041A/HCV-10242A Failed Closed Upon Loss of All 125 Volt Dc Power Feeding Bus A1-41B.Caused by Damaged Cable on 100 Amp Switch.Switch & Cable Replaced.All Breaker Panel Lugs Checked for Tightness | /01T-0:on 810428,MSIVs HCV-1041A/HCV-10242A Failed Closed Upon Loss of All 125 Volt Dc Power Feeding Bus A1-41B.Caused by Damaged Cable on 100 Amp Switch.Switch & Cable Replaced.All Breaker Panel Lugs Checked for Tightness | | | 05000285/LER-1981-004-01, /01T-0:on 810430,personnel Air Lock Door Seals Leak Rate Exceeded Allowable Rate.Caused by Mechanical Door Seals Not Sealing Properly.Seals Repaired | /01T-0:on 810430,personnel Air Lock Door Seals Leak Rate Exceeded Allowable Rate.Caused by Mechanical Door Seals Not Sealing Properly.Seals Repaired | | | 05000285/LER-1981-004, Forwards Revised Attachment 3 to LER 81-04 Re Tech Spec 2.01.Since startup,34 Maint Orders Written on Single Pal Door Seal Failures | Forwards Revised Attachment 3 to LER 81-04 Re Tech Spec 2.01.Since startup,34 Maint Orders Written on Single Pal Door Seal Failures | | | 05000285/LER-1981-005-03, /03L-0:on 810423,dc Sequencer Timers AC-3A (Component Cooling Water Pump) & AC-102A (Raw Water Pump) Failed to Time Out within Prescribed Limit.Cause Unknown Mechanisms Satisfactorily Inspected | /03L-0:on 810423,dc Sequencer Timers AC-3A (Component Cooling Water Pump) & AC-102A (Raw Water Pump) Failed to Time Out within Prescribed Limit.Cause Unknown Mechanisms Satisfactorily Inspected | | | 05000285/LER-1981-005, Forwards LER 81-005/03L-0 | Forwards LER 81-005/03L-0 | | | 05000285/LER-1981-006-03, /03L-0:on 810624,reactor Protection Sys Nuclear Power Recorder Channel B Trip Setpoints Determined to Be Nonconservative.Caused by Faulty Temp Change Power Calculation Due to Grounded Hot Leg Temp Loop | /03L-0:on 810624,reactor Protection Sys Nuclear Power Recorder Channel B Trip Setpoints Determined to Be Nonconservative.Caused by Faulty Temp Change Power Calculation Due to Grounded Hot Leg Temp Loop | | | 05000285/LER-1981-006, Forwards LER 81-006/03L-0 | Forwards LER 81-006/03L-0 | | | 05000285/LER-1981-007, Forwards LER 81-007/03L-0 | Forwards LER 81-007/03L-0 | | | 05000285/LER-1981-007-03, /03L-0:on 810706,discovered That Diesel Generator DG-1 Had Not Started Despite Indications of Attempted Starts.Caused by Faulty Speed Sensing Control Unit.Speed Sensing Unit Replaced | /03L-0:on 810706,discovered That Diesel Generator DG-1 Had Not Started Despite Indications of Attempted Starts.Caused by Faulty Speed Sensing Control Unit.Speed Sensing Unit Replaced | | | 05000285/LER-1981-008-03, /03L-0:on 810813,86B/CRHS (Containment Radiation High Signal) Lockout Relay Failed to Actuate When RM-062 Was Placed in Alarm,Resulting in Failure of 86B1/CRHS Relay to Actuate.Caused by Dirt in Relay Latching Mechanism | /03L-0:on 810813,86B/CRHS (Containment Radiation High Signal) Lockout Relay Failed to Actuate When RM-062 Was Placed in Alarm,Resulting in Failure of 86B1/CRHS Relay to Actuate.Caused by Dirt in Relay Latching Mechanism | | | 05000285/LER-1981-008, Forwards LER 81-008/03L-0 | Forwards LER 81-008/03L-0 | | | 05000285/LER-1981-009-03, /03L-0:on 810924,during Shutdown,Cooling Fan/Coil Placed in Svc for Containment Air Cooling.Pressurized Leak Developed When Coil End Plug Blew Out.Caused by Stripped Threads on Loosely Installed Thread End Plug | /03L-0:on 810924,during Shutdown,Cooling Fan/Coil Placed in Svc for Containment Air Cooling.Pressurized Leak Developed When Coil End Plug Blew Out.Caused by Stripped Threads on Loosely Installed Thread End Plug | | | 05000285/LER-1981-009, Forwards LER 81-009/03L-0 | Forwards LER 81-009/03L-0 | | | 05000285/LER-1981-010-03, /03L-0:on 811027,D/LC-383-1 Left & Right Switches & D/LC-383-2 Left & Right Switches Found Out of Setpoint Tolerances.Caused by D Channel Level Switches Drifting Out of Calibr for Unknown Reasons.Switches Recalibr | /03L-0:on 811027,D/LC-383-1 Left & Right Switches & D/LC-383-2 Left & Right Switches Found Out of Setpoint Tolerances.Caused by D Channel Level Switches Drifting Out of Calibr for Unknown Reasons.Switches Recalibr | | | 05000285/LER-1981-010, Forwards LER 81-010/03L-0 | Forwards LER 81-010/03L-0 | | | 05000285/LER-1981-011, Forwards LER 81-011/03L-0 | Forwards LER 81-011/03L-0 | | | 05000285/LER-1981-011-03, /03L-0:on 811113,containment Isolation Valves Opened & Ventilation Process Initiated W/Containment Air Monitor RM-050/051 Inoperable.Caused by Personnel Error. Valves Closed | /03L-0:on 811113,containment Isolation Valves Opened & Ventilation Process Initiated W/Containment Air Monitor RM-050/051 Inoperable.Caused by Personnel Error. Valves Closed | |
|