ML19338G523

From kanterella
Jump to navigation Jump to search
Notice of Violation from Insp on 800602-27
ML19338G523
Person / Time
Site: Catawba  
Issue date: 07/18/1980
From:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
To:
Shared Package
ML19338G520 List:
References
50-413-80-14, 50-414-80-14, NUDOCS 8010310031
Download: ML19338G523 (1)


Text

--

~

O a

1 1

APPENDIX A NOTICE OF VIOLATION 4

Duke Power Company License Nos. CPPR-116 i

Catawba Nuclear Station

& CPPR-117 l

j Based on the NRC inspection June 2-27, 1980, certain of your activities were apparently not conducted in f all compliance with NRC requirements as indicated j

below. These items have been categorized as described in correspondence to you dated December 31, 1974.

i i

A.

As required by Criterion V of Appendix B to 10 CFR 50, as implemented by I

Duke's Topical Report, paragraph 17.1.5.2, work is to be performed in l

accordance with drawings and procedures.

i Contrary to the above, a unit 1 pipe strut was found to have its ball bushing wedged with a piece of metal; restricting movement of the strut bar.

Placement of this wedge in the bushing was not according to procedure.

i This is an infraction. This infraction applies to CPPR-116 only.

B.

As required by Criterion V of Appendix B to 10 CFR 50, as implemented by Duke's Topical Report, paragraph 17.1.5.2, work is to be performed in accordance with drawings.

Contrary to the above, two structural steel welds were found to be shorter than the lengths required by the applicable DPC drawing.

7 This is an infraction -

i C.

As required by Criterion III of Appendix B to 10 CFR 50, as implemented by 1

Duke's Topical Report, paragraph 17.1.3, design documents specify materials that are compatible with each other, environmental conditions to which i

materials can be exposed and the quality assurance requirements.

Contrary to the above, design documents did not specify the type fastening 1

materials or their quality requirements for terminations at the motor end of medium and high voltage class 1E motors.

I This is a deficiency.

i i

4 a

1 gases" i

i

?

,~c,

-n

,m-

~


~n.--+.,.,.--non--

-,n,

,.,p-e-p7, m--