ENCLOSURE 1 MONTICELLO NUCLEAR GENERATING PLANT Notification of Changes to the Emergency Response Data System (EROS)

EROS DATA POINT LIBRARY (66 Pages Follow)

Northern States Power Company Monticello Nuclear Generating Plant

Title:

Software Requirement Specification Number:

SRS Plant Process Computer System - Emergency Response Data System (EROS) - Data Point Library SRS-MT-PPCS-ERDS-DPL-013 Sheet No:

1 Prepared By:

Effective Date:

Reviewed By:

LIST OF PAGES SHEET DESCRIPTION 1

LIST OF PAGES 2

NI POWER RANGE 7

NI INTER RANGE 8

NI SOURC RNG 9

REAC VES LEV 10 RCS PRESSURE 11 MAIN FD FLOW 13 HPCI FLOW 14 RCIC FLOW 15 LPCI FLOW 19 CR SPRAYFL 21 DW ED SMP LV 22 DW FD SMP LV 23 EFF GAS 27 EFF LIQ RAD 33 COND A/E RAD 35 DW RAD 37 MN STEAM RAD 41 DWPRESS 42 DWTEMP 43 SP TEMP 44 SP LEVEL 45 H2 CONG 47 02 CONG REVISION and DATE Revision 8, 5/12/06 Revision 8, 5/12/06 Revision 9, 5/06/09 Revision 9, 5/06/09 Revision 9, 5/06/09 Revision 9, 5/06/09 Revision 9, 5/06/09 Revision 9, 5/06/09 Revision 9, 5/06/09 Revision 9, 5/06/09 Revision 9, 5/06/09 Revision 9, 5/06/09 Revision 9, 5/06/09 Revision 13, 10/08/19 Revision 9, 5/06/09 Revision 9, 5/06/09 Revision 9, 5/06/09 Revision 11, 4/20/12 Revision 9, 5/06/09 Revision 9, 5/06/09 Revision 9, 5/06/09 Revision 9, 5/06/09 Revision 9, 5/06/09


~--49--G-S--f-L:EVEL--* ------

Revision 9, 5/06/09 Revision-9;-5/06/09 Revision 10, 3/15/12 51 WIND SPEED

__ 55_

_WIND_DIR_~_ ____

_________ B.evision 10, 3/15/12. __________ _

59 STAB CLASS Revision 10, 3/15/12 63 Contacts Revision 13, 10/08/19 65 Data Feeder Information Revision 13, 10/08/19

Northern States Power Company Monticello Nuclear Generatinq Plant

Title:

Software Reauirement Specification Number:

SRS Plant Process Computer System - Emergency Response Data System (EROS) - Data Point Library SRS-MT-PPCS-ERDS-DPL-013 Date:

Reactor Unit:

Data Feeder:

NRG EROS Parameter:

Point ID:

Plant Spec Point Desc.:

Generic/Cond Desc.:

Analog/Digital Engr Units/Dig States:

Engr Units Conversion:

Minimum 1n*str Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

Alarm/Trip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

remperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 01/07/92 M01 PCS NI POWER RNG C51C4001 Sheet No:

2 AVERAGE CONSISTENT APRM READING NUCLEAR INSTRUMENTS, POWER RANGE A

N/A 0

125 N/A N/A p

12 AVERAGE OF CONSISTENT APRMS APRM UTILIZE 24 LPRMS LOCATED IN CORE HI-HI TRIP=(.58W+62%),W=%RECIRC FLOW N/A N/A DOWNSCALE(3%),INOP,BYPASS N/A N/A This point consists of either an average of all consistent APRMs or an average of in-range APRMs if there are less than the required number of consistent signals.

APRMS(Average Power Range Monitors) consist of an average of 24 LPRMs (Local Power Range Monitors). Each individual APRM signal will fail on Downscale(3%), lnop, or Bypass. HI-HI trip feed RPS SCRAM for one-out-of-three-twice logic. HI trip (.58W+50%) results in Rod Withdraw Block.

Northern States Power Company Monticello Nuclear Generating Plant

Title:

Software Requirement Specification Number:

SRS Plant Process Computer System - Emergency Response Data System (EROS) - Data Point Library SRS-MT-PPCS-ERDS-DPL-013 Date:

Reactor Unit:

Data Feeder:

NRG EROS Parameter:

Point ID:

Plant Spec Point Desc.:

Generic/Cond Desc.:

Analog/Digital Engr Units/Dig States:

Engr Units Conversion:

Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

Alarm/Trip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 05/06/09 M01 PCS NI POWER RNG NUl196 APRM #1 Sheet No:

3 NUCLEAR INSTRUMENTS, POWER RANGE A

N/A 0

125 N/A N/A s

24 AVERAGE OF 24 LPRMs APRM UTILIZE 24 LPRMs LOCATED IN CORE Note A N/A N/A HIGH & LOW SENSOR N/A N/A N/A The APRM provides overall power range monitoring, the range monitored is from approximately 3 to 100% power. The reading of APRM is the average of 24 LPRM signals and provides output signal that are proportional to average neutron flux. The output signal is recorded on reactor control console recorder and indicated on the APRM Panel indicator. Trip circuit associated with APRM channel provides trip output signals to the RMCS rod withdrawal block circuits and the RPS

~scram-circuitry~. ------------------

Note A: Three Alarm/Trip Set Points:

- --Hl_;HI TRIP;;(.66W+59~6%},W;;%RECIRC FLOW UPSCALE TRIP==119.5% (MODE SWITCH IN RUN)

UPSCALE TRIP==18% (MODE SWITCH NOT IN RUN)

Northern States Power Company Monticello Nuclear GeneratinQ Plant

Title:

Software Requirement Specification Number:

SRS Plant Process Computer System - Emergency Response Data System (EROS) - Data Point Library SRS-MT-PPCS-ERDS-DPL-013 Date:

Reactor Unit:

Data Feeder:

NRG EROS Parameter:

Point ID:

Plant Spec Point Desc.:

Generic/Cond Desc.:

Analog/Digital Engr Units/Dig States:

Engr Units Conversion:

Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

Alarm/Trip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 05/06/09 M01 PCS NI POWER RNG NUl197 APRM #4 Sheet No:

4 NUCLEAR INSTRUMENTS, POWER RANGE A

N/A 0

125 N/A N/A s

24 AVERAGE OF 24 LPRMs APRM UTILIZE 24 LPRMs LOCATED IN CORE Note A N/A N/A HIGH & LOW SENSOR N/A N/A N/A The APRM provides overall power range monitoring, the range monitored is from approximately 3 to 100% power. The reading of APRM is the average of 24 LPRM signals and provides output signal that are proportional to average neutron flux. The output signal is recorded on reactor control console recorder and indicated on the APRM Panel indicator. Trip circuit associated with APRM channel provides trip output


~-~---~-~--------~~-signals to-the-RMG£-rodwithdrawal block-circuits and the-RR-£~--

scram circuitry.

-Note*A:-Three-AlarmTTrip-serPoints: * -

HI-HI TRIP=(.66W+59.6%),W=%RECIRC FLOW UPSCALE TRIP=119.5% (MODE SWITCH IN RUN)

UPSCALE TRIP=18% (MODE SWITCH NOT IN RUN)

Northern States Power Company Monticello Nuclear Generatina Plant

Title:

Software Requirement Specification Number:

SRS Plant Process Computer System - Emergency Response Data System (EROS) - Data Point Library SRS-MT-PPCS-ERDS-DPL-013 Date:

Reactor Unit:

Data Feeder:

NRC EROS Parameter:

Point ID:

Plant Spec Point Desc.:

Generic/Cond Desc.:

Analog/Digital Engr Units/Dig States:

Engr Units Conversion:

Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

Alarm/Trip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 05/06/09 M01 PCS NI POWER RNG NUl198 APRM #2 Sheet No:

5 NUCLEAR INSTRUMENTS, POWER RANGE A

N/A 0

125 N/A N/A s

24 AVERAGE OF 24 LPRMs APRM UTILIZE 24 LPRMs LOCATED IN CORE sNote A N/A N/A HIGH & LOW SENSOR N/A N/A N/A The APRM provides overall power range monitoring, the range monitored is from approximately 3 to 100% power. The reading of APRM is the average of 24 LPRM signals and provides output signal that are proportional to average neutron flux. The output signal is recorded on reactor control console recorder and indicated on the APRM Panel indicator. Trip circuit associated with APRM channel provides trip output signals-to the-RMCS rod withdrawal-block-circuits and-the-RRS--

scram circuitry.


-Note A:-ThreEfAlarmTTripSet-Points~--

HI-HI TRIP=(.66W+59.6%),W=%RECIRC FLOW UPSCALE TRIP=119.5% (MODE SWITCH IN RUN)

UPSCALE TRIP=18% (MODE SWITCH NOT IN RUN)

~----------------------

Northern States Power Company Monticello Nuclear Generatina Plant

Title:

Software Requirement Soecification Number:

SRS Plant Process Computer System - Emergency Response Data System (EROS) - Data Point Library SRS-MT-PPCS-ERDS-DPL-013 Date:

Reactor Unit:

Data Feeder:

NRC EROS Parameter:

Point ID:

Plant Spec Point Desc.:

Generic/Cond Desc.:

Analog/Digital Engr Units/Dig States:

Engr Units Conversion:

Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

Alarm/Trip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 05/06/09 M01 PCS NI POWER RNG NUl200 APRM #3 Sheet No:

6 NUCLEAR INSTRUMENTS, POWER RANGE A

N/A 0

125 N/A N/A s

24 AVERAGE OF 24 LPRMs APRM UTILIZE 24 LPRMs LOCATED IN CORE Note A N/A N/A HIGH & LOW SENSOR N/A N/A N/A The APRM provides overall power range monitoring, the range monitored is from approximately 3 to 100% power. The reading of APRM is the average of 24 LPRM signals and provides output signal that are proportional to average neutron flux. The output signal is recorded on reactor control console recorder and indicated on the APRM Panel indicator. Trip circuit associated with APRM channel provides trip output

---~--~---------- ---- -----signals-to-the-RMGS-rod-withdrawal-block-circuits-and-the-RRS---

scram circuitry.

-- Note-A~Three AlarrnlTrip-setPoints: ------

HI-HI TRIP=(.66W+59.6%),W=%RECIRC FLOW UPSCALE TRIP=119.5% (MODE SWITCH IN RUN)

UPSCALE TRIP=18% (MODE SWITCH NOT IN RUN)

Northern States Power Company Monticello Nuclear GeneratinQ Plant

Title:

Software Requirement Specification Number:

SRS Plant Process Computer System - Emergency Response Data System (EROS) - Data Point Library SRS-MT-PPCS-ERDS-DPL-013 Date:

Reactor Unit:

Data Feeder:

NRG EROS Parameter:

Point ID:

Plant Spec Point Desc.:

Generic/Cond Desc.:

Analog/Digital Engr Units/Dig States:

Engr Units Conversion:

Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

Alarm/Trip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

System.

DATA POINT LIBRARY REFERENCE FILE 01/07/92 M01 PCS NI INTER RNG (not available)

Sheet No:

7 NUCLEAR INSTRUMENTS, INTERMEDIATE RANGE Not available to Process Computer

Northern States Power Company Monticello Nuclear Generating Plant

Title:

Software Requirement Specification Number:

SRS Plant Process Computer System - Emergency Response Data System (EROS) - Data Point Library SRS-MT-PPCS-ERDS-DPL-013 Date:

Reactor Unit:

Data Feeder:

NRG EROS Parameter:

Point ID:

Plant Spec Point Desc.:

Generic/Cond Desc.:

Analog/Digital Engr Units/Dig States:

Engr Units Conversion:

Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

Alarm/Trip Set Points:

NID~eciorPowerSupp~

Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 01/07/92 M01 PCS NI SOURC RNG (not available)

Sheet No:

8 NUCLEAR INSTRUMENTS, SOURCE RANGE Not available to Process Computer System.

Northern States Power Company Monticello Nuclear GeneratinQ Plant

Title:

Software Requirement Specification Number:

SRS Plant Process Computer System - Emergency Response Data System (EROS) - Data Point Library SRS-MT-PPCS-ERDS-DPL-013 Date:

Reactor Unit:

Data Feeder:

NRG EROS Parameter:

Point ID:

Plant Spec Point Desc.:

Generic/Cond Desc.:

Analog/Digital Engr Units/Dig States:

Engr Units Conversion:

Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

Alarm/Trip Set Points:

NID~eciorPowerSupp~

Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 01/07/92 M01 PCS REAC VES LEV B21C0010 RPV VALIDATED WATER LEVEL REACTOR VESSEL WATER LEVEL A

INCHES N/A

-350 350 MSSKRT Sheet No:

9 O" CORRESPONDS TO 126" ABOVE TOP OF FUEL p

28 WEIGHTED AVERAGE OF CONSISTENT LEVELS LEVEL REF LEGS - 5 HOT(IN OW) & 2 COLD

-48"=ECCS INIT, 9"=SCRAM, 48"=HI TRIP N/A N/A

+280" TOP OF REACTOR HEAD N/A WET This point consists of either a weighted average of all consistent level indicators or an average of in-range level indicators if there are less than the required number of consistent signals. Algorithm performs temperature compensation and evaluates reference leg flashing on 7 level signals. Safeguards Levels (-50" to 50") utilize cold reference leg design outside of drywell. EGGS levels (-335" to 65") are invalidated with recirc pumps running. Other levels include 2


~--feedwater-( 0-to -60-}-and J_vesseUlood-(--50"---to 350"-). ~~~~~-


~-----------~-------------~--

Northern States Power Company Monticello Nuclear Generatina Plant

Title:

Software Requirement Specification Number:

SRS Plant Process Computer System - Emergency Response Data System (EROS) - Data Point Library SRS-MT-PPCS-ERDS-DPL-013 Sheet No:

10 Date:

Reactor Unit:

Data Feeder:

NRC EROS Parameter:

Point ID:

Plant Spec Point Desc.:

Generic/Cond Desc.:

Analog/Digital Engr Units/Dig States:

Engr Units Conversion:

Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

Alarm/Trip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 01/19/93 M01 PCS RCS PRESSURE B21C0210 RPV VALIDATED PRESSURE REACTOR COOLANT SYSTEM PRESSURE A

PSIG N/A 0.00 1500 N/A N/A p

3 WEIGHTED AVERAGE OF CONSISTENT LEVELS PRESSURE SENSED OFF LEVEL REF LEGS 1056 PSIG=SCRAM N/A N/A HI/LOW SENSOR N/A N/A This point consists of either a weighted average of all consistent pressure indicators or an average of in-range pressure level indicators if there are less than the required number of consistent signals.

Northern States Power Company Monticello Nuclear Generatinq Plant

Title:

Software Requirement Specification Number:

SRS Plant Process Computer System - Emergency Response Data System (EROS) - Data Point Library SRS-MT-PPCS-ERDS-DPL-013 Date:

Reactor Unit:

Data Feeder:

NRG EROS Parameter:

Point ID:

Plant Spec Point Desc.:

Generic/Cond Desc.:

Analog/Digital Engr Units/Dig States:

Engr Units Conversion:

Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

Alarm/Trip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 01/07/92 M01 PCS MAIN FD FLOW C51 C9001 Sheet No:

11 SMOOTHED FEEDWATER FLOW LOOP A FEEDWATER FLOW INTO THE REACTOR SYSTEM A

MLB/HR N/A 0

4 N/A N/A p

4 SMOOTHED FW FLOW CALC FROM A NOZZLE D/P FW NOZZLE IS DOWNSTREAM OF RX FW PUMPS N/A N/A N/A HI/LOW SENSOR N/A N/A N/A SMOOTHED FW FLOW LOOP A is calculated using Feedwater nozzle D/P, Pressure, and temperature. Smoothing algorithm sums 1 /12 current sample + 11 /12 of previous smoothed value. Sampling frequency is 5 seconds. Feedwater nozzles are located downstream of Reactor Feedwater Pumps and ahead of high pressure heaters.

Northern States Power Company Monticello Nuclear GeneratinQ Plant

Title:

Software Reouirement Specification Number:

SRS Plant Process Computer System - Emergency Response Data System (EROS) - Data Point Library SRS-MT-PPCS-ERDS-DPL-013 Date:

Reactor Unit:

Data Feeder:

NRG EROS Parameter:

Point ID:

Plant Spec Point Desc.:

Generic/Cond Desc.:

Analog/Dig ital Engr Units/Dig States:

Engr Units Conversion:

Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

Alarm/Trip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

~~-----------

DATA POINT LIBRARY REFERENCE FILE 01/07/92 M01 PCS MAIN FD FLOW C51C9002 Sheet No:

12 SMOOTHED FEEDWATER FLOW LOOP B FEEDWATER FLOW INTO THE REACTOR SYSTEM A

MLB/HR N/A 0

4 N/A N/A p

4 SMOOTHED FW FLOW CALC FROM B NOZZLE D/P FW NOZZLE IS DOWNSTREAM OF RX FW PUMPS N/A N/A N/A HI/LOW SENSOR N/A N/A N/A SMOOTHED FW FLOW LOOP Bis calculated using Feedwater nozzle O/P, Pressure, and temperature. Smoothing algorithm sums 1 /12 current sample + 11 /12 of previous smoothed value. Sampling frequency is 5 seconds. Feedwater nozzles are located downstream of Reactor Feedwater Pumps and ahead of high pressure heaters.

Northern States Power Company Monticello Nuclear Generatinq Plant

Title:

Software Requirement Specification Number:

SRS Plant Process Computer System - Emergency Response Data System (EROS) - Data Point Library SRS-MT-PPCS-ERDS-DPL-013 Date:

Reactor Unit:

Data Feeder:

NRG EROS Parameter:

Point ID:

Plant Spec Point Desc.:

Generic/Cond Desc.:

Analog/Digital Engr Units/Dig States:

Engr Units Conversion:

Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

Alarm/Trip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 01/19/93 M01 PCS HPCI FLOW HPC100 HPCI PUMP DISCHARGE FLOW Sheet No:

13 HIGH PRESSURE COOLANT INJECTION FLOW A

GPM N/A 0

3500 N/A N/A s

1 SIGNAL INPUT FROM FLOW TRANSMITTER FLOW ELEMENT ON HPCI PUMP DISHARGE N/A N/A N/A HIGH & LOW SENSOR N/A N/A N/A HPCI is a steam turbine driven pump designed to deliver 2700 gpm over reactor pressure range of 150-1120 psig. Flow element is located on pump discharge line ahead of the test return line to the CST tanks and injection line into "B" feedwater line. HPCI injects into feedwater line prior to the line entering containment.

Northern States Power Company Monticello Nuclear Generatina Plant

Title:

Software Reauirement Specification Number:

SRS Plant Process Computer System - Emergency Response Data System (EROS) - Data Point Library SRS-MT-PPCS-ERDS-DPL-013 Date:

Reactor Unit:

Data Feeder:

NRG EROS Parameter:

Point ID:

Plant Spec Point Desc.:

Generic/Cond Desc.:

Analog/Digital Engr Units/Dig States:

Engr Units Conversion:

Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

Alarm/Trip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:


*~~

DATA POINT LIBRARY REFERENCE FILE 01/07/92 M01 PCS RCIC FLOW RCl100 Sheet No:

14 RCIC PUMP DISCHARGE FLOW REACTOR CORE ISOLATION COOLING A

GPM N/A 0

500 N/A N/A s

1 SIGNAL INPUT FROM FLOW TRANSMITTER FLOW ELEMENT ON RCIC PUMP DISHARGE N/A N/A N/A HIGH & LOW SENSOR N/A N/A N/A RCIC is a steam turbine driven pump designed to deliver 400 gpm over reactor pressure range of 150-1120 psig. Flow element is located on pump discharge line ahead of the test return line to the CST tanks and injection line into "A" feedwater line. RCIC injects into feedwater line prior to the line entering containment.

Northern States Power Company Monticello Nuclear GeneratinQ Plant

Title:

Software Requirement Specification Number:

SRS Plant Process Computer System - Emergency Response Data System (EROS) - Data Point Library SRS-MT-PPCS-ERDS-DPL-013 Sheet No:

15 Date:

Reactor Unit:

Data Feeder:

NRG EROS Parameter:

Point ID:

Plant Spec Point Desc.:

Generic/Cond Desc.:

Analog/Digital Engr Units/Dig States:

Engr Units Conversion:

Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

Alarm/Trip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 01/07/92 M01 PCS LPCI FLOW RHR100 CONTAINMENT SPRAY/COOLING A LOOP LOW PRESSURE COOLANT INJECTION FLOW A

GPM N/A 0

10000 N/A N/A s

1 SIGNAL INPUT FROM FLOW TRANSMITTER DISCHARGE OF RHR HEAT EXCHANGERS N/A N/A N/A HIGH & LOW SENSOR N/A N/A N/A CONTAINMENT SPRAY/COOLING A LOOP flow is the RHR flow to the A loop drywell spray, torus spray and torus cooling.

Each RHR pump is approximately rated at 4000 gpm depending on system head. Two pumps are located in each loop although flow can be cross tied between A and B loops.

---~----

Northern States Power Company Monticello Nuclear Generatina Plant

Title:

Software Requirement Specification Number:

SRS Plant Process Computer System - Emergency Response Data System (EROS) - Data Point Library SRS-MT-PPCS-ERDS-DPL-013 Sheet No:

16 Date:

Reactor Unit:

Data Feeder:

NRG EROS Parameter:

Point ID:

Plant Spec Point Desc.:

Generic/Cond Desc.:

Analog/Dig ital Engr Units/Dig States:

Engr Units Conversion:

Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

Alarm/Trip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 01/07/92 M01 PCS LPCI FLOW RHR101 CONTAINMENT SPRAY/COOLING BLOOP LOW PRESSURE COOLANT INJECTION FLOW A

GPM N/A 0

10000 N/A N/A s

1 SIGNAL INPUT FROM FLOW TRANSMITTER DISCHARGE OF RHR HEAT EXCHANGERS N/A N/A N/A HIGH & LOW SENSOR N/A N/A N/A CONTAINMENT SPRAY/COOLING BLOOP flow is the RHR flow to the Bloop drywell spray, torus spray and torus cooling.

Each RHR pump is approximately rated at 4000 gpm depending on system head. Two pumps are located in each loop although flow can be cross tied between A and B loops.

Northern States Power Company Monticello Nuclear Generatinq Plant

Title:

Software Reauirement Specification Number:

SRS Plant Process Computer System - Emergency Response Data System (EROS) - Data Point Library SRS-MT-PPCS-ERDS-DPL-013 Date:

Reactor Unit:

Data Feeder:

NRG EROS Parameter:

Point ID:

Plant Spec Point Desc.:

Generic/Cond Desc.:

Analog/Digital Engr Units/Dig States:

Engr Units Conversion:

Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

Alarm/Trip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 01/07/92 M01 PCS LPCI FLOW RHR102 RHR LOOP A INJECT FLOW Sheet No:

17 LOW PRESSURE COOLANT INJECTION FLOW A

GPM N/A 0

10000 N/A N/A s

1 SIGNAL INPUT FROM FLOW TRANSMITTER DISCHARGE OF RHR HEAT EXCHANGERS N/A N/A N/A HIGH & LOW SENSOR N/A N/A N/A RHR LOOP A INJECT FLOW is the RHR flow to the A Recirc Loop, Reactor Head Cooling, Waste Surge Tank, and cross tie to B Loop. Each RHR pump is rated at about 4000 gpm depending on system head. Two pumps are located in each loop although flow can be cross tied between A and B loops.

Northern States Power Company Monticello Nuclear Generating Plant

Title:

Software Requirement Specification Number:

SRS Plant Process Computer System - Emergency Response Data System (EROS) - Data Point Library SRS-MT-PPCS-ERDS-DPL-013 Sheet No:

18 Date:

Reactor Unit:

Data Feeder:

NRC EROS Parameter:

Point ID:

Plant Spec Point Desc.:

Generic/Cond Desc.:

Analog/Dig ital Engr Units/Dig States:

Engr Units Conversion:

Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

Alarm/Trip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 01/07/92 M01 PCS LPCI FLOW RHR103 RHR LOOP B INJECT FLOW LOW PRESSURE COOLANT INJECTION FLOW A

GPM NIA 0

10000 N/A NIA s

1 SIGNAL INPUT FROM FLOW TRANSMITTER DISCHARGE OF RHR HEAT EXCHANGERS N/A NIA N/A HIGH & LOW SENSOR N/A N/A N/A RHR LOOP B INJECT FLOW is the RHR flow to the B Recirc Loop and cross tie to A Loop. Each RHR pump is rated at about 4000 gpm depending on system head. Two pumps are located in each loop although flow can be cross tied between A and B loops.

--~~-----

Northern States Power Company Monticello Nuclear Generatina Plant

Title:

Software Requirement Specification Number:

SRS Plant Process Computer System - Emergency Response Data System (EROS) - Data Point Library SRS-MT-PPCS-ERDS-DPL-013 Sheet No:

19 Date:

Reactor Unit:

Data Feeder:

NRG EROS Parameter:

Point ID:

Plant Spec Point Desc.:

Generic/Cond Desc.:

Analog/Digital Engr Units/Dig States:

Engr Units Conversion:

Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

Alarm/Trip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 01/07/92 M01 PCS CR SPRAY FL CSP100 CS LOOP 11 FLOW Core Spray Cooling System Flow A

GPM N/A 0

5000 N/A N/A s

1 SIGNAL INPUT FROM FLOW TRANSMITTER ON PUMP DISCHARGE LINE N/A N/A HIGH & LOW SENSOR N/A N/A The loop A Core Spray system consists of one electric driven pump designed to deliver 3020 gpm against a system head corresponding to a reactor pressure of 130psi above containment pressure. The flow element is located on the pump discharge line just a head of the reactor vessel injection and test return lines.

Northern States Power Company Monticello Nuclear Generatina Plant

Title:

Software Reauirement Specification Number:

SRS Plant Process Computer System - Emergency Response Data System (EROS) - Data Point Library SRS-MT-PPCS-ERDS-DPL-013 Date:

Reactor Unit:

Data Feeder:

NRC EROS Parameter:

Point ID:

Plant Spec Point Desc.:

Generic/Cond Desc.:

Analog/Digital Engr Units/Dig States:

Engr Units Conversion:

Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

Alarm/Trip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 01/07/92 M01 PCS CR SPRAY FL CSP101 CS LOOP 12 FLOW Sheet No:

20 CORE SPRAY COOLING SYSTEM FLOW A

GPM N/A 0

5000 N/A N/A s

1 SIGNAL INPUT FROM FLOW TRANSMITTER ON PUMP DISCHARGE LINE N/A N/A HIGH & LOW SENSOR N/A N/A The loop B Core Spray system consists of one electric driven pump designed to deliver 3020 gpm against a system head corresponding to a reactor pressure of 130psi above containment pressure. The flow element is located on the pump discharge line just a head of the reactor vessel injection and test return lines.

Northern States Power Company Monticello Nuclear Generatina Plant

Title:

Software Reauirement Soecification Number:

SRS Plant Process Computer System - Emergency Response Data System (EROS) - Data Point Library SRS-MT-PPCS-ERDS-DPL-013 Sheet No:

21 Date:

Reactor Unit:

Data Feeder:

NRC EROS Parameter:

Point ID:

Plant Spec Point Desc.:

Generic/Cond Desc.:

Analog/Digital Engr Units/Dig States:

Engr Units Conversion:

Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

Alarm/Trip Set Points:

NID~eciorPowerSup~y Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 01/07/92 M01 PCS OW ED SMP LV PCT138 OW EQUIP DRAIN SUMP VOL DRYWELL FLOOR DRAIN SUMP LEVEL A

GAL N/A 164 565 N/A N/A s

1 SIGNAL INPUT FROM LEVEL TRANSMITTER DIRECTLY BELOW RX VESSEL IN DRYWELL Hl=555 N/A N/A HIGH & LOW SENSOR N/A N/A This sump collects liquid effluent from valve stem leak-offs, Rx Recirc Pump and piping maintenance drains, reactor well bulkhead and bellows drains, reactor vessel flange leakoff and Drywell Equipment Drain Sump heat exchanger drain. Two 50 GPM pumps discharge the water to the Waste Collector Tank in the Reactor building. Sump is isolated by Group II Isolation or manually from control room. Sump overflows into Drywell Floor Drain Sump at 1090 Gallons.

Northern States Power Company Monticello Nuclear Generating Plant

Title:

Software Requirement Specification Number:

SRS Plant Process Computer System - Emergency Response Data System (EROS) - Data Point Library SRS-MT-PPCS-ERDS-DPL-013 Sheet No:

22 Date:

Reactor Unit:

Data Feeder:

NRG EROS Parameter:

Point ID:

Plant Spec Point Desc.:

Generic/Cond Desc.:

Analog/Digital Engr Units/Dig States:

Engr Units Conversion:

Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

Alarm/Trip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 01/07/92 M01 PCS OW FD SMP LV PCT139 OW FLOOR DRAIN SUMP VOL DRYWELL FLOOR DRAIN SUMP LEVEL A

GAL N/A 164 565 N/A N/A s

1 SIGNAL INPUT FROM LEVEL TRANSMITTER DIRECTLY BELOW RX VESSEL IN DRYWELL Hl=555 N/A N/A HIGH & LOW SENSOR N/A N/A This sump collects liquid effluent from Drywell cooler drains, floor drains, control rod drive leakage and drains, closed cooling water piping drains, and piping and equipment maintenance vents. Two 50 GPM pumps discharge the water to the Floor Drain Collector Tank in the Reactor building.

Sump is isolated by Group II Isolation or manually from control room. Sump overflows into Drywell Equipment Drain Sump at 1090 Gallons.

Northern States Power Company Monticello Nuclear Generatino Plant

Title:

Software Requirement Specification Number:

SRS Plant Process Computer System - Emergency Response Data System (EROS) - Data Point Library SRS-MT-PPCS-ERDS-DPL-013 Sheet No:

23 Date:

Reactor Unit:

Data Feeder:

NRG EROS Parameter:

Point ID:

Plant Spec Point Desc.:

Generic/Cond Oesc.:

Analog/Dig ital:

Engr Units/Dig States:

Engr Units Conversion:

Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

Alarm/Trip Set Points:

NID~ectorPowerSup~y Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 10/08/19 M01 PCS EFF GAS RAD PRM121 FA STACK EFF RAD A 15MRUN RADIOACTIVITY OF RELEASED GASES A

uCI/S N/A 1

10E12 N/A N/A p

1 15 MINUTE AVERAGE OF 5 SECOND VALUES FOUR ISOKINETIC PROBES IN OFF GAS STACK N/A N/A N/A HIGH & LOW SENSOR N/A N/A Data is collected every five seconds, averaged every minute, and stored in data files as 15-minute average.

Northern States Power Company Monticello Nuclear Generatina Plant

Title:

Software Reauirement Specification Number:

SRS Plant Process Computer System - Emergency Response Data System (EROS) - Data Point Library SRS-MT-PPCS-ERDS-DPL-013 Sheet No:

24 Date:

Reactor Unit:

Data Feeder:

NRG EROS Parameter:

Point ID:

Plant Spec Point Desc.:

Generic/Cond Desc.:

Analog/Digital:

Engr Units/Dig States:

Engr Units Conversion:

Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

Alarm/Trip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 10/08/19 M01 PCS EFF GAS RAD PRM122FA STACK EFF RAD B 15MRUN RADIOACTIVITY OF RELEASED GASES A

uCI/S N/A 1

10E12 N/A N/A p

1 15 MINUTE AVERAGE OF 5 SECOND VALUES FOUR ISOKINETIC PROBES IN OFF GAS STACK N/A N/A N/A HIGH & LOW SENSOR N/A N/A Data is collected every five seconds, averaged every minute, and stored in data files as 15-minute average.

---.--.----~-----

Northern States Power Company Monticello Nuclear Generatinq Plant

Title:

Software Requirement Specification Number:

SRS Plant Process Computer System - Emergency Response Data System (EROS) - Data Point Library SRS-MT-PPCS-ERDS-DPL-013 Sheet No:

25 Date:

Reactor Unit:

Data Feeder:

NRG EROS Parameter:

Point ID:

Plant Spec Point Desc.:

Generic/Cond Desc.:

Analog/Digital:

Engr Units/Dig States:

Engr Units Conversion:

Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

Alarm/Trip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 10/08/19 M01 PCS EFF GAS RAD PRM123FA RBV EFFLUENT MONITOR CHA 15MAVG RADIOACTIVITY OF RELEASED GASES A

uCI/S N/A 1

10E12 N/A N/A p

1 15 MINUTE AVERAGE OF 5 SECOND VALUES ISOKINETIC PROBES IN EACH RX BLDG VENT N/A N/A N/A HIGH & LOW SENSOR N/A N/A Data is collected every five seconds, averaged every minute, and stored in data files as 15-minute average.

--- -------~*---- ---~--*

Northern States Power Company Monticello Nuclear Generatinq Plant

Title:

Software Requirement Specification Number:

SRS Plant Process Computer System - Emergency Response Data System (EROS) - Data Point Library SRS-MT-PPCS-ERDS-DPL-013 Sheet No:

26 Date:

Reactor Unit:

Data Feeder:

NRG EROS Parameter:

Point ID:

Plant Spec Point Desc.:

Generic/Cond Desc.:

Analog/Digital:

Engr Units/Dig States:

Engr Units Conversion:

Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

Alarm/Trip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

--~ ---~---------

DATA POINT LIBRARY REFERENCE FILE 10/08/19 M01 PCS EFF GAS RAD PRM124FA RBV EFFLUENT MONITOR CHB 15MAVG RADIOACTIVITY OF RELEASED GASES A

uCI/S N/A 1

10E12 N/A N/A p

1 15 MINUTE AVERAGE OF 5 SECOND VALUES ISOKINETIC PROBES IN EACH RX BLDG VENT N/A N/A N/A HIGH & LOW SENSOR N/A N/A Data is collected every five seconds, averaged every minute, and stored in data files as 15-minute average.

Northern States Power Company Monticello Nuclear Generating Plant

Title:

Software Requirement Specification Number:

SRS Plant Process Computer System - Emergency Response Data System (EROS) - Data Point Library SRS-MT-PPCS-ERDS-DPL-013 Sheet No:

27 Date:

Reactor Unit:

Data Feeder:

NRG EROS Parameter:

Point ID:

Plant Spec Point Desc.:

Generic/Cond Desc.:

  • Analog/Digital:

Engr Units/Dig States:

Engr Units Conversion:

Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

Alarm/Trip Set Points:

NI Detector Power Supply Cut-off Power Level:

NID~eciorPowerSup~y Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 01/07/92 M01 PCS EFF LIQ RAD PRM107 SERVICE WATER EFFLUENT RADIOACTIVITY OF RELEASED LIQUIDS A

CPS uCi/Ml=((PRM107 in CPS)-5)*(4.3E-7)

.1 10E6 N/A N/A s

1 SIGNAL INPUT FROM MONITOR SAMPLES SW PRIOR TO SW LEAVING RX BLDG Hl=20; HI-Hl=31400 N/A N/A DOWNSCALE & UPSCALE N/A N/A Gamma radiation emitted by radioactive materials contained in process liquid are detected by a scintillation detector housed in shielded sampler. Sidestream sample is used from the service water line prior to leaving the Reactor Building. After leaving Reactor Building, line discharges into circ water discharge pipe. Alarm setpoints vary with plant operation as determined by plant chemist.


-~

Northern States Power Company Monticello Nuclear Generatina Plant

Title:

Software Reauirement Specification Number:

SRS Plant Process Computer System - Emergency Response Data System (EROS) - Data Point Library SRS-MT-PPCS-ERDS-DPL-013 Sheet No:

28 Date:

Reactor Unit:

Data Feeder:

NRG EROS Parameter:

Point ID:

Plant Spec Point Desc.:

Generic/Cond Desc.:

Analog/Dig ital:

Engr Units/Dig States:

Engr Units Conversion:

Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

Alarm/Trip Set Points:

NI Detector Power Supply Cut-off Power Level:

NID~eciorPowerSupp~

Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 01/07/92 M01 PCS EFF LIQ RAD PRM109 RADWASTE EFFLUENT RADIOACTIVITY OF RELEASED LIQUIDS A

CPS uCi/Ml=((PRM109 in CPS)-7)*(2.5E-6)

.1 10E6 N/A N/A s

1 SIGNAL INPUT FROM MONITOR SAMPLED PRIOR TO LEAVING RADWASTE BLDG Hl=70; HI-H1=10000000 N/A N/A DOWNSCALE & UPSCALE, INOP N/A N/A Gamma radiation emitted by radioactive materials contained in process liquid are detected by a scintillation detector housed in shielded sampler. Liquid is sampled prior to leaving the Radwaste Building. After leaving Radwaste Building, line discharges into discharge canal. Although Monticello has permits, Monticello maintains a policy of zero liquid radwaste releases into the river. Alarm setpoints vary with plant operation as determined by plant chemist.

Northern States Power Company Monticello Nuclear Generatina Plant

Title:

Software Reauirement Specification Number:

SRS Plant Process Computer System - Emergency Response Data System (EROS) - Data Point Library SRS-MT-PPCS-ERDS-DPL-013 Date:

Reactor Unit:

Data Feeder:

NRC EROS Parameter:

Point ID:

Plant Spec Point Desc.:

Generic/Cond Desc.:

Analog/Dig ital:

Engr Units/Dig States:

Engr Units Conversion:

Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

Alarm/Trip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 01/07/92 MO1 PCS EFF LIQ RAD PRM110 Sheet No:

29 TB NORMAL WASTE SUMP CH A RADIOACTIVITY OF RELEASED LIQUIDS A

CPM uCi/Ml=((PRM110 in CPM)-400)*(3.SE-9) 10 10E6 N/A N/A s

1 SIGNAL INPUT FROM MONITOR SAMPLED PRIOR TO LEAVING TURBINE BLDG Hl=4000;HI-Hl=3780000 N/A N/A DOWNSCALE & UPSCALE, INOP N/A N/A Gamma radiation emitted by radioactive materials contained in process liquid are detected by a scintillation detectors in dry tube in sump. Sampled prior to leaving the Turbine Building.

Alarm setpoints vary with plant operation as determined by plant chemist.


~----- ------------------ -~~---

Northern States Power Company Monticello Nuclear Generatina Plant

Title:

Software Requirement Specification Number:

SRS Plant Process Computer System - Emergency Response Data System (EROS) - Data Point Library SRS-MT-PPCS-ERDS-DPL-013 Date:

Reactor Unit:

Data Feeder:

NRC EROS Parameter:

Point ID:

Plant Spec Point Desc.:

Generic/Cond Desc.:

Analog/Dig ital:

Engr Units/Dig States:

Engr Units Conversion:

Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

Alarm/Trip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 01/07/92 M01 PCS EFF LIQ RAD PRM111 Sheet No:

30 TB NORMAL WASTE SUMP CH B RADIOACTIVITY OF RELEASED LIQUIDS A

CPM uCi/Ml=((PRM111 in CPM)-400)*(3.SE-9) 10 10E6 N/A N/A s

1 SIGNAL INPUT FROM MONITOR SAMPLED PRIOR TO LEAVING TURBINE BLDG Hl=4000;HI-Hl=3780000 N/A N/A DOWNSCALE & UPSCALE, INOP N/A N/A Gamma radiation emitted by radioactive materials contained in process liquid are detected by a scintillation detectors in dry tube in sump. Sampled prior to leaving the Turbine Building.

Alarm setpoints vary with plant operation as determined by plant chemist.

Northern States Power Company Monticello Nuclear Generating Plant

Title:

Software Requirement Specification Number:

SRS Plant Process Computer System - Emergency Response Data System (EROS) - Data Point Library SRS-MT-PPCS-ERDS-DPL-013 Date:

Reactor Unit:

Data Feeder:

NRG EROS Parameter:

Point ID:

Plant Spec Point Desc.:

Generic/Cond Desc.:

Analog/Digital:

Engr Units/Dig States:

Engr Units Conversion:

Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

Alarm/Trip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 01/07/92 M01 PCS EFF LIQ RAD PRM112 Sheet No:

31 DISCHARGE CANAL MONITOR A RADIOACTIVITY OF RELEASED LIQUIDS A

CPS uCi/Ml=((PRM112 in CPS)-2)*(1.4E-7)

.1 10E6 N/A N/A s

1 SIGNAL INPUT FROM MONITOR 550FT DOWNSTREAM FROM DISCHARGE STRUCTURE Hl=40; HI-Hl=93000 N/A N/A DOWNSCALE & UPSCALE, INOP N/A N/A Gamma radiation emitted by radioactive materials contained in process liquid are detected by a scintillation detectors. Sample is drawn from 4 standpipes in canal 550 feet downstream from the discharge structure. Alarm setpoints vary with plant operation as determined by plant chemist.

Northern States Power Company Monticello Nuclear Generatina Plant

Title:

Software Reauirement Specification Number:

SRS Plant Process Computer System - Emergency Response Data System (EROS) - Data Point Library SRS-MT-PPCS-ERDS-DPL-013 Date:

Reactor Unit:

Data Feeder:

NRG EROS Parameter:

Point ID:

Plant Spec Point Desc.:

Generic/Cond Desc.:

Analog/Digital:

Engr Units/Dig States:

Engr Units Conversion:

Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

Alarm/Trip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 01/07/92 M01 PCS EFF LIQ RAD PRM113 Sheet No:

32 DISCHARGE CANAL MONITOR 8 RADIOACTIVITY OF RELEASED LIQUIDS A

CPS uCi/Ml=((PRM113 in CPS)-2)*(1.4E-7)

.1 10E6 N/A N/A s

1 SIGNAL INPUT FROM MONITOR 550FT DOWNSTREAM FROM DISCHARGE STRUCTURE Hl=40; HI-Hl=93000 N/A NIA DOWNSCALE & UPSCALE, INOP N/A NIA Gamma radiation emitted by radioactive materials contained in process liquid are detected by a scintillation detectors. Sample is drawn from 4 standpipes in canal 550 feet downstream from the discharge structure. Alarm setpoints vary with plant operation as determined by plant chemist.


~---------------

Northern States Power Company Monticello Nuclear GeneratinQ Plant

Title:

Software Requirement Specification Number:

SRS Plant Process Computer System - Emergency Response Data System (EROS) - Data Point Library SRS-MT-PPCS-ERDS-DPL-013 Date:

Reactor Unit:

Data Feeder:

NRG EROS Parameter:

Point ID:

Plant Spec Point Desc.:

Generic/Cond Desc.:

Analog/Digital:

Engr Units/Dig States:

Engr Units Conversion:

Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

Alarm/Trip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 01/07/92 M01 PCS CNDA/E RAD PRM118 OFF GAS CH 1 Sheet No:

33 CONDENSER AIR EJECTOR RADIOACTIVITY A

MR/HR N/A 1

10E6 N/A N/A s

1 SIGNAL OUTPUT FROM MONITOR SAMPLE DRAWN FROM OFF GAS LINE Hl=2500; HI-Hl=200000 N/A N/A LOW N/A N/A OFF GAS CH 1 radiation monitor is positioned adjacent to a vertical sample chamber. A continuous sample is drawn from the off gas line downstream from the Steam Jet Air Ejectors and ahead of the Recombiner trains. The sample is monitored after a time delay of approximately 2 minutes to permit Nitrogen-16 and Oxygen-19 to decay. Alarm setpoints vary with plant operation as determined by plant chemist.

Northern States Power Company Monticello Nuclear Generating Plant

Title:

Software Requirement Specification Number:

SRS Plant Process Computer System - Emergency Response Data System (EROS) - Data Point Library SRS-MT-PPCS-ERDS-DPL-013 Sheet No:

34 Date:

Reactor Unit:

Data Feeder:

NRG EROS Parameter:

Point ID:

Plant Spec Point Desc.:

Generic/Cond Desc.:

Analog/Digital:

Engr Units/Dig States:

Engr Units Conversion:

Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

Alarm/Trip Set Points:

NI Detector Power Supply Cut-off Power Level:

NID~ectorPowerSupp~

Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 01/07/92 M01 PCS CND A/E RAD PRM119 OFF GAS CH 2 CONDENSER AIR EJECTOR RADIOACTIVITY A

MR/HR N/A 1

10E6 N/A N/A s

1 SIGNAL OUTPUT FROM MONITOR SAMPLE DOWNSTREAM OF STEAM JET AIR EJECT Hl=2500; HI-Hl=200000 NIA N/A LOW N/A N/A OFF GAS CH 2 radiation monitor is positioned adjacent to a vertical sample chamber. A continuous sample is drawn from the off gas line downstream from the Steam Jet Air Ejectors and ahead of the Recombiner trains. The sample is monitored after a time delay of approximately 2 minutes to permit Nitrogen-16 and Oxygen-19 to decay. Alarm setpoints vary with plant operation as determined by plant chemist.

Northern States Power Company Monticello Nuclear Generatinq Plant

Title:

Software Requirement Specification Number:

SRS Plant Process Computer System - Emergency Response Data System (EROS) - Data Point Library SRS-MT-PPCS-ERDS-DPL-013 Sheet No:

35 Date:

Reactor Unit:

Data Feeder:

NRG EROS Parameter:

Point ID:

Plant Spec Point Desc.:

Generic/Cond Desc.:

Analog/Digital:

Engr Units/Dig States:

Engr Units Conversion:

Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

Alarm/Trip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 01/07/92 M01 PCS DWRAD PCT109 DRYWELL RADIATION CH A RADIATION LEVEL IN THE DRYWELL A

R/HR N/A 1

10E8 N/A N/A s

1 SIGNAL INPUT FROM RADIATION MONITOR DRYWELL 180 DEGREE AZIMUTH AT 944' H1=49.999, HI-Hl=35 N/A N/A HIGH SENSOR, INOP N/A N/A Purpose is to provide estimate of core damage by measuring drywell gamma radiation fields caused by fission product leakage from the core. Each sensor is an ionization chamber with an internal U-234 source which gives 1 R/HR reading for operation verification. Elevation 944' is just below bottom of reactor vessel (949').

Northern States Power Company Monticello Nuclear Generating Plant

Title:

Software Requirement Specification Number:

SRS Plant Process Computer System - Emergency Response Data System (EROS) - Data Point Library SRS-MT-PPCS-ERDS-DPL-013 Sheet No:

36 Date:

Reactor Unit:

Data Feeder:

NRC EROS Parameter:

Point ID:

Plant Spec Point Desc.:

Generic/Cond Desc.:

Analog/Digital:

Engr Units/Dig States:

Engr Units Conversion:

Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

Alarm/Trip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Sply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 01/07/92 M01 PCS DWRAD PCT110 DRYWELL RADIATION CH B RADIATION LEVEL IN THE DRYWELL A

R/HR N/A 1

10E8 N/A N/A s

1 SIGNAL INPUT FROM RADIATION MONITOR DRYWELL O DEGREE AZIMUTH AT 944' HI=49.999, Hl-Hl=35 N/A N/A HIGH SENSOR, INOP N/A N/A Purpose is to provide estimate of core damage by measuring drywell gamma radiation fields caused by fission product leakage from the core. Each sensor is an ionization chamber with an internal U-234 source which gives 1 R/HR reading for operation verification. Elevation 944' is just below bottom of reactor vessel (949').

Northern States Power Company Monticello Nuclear Generatina Plant

Title:

Software Requirement Specification Number:

SRS Plant Process Computer System - Emergency Response Data System (EROS) - Data Point Library SRS-MT-PPCS-ERDS-DPL-013 Sheet No:

37 Date:

Reactor Unit:

Data Feeder:

NRC EROS Parameter:

Point ID:

Plant Spec Point Desc.:

Generic/Cond Desc.:

Analog/Digital:

Engr Units/Dig States:

Engr Units Conversion:

Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

Alarm/Trip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 04/20/12 M01 PCS MN STEAM RAD PRM125 MAIN STEAM LINE RAD CH A RADIATION LEVEL OF THE MAIN STEAM LINE A

MR/H N/A 1

10E6 N/A N/A s

1 SIGNAL INPUT FROM RM-17-251A C10 ADMIN 951' CONTROL ROOM The Main Steam Line Radiation Monitoring System provides continuous control room indication of the gamma radiation level of the main steam tunnel area lines immediately downstream of the outboard main steam isolation valves.

When the gamma sensitive ion chamber (supplied by General Electric) is exposed to gamma radiation, producing current flow is proportional to the gamma radiation level, and serves as the input signal to the logarithmic radiation monitor. The


--monitor-then provides an output-voltage signalproportional to ____ _

the logarithm of the input current. The output voltage signal of the main steam line monitor is also continuously recorded on the plant process computer point (PRM125).- --


~- --------~

Northern States Power Company Monticello Nuclear Generatina Plant

Title:

Software Requirement Specification Number:

SRS Plant Process Computer System - Emergency Response Data System (EROS) - Data Point Library SRS-MT-PPCS-ERDS-DPL-013 Date:

Reactor Unit:

Data Feeder:

NRG EROS Parameter:

Point ID:

Plant Spec Point Desc.:

Generic/Cond Desc.:

Analog/Digital:

Engr Units/Dig States:

Engr Units Conversion:

Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

Alarm/Trip Set Points:

NI Detector Power Supply Cut-off Power Level:

NID~eciorPowerSupp~

Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 04/20/12 M01 PCS MN STEAM RAD PRM126 MAIN STEAM LINE RAD CH B Sheet No:

38 RADIATION LEVEL OF THE MAIN STEAM LINE A

MR/H N/A 1

10E6 N/A N/A s

1 SIGNAL INPUT FROM RM-17-251 B C10 ADMIN 951' CONTROL ROOM The Main Steam Line Radiation Monitoring System provides continuous control room indication of the gamma radiation level of the main steam tunnel area lines immediately downstream of the outboard main steam isolation valves.

When the gamma sensitive ion chamber (supplied by General Electric) is exposed to gamma radiation, producing current flow is proportional to the gamma radiation level, and serves as the input signal to the logarithmic radiation monitor. The


monitor-then provides-an-output-voltage-signal-proportional-to the logarithm of the input current. The output voltage signal of the main steam line monitor is also continuously recorded on

-the plant process computer point (PRM126):

Northern States Power Company Monticello Nuclear Generatinq Plant

Title:

Software Requirement Specification Number:

SRS Plant Process Computer System - Emergency Response Data System (EROS) - Data Point Library SRS-MT-PPCS-ERDS-DPL-013 Sheet No:

39 Date:

Reactor Unit:

Data Feeder:

NRG EROS Parameter:

Point ID:

Plant Spec Point Desc.:

Generic/Cond Desc.:

Analog/Digital:

Engr Units/Dig States:

Engr Units Conversion:

Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

Alarm/Trip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 04/20/12 M01 PCS MN STEAM RAD PRM127 MAIN STEAM LINE RAD CH C RADIATION LEVEL OF THE MAIN STEAM LINE A

MR/H N/A 1

10E6 N/A N/A s

1 SIGNAL INPUT FROM RM-17-251C C10 ADMIN 951' CONTROL ROOM The Main Steam Line Radiation Monitoring System provides continuous control room indication of the gamma radiation level of the main steam tunnel area lines immediately downstream of the outboard main steam isolation valves.

When the gamma sensitive ion chamber (supplied by General Electric) is exposed to gamma radiation, producing current flow is proportional to the gamma radiation level, and serves as the input signal to the logarithmic radiation monitor. The

_____ --------- ------------ monitor-then-provides-an output-voltage signal proportional-to ___ _

the logarithm of the input current. The output voltage signal of the main steam line monitor is also continuously recorded on the plant process computer point (PRM127):--

Northern States Power Company Monticello Nuclear Generatinq Plant

Title:

Software Requirement Specification Number:

SRS Plant Process Computer System - Emergency Response Data System (EROS) - Data Point Library SRS-MT-PPCS-ERDS-DPL-013 Sheet No:

40 Date:

Reactor Unit:

Data Feeder:

NRC EROS Parameter:

Point ID:

Plant Spec Point Desc.:

Generic/Cond Desc.:

Analog/Digital:

Engr Units/Dig States:

Engr Units Conversion:

Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

Alarm/Trip Set Points:

NI Detector Power Supply Cut-off Power Level:

NID~ectorPowerSupp~

Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 04/20/12 M01 PCS MN STEAM RAD PRM128 MAIN STEAM LINE RAD CH D RADIATION LEVEL OF THE MAIN STEAM LINE A

MR/H N/A 1

10E6 N/A N/A s

1 SIGNAL INPUT FROM RM-17-251D C10 ADMIN 951' CONTROL ROOM The Main Steam Line Radiation Monitoring System provides continuous control room indication of the gamma radiation level of the main steam tunnel area lines immediately downstream of the outboard main steam isolation valves.

When the gamma sensitive ion chamber (supplied by General Electric) is exposed to gamma radiation, producing current flow is proportional to the gamma radiation level, and serves as the input signal to the logarithmic radiation monitor. The

---~-- _____________ --monitor-then-provides-an output-voltage-signal-proportional-to ___ _

the logarithm of the input current. The output voltage signal of the main steam line monitor is also continuously recorded on

-- the plant process computer point (PRM128).

Northern States Power Company Monticello Nuclear GeneratinQ Plant

Title:

Software Requirement Specification Number:

SRS Plant Process Computer System - Emergency Response Data System (EROS) - Data Point Library SRS-MT-PPCS-ERDS-DPL-013 Date:

Reactor Unit:

Data Feeder:

NRG EROS Parameter:

Point ID:

Plant Spec Point Desc.:

Generic/Cond Desc.:

Analog/Digital:

Engr Units/Dig States:

Engr Units Conversion:

Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

Alarm/Trip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 01/07/92 M01 PCS OW PRESS D23C0010 VALIDATED DRYWELL PRESSURE DRYWELL PRESSURE A

PSIG N/A

-5 250 N/A N/A p

4 Sheet No:

41 WEIGHTED AVERAGE OF CONSISTENT OW PRESS SENSING LINES FROM DRYWELL ALARMS LOW=0.1, HIGH=1.5 N/A N/A HIGH & LOW SENSOR N/A N/A This point consists of either a weighted average of all consistent drywell pressure or an average of in-range drywell pressures if there are less than the required number of consistent signals. Four drywell pressure signals consist of one narrow range (-2 to 3), one wide range (0 to 80) and two accident (-5 to 250) ranges. Weighted averages produces average that is weighted based on instrument accuracy.

Drywell internal design pressure is 56 PSIG at 281 Degrees F.

AL2J~SIG,-Bes initiates-ReactorSCRAM-and-erimary _____ _

Containment Isolation initiates Group 2 & 3.

--~----- --*--- --* *-------------**---~-**------

Northern States Power Company Monticello Nuclear GeneratinQ Plant

Title:

Software Reauirement Specification Number:

SRS Plant Process Computer System - Emergency Response Data System (EROS) - Data Point Library SRS-MT-PPCS-ERDS-DPL-013 Sheet No:

42 Date:

Reactor Unit:

Data Feeder:

NRC EROS Parameter:

Point ID:

Plant Spec Point Desc.:

Generic/Cond Desc.:

Analog/Digital:

Engr Units/Dig States:

Engr Units Conversion:

Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

Alarmff rip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 01/07/92 M01 PCS DWTEMP D23C0310 VALIDATED DRYWELL TEMPERATURE DRYWELL TEMPERATURE A

DEGF N/A 0

600 N/A N/A p

16 AVERAGE OF CONSISTENT OW TEMPERAURES 16 SENSORS AT 8 DRYWELL LOCATIONS Hl==150 DEGF N/A N/A HIGH & LOW SENSOR N/A N/A This point consists of either a weighted average bulk temperature of consistent regional temperatures or an unvalidated, non-weighted average of all in-range drywell temperatures. Regional weighting factors compensate for differences in drywell volume at the various elevations. Each location utilizes two sensors and are located in Drywell at: Elev 932' (East & West), Elev 951 '(North & South), Elev 970' (East

& West), and Elev 994' (North & South).

Northern States Power Company Monticello Nuclear Generatina Plant

Title:

Software Reauirement Specification Number:

SRS Plant Process Computer System - Emergency Response Data System (EROS) - Data Point Library SRS-MT-PPCS-ERDS-DPL-013 Sheet No:

43 Date:

Reactor Unit:

Data Feeder:

NRG EROS Parameter:

Point ID:

Plant Spec Point Desc.:

Generic/Cond Desc.:

Analog/Dig ital:

Engr Units/Dig States:

Engr Units Conversion:

Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

Alarm/Trip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 01/07/92 M01 PCS SP TEMP D23C0210 VALIDATED TORUS TEMPERATURE SUPPRESSION POOL TEMPERATURE A

DEGF N/A 30 240 N/A N/A p

16 AVERAGE OF 2 SPOTMOS (8 SENSORS EACH) 2 SENSORS IN EACH OF 8 TORUS SRV BAYS HIGH=90 N/A N/A HIGH & LOW SENSOR, SPOTMOS INOP N/A N/A VALIDATED TORUS TEMPERATURE is the average of the inputs from two Suppression Pool Temperature Monitoring Systems (SPOTMOS). Each system generates an average of eight sensors. Each sensor is located in one of the eight bays that Safety Relief Valves discharge into.

Northern States Power Company Monticello Nuclear GeneratinQ Plant

Title:

Software Requirement Specification Number:

SRS Plant Process Computer System - Emergency Response Data System (EROS) - Data Point Library SRS-MT-PPCS-ERDS-DPL-013 Sheet No:

44 Date:

Reactor Unit:

Data Feeder:

NRG EROS Parameter:

Point ID:

Plant Spec Point Desc.:

Generic/Cond Desc.:

Analog/Digital:

Engr Units/Dig States:

Engr Units Conversion:

Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

Alarm/Trip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 01/07/92 M01 PCS SP LEVEL G43C0015 VALIDATED TORUS WATER LEVEL SUPPRESSION POOL WATER LEVEL A

INCHES N/A

-96 180 N/A 0"=ELEVATION 910'= 530,000 GALLONS p

4 WEIGHTED AVERAGE OF CONSISTENT LEVELS LEVEL TAPS OFF TORUS SHELL HIGH=2, LO=-2 N/A N/A HIGH & LOW SENSOR N/A N/A This point consists of either a weighted average of all consistent torus water levels or an average of in-range torus water levels if there are less than the required number of consistent signals. Four torus water level signals consist of two narrow range (-15 to 15) and two wide range (-96 to 180).

Weighted averages produce an average that is based on instrument accuracy. HPCI suction transfer occurs at 2". Tech Specs level greater than -4" and less than 2.9".

~~--~--------

~~~------~--

Northern States Power Company Monticello Nuclear Generatinq Plant

Title:

Software Requirement Specification Number:

SRS Plant Process Computer System - Emergency Response Data System (EROS) - Data Point Library SRS-MT-PPCS-ERDS-DPL-013 Sheet No:

45 Date:

Reactor Unit:

Data Feeder:

NRG EROS Parameter:

Point ID:

Plant Spec Point Desc.:

Generic/Cond Desc.:

Analog/Digital:

Engr Units/Dig States:

Engr Units Conversion:

Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

Alarm/Trip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 01/07/92 M01 PCS H2 CONG PCT116 PCTMT H2 ANALYZER A DRYWELL OR TORUS HYDROGEN CONCENTRATION A

N/A 0

20 N/A N/A s

1 SIGNAL OUTPUT FROM H2 ANALYZER SAMPLE LINES UPPER DW,TORUS,CGCS IN & OUT N/A N/A N/A HIGH & LOW SENSOR, SYSTEM OFF N/A N/A Analyzers are normally shutdown and values will usually read less than 0.75%. System is capable of analyzing samples from Drywell (elev 994'), Torus and Combustible Gas Control System inlet and outlet. Sample line and sample return valves close on Group 2 Isolation.

Northern States Power Company Monticello Nuclear Generatino Plant

Title:

Software Reauirement Soecification Number:

SRS Plant Process Computer System - Emergency Response Data System (EROS) - Data Point Library SRS-MT-PPCS-ERDS-DPL-013 Sheet No:

46 Date:

Reactor Unit:

Data Feeder:

NRC EROS Parameter:

Point ID:

Plant Spec Point Desc.:

Generic/Cond Desc.:

Analog/Digital:

Engr Units/Dig States:

Engr Units Conversion:

Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

Alarm/Trip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 01/07/92 M01 PCS H2 CONG PCT117 PCTMT H2 ANALYZER B DRYWELL OR TORUS HYDROGEN CONCENTRATION A

N/A 0

20 N/A N/A s

1 SIGNAL OUTPUT FROM H2 ANALYZER SAMPLE LINES UPPER DW,TORUS,CGCS IN & OUT N/A N/A N/A HIGH & LOW SENSOR, SYSTEM OFF N/A N/A Analyzers are normally shutdown and values will usually read less than 0.75%. System is capable of analyzing samples from Drywell (elev 994'), Torus and Combustible Gas Control System inlet and outlet. Sample line and sample return valves close on Group 2 Isolation.

Northern States Power Company Monticello Nuclear Generatina Plant

Title:

Software Reauirement Specification Number:

SRS Plant Process Computer System - Emergency Response Data System (EROS) - Data Point Library SRS-MT-PPCS-ERDS-DPL-013 Sheet No:

47 Date:

Reactor Unit:

Data Feeder:

NRG EROS Parameter:

Point ID:

Plant Spec Point Desc.:

Generic/Cond Desc.:

Analog/Digital:

Engr Units/Dig States:

Engr Units Conversion:

Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

Alarm/Trip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 01/07/92 MO1 PCS 02CONC PCT118 PCTMT 02 ANALYZER A DRYWELL OR TORUS OXYGEN CONCENTRATION A

N/A 0

25 N/A N/A s

1 SIGNAL OUTPUT FROM 02 ANALYZER SAMPLE LINES UPPER DW,TORUS,CGCS IN & OUT N/A N/A N/A HIGH & LOW SENSOR, SYSTEM OFF N/A N/A Analyzers are normally shutdown and values will usually read less than 0.75%. System is capable of analyzing samples from Drywell (elev 994'), Torus and Combustible Gas Control System inlet and outlet. Sample line and sample return valves close on Group 2 Isolation. Normal operation concentrations are 2.4%.

-~~~~~~~---------~---

Northern States Power Company Monticello Nuclear Generating Plant

Title:

Software Requirement Specification Number:

SRS Plant Process Computer System - Emergency Response Data System (EROS) - Data Point Library SRS-MT-PPCS-ERDS-DPL-013 Date:

Reactor Unit:

Data Feeder:

NRC EROS Parameter:

Point ID:

Plant Spec Point Desc.:

Generic/Cond Desc.:

Analog/Digital:

Engr Units/Dig States:

Engr Units Conversion:

Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

Alarm/Trip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 01/07/92 M01 PCS 02 CONG PCT119 PCTMT 02 ANALYZER B Sheet No:

48 DRYWELL OR TORUS OXYGEN CONCENTRATION A

N/A 0

25 N/A N/A s

1 SIGNAL OUTPUT FROM 02 ANALYZER SAMPLE LINES UPPER DW,TORUS,CGCS IN & OUT N/A N/A N/A HIGH & LOW SENSOR, SYSTEM OFF N/A N/A Analyzers are normally shutdown and values will usually read less than 0.75%. System is capable of analyzing samples from Drywell (elev 994'), Torus and Combustible Gas Control System inlet and outlet. Sample line and sample return valves close on Group 2 Isolation. Normal operation concentrations are 2.4%.

Northern States Power Company Monticello Nuclear Generatina Plant

Title:

Software Requirement Specification Number:

SRS Plant Process Computer System - Emergency Response Data System (EROS) - Data Point Library SRS-MT-PPCS-ERDS-DPL-013 Date:

Reactor Unit:

Data Feeder:

NRG EROS Parameter:

Point ID:

Plant Spec Point Desc.:

Generic/Cond Desc.:

Analog/Digital:

Engr Units/Dig States:

Engr Units Conversion:

Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

Alarm/Trip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 01/07/92 MO1 PCS CST LEVEL CST100 CST TANK LEVEL A CONDENSATE STORAGE TANK LEVEL A

FEET N/A 5

30 N/A N/A s

1 Sheet No:

49 SIGNAL FROM LEVEL TRANSMITTER LEVEL TX ON WATER COLUMN IN RX BLDG Hl=24'(225,600gal) LO=11.5'(108, 1 00gal)

N/A N/A LOW N/A N/A Condensate Storage Tank (CST) Level A is the water level in the A CST. Two CSTs exist with a tank capacity of 230,000 gallons each. Makeup condensate water is provided through 3 electric pumps from the CST tanks to various plant systems.

Each tank has suction line for Control Rod Drive, HPCI, Core Spray, RHR, and RCIC systems. At 7'(65,800gal) receive CST Low-Low Level alarm and condensate service pumps trip.

At 2'8"(25, 1 00gal) HPCI and RCIC transfer to Torus suction.

Northern States Power Company Monticello Nuclear Generatinq Plant

Title:

Software Requirement Specification Number:

SRS Plant Process Computer System - Emergency Response Data System (EROS) - Data Point Library SRS-MT-PPCS-ERDS-DPL-013 Sheet No:

50 Date:

Reactor Unit:

Data Feeder:

NRG EROS Parameter:

Point ID:

Plant Spec Point Desc.:

Generic/Cond Desc.:

Analog/Digital:

Engr Units/Dig States:

Engr Units Conversion:

Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

Alarm/Trip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 01/07/92 MO1 PCS CST LEVEL CST101 CST TANK LEVEL B CONDENSATE STORAGE TANK LEVEL A

FEET N/A 5

30 N/A N/A s

1 SIGNAL FROM LEVEL TRANSMITTER LEVEL TX ON WATER COLUMN IN RX BLDG Hl=24'(225,600gal) LO=11.5'(108, 1 00gal)

N/A N/A LOW N/A N/A Condensate Storage Tank (CST) Level Bis the water level in the B CST. Two CSTs exist with a tank capacity of 230,000 gallons each. Makeup condensate water is provided through 3 electric pumps from the CST tanks to various plant systems.

Each tank has suction line for Control Rod Drive, HPCI, Core Spray, RHR, and RCIC systems. At 7'(65,800gal) receive CST Low-Low Level alarm and condensate service pumps trip.

At 2'8"(25, 1 OOgal) HPCI and RCIC transfer to Torus suction.

Northern States Power Company Monticello Nuclear Generatina Plant

Title:

Software Reauirement Specification Number:

SRS Plant Process Computer System - Emergency Response Data System (EROS) - Data Point Library SRS-MT-PPCS-ERDS-DPL-013 Date:

Reactor Unit:

Data Feeder:

NRG EROS Parameter:

Point ID:

Plant Spec Point Desc.:

Generic/Cond Desc.:

Analog/Digital:

Engr Units/Dig States:

Engr Units Conversion:

Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

Alarm/Trip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 3/15/12 M01 PCS WIND SPEED MET122FR MT 43M A WIND SPEED 15MRUN WIND SPEED AT THE REACTOR SITE A

MPH N/A 0

100.00 N/A N/A p

1 Sheet No:

51 15 MINUTE AVERAGE OF 5 SECOND VALUES PRIMARY MET TOWER AT 43 METER HEIGHT N/A N/A N/A HIGH & LOW SENSOR N/A N/A Data is collected every five seconds, averaged every minute, and stored in data files as 15-minute average.

Northern States Power Company Monticello Nuclear GeneratinQ Plant

Title:

Software Requirement Specification Number:

SRS Plant Process Computer System - Emergency Response Data System (EROS) - Data Point Library SRS-MT-PPCS-ERDS-DPL-013 Sheet No:

52 Date:

Reactor Unit:

Data Feeder:

NRG EROS Parameter:

Point ID:

Plant Spec Point Desc.:

Generic/Cond Desc.:

Analog/Digital:

Engr Units/Dig States:

Engr Units Conversion:

Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

Alarm/Trip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 3/15/12 MO1 PCS WIND SPEED MET123FR MT 43M B WIND SPEED 15MRUN WIND SPEED AT THE REACTOR SITE A

MPH N/A 0

100.00 N/A N/A p

1 15 MINUTE AVERAGE OF 5 SECOND VALUES PRIMARY MET TOWER AT 43 METER HEIGHT N/A N/A N/A HIGH & LOW SENSOR N/A N/A Data is collected every five seconds, averaged every minute, and stored in data files as 15-minute average.

Northern States Power Company Monticello Nuclear Generatina Plant

Title:

Software Reauirement Specification Number:

SRS Plant Process Computer System - Emergency Response Data System (EROS) - Data Point Library SRS-MT-PPCS-ERDS-DPL-013 Date:

Reactor Unit:

Data Feeder:

NRC EROS Parameter:

Point ID:

Plant Spec Point Desc.:

Generic/Cond Desc.:

Analog/Digital:

Engr Units/Dig States:

Engr Units Conversion:

Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

Alarm/Trip Set Points:

NID~ectorPowerSup~y Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 3/15/12 M01 PCS WIND SPEED MET120FR MT 1 QOM A WIND SPEED 15MRUN WIND SPEED AT THE REACTOR SITE A

MPH N/A 0

100.00 N/A N/A p

1 Sheet No:

53 15 MINUTE AVERAGE OF 5 SECOND VALUES PRIMARY MET TOWER AT 100 METER HEIGHT N/A N/A N/A HIGH & LOW SENSOR N/A N/A Data is collected every five seconds, averaged every minute, and stored in data files as 15-minute average.

- - - ----- -----~--- - - - - - - - -

Northern States Power Company Monticello Nuclear Generatino Plant

Title:

Software Reauirement Specification Number:

SRS Plant Process Computer System - Emergency Response Data System (EROS) - Data Point Library SRS-MT-PPCS-ERDS-DPL-013 Sheet No:

54 Date:

Reactor Unit:

Data Feeder:

NRG EROS Parameter:

Point ID:

Plant Spec Point Desc.:

Generic/Cond Desc.:

Analog/Digital:

Engr Units/Dig States:

Engr Units Conversion:

Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

Alarm/Trip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg: N/A Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 3/15/12 M01 PCS WIND SPEED MET121 FR MT 1 00M B WIND SPEED 15MRUN WIND SPEED AT THE REACTOR SITE A

MPH N/A 0

100.00 N/A N/A p

1 15 MINUTE AVERAGE OF 5 SECOND VALUES PRIMARY MET TOWER AT 100 METER HEIGHT N/A N/A N/A HIGH & LOW SENSOR N/A Data is collected every five seconds, averaged every minute, and stored in data files as 15-minute average.

Northern States Power Company Monticello Nuclear Generating Plant

Title:

Software Requirement Specification Number:

SRS Plant Process Computer System - Emergency Response Data System (EROS) - Data Point Library SRS-MT-PPCS-ERDS-DPL-013 Sheet No:

55 Date:

Reactor Unit:

Data Feeder:

NRC EROS Parameter:

Point ID:

Plant Spec Point Desc.:

Generic/Cond Desc.:

Analog/Digital:

Engr Units/Dig States:

Engr Units Conversion:

Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

Alarm/Trip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 3/15/12 MO1 PCS WIND DIR MET128FR MT 43M A WIND DIR 15MRUN WIND DIRECTION AT THE REACTOR SITE A

DEGFR N/A 0

540.00 N/A N/A p

1 15 MINUTE AVERAGE OF 5 SECOND VALUES PRIMARY MET TOWER AT 43 METER HEIGHT N/A N/A N/A HIGH & LOW SENSOR N/A N/A Data is collected every five seconds, averaged every minute, and stored in data files as 15-minute average.

- - - - - - - - - - - - - - - ~ - - - -

Northern States Power Company Monticello Nuclear Generatinq Plant

Title:

Software Requirement Specification Number:

SRS Plant Process Computer System - Emergency Response Data System (EROS) - Data Point Library SRS-MT-PPCS-ERDS-DPL-013 Sheet No:

56 Date:

Reactor Unit:

Data Feeder:

NRG EROS Parameter:

Point ID:

Plant Spec Point Desc.:

Generic/Cond Desc.:

Analog/Digital:

Engr Units/Dig States:

Engr Units Conversion:

Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

Alarm/Trip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:


~~---

DATA POINT LIBRARY REFERENCE FILE 3/15/12 MO1 PCS WIND DIR MET129FR MT 43M B WIND DIR 15MRUN WIND DIRECTION AT THE REACTOR SITE A

DEGFR N/A 0

540.00 N/A N/A p

1 15 MINUTE AVERAGE OF 5 SECOND VALUES PRIMARY MET TOWER AT 43 METER HEIGHT N/A N/A N/A HIGH & LOW SENSOR N/A N/A Data is collected every five seconds, averaged every minute, and stored in data files as 15-minute average.

Northern States Power Company Monticello Nuclear Generatini:i Plant

Title:

Software Requirement Specification Number:

SRS Plant Process Computer System - Emergency Response Data System (EROS) - Data Point Library SRS-MT-PPCS-ERDS-DPL-013 Sheet No:

57 Date:

Reactor Unit:

Data Feeder:

NRG EROS Parameter:

Point ID:

Plant Spec Point Desc.:

Generic/Cond Desc.:

Analog/Digital:

Engr Units/Dig States:

Engr Units Conversion:

Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

Alarm/Trip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 3/15/12 M01 PCS WIND DIR MET126FR MT 100M A WIND DIR 15MRUN WIND DIRECTION AT THE REACTOR SITE A

DEGFR N/A 0

540.00 N/A N/A p

1 15 MINUTE AVERAGE OF 5 SECOND VALUES PRIMARY MET TOWER AT 100 METER HEIGHT N/A N/A N/A HIGH & LOW SENSOR N/A N/A Data is collected every five seconds, averaged every minute, and stored in data files as 15-minute average.

Northern States Power Company Monticello Nuclear Generating Plant

Title:

Software Requirement Specification Number:

SRS Plant Process Computer System - Emergency Response Data System (EROS) - Data Point Library SRS-MT-PPCS-ERDS-DPL-013 Sheet No:

58 Date:

Reactor Unit:

Data Feeder:

NRC EROS Parameter:

Point ID:

Plant Spec Point Desc.:

Generic/Cond Desc.:

Analog/Digital:

Engr Units/Dig States:

Engr Units Conversion:

Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

Alarm!Trip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:


----- --~

DATA POINT LIBRARY REFERENCE FILE 3/15/12 M01 PCS WIND DIR MET127FR MT 100M B WIND DIR 15MRUN WIND DIRECTION AT THE REACTOR SITE A

DEGFR N/A 0

540.00 N/A N/A p

1 15 MINUTE AVERAGE OF 5 SECOND VALUES PRIMARY MET TOWER AT 100 METER HEIGHT N/A N/A N/A HIGH & LOW SENSOR N/A N/A Data is collected every five seconds, averaged every minute, and stored in data files as 15-minute average.

Northern States Power Company Monticello Nuclear Generatina Plant

Title:

Software Reauirement Soecification Number:

SRS Plant Process Computer System - Emergency Response Data System (EROS) - Data Point Library SRS-MT-PPCS-ERDS-DPL-013 Sheet No:

59 Date:

Reactor Unit:

Data Feeder:

NRG EROS Parameter:

Point ID:

Plant Spec Point Desc.:

Generic/Cond Desc.:

Analog/Digital:

Engr Units/Dig States:

Engr Units Conversion:

Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

Alarm/Trip Set Points:

NI Detector Power Supply Cut-off Power Level:

NID~eciorPowerSupp~

Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 3/15/12 M01 PCS STAB CLASS MET140FR MT 43M-1 OM A DEL TA AIR T 15MRUN AIR STABILITY AT THE REACTOR SITE A

DEGF N/A

-9.0 9.0 N/A N/A PROC 2

AVERAGED DIFFERENTIAL PRIMARY MET AT 10 & 43 METER HEIGHT N/A N/A N/A HIGH & LOW SENSOR N/A N/A Data is collected every five seconds, averaged every minute, and stored in data files as 15-minute average. This value represents the difference in temperature in degF/100ft.

Northern States Power Company Monticello Nuclear Generatini:i Plant

Title:

Software Requirement Specification Number:

SRS Plant Process Computer System - Emergency Response Data System (EROS) - Data Point Library SRS-MT-PPCS-ERDS-DPL-013 Sheet No:

60 Date:

Reactor Unit:

Data Feeder:

NRC EROS Parameter:

Point ID:

Plant Spec Point Desc.:

Generic/Cond Desc.:

Analog/Dig ital:

Engr Units/Dig States:

Engr Units Conversion:

Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

Alarm/Trip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 3/15/12 M01 PCS STAB CLASS MET141 FR MT 43M-1 OM B DEL TA AIR T 15MRUN AIR STABILITY AT THE REACTOR SITE A

DEGF N/A

-9.0 9.0 N/A N/A PROC 2

AVERAGED DIFFERENTIAL PRIMARY MET AT 10 & 43 METER HEIGHT N/A N/A N/A HIGH & LOW SENSOR N/A N/A Data is collected every five seconds, averaged every minute, and stored in data files as 15-minute average. This value represents the difference in temperature in degF/100ft.

Northern States Power Company Monticello Nuclear Generatina Plant

Title:

Software Requirement Specification Number:

SRS Plant Process Computer System - Emergency Response Data System (EROS) - Data Point Library SRS-MT-PPCS-ERDS-DPL-013 Sheet No:

61 Date:

Reactor Unit:

Data Feeder:

NRC EROS Parameter:

Point ID:

Plant Spec Point Desc.:

Generic/Cond Desc.:

Analog/Digital:

Engr Units/Dig States:

Engr Units Conversion:

Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

Alarm/Trip Set Points:

NI Detector Power Supply Cut-off Power Level:

NID~eciorPowerSupp~

Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 3/15/12 1

s AB CLASS MET138FR I -

MT 100M-10M A DELTA AIR T 15MRUN AIR STABILITY AT THE REACTOR SITE A

DEGF N/A

-9.0 9.0 N/A N/A PROC 2

AVERAGED DIFFERENTIAL PRIMARY MET AT 10 & 100 METER HEIGHT N/A N/A N/A HIGH & LOW SENSOR N/A N/A Data is collected every five seconds, averaged every minute, and stored in data files as 15-minute average. This value represents the difference in temperature in degF/100ft.

Northern States Power Company Monticello Nuclear Generatina Plant

Title:

Software Reauirement Specification Number:

SRS Plant Process Computer System - Emergency Response Data System (EROS) - Data Point Library SRS-MT-PPCS-ERDS-DPL-013 Date:

Reactor Unit:

Data Feeder:

NRC EROS Parameter:

Point ID:

Plant Spec Point Desc.:

Generic/Cond Desc.:

Analog/Digital:

Engr Units/Dig States:

Engr Units Conversion:

Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Location:

Alarmff rip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

DATA POINT LIBRARY REFERENCE FILE 3/15/12 M01 PCS STAB CLASS MET139FR MT 100M-10M B DELTA AIR T 15MRUN AIR STABILITY AT THE REACTOR SITE A

DEGF N/A

-9.0 9.0 N/A N/A PROC 2

AVERAGED DIFFERENTIAL Sheet No:

62 PRIMARY MET AT 10 & 100 METER HEIGHT N/A N/A N/A HIGH & LOW SENSOR N/A N/A Data is collected every five seconds, averaged every minute, and stored in data files as 15-minute average. This value represents the difference in temperature in degF/100ft.


~-----------------

- - - - - - ~

  • "---- ------------------~

Northern States Power Company Monticello Nuclear GeneratinQ Plant Software Requirement Specification SRS

Title:

Plant Process Computer System - Emergency Response Data System (EROS) - Data Point Library I.

Contacts Note: Please provide name, title, mailing address and phone number.

Number:

SRS-MT-PPCS-ERDS-DPL-013 Sheet No:

63 A.

Survey Coordinator (i.e. contact for later clarification of questionnaire answers):

Brandon Glaser IT Manager, Xcel Energy, Inc.

Monticello Nuclear Generating Plant 2807 West County Road 75 Monticello, MN 55362 (763) 295-1048 B.

Systems Software Specialist(s):

Easthouse, Jeff D.

Engineer Xcel Energy, Inc.

Monticello Nuclear Generating Plant 2807 West County Road 75 Monticello, MN 55362 (763) 271-5863 C.

Application-level Software Specialist(s):

Nai-Tai (Nelson) Fei Engineer Xcel Energy, Inc.

Monticello Nuclear Generating Plant 2807 West County Road 75 Monticello, MN 55362 (763) 271-5180

Northern States Power Company Monticello Nuclear Generatina Plant Software Reauirement Specification SRS

Title:

Plant Process Computer System - Emergency Response Data System (EROS) - Data Point Library D.

Telephone Systems Specialist(s):

Tim Porter Communication Technician Xcel Energy, Inc.

Monticello Nuclear Generating Plant 2807 West County Road 75 Monticello, MN 55362 (763) 261-3252 Number:

SRS-MT-PPCS-ERDS-DPL-013 Sheet No:

64

Northern States Power Company Monticello Nuclear Generatina Plant Software Requirement Specification SRS

Title:

Plant Process Computer System - Emergency Response Data System (EROS) - Data Point Library

1. "GENERAL DESCRIPTION Number:

SRS-MT-PPCS-ERDS-DPL-013 Sheet No:

65 1.1.

Describe the product perspective (dependencies, interfaces, memory constraints.)

The Public Server System (PSS) executing the R*TIME EROS interface is the vendor software (R*Time) developed by Curtiss-Wright Nuclear for use in the Nuclear Industry to send data from Plant Process Computers to an NRG provided VPN appliance. The windows based PSS to NRG interface passes selected process data (temperatures, radiation levels, MET data, etc.) from Plant Process Computers to the NRG during emergency events classified as an "Alert" of higher thru a VPN network connection.

The two primary sources for R*Time EROS data is from the PSS and the Simulator servers (i.e. in support of EP drills). The plant process data will be acquired from the active PSS Server (CP-SVR-PSSM or CP-SVR-PSSL), while the simulator process data will be acquired from the active Simulator Server (CP-SVR-SHEMP or CP-SVR-CURL Y). This data transfer functionality is achieved by running two separate and independent instances of the R*Time EROS to NRG interface, one configured to transfer plant process data from the active PSS Server (CP-SVR-PSSM or CP-SVR-PSSL), and the other configured to transfer simulator process data from active Simulator Server (CP-SVR-SHEMP or CP-SVR-CURL Y).

A Plant Process Computer System (PPCS) EROS Display will be used to initiate/terminate data transfer to the NRG, display the current status of the NRG connection, number of NRG messages send, and display the current value/status of the process data being transferred to the NRG. Only users with allowed access will have I

the.capability.of_initiating/terminating.process.data.transferJoJheNRC. All.other.users.-~ _______ _

will only be capable of displaying the value/status of the process data being sent to the NRG.

1.2.

Summarize the major functions.

The EROS R*Time to NRG interface implements the data link from a R*Time Server to the NRG and supports the NRC-317 communications format (as was used for the prior modem communication) using a VPN connection. Both instances of the EROS R*Time

Northern States Power Company Monticello Nuclear Generating Plant Software Requirement Soecitication SAS

Title:

Plant Process Computer System - Emergency Response Data System (EROS) - Data Point Library Number:

SRS-MT-PPCS-ERDS-DPL-013 Sheet No:

66 to NRG interface will be configured to execute as a windows service and thus will be able to startup automatically during a system reboot.

A PPCS EROS Display will be used to initiate/terminate data transfer to the NRG, display the current status of the NRG connection, number of NRG messages send, and display the current value/status of the process data being transferred to the NRG.

1.3.

Describe the users (technical expertise and physical location.)

The EROS R*Time to NRG interface operates as a windows service and will not communicate directly to end users. Qualified IT personnel will be able to setup the required EROS R*Time interface parameters needed to support the data transfer capability to the NRC.

The PPCS EROS Display will contain two command buttons that can be used by trained end users who are given access to initiate or terminate process data transfers to the NRG.

1.4.

Describe any constraints that restrict the scope (regulatory processes, budgetary, etc.)

EROS is required to be operational and able to be activated within one hour of a declaration of an ALERT or higher emergency classification level per 1 0CFR50 Appendix E,Section VI. Therefore, the design function of the EROS data transfer is to be activated from an "EROS Enabled" PPCS EROS Display within one hour of a declaration of an ALERT or higher emergency classification level and initiate transfer of EROS process data to the NRC.


---~~---~~-----------~-