  • C L CLtJ f' f f 1 L . .: .*"_*
  • M'IDWE""PN3 To: Director of Regulatory Operation 70: Executive Director Ch=Irrun. SRC 05hRC Renton i Hansiger of Nuclear Operations 631 Pcrk Avanue King of Prussia, Pennsylvania 19406 DA TE/T lHE : 8/30/79 - P.M- DATE/TlHE: 8/30/79 - P.M.

FROM: James A. Fi tzPatrick Nuc3=ar Power Plant.

P.O. Box 41 Lycoming, New York 13033 PROMPT REpdRTABLE OCCURRENCE

SUBJECT:

DOCKCT NO. 50-333 LICENSE NO. OPR-59 ASSIGNED OR HO.79-118 LER NO. l9-046 August 30 1979 REPORT DATE: August 30, 1979 EVENT DATE:

EVENT DESCRIPTION:

At approximately 12:30 p.m. August 30, 1979 the nur. lear steem supply syst.em vendor and the architert-enginoer informed the staf f at the Fit 7 Patrick Plant tha t they cuncurred that the prosent routing of the high pressure coolant injection system steam isolation valve control cabic and the thermocouple temperature detector cabling for the high pressure contant injection system was such that sufficient cable separation did not axist betwaan these cables and the control cablas of the aistomatic depressuri7ation c.y s tem. This was discovered during the review of cable separation for the . lamas A.

l'itzpatrick fire hazards analysis sturly. Although not clearly a design requirement for the FitzPatrick Plant during the design phase, the prasent study indicates the separation sceween these cables should be increased. We are therefore presently re-routic y these rabies to locations approved by the architect-er,gineer prior to startup of the FitzPatrick

'l a n t.

CCMPONENTS INVOLVED:

Cables it.K0ARX020 ILK 0AftXO21 and 1HPIARC103 assnc'ated M th steam lank detection and valve 23-NV 15 (Inside ni'Cl steam isolation valves CAUSE AND RFHEDlAL ACTION:

Suse - indeteminate i emadia l Action - Set forth above

't THERMAL P0" DER N/A JACILITY STATUS:

Shis t dnwn X Routine Startup Rnutin* Shutdown RefueIing Standy State !' owe r Urner Loacs Lisange Not Applicable Oh.NM e6 written foilow up report wi11 be sent wi thin two weeks.