ML19163A365
| ML19163A365 | |
| Person / Time | |
|---|---|
| Site: | 07000371 |
| Issue date: | 11/30/2018 |
| From: | Cabrera Services |
| To: | NRC Region 1 |
| Shared Package | |
| ML051740240, ML19095A008 | List:
|
| References | |
| Download: ML19163A365 (2) | |
Text
Sample ID Cabrera Gamma Spectrometry Sample Value 235U, pCi/g Cabrera 2 s Error of Sample GEL Gamma Spectrometry Sample Value 235U, pCi/g GEL 1.96 s Error of Sample Z-Score Fail if Z-score >
2.57 UNC-FSS-DR-002 0.516 0.148 1.08 0.390 2.66 Fail UNC-FSS-DR-005 0.1785 0.118 0.425 0.299 1.51 Pass UNC-FSS-DR-010 0.0000 0.0000 0.836 0.368 4.45 Fail UNC-FSS-HR-004B 0.000 0.000 0.0593 0.130 0.89 Pass UNC-FSS-LDA-005 0.6813 0.1406 0.438 0.255 1.64 Pass UNC-FSS-LDA-007 0.000 0.000
-0.00707 0.134 0.10 Pass UNC-FSS-LDA-013 0.000 0.000 0.103 0.109 1.85 Pass UNC-FSS-RA-004 0.051 0.021
-0.066 0.107 2.10 Pass UNC-FSS-RA-017 0.040 0.019 0.0334 0.0967 0.13 Pass UNC-FSS-SR-003 0.000 0.000 0.0846 0.200 0.83 Pass UNC-FSS-SR-007 0.000 0.000
-0.0442 0.114 0.76 Pass UNC-FSS-SR-013 0.000 0.000 0.0604 0.132 0.90 Pass UNC-FSS-SR-022 0.000 0.000 0.0118 0.0943 0.25 Pass UNC-FSS-SR-028B 0.000 0.000 0.0248 0.0971 0.50 Pass UNC-FSS-SR-035B 0.000 0.000
-0.0619 0.085 1.43 Pass UNC-FSS-SR-039B 0.000 0.000 0.0341 0.0782 0.85 Pass UNC-FSS-SR-044B 0.000 0.000
-0.0476 0.0958 0.97 Pass UNC-FSS-SR-051B 0.000 0.000 0.110 0.0901 2.39 Pass UNC-FSS-SR-057B 0.000 0.000 0.0891 0.154 1.13 Pass UNC-FSS-XY-013 0.765 0.162 1.25 0.386 2.28 Pass UNC-FSS-XY-017 0.473 0.163 0.399 0.240 0.50 Pass UNC-FSS-XY-019 0.000 0.000
-0.0549 0.187 0.58 Pass Sample ID Cabrera Gamma Spectrometry Sample Value 238U, pCi/g Cabrera 2 s Error of Sample GEL Gamma Spectrometry Sample Value 238U, pCi/g GEL 1.96 s Error of Sample Z-Score Fail if Z-score >
2.57 UNC-FSS-DR-002 2.195 0.836 0.161 1.32 2.57 Pass UNC-FSS-DR-005 1.2907 0.485 0.829 2.14 0.41 Pass UNC-FSS-DR-010 2.2156 0.3650 1.72 1.60 0.59 Pass UNC-FSS-HR-004B
-0.680 0.000 0.356 1.13 1.80 Pass UNC-FSS-LDA-005 1.9970 0.7437 0.767 1.49 1.45 Pass UNC-FSS-LDA-007 1.120 0.000 0.00 2.22 0.99 Pass UNC-FSS-LDA-013 0.933 0.000 0.271 0.875 1.48 Pass UNC-FSS-RA-004 0.051 0.021 0.0149 0.847 0.08 Pass UNC-FSS-RA-017 0.040 0.019 0.904 0.769 2.20 Pass UNC-FSS-SR-003 0.535 0.270 0.402 0.901 0.28 Pass UNC-FSS-SR-007 0.955 0.288
-0.597 1.16 2.55 Pass UNC-FSS-SR-013 0.464 0.236 0.701 1.03 0.44 Pass UNC-FSS-SR-022 1.121 0.533 0.274 0.953 1.53 Pass UNC-FSS-SR-028B 0.703 0.351 0.737 0.547 0.10 Pass UNC-FSS-SR-035B 0.607 0.267 0.481 1.07 0.22 Pass UNC-FSS-SR-039B 0.625 0.231 0.467 0.417 0.65 Pass UNC-FSS-SR-044B 0.840 0.355 0.889 1.30 0.07 Pass UNC-FSS-SR-051B 0.550 0.200 1.71 1.57 1.44 Pass UNC-FSS-SR-057B 0.754 0.320 0.0687 1.34 0.98 Pass UNC-FSS-XY-013 1.724 0.666 1.05 1.40 0.86 Pass UNC-FSS-XY-017 1.045 1.237 0.470 1.28 0.64 Pass UNC-FSS-XY-019 0.217 0.241 1.03 1.22 1.28 Pass
Sample ID Cabrera Gamma Spectrometry Sample Value 235U, pCi/g Cabrera 2 s Error of Sample GEL Alpha Spectrometry Sample Value 235U, pCi/g GEL 1.96 s Error of Sample Z-Score Fail if Z-score >
2.57 UNC-FSS-DR-002 0.516 0.148 0.330 0.207 1.44 Pass UNC-FSS-LDA-013 0.0000 0.0000
-0.035 0.0957 0.72 Pass UNC-FSS-SR-003 0.0000 0.0000
-0.0485 0.143 0.66 Pass UNC-FSS-SR-007 0.000 0.000 0.0601 0.159 0.74 Pass UNC-FSS-SR-022 0.0000 0.0000 0.00 0.141 0.00 Pass UNC-FSS-SR-035B 0.000 0.000 0.141 0.195 1.42 Pass UNC-FSS-SR-044B 0.000 0.000 0.0692 0.136 1.00 Pass UNC-FSS-SR-057B 0.000 0.000 0.0434 0.173 0.49 Pass UNC-FSS-XY-019 0.000 0.000 0.230 0.201 2.24 Pass Sample ID Cabrera Gamma Spectrometry Sample Value 235U, pCi/g Cabrera 2 s Error of Sample GEL Alpha Spectrometry Sample Value 235U, pCi/g GEL 1.96 s Error of Sample Z-Score Fail if Z-score >
2.57 UNC-FSS-DR-002 2.195 0.836 0.560 0.234 3.76 Fail UNC-FSS-LDA-013 0.9330 0.0000 0.721 0.315 1.32 Pass UNC-FSS-SR-003 0.5355 0.2700 0.506 0.341 0.13 Pass UNC-FSS-SR-007 0.955 0.288 1.01 0.502 0.19 Pass UNC-FSS-SR-022 1.1214 0.5329 0.555 0.363 1.75 Pass UNC-FSS-SR-035B 0.607 0.267 0.386 0.297 1.09 Pass UNC-FSS-SR-044B 0.840 0.355 0.452 0.355 1.53 Pass UNC-FSS-SR-057B 0.754 0.320 0.508 0.377 0.98 Pass UNC-FSS-XY-019 0.217 0.241 0.873 0.370 2.93 Fail