ML18059B096

From kanterella
Jump to navigation Jump to search
Application for Amend to License DPR-20,revising TS Re Shutdown Cooling.Changes Intended to Resolve Concerns Arose During NRC Review of Change Request
ML18059B096
Person / Time
Site: Palisades Entergy icon.png
Issue date: 07/07/1994
From: Rogers D
CONSUMERS ENERGY CO. (FORMERLY CONSUMERS POWER CO.)
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
Shared Package
ML18059B097 List:
References
NUDOCS 9407180235
Download: ML18059B096 (3)


Text

consumers Power David W. Rogers Plant Safety and Licensing Director POWERiNii MICHlliAN"S PROliRESS Palisades Nuclear Plant: 27780 Blue Star Memorial Highway, Covert, Ml 49043 July 7, 1994 Nuclear Regulatory Commission Document Control Desk Washington, DC 20555 DOCKET 50-255 - LICENSE DPR PALISADES PLANT - TECHNICAL SPECIFICATIONS CHANGE REQUEST - SHUTDOWN COOLING - REVISED PAGES.

Attachment 1 contains three revised Shutdown Cooling Technical Specification change request pages. Two of these changes are intended to resolve concerns which arose during the NRC review of this change request.

1) Proposed pages 3-25i and 3-25h have been revised to add a two hour time limitation to Exception number 2.
2) Proposed page 3-45a has been revised to clarify that the exceptions of proposed LCO 3.1.9 do not ~llow reducing the available AC electrical sources below one offsite supply and one onsite supply.

In addition, a revision has been made to LCO 3.1:9.2 to allow stoppage of a shutdown cooling pump during plant heatup once a primary coolant pump has been placed in service.

1) Proposed page 3-25i has been revised so that the LCO 3.1.9.2 would, like LCO 3.1.9.1, allow use of a Primary Coolant Pump or a shutdown cooling pump to induce the required flow.

Attachment 2 contains the same 3 pages marked up to show the changes from our May 5, 1994 submittal.

As mentioned in our May 19, 1993 letter, we request that the associated license amendment become effective no sooner than 90 days after approval, to allow completion of the associated training and procedure changes.

The changes proposed in this letter do not alter the conclusions of the No Significant Hazards Analysis contained in our April 15, 1992 letter on this subject. A copy of this letter has been sent to the State of Michigan.

Ovv:;_~w. Q~

David W. Roger~

Plant Safety and Licensing Director CC Administrator, Region III, USNRC Resident Inspector, Palisades Attachments 9407180235 940707 PDR ADOCK 05000255 P PDR A CMS ENERGY COMPANY

ATTACHMENT I Consumers Power Company Palisades Plant Docket 50-255 SHUTDOWN COOLING TECHNICAL SPECIFICATIONS CHANGE REQUEST Revised Proposed Pages 3 Pages

CONSUMERS POWER COMPAN~

  • To.the best of my knowledge, the contents of this letter, which updates the proposed pages of the Shutdown Cooling Technical Specifications change request, are truthful and complete.

By -"".*4"-"-.e,....-......_.;f_._C_-._£=_~---

Robert A~ Fenech, Vice President Nuclear Operations Sworn and subscribed to before me this ]!!:_ day of ---""~~1+l~d1--~~- 1994.

Li OAAM .vn191W. ~

LeAnn Morse, Notary Public Berrien County, Michigan Acting in Van Buren County My commission expires February 4, 1997