Justification Rept for Fisher Valves in EPRI Test Program
ML18047A456
Person / Time
Site: Palisades 
Issue date: 10/28/1981
From: Buresh T, Jury F, Klinkefus O
FISHER CONTROLS CO., INC. (SUBS. OF MONSANTO CO.)
To:
Shared Package
ML18047A442 List:
References
NUDOCS 8207160351
Download: ML18047A456 (7)


Text

{{#Wiki_filter:FISHER CONTROLS CO~IPANY MARSHALLTOWN, IOWA 50158 AUTOMATIC CONTROL EQUIPMENT SINCE 11180 Reply to: FISHER CONTROLS COMPANY, R. A. Entel Technlcol Center, P.O. 8011 11, Marshalltown, Iowa SG158 October 28, 1981 - - Subject~_--* Justification Report for Fisher Valves in EPRI Test Program I. Introduction - The basic valve body construction that Fisher Controls has sold for Power Operated Relief Valve applications (PORV) is the 3 11 Type SS-95 valve body _with_ a Type SS-103 pneumatic loaded diaphragm actuator. totaL-.ofeleven units-have been sold to Westinghouse to be supplied to variou~_~specified utilities. Utility.. Plant Valve Model Drawing No. Serial No. OuQuesne Beaver 3 11 SS-95/ SS-103 56A2262 5916734 5916735 5916736 -pi-;'.:/ --!.,.<Power and - :_Valley #2 ,'.*':;.~-;?~,~: -~:'. -.:';Light Co *. _' _ ( OMW) ~;~1)"~~~,f-- ~~~i~o. ::n; e ~* _,- .Vogtl e --

  • Tennessee

... -_Valley -- *Authority

  1. 2 (GBE)

Watts Bar

  1. 1 (WAT)

Watts Bar

  1. 2 (WBT)

Same Same Same Same II. Description of Basic Valve Model 56A2263 56A2263 54A0273 54A0273 6499426 6499429 5916732 5916733 5916726 5916727 5916728 5916729 The Fisher Type SS-95 is a cage guided globe valve body designed for high pressure service. As a PORV it is supplied as a 3-inch size in the ANSI Class 1500 and. 1512 ratings. The quick opening cage provides guiding for the valve plug. IF IT FLOWS THROUGH PIPE *** CHANCES ARE IT'S CONTROLLED BY. * * ~ TELEPHONE (515) 754-3011.** TWX 910*520*1420. *

  • TELEX 478456

,--s207i6o3_s_1--0204o1 ___ -- --. ---, PDR ADOCK 05000255 P PDR Jl'ISHCR C:ONTROl..S COMPANY It is made from cast 17-4 SST hardened to condition H 1100. The valve plug is of unbalanced design and is 316 SST with Alloy 6 hard facing on seats and guides. Tr~ seat ring is 316 SST also with Alloy 6 hard facing in the seat area. I The actuator is Fisher Type SS-103 designed for high pressure valves with large actuator loads. It is a reverse-acting, spring-opposed diaphragm actuator that is used for automatic operation of the SS-95 valve body. The opening or closing of the valve plug in the body is accomplished by varying the pneumatic loading pressure from the diaphragm. On loss of air signal to the actuator, the spring will automatically move the valve plug to the closed position. III. Selected Test Valves The valves selected for the EPRI test program were production units originally destined for use in Vogtle Unit No. 2 {Georgia Power Co.). Therefore, the valve model construction is as represented by the bill of material drawing no. 56A2263. {See Attachnent A.) IV. Conclusion The Fisher valve body assembly selected for the EPRI test program was a production unit originally intended for use as a PORV in Vogtle Unit No. 2. It i-s identical in design and construction to all other Fisher Type SS-95/SS-103 valve body assemblies specified for PORV application. As a test model, therefore, it is representative of all of the Fisher valves listed in the in~ troductory paragraph of this report. V. Attachment A Bill of Material Drawings for Fisher PORV'so Prepared by: qJ~n:l~~~ Nuclear Qualification Engineer /km cc - Wayne Bailey Gary Icenogle John Channing Larry Bohnsack Reviewed by: ~' ~lo~~ Ma~*~;~r~u~ e~ Qualification Group Approved by: ~ Tom Buresh Manager. Evaluation & Analysis

ATTACHMENT A Bill of Material Drawings for Fisher PORV 1s

.) + I I+- 8-4 8-o AC TUA.TOR. REMOV'°'L CLE'°'R'°'NCE Zl.G APPROX I I B-:t-4 B RELEASE TO MFG PRELIMINARY PRINT UNLESS SIGNED DATE ___ BY ___ _ A:: Lil Lf) l9 Lf) 00 2.997 01" 2.995 l .105 ~==~~ _r-.095 COMPRESSED \\GASKET 1§881

J l----i__.125 UNCOMPRESSED

-3.091.~ -3590.D. BONNET, G'°'SKET, & BODY '°'SSEMBLY FIND NO I.,, * '

  • 1
  • 9 10 II 12 13 15 "

\\1 "

  • 19
  • 20
  • 21 22 23 " "

27 " 29 JO JI 32 320 Jl,.. 39 40

  • 41..,

" '° ".,, REDD I I I I I *,,,, I 2

  • I I

I I I I I I 2 I I 2 2 I I I, I I I 2 I 2 I 10 I I I I I I I I I I 2 2

  • I 2

I PAllT DEsatlflTION NUMflEft 22A550\\XD12 SPRING CASE 12A&S4lX012 DW'!t\\IAGM 1C7914XDOl2 MEX JlllUT. 1*-1 12Aaft49XOl2 l.IPPlll DWffflAGM 1'1.ATE 12ABWIX012 LOWER DW'HMGM ftlATE 1M5"4124052 CAI' SCREW. 5/1-111 I 3/4 tA!i!il\\24052 W SCMW. 7/18-20 12 1/4 IA340324122 HEX NUT. 7/111-20 12ABS45X012.ADJUSTWG satEW 12.H5"8XOl2 BEARING WASHEii lMs-4124052 CAP SCREW. !i/1-11 1 1 3/4 12ASS42X0\\2 UfffR SPRWG SEAT 22A8539XD12 LOWER olAPtfRsM WE 22All!i5DXD12 UPPER OW'HM.GM WE 111211128232 Pl'ENl'PLE. 1/412* AF~9lOOOA2 VENT J2AS!i07X012 YOU 1N13UX0012 SEAL ~SHWG 1E845106992 D-RWG.11/1121/811/11 1E1311108912 0..flSJl&G.11/4111/211/11 12A8SWXD12 D-fHfilG. 12112 1/41 I/II IE84st31992 SfllAP K*i. 2 1/19 DIA 1E831JJll992 SELF TAPPING SCMW. ND. I 1 3/4 \\E1173028992 WASHER NO. I 1H747lX0012 OUTER SPltltS. MU 2100 LIS/IN 12A55B!X022 MIJOLE SPlllNG. !UTE MIS LBS/IN 12A5!>09XD22 lfllNER SPfUfllG. RATE 217 LSS/lfll IJJe2724092 TRAVEL STOP IH7457Jl992 INDICATOfl SCALE 12A85"t7X012 ACTUATOf!. STEM 21A7470XOl2 STEM CUNNECTOR IA5141Z4052 CAP salEW, 1/2-13 1 2 1/4 1Hl111J8992 l'l>ICATOftOISC 1C635224122 HEX NUT.1s*l4 \\1(325131992 NAMEPLATE 1A311J21912 DftlVE SCREW NO. 2 1 3/18 1AMOS21t92 HEX SUSHING. 3/4 1 J/11 NPT J2A3112XD12 VALVE !ODY 12A5541XD22 CASE \\ 1AlllQX012 SEAT RltG 21AltlZX012 VAlVE f'lUG 1U051XD012 61\\00YE"" llA!42tX27Z VAlV'E STEM. I" DIA JIAIM171022 _, IV541ZXOI02 !'ft NPPU 1/2 1 !I 5/1!1SCH110 lH781235-072 PAClll6 FIJMGE OY002535222 STUO. 5/8-llX4 114 lA341335252 HEXMUT.5/fl-11 \\A5446Z40!52 WSDIEW.S/1*1112114 13A2127X012 WAllflEf'lATE I0751SXOI02 PACKllG ""6. I" XI 314 X 318 IY70Z335012 INllTU*RING IJ87l435072 PACXllG !IQX l!!l.WG lllATEJllAl MATERIAL SPECS ASSEMBU CAMOtll STEEL/SHH ASME SA-105 NEOf>flENE STEEL ASME SA-194-2H STEEL ASME SA-218-wtB r.ARBONSTEEl COMMERCIAL STEEL STEEL SAE 6115 CDP~ STEEL SAE Gii !i CD Pl STEEL ASTM A307 GR BCD Pl 4111SST ASTM A!i82 CDND A 44llC SST ASUllA.278-HTTR STEEl SAE GAS CD Pl W80ti1 STEEL COIMIUICLALSTHl STEEL ASME SA-2111-WCB SJEEl ASME SA-216-wtB STEEi ASME SA-108-S GALV ZN Pl ASSlllSlY ZINC ASTM BU AG40A. IRIOITE STEB. ASME SA-216*WCB 4111SST ASTMA5112 HT TR NITllLE NITRILE MOlYBDEHUM IMPREGNATEO NITRLE 302SST ASTM AJ13*3D2 18-tlSST COMMERCIAL PART CARBON STEEL COMMERCIAL STEEL STEEl AJSI SIBOH CD PL STEEL AISI JlBOH COPL STEEL AISI 5160H CD Pl STEEL AISI 12ll4 !USST 418SST ASTM A582 HT TR CHR Pl 418SST ASTM A582-416 STEEL SAE GR 5 CO Pl SST STEEL ASTM A307 GR 8 CO Pl 18-tl SST 18-11.SST COMMERCIAL PART MALLEABLE IRON ASTM A.197 47 Jl8SST ASME SA*l8H316 17-4PH SST FMS 20818*1 HT HllOO 3111SST ASME SA*479*316/STEU 6 SEAT 3111SS1 ASME SA*479 316/STELL 6 SEATS r.'GUIDE l\\llSST ASME SA479*316 318SST ASTM A276*316 COND 8 318SST ASMESA*35J-CF8M/COCR-A 1115 32A3 3111SSt ASME SA-312 TP316 SEAMLESS PIP{ JIB SST ASME SA-479-316 318SST ASllilE SA* 193 CLASS 2 B8M/STRAIN HARDENED 318SST ASME SA*194*8M STEEL SAE GR 5 CO PL IUSST ASBESTllS*GRAPtllTE CRANE Z.CR*J 318SST ASME SA-479 J16 3\\llSST ASMESA-479-316 I IH911Z335072 PACXllG FOLLOWER 318SST ASME SA-479 316 not=roETGASl:ET.33/321319/321125 J18LSST l 3" SCH 100 E\\UTT WELD END TUE.ING "-/sOD Ml\\..I 6 6 FIELD SUPPLIED TYPE 3GI NOT VALVE MTO .,4 ~~; V~~~ MTO -. --;J---1 1'!11v2NPT- - SUPPLY CONN ASCO SOLENOID VALVE J'.."T831GA74 NOT VALVE MTD TYPE 55-103 INSTALLATION SCHEMATIC I \\1.l89117XD12 ASBESTOS 1 \\Ati&llX0\\2 SEATl'ING&ASKET.25/1111213/1!11 115 lNCONEl l GRAPHITE INCONEl ALLOY 600 g GTB GRAPHIH LAMlNAH 12AM59XD12 "'"""' 111-SSST S9 12AOS42X012 NAMEl'\\.ATE.NIJClEIJI 18*8SST BO IC25111X0052 STUD. 7/1*914 1/11 SST ASME SA*453*660 COND B Bl 1C17Z7XOOJ2 HEX NUT. 7/"9 410SST ASME SA-194-6 EA)71J.Jll02 NATIOIUL ADIE SWITCH ASSEMBLY SWITCH MTG P'AllTS 35A2769XD\\2 MTG.PLUE CARBON STEEL COMMERCIAL STEEL IV102124092 Sl'AClR STEEL AISl 12L14 E\\ONNET ~ VA.LYE PLLJG ~EG-IF9IOJ24'>52 CAP stflEW. 5/15-1111 2 1 /4 STEEL IC831224'>52 CAI' scg[W, 5/111*1C 15/11 STEEL TYl'E9SH l'MSSUM "EGULATOR ASSEMBLY FTll31!1A14 ASCO SOLENOID VALVE ASSEMBLY TYP'E361 FILTER ASSEMBLY

NOTES, I. MAXIMUM C, 4 S AT.7 S 0" STROKE
2. OPERATING TEMPERATURE' G.SO ° F
3. AIR PRESSURE IN THE DIAPHRAGM CHAMBER IS NOT TO EXCEED BO PSIG TO PREVENT COMPONENT DAMAGE.
4. APPROXIMATE TOTAL VALVE WEIGHT,B30LBS t IO%
5. RECOMMENDED SPARE PARTS ARE MARKED WITH AN ASTERISK ( *) ON THE BILL OF MATERIAL.
6. 4 RINGS OF PACKING ARE TO BE UNDER THE LANTERN RING ANO 2 ABOVE.

SAEGRS CO Pl SAE GR S COPL

7. REQUIRED AIR PRESSURE FOR SHUT OFF OF MAIN SEAT' O PSIG
8. REQUIRED AIR: PRESSURE FOR BACKSEAT* C..4 PSIG
9. MINIMUM REQUIRED WALL THICKNESS* BODY-.S~

BONNET-.S~ IC.PRESSURE RATING,ASME 5.ECTION ll,CLASS I -IS12 LB II. EFFECTIVE Di'APHRAGM AREA,:z.ZoSQ. IN ~ MARSHALLTOWN. 10\\VA CODE 2:1501 OUR NO. OWN CDR 8-13*(!;> CHKD,t>.,LB S-14-r9 APVD ~ ~-IS-,"\\ SCALE NONE. P.O. NO. & A.LE> 3-Z.S-BO C Will'- 11*14-BO REVISIONS TAG NO. 2.-ll>-B~~G DIMENSIONS CERTIFIED CORRECT DATE BY REF D04 \\TE.M 4 TYPE SS-103-SS.-~S S.121'. 3:'1'>0D'I DWG NO REV. 5GA22.E.3 C .. ~

+ I I+- 8-4 8-o ACTUl'-TOR REMOVAL CLEARANCE S" ~(MAX) 21.G APPROX I I B-~- 4 B RELEASE TO M~G PRELIMINARY PRINT UNLESS SIGNED DATE __ BY c--------ZO~'.t~DIA-----~-i I I ---128'16---~"" ~;~~~~~~1:iMrz:1'5 s~~r;.~::: ~:o7 =i~ ~~~:~ ~z°["CI:JRATlNGISEE BE.J...OW!TRAvtL~

l~r 1 316 SST 1~~1 QUICK OPENING UA'}tJ 31c;:.ssr/.tu.:o lcuJDES~

ORDER l otUrTAG) UaA ~ ~ c:=') 4LVE ID LOCJ\\TE.D HE.RE. Lil Ul 0l Ul QQ <( <( 0 '<.1$i5 0 N N 0 -I~ +- lfl!IXl 0) 0 + I I J~ C\\l ~ f'": Q]I~ <fl NATIONAL BOARD ~ YEAR c::::::::J 0 FISHER CONTROLS CO. MARSHALLTOWN, lOWA, USA SERIAL l I CLASSU:::: DSGN PRESSc::::=JPSI ATc=:::J°F ASllllE $ECTIOM m CLASS I I ~<:<,oo I PSIG AT 100,. 2.997 2.995 DIP.. .IDS --. ___s-- _095 COMPRE.SSE.D '-l>r.~A'S~K=E=T~@=*~~ ~ 1----i__.125 UNCOMPRESSE.D -3.09 1.[}----1 -3590.D. FINO NO NO REOO I I I 3 I 4 I I 6 8 7 32 8 32 9 I 10 2 II 8 12 I 13 I 14 I 15 I 16 I 17 I 18 I I '20 2 I 22 I 23 2 25 2 26 I 27 I 28 I 29 3 30 I 31 I 32 I 320 2 33 I 34 2 35 I 36 IO 31 I 39 I 40 I

  • 41 I
  • 42 I
  • 43 I

I 45 I 46 1 41 I 48 2 49 2 50 8 PAl!t DESCRIPTION NUMBER 22A550~X012 SPRING CASE 12A654lX012 DIAPHRAGM IC79B4~0012 HEXNUT.1"*8 12A6549X012 UPPER DIAPHRAGM PLATE 12A6548X012 LOWEROIAPHRAGMPLATE 1A454124052 CAPSCREW.S.8*11ll3 4 1A551124052 CAP SCREW. 7*16*20

  • 2 1 4 1A340324122 HEX NUT. 7 16-20 12A654SXD12 ADJUSTING SCREW 12A654SX012 BEARING WASHER 1A454124052 CAPSCREW.518.111 l 3 4 12A6542X012 UPPER SPRING SEAT 22A6539X012 l0WER01APHRGMCASE 22A65~0X012 UPPEROlAPHRAGM CASE 18218826232 PIPENIPPLE.114*2" AF5!'19l000A2 VENT 32A5507X012 YOKE IN1316X0012 SEAL BUSHING 1E845806992 O*RING. 1718121181 118 1F.736SU6992 O*RING.11141l\\121l18 12A6544X012 Q.R\\NG.121121141118 1E845638992 SNAP RING. 2 7116 DIA IE83133B992 SELF TAPPING SCREW.NO 81 J 4 1E873028992 WASHER NO 8 1H7473X0012 OUTER SPRING.RATE 2100 LBS1IN 12ASS08X022 MIOOLESPRJNG.RATE 685 LBS1lN 12A5509X022 INNERSPRING. RAH 287 LSS/IN IJ362724092 TRAVEL STOP 1H745138992 INOlCATORSCALE 12A6547XOl2 ACTUATOR STEM 21A741QX012 STEM CONNECTOR 1A!'l14124052 CAPSCREW.112*13
  • 2 114 1HB71838992 INDICATOR DISC 1C635224122 HEX NUT. 1"*14 IK325738992 NAMEPLATE IA366228982 DRIVE SCREW NO 213,16

\\A64C521992 HEXBUSHING.314 1 318 NPT 32A3712XD12 VALVE BODY 12A5547X022 CAGE 1\\A8980X012 SEAT RING 21A8982X012 VALVE PLUG IR7058X0012 GROOVE PIN 11:.J429X272 VALVE STEM. I" DIA 36A0417X022 BONNET \\V54B2X0102 PIPE NIPPLE 112 16 5 16 SCH80 IH786235072 PACKING FLANGE OV002.535222 STUD. SIB-II X4 114 lA343335252 HEX NUT.518-11 IA54'624052 CAPSCREW.5,811x21/4 MATERIAL MATERIAL SPECS ASSEMEILY CARBON STEEL STEEL ASME SA 105 NEOPRENE STEEL ASME SA 194 2H STEEL ASMESA216WC8 CARBON STEEL COMMERCIALSTHL STEEL SAE GR 5 CDP~ STEEL SAEGR5CDPL STEEL ASTM AJ07 GRBCOPL 4\\SSST ASTM A582 CDNO A 440CSST ASTM A27S HT TR STEEl SAE GR 5 CO Pl CARBON STEEL COMMERCIAL STEEL STEEL ASME SA 216WCB STEEL ASMESA 2\\6WCB STEEL ASME SA 106 B GALV ZNPL ASSEMBLY ZINCASTMB86 AG40A IRIOITE SHEL ASMESA2\\6WCB 416SST ASTMA582HTTR NlTRtlE NllRILE MOLYBDENUM IMPREGNAHO NIT RILE 302SST ASTMA313302 188SST COMMERCIAL PAR! CARBON STEEL COMMERCIAL STEEL STEEL AJSI 5160H ca Pl STEH AISl'.'i160HCOPL STEEL AlSI 5160H COPL STEEL AISl12l14 188SST 416SST ASTM A582 HT TRCHRPt 416SST ASTM A582416 SHEL SAEGR5COPL SST STEEL ASTM A307 GR BCD PL 18BSST lBBSST COMMERCIAL PART MALLEABLE IRON ASTM A197 47 316SS1 ASME SA 182 F316 174PHSST FMS208181 HTH\\100 316SST ASME SA 479 316 STELL 6 SEAT 316SST ASME SA 479 316 SHU 6 SEATS & GUIDE 316SST ASMESA479 316 316SST ASTMA276 316 CONO B 316SST ASME SA 351-CF8M/COCR-A FMS 32A3 316SST ASME SA 312 TP316 SEAMLESS PIPE 316SST ASMESA479 316 316SST ASME SA 193 CLASS 2 B8M STRAIN HARDENED 316SST ASMESA 194 BM STEEL SAE GR 5 CO Pl 188SST 3 4 51

  • 52 I

6 13A2827X012 WARNING PLATE ID75l8XOI02 PACKING RING. 1" XI 3/4 X 3/8 ASBESTOS GRAPHITE CRANE 2 CR J BONNET, GASKET, & BODY ASSEMBLY 53 2 lV702335072 LANTERN RING 316SST IJB7H35072 PACKING BOX RING 316SST 3" SCH IG;O !SUTT WELD END TYPE 9SH NOT VALVE MTD TUE.ING ;,/sOD Ml"-1 TYPE 3G~6 6 h FIELD SUPPLIED NOT VALVE MTD Ji --- t's I lllY2NPT-- ~ -~--- SUPPLY CONN J ~ ASCO SOLENOID 65 VALVE FT831GA74 NOT VALVE MTD TYPE SS-103 INSTALLATION SCHEMATIC 44 (MAX) CG a~*" 1"-Jll/zNPT C.ON-1<>*a DUIT C.ONN ONE CONN PER SWITCH BONNET~ ~EG-s:TE~ SEl'-TRING~ 54 I 55 I IH982335072 PACKING FOLLOWER 316SST

  • 50 I

11A8987Y.012 BONNET GASKET. 3 3/32 I 3 19132 I 125 316LSST& ASBESTOS SEA(RING GASKET.2 511612 131161 115

  • 57 llA8988X012

\\NCONEL&GRAPHITE 58 12A6559X012 NAMEPLATE 18-BSSI 12A0542X012 NAMEPLATE. NUCLEAR 188SST 60 1C2516X0052 STU0.7/8-9141/B SST 61 ICl727XOOJ2 HEXNUT.118*9 410SST 62 EA)7p1302 NATIONAL ACME SWITCH ASSEMBlY 63 SWITCH MTG PARTS 35A2769X012 MTG PLATE CARBON STEH 1V102624092 SPACER STEEL 1F96[)324052 CAPSCREW.5/16*1812114 SHH 1C631224052 CAPSCREW.5/16*1815/8 STEEL 64 TYPE9!'1H PRESSURE REGULATOR ASSEMBLY 65 FT8316A74 ASCO SOLENOID VALVE ASSEMBLY 66 TYPE361 FILTER ASSEMBLY NOTES I. MAXIMUM c, 4S AT.1so** STROKE

2. OPERATING TEMPERATURE,GSO'F
3. AIR PRESSURE IN THE DIAPHRAGM CHAMBER IS NOT TO EXCEED 80 PSIG TO PREVENT COMPONENT DAMAGE.
4. APPROXIMATE 1 TOTAL VALVE WEIGHT,830L8S +/- 10%
5. RECOMMENDED SPARE PARTS ARE MARKED WITH AN ASTERISK { *) ON THE BILL OF MATERIAL.
6. 4 RINGS OF* PACKING ARE TO BE UNDER THE LANTERN RING AND 2. ABOVE.
7. REQUIRED AIR PRESSURE FOR SHUT OFF OF MAIN SEAT, o PSIG
8. REQUIRED AIR. PRESSURE FOR BACKSEAT' C..4 PSIG 9 MINIMUM REQUIRED WALL THICKNESS' BODY-.S'.':>

BONNET-.S~ IQ.PRESSURE RATING,ASME SECTION III,CLASS I -ISOOLB

11. EFFECTIVE DIAPHRAGM AREA,Z.20SQ. IN

~~~~

  • ~H CUSTOMER P.0.NO SERIAL NO.

OUR NO. ASME SA 479 316 ASMESA479 316 ASMESA479316 INCONH ALLOY 600 & GT~ GRAPHITE LAMINATE ASME SA 453 660 CONO B ASMESA 1946 COMMERCIAL STEEL AIS!12l14 SAE GR 5 CO PL SAE GR~ CO PL TAG NO. 2' -ll\\8C>RG ~(ti '.p. :._ OJ l> DIMENSIONS CERTIFIED CORRECT (Tl_flolJ1-{ (' 'tn ~ rn ;u ~ ::0 t---------r--_JL __________ _JL.:D:'.'.A::.T'..'.E_J __ ,."'.'..Y:..... ________ J @~~~~ :l) rT1 ~~~~~ ~ ~ ~~~~~ ~ ~ TYPE SS-103.-SS-~S. Sl2E ~*'COD'! r' 1'1*111!:< 0 z 9'0.0ti' ~ MARSHALLTOWN. 10\\VA CODE 12501 "-IR Ol'E.R"'-IE.D CDNTRDL V!>.l._'IE OWN JCW G-8-7G CHKD RLU G:,-'=>*'Co APVD SCALE NONE.. D N....B 3-2.S-8.0 C CDR 8*7-79 E Wl11\\.. l\\*19*80 REVISIONS REF DD4 \\TE.M4 4-3.4~11 DWG NO 54--l0273 REV. E

+ I I+- 8-4 8-o ACTUATOR REMOV-"L CLE-"R1'NCE 53 ~ (M-"X) ~l.G APPROX RELEASE TO M'G PRELIMINARY PRI~' UNLESS SIGNED DATE __ BY ___ 1-4--------ZO~'.t~ DIA-----~_, / Q FISHER CONTROLS CO, aU.lli;HAL T,.ClllN c:::> SERIALc:::==::=JTYP[ SS-I03-$- SIZE C::::J [JI]ro(0PSI 01.t.PH PRE~ OPENS I POAT WITH! 3130 )PSI DROP O~~T (§DTO~PSI ~z°l IT:]RATIPo!G iSEE: BE.1-0W!TAAVEL~

l~r 1 31b 55T 1~~'i':1 Qt.JICK OPENING 1

CA,'}fJ 3rc; SST/*im. iGUlDES~ ORDER Lfl li1 1.9 Lfl qo 0 Cl.1ji5 O N 1.. 1 N N 0 -Im -t-lflJQ} co 0 + ~ ICC. N ~ t-: ~I~ 4-o N ru rn 2.997


101-"

2.995 l .105

=====_____r- _095 COMPRESSED ljGASKET&$&ll

J l~.125 UNCOMPRESSED 3.09 1.D:-----l

--.--3.59 O.D. Ft ND NO I '2 J * ' 6 1 9 10 11 12 13 18 17 18 '19 '20 '21 22 23 " 26 21 28 29 JO JI J2 320 33 36 JI 39 40.., NO. . PART REDD NUMBER I 22A5S05X012 1 12A6543X012 I 1C798'X0012 1 12A6549X012 I 12A6548X012 1A454124052 J2 1A!i51124052 J2 1AJ40324122 I 12A6545X012 2 12A6546X012 8 lA-454124052 I 12AS!i.(2XOl2 1 22A6539X012 I 22A65SOX012 I 18218826232 1 AF5592000A2 I 32A5507X012 I 1N1316X0012 I IE845806992 2 1£736906992 I 12A6544X012 I IE84!i638992 2 IE83\\l38992 2 1E873028992 I 1H747iX0012 I 12A5508XD22 I 12A5509X022 J IJJ62124092 1 1H745738992 1 12A6541X012 I 21A74TOXOl2 2 IA514124052 I 1H871838992 2 1C63!i224122 I 1K325738992 10 1A368228982 I 1A64-0521992 I 32A3112X012 I 12A5~47X022 I 1\\A8980X012 I 21AB982X012 I IR7058X0012 I llf.3429X272 I 3f.iA0'77l022 I 1V5'82X0102 DESCRIPTION MATERIAL MA TE RIAL SPECS SPRING CASE ASSEMBLY CARBON SHH/STEEL ASME SA*l 05 DIAPHRAGM NEOPRENE HEX NUT, 1*-8 STEH ASME SA*194*2H UPPER DIAPHRAGM PLATE STEEL ASMESA-216-WCB LOWER DIAPHRAGM PLATE CARBON STEH COMMERClAlSTEEL CAPSCREW.!i/8-11x1 3/4 STEEL SAE GR 5 CO PL CAPSCREW, 7/18-20 1 2 1/4 STEH SAE GR!i CO Pl HEX NUT. 7116*20 STEEl ASTM A307 GR8 CO PL ADJUSTING SCREW 416SST ASTM A582 CONO A 8EARINGWASHER UOC SST ASTM A276-HT TR CA.PSCREW.5/8-111 I 3/4 STEEL SAE GR5 CO Pl UPPER SPRING.SEAT CAR80NSTEEL COMMERCIAL STEEL LOWER OIAPHRGM CASE STEEL ASMESA-216-WC8 UPPER DIAPHRAGM CASE STEEL ASME SA-216.WCB PIPENf'PLE.1/41r SHH ASME SA* 106*8 GALV ZN Pl VENT ASSEMBLY ZINC ASTM 886 AG40A. IRIOITE YOKE STEEL ASMESA-218-WCB SEAL BUSHING 416SST ASTM ASB2 HT TR O*RING,17/8121/811/8 NIT RILE 0-RJNG. 11/41 I 1/2 I 1/8 NlTRILE MOLYBDENUM IMPREGNATED 0-RING. 12 I 12 1/4 I 1/8 NITRILE SNAPRING.2 7116 OLA 302SST ASTM A313*302 SHFTAPP1NG SCREW.ND.a 1 3/4 1B*8SST COMMERCIAlPART WASHER NO 8 CARBON STEH COMMERCIALSTEH OUTER SPRING. RATE 2100 LBS/IN STEEL AISI S\\60HCO Pl MIDDLE SPRING. RATE 685 LBS/IN STEEL AISI jlSOH CO Pl INNER SPRING. RATE 287 LBS/IN STEEL AISl 5160H CO Pl TRAVEL STOP STEEL AlSI 12l\\4 INDICATOR SCALE 18-8SST ACTUATOR STEM 416SST ASTM A582 HT TR CHA Pl STEM CONNECTOR 416SST ASTM A582-416 CAPSCREW.112-13121/4 STEEL SAE GR 5 CDPL INDICATOR DISC SST HEXNUT,1n.14 STEEl ASlM A307 GR 8 CO Pl NAMEPLATE 18*8SST DRIVESCREWNO 213/16 18-8SST COMMERC1ALPART HEX 8USHING.3/4 1 3/8 NPT MALLEABLE IROH ASTMA197*47 VAlVEBOOY 316SST ASME SA-182 F316 CAGE 17-4PHSST FMS20B18*1 HTHllOO SEAT RING 316SST ASME SA-479-316/STELL 6 SEAT VALVEPlUG 316SST ASME SA-479 316/STELL 6SEATS &.GUIDE GROOVE PIN 316SST ASME SA-479-316 VALVE STEM. !DIA 316SST ASTM A276-316 CONO B BONNET 316SST ASME SA*351-Cf8lil/COCR-A flllS 32A3 PIPENIPPLE1/216!i/16SCH80 JISSST ASME SA*312-TP316 SEAMLESS PIPf: ASME SA-479-316 I IH7B8235072 PACKING FtANGE 316SST 2 Ol/002535222 STUD, 5/8-11X4 114 316SST ASME SA-193*CLASS 2*88M/STRAIN HARDENED 2 IA34l335252 HEXNUT.518-ll 316SST ASMESA-194*BM so 8 IA544624052 CAP SCREW,5/B-11121/4 STEEL SAEGRSCDPL I 13A2B27X012 WARNING PLATE 18-BSST PACKING RING. 1" XI 3/4 X 3/8 ASBESTOS*GRAPHITE CRANEHRJ 3 BONNET, GASKET, & BODY ASSEMBLY '3 6 2 ID751BXOl02 IV702335012 LANTERN RING 316SST ASME SA-479 316 PACKING BOX RING 316SST ASME SA 479 316 3" SCH IGO BUTT WELD END TYPE 95H NOT VALVE NTD h;~~~~~;~~E~IN TYPE 3G il lllY2NPT--~ -u--- NOTVALV tr t SUPPLY CONN ' ASCO SOLENOID VALVE l'T831GA74 NOT VALVE MTO TYPE SS-103 INSTALLATION SCHEMATIC I I zoz_:: 8 DIA 5,lj 1"-111/zNPT C.ON-8j~-B DUIT CONN ONE CONN PER SW ITCH I IJB73435072 I IH982335072 PACKING FOLLOWER 316SST ASMESA 479 316 I 11A89B7XOl2 BONNET GASKET.3 3/32 13 19/32 1 125 316LSST&. ASBESTOS '51 11AB9BBX012 SEAT RING GASKET. 2 !i/16 1213/161 175 lNCONH &. GRAPHITE INCONH ALLOY 600 &. GTB GRAPHITE LAMINAH 58 12A6559X012 NAMEPLATE 18-BSST 12A0542X012 NAMEPLATE. NUCLEAR 18BSST 60 1C2516XD052 STUD. 7/8-9 14 1/8 SST ASME SA 4!13-660 COND 8 BONNET~ 61 ICl727X0032 HEXNUT. 718-9 410SST ASME SA 194 6 62 EAJ70-31302 NATIONAl ACME SWITCH ASSEMBLY 63 SWITCH MTG PARTS I 35A2769XOl2 MTG PtATE CARBON STEEL COMMERCIAL STEEL I 1Vl02624092 SPACER STEH AIS112l14 ~EG-I 1F960324D52 CAPSCREW.5/16*18121/4 STEEL SAEGR5CDPl 2 - 1C631224052 CAP SCREW. 5/16-18 1 5/8 SHH SAEGR5CDPL I TYPE95H PRESSURE REGULATOR ASSEMBLY 2 FTB316A74 ASCO SOLENOID VALVE ASSEMBLY V-"LVE PLLJ6 s:TEG SEATRING~ 66 I TYPE361 FILTER ASSEMBLY NOTES I. MAXIMUM C, 4S AT.'7SO" STROKE

2. OPERATING TEMPERATURE'.;,so. F
3. AIR PRESSURE IN THE DIAPHRAGM CHAMBER IS NOT TO EXCEED 80 PSIG TO PREVENT COMPONENT DAMAGE.
4. APPROXIMATE 1 TOTAL VALVE WEIGHT,830LBS t 10%
5. RECOMMENDED SPARE PARTS ARE MARKED WITH AN ASTERISK ( *) ON THE BILL OF MATERIAL.
6. 4 RINGS OF PACKING ARE TO BE UNDER THE LANTERN RING AND 2. ABOVE.
7. REQUIRED AIR PRESSURE FOR SHUT OFF OF MAIN SEAT' O PSIG 8 REQUIRED AIR. PRESSURE FOR BACKSEAT' G,4 PSIG 9 MINIMUM REQUIRED WALL THICKNESS' BODY-.S':>

BONNET-. S~ 10.PRESSURE RATING,ASME SECTION ill,CLASS I -ISOOLB II. EFFECTIVE DIAPHRAGM AREA,1.'ZOSQ. IN P.O. NO. OUR NO. "-IR O?E.R"'-'TE.D <:..DNTRDL VA.\\..YE. TAG NO. ~ -11>.B'ORG DIMENSIONS CERTIFIED CORRECT DATE BY TYPE SS-103.-SS.-'.:>S S12E. ?." e.OD'f ~ OWN CDR 8-13-19 CHKD A...LB 8-14 -19 &,0...L& 3-2..S-SO c w1m:. 11-11-eo REF D04 '1'EM4 OWG NO SGAZZGZ REV. MARSHALL TOWN, IOWA COOE 2UOI APVD !'2.L..f' 6-1S-)<\\ SCALE NON.E.. c REVISIONS

86 - GARRETT PNEUMATIC SYSTEMS DIVISION

  • }}