MONTHYEARML20034E8942020-02-11011 February 2020 Relief Request Gen-ISI-ALT-2019-01 for Proposed Alternative to Use of ASME Code Case N-831-1, Ultrasonic Examination in Lieu of Radiography for Welds in Ferritic or Austenitic Pipe Section XI, Division 1 ML19192A1712019-08-0202 August 2019 Relief from Inservice Impractical ASME Code Requirements (FNP-ISI-RR-03) ML18334A2282018-12-10010 December 2018 Proposed Inservice Inspection Alternative FNP-ISI-ALT-05-03 ML18320A0572018-11-30030 November 2018 Plant, Units 1 and 2 - Proposed Inservice Inspection Alternative GEN-ISI-ALT-2017-03, Code Case N-513-4 for Moderate Pressure NL-18-0428, Withdrawal of Proposed Alternative GEN-ISI-ALT-2017-001 Implementation of Code Case N-786-12018-04-0909 April 2018 Withdrawal of Proposed Alternative GEN-ISI-ALT-2017-001 Implementation of Code Case N-786-1 ML17354A9162017-12-28028 December 2017 Inservice Inspection Alternative FNP-ISI-ALT-05-01, Version 1, to Use ASME Code N-854 (CAC Nos. MG0107 and MF0108; EPID L-2017-LLR-0086) ML17298A4162017-11-0101 November 2017 Relief Request FNP-ISI-ALT-22, Inservice Inspection Alternative for Code Case N-786-1 ML17121A0592017-05-18018 May 2017 Inservice Inspection Alternative (FNP-ISI-ALT-20) ML17006A1092017-01-26026 January 2017 Alternative to Inservice Inspection Regarding Reactor Pressure Vessel Threads Inflange Inspection ML16323A3022016-12-0606 December 2016 Alternative to Inservice Inspection Regarding Spent Fuel Pool Cooling System Drain Line Weld ML16264A3212016-10-14014 October 2016 Alternatives for Pumps and Valves Inservice Testing Program NL-15-0942, Proposed Lnservice Inspection Alternative FNP-ISI-ALT-18, Version 1.02015-07-17017 July 2015 Proposed Lnservice Inspection Alternative FNP-ISI-ALT-18, Version 1.0 ML15104A1922015-05-0505 May 2015 Alternative to Inservice Inspection Regarding Reactor Closure Head Closure Head Nozzle and Partial Penetration Welds ML14262A3172014-12-0505 December 2014 (FNP-ISI-ALT-15, Version 1) Alternative to Inservice Inspection Regarding Reactor Pressure Vessel Cold Leg Nozzle Dissimilar Metal Welds (TAC Nos. MF3687 and MF3688) ML14252A0762014-09-23023 September 2014 Alternative to Inservice Inspection for Reactor Vessel Flange Leak-off Lines ML14169A1952014-07-11011 July 2014 Alternative Request Regarding Containment Building Tendon Examination Schedule NL-11-1543, Response to NRC Request for Additional Information Proposed Relief Request FNP-ISI-RR-012011-08-11011 August 2011 Response to NRC Request for Additional Information Proposed Relief Request FNP-ISI-RR-01 ML1017504022010-07-12012 July 2010 Relief Request for Extension of the Reactor Vessel Inservice Inspection (ISI) Date to the Year 2020 (Plus or Minus One Outage) (Tac No. ME3010) ML1005603342010-03-0202 March 2010 Safety Evaluation of Relief Request FNP-ISI-ALT-08 Version 1.0 for Reactor Vessel Nozzle to Safe-end Dissimilar Metal Weld and Adjacent Austenitic Safe-end Weld Examinations NL-09-1379, Evaluation Results Associated with Relief Request RR-P-32009-09-0808 September 2009 Evaluation Results Associated with Relief Request RR-P-3 ML0917300752009-06-29029 June 2009 (Fnp), Units 1 and 2, Evaluation of Third 10-Year Interval Inservice Inspection Program Plan Requests for Relief ML0820500022008-08-0606 August 2008 Safety Evaluation on Relief Request RR-P-2, RR-P-3 from ASME OM Code Requirements NL-07-1718, Relief Request RR-60 (Version 2.0) Proposed Alternative in Accordance with 10 CFR 50.55a(a)(3)(ii)2007-09-12012 September 2007 Relief Request RR-60 (Version 2.0) Proposed Alternative in Accordance with 10 CFR 50.55a(a)(3)(ii) ML0713602972007-06-0505 June 2007 Relief, Evaluation of Third 10-Year Interval Inservice Inspection Program Plan Request to Relief Nos. RR-42 Through RR-45, RR- 51, RR-58, RR-59, RR-60, & RR-62 ML0705903082007-03-30030 March 2007 Safety Evaluation of Revised Relief Request RR-12 for the Third-Year Interval and Examination Program for Snubbers ML0627703592006-09-29029 September 2006 Evaluation of Relief Request ISI-GEN-ALT-06-02 NL-06-1713, Proposed Alternative for Application of Pressurizer Nozzle Full-Structural Weld Overlays2006-08-10010 August 2006 Proposed Alternative for Application of Pressurizer Nozzle Full-Structural Weld Overlays ML0608302212006-03-28028 March 2006 Request for Relief No. RR-57 and RR-58 Regarding Containment Tendon Inspections ML0511604142005-05-19019 May 2005 Relief, RR-56, Examination of RPV Lower Shell to Bottom Head Circumferential Weld No. APRI-1-1100-8 ML0510301992005-04-25025 April 2005 RR, ISI Program Intervals for Alternative Alignment of Iwe/Iwl Inspection Program (Tac No. MC4870, MC4871, MC4872, MC4873, MC4874, MC4875) ML0418401692004-06-25025 June 2004 Request for Relief No. 55 from ASME Code Repair Requirements for ASME Code Class 3 Service Water System Piping ML0414800332004-05-26026 May 2004 Relief Request, Use of Alternate Code Case ML0407002582004-03-0909 March 2004 Risk-Informed Inservice Inspection Program - ASME Code Category B-F, B-J, C-F-1, and C-F-2 Piping ML0332800372003-11-21021 November 2003 Safety Evaluation Re. Request to Use ASME Code Case N-661 ML0319904652003-07-17017 July 2003 Second and Third 10-Year Interval Inservice Inspection NL-03-0941, Additional Information Re Request for Technical Specification Changes Unit Two Pressurizer Power Operated Relief Valve Block Valve Surveillance2003-04-29029 April 2003 Additional Information Re Request for Technical Specification Changes Unit Two Pressurizer Power Operated Relief Valve Block Valve Surveillance NL-03-0684, ASME Section XI Requests for Relief Number RR-51 and RR-52 Alternative Repair Technique and Inspection Requirement - Reactor Vessel Head2003-03-28028 March 2003 ASME Section XI Requests for Relief Number RR-51 and RR-52 Alternative Repair Technique and Inspection Requirement - Reactor Vessel Head NL-03-0455, Inservice Inspection Program, Additional Information for Request for Relief No. RR-482003-03-10010 March 2003 Inservice Inspection Program, Additional Information for Request for Relief No. RR-48 L-02-023, Updated Interval (Second 10-Year Interval, Third Period and Third 10-Year Interval, First and Second Periods) Request for Relief No. RR-47 from 1989 ASME Code Requirements2002-12-0505 December 2002 Updated Interval (Second 10-Year Interval, Third Period and Third 10-Year Interval, First and Second Periods) Request for Relief No. RR-47 from 1989 ASME Code Requirements ML0231100042002-11-0707 November 2002 Relief Request, Third 10-Year Interval Inservice Inspection Program Request for Relief, TAC No. MB3776 L-02-018, ASME Section XI Relief Requests Number RR-51 and RR-52 Alternative Repair Technique and Inspection Requirement - Reactor Vessel Head2002-09-18018 September 2002 ASME Section XI Relief Requests Number RR-51 and RR-52 Alternative Repair Technique and Inspection Requirement - Reactor Vessel Head ML0220704762002-07-26026 July 2002 Relief Requests for Third 10 Year Inservice Inspection (ISI) Interval ML0220706212002-07-26026 July 2002 7/26/02, Joseph M. Farley, Unit 2, Request for Relief No. RR-46 for the Third 10-Year Inservice Inspection (ISI) Interval 2020-02-11
[Table view] Category:Letter
MONTHYEARNL-24-0320, License Amendment Request Proposing a New Set of Fission Gas Gap Release Fractions for High Burnup Fuel Rods That Exceed the Linear Heat Generation Rate Limit Detailed in Regulatory Guide 1.183, Table 3,.2024-09-27027 September 2024 License Amendment Request Proposing a New Set of Fission Gas Gap Release Fractions for High Burnup Fuel Rods That Exceed the Linear Heat Generation Rate Limit Detailed in Regulatory Guide 1.183, Table 3,. NL-24-0349, Units 1 and 2 - 10 CFR 26.719(c)(1) 30-Day Report Blind Performance Test Results Inconsistent with Sample Provided2024-09-20020 September 2024 Units 1 and 2 - 10 CFR 26.719(c)(1) 30-Day Report Blind Performance Test Results Inconsistent with Sample Provided NL-24-0341, Response to Request for Additional Information Related to the Application to Revise Technical Specifications Regarding Change to Containment Spray Nozzle Test Frequency2024-09-10010 September 2024 Response to Request for Additional Information Related to the Application to Revise Technical Specifications Regarding Change to Containment Spray Nozzle Test Frequency IR 05000348/20244012024-09-10010 September 2024 Security Baseline Inspection Report 05000348-2024401 and 05000364-2024401 ML24247A1102024-09-0505 September 2024 Corporate Notification Letter Aka 210-day Letter NUREG Rev 12 NL-24-0259, License Amendment Request to Revise Technical Specification 3.4.14, Reactor Coolant System Pressure Isolation Valve Leakage, Surveillance Requirement 3.4.14.3 Acceptance Criteria and Miscellaneous Obsolete Changes2024-09-0404 September 2024 License Amendment Request to Revise Technical Specification 3.4.14, Reactor Coolant System Pressure Isolation Valve Leakage, Surveillance Requirement 3.4.14.3 Acceptance Criteria and Miscellaneous Obsolete Changes NL-24-0340, Unit 1 - Inservice Inspection Program Owners Activity Report (OAR-1) for Outage 1 R322024-09-0404 September 2024 Unit 1 - Inservice Inspection Program Owners Activity Report (OAR-1) for Outage 1 R32 ML24242A1332024-08-29029 August 2024 Issuance of Amendment Nos. 250 and 247, Regarding License Amendment Request to Revise Technical Specification 3.6.5, Containment Air Temperature, Actions (EPID L-2024-LLA-0098) - Non-Proprietary ML24240A0812024-08-27027 August 2024 License Amendment Request to Change Technical Specification 3.6.5, Containment Air Temperature Actions - Revised Completion Time ML24233A0022024-08-27027 August 2024 Request for Withholding Information from Public Disclosure for Joseph M. Farley Nuclear Plant, Units 1 and 2, License Amendment Request Supplement to Change Technical Specification 3.6.5, Containment Air Temperature Actions IR 05000348/20240052024-08-26026 August 2024 Updated Inspection Plan for Joseph M. Farley Nuclear Plant, Units 1 and 2 - Report 05000348/2024005 and 05000364/2024005 IR 05000348/20244022024-08-26026 August 2024 Information Request for the Cyber Security Baseline Inspection, Notification to Perform Inspection 05000348/2024402 and 05000364/2024402 ML24226B2112024-08-22022 August 2024 Regulatory Audit Summary in Support of License Amendment Requests to Revise Technical Specification 3.6.5, Containment Air Temperature, Actions NL-24-0321, License Amendment Request to Change Technical Specification 3.6.5, Containment Air Temperature Actions - Supplemental Information2024-08-16016 August 2024 License Amendment Request to Change Technical Specification 3.6.5, Containment Air Temperature Actions - Supplemental Information IR 05000348/20240022024-08-12012 August 2024 – Integrated Inspection Report 05000348-2024002 and 05000364-2024002 and Exercise of Enforcement Discretion ML24215A3772024-08-0707 August 2024 2024 Farley Requal Inspection Corporate Notification Letter ML24201A2032024-08-0101 August 2024 Request for Withholding Information from Public Disclosure for Joseph M. Farley Nuclear Plant, Units 1 and 2, License Amendment Request to Change Technical Specification 3.6.5, Containment Air Temperature Actions ML24200A1392024-07-25025 July 2024 Regulatory Audit in Support of Review of the License Amendment Request to Revise Technical Specification 3.6.5, Containment Air Temperature ML24199A2072024-07-24024 July 2024 TS 3-6-5 LAR - Individual Notice Transmittal Letter and NSHC - Rev 1 (1) - Letter NL-24-0261, 10 CFR 50.46 ECCS Evaluation Model Annual Report for 20232024-07-19019 July 2024 10 CFR 50.46 ECCS Evaluation Model Annual Report for 2023 NL-24-0281, License Amendment Request to Change Technical Specification 3.6.5, Containment Air Temperature Actions2024-07-18018 July 2024 License Amendment Request to Change Technical Specification 3.6.5, Containment Air Temperature Actions NL-24-0227, Proposed Inservice Inspection Alternative GEN-ISI-AL T-2024-03 for Pressurizer Welds in Accordance with 10 CFR 50.55a(z)(1)2024-07-0303 July 2024 Proposed Inservice Inspection Alternative GEN-ISI-AL T-2024-03 for Pressurizer Welds in Accordance with 10 CFR 50.55a(z)(1) ML24184A0452024-07-0202 July 2024 Notification of Inspection and Request for Information for NRC Problem Identification and Resolution Inspection ML24178A3762024-07-0101 July 2024 Nonacceptance of Requested Licensing Action License Amendment Request to Revise Technical Specification 3.6.5, Containment Air Temperature, Using Risk-Informed Process for Evaluations NL-24-0234, Application to Revise Technical Specifications to Adopt TSTF-589, Eliminate Automatic Diesel Generator Start During Shutdown2024-06-28028 June 2024 Application to Revise Technical Specifications to Adopt TSTF-589, Eliminate Automatic Diesel Generator Start During Shutdown NL-24-0230, License Amendment Request for Adoption of Technical Specifications Task Force (TSTF) Traveler TSTF-500, Revision 2, DC Electrical Rewrite – Update to TSTF-3602024-06-28028 June 2024 License Amendment Request for Adoption of Technical Specifications Task Force (TSTF) Traveler TSTF-500, Revision 2, DC Electrical Rewrite – Update to TSTF-360 NL-24-0143, Proposed Alternative to Use ASME Code Case N-752, Risk-Informed Categorization and Treatment for Repair/ Replacement Activities in2024-06-27027 June 2024 Proposed Alternative to Use ASME Code Case N-752, Risk-Informed Categorization and Treatment for Repair/ Replacement Activities in NL-24-0235, Manual Reactor Trip Due to Loss of Power to the 2A 125 Volt DC Distribution Panel2024-06-19019 June 2024 Manual Reactor Trip Due to Loss of Power to the 2A 125 Volt DC Distribution Panel NL-24-0201, Proposed Inservice Inspection Alternative GEN-ISI-ALT-2024-002 for Steam Generator Welds in Accordance with 10 CFR 50.55a(z)(1)2024-06-18018 June 2024 Proposed Inservice Inspection Alternative GEN-ISI-ALT-2024-002 for Steam Generator Welds in Accordance with 10 CFR 50.55a(z)(1) NL-24-0221, Pressurizer Safety Valve Lift Pressure Outside of Technical Specifications Limits Due to Setpoint Drift2024-06-17017 June 2024 Pressurizer Safety Valve Lift Pressure Outside of Technical Specifications Limits Due to Setpoint Drift NL-24-0238, RIPE License Amendment Request to Change Containment Air Temperature Actions, Supplemental Information2024-06-14014 June 2024 RIPE License Amendment Request to Change Containment Air Temperature Actions, Supplemental Information NL-24-0229, Notice of Intent to Pursue Subsequent License Renewal2024-06-0707 June 2024 Notice of Intent to Pursue Subsequent License Renewal ML24149A0492024-06-0404 June 2024 SNC Fleet - Regulatory Audit in Support of Review of the License Amendment Request to Revise TS 1.1, Use and Application Definitions, and Add New Technical Specification 5.5.21 and 5.5.17, Online Monitoring Program, ML24143A0412024-05-28028 May 2024 Supplemental Information Needed for Using the Risk-Informed Process for Evaluation for the LAR to Change Technical Specification 3.6.5, Containment Air Temperature, Actions NL-24-0202, SNC Response to Regulatory Issue Summary 2024-01: Preparation and Scheduling of Operator Licensing Examinations2024-05-24024 May 2024 SNC Response to Regulatory Issue Summary 2024-01: Preparation and Scheduling of Operator Licensing Examinations NL-24-0191, Annual Radiological Environmental Operating Reports for 20232024-05-10010 May 2024 Annual Radiological Environmental Operating Reports for 2023 NL-24-0064, Units 1 & 2 and Hatch Nuclear Plant - Units 1 & 2 License Amendment Request to Revise Technical Specification 1.1 and Add Online Monitoring Program to Technical Specification 5.52024-05-0303 May 2024 Units 1 & 2 and Hatch Nuclear Plant - Units 1 & 2 License Amendment Request to Revise Technical Specification 1.1 and Add Online Monitoring Program to Technical Specification 5.5 NL-24-0188, Cycle 33 Core Operating Limits Report2024-05-0101 May 2024 Cycle 33 Core Operating Limits Report NL-24-0165, Annual Non-Radiological Environmental Operating Reports and Annual Radioactive Effluent Release Reports for 20232024-04-25025 April 2024 Annual Non-Radiological Environmental Operating Reports and Annual Radioactive Effluent Release Reports for 2023 IR 05000348/20240012024-04-24024 April 2024 Integrated Inspection Report 05000348/2024001 and 05000364/2024001 NL-24-0137, RIPE License Amendment Request to Change Containment Air Temperature Actions2024-04-19019 April 2024 RIPE License Amendment Request to Change Containment Air Temperature Actions IR 05000348/20240102024-04-16016 April 2024 NRC Inspection Report 05000348/2024010 and 05000364/2024010 NL-24-0123, for Manual Reactor Trip Due to Loss of Power to the 2A 125 Volt DC Distribution Panel2024-04-15015 April 2024 for Manual Reactor Trip Due to Loss of Power to the 2A 125 Volt DC Distribution Panel NL-24-0134, Renewed National Pollutant Discharge Elimination System (NPDES) Permit2024-04-12012 April 2024 Renewed National Pollutant Discharge Elimination System (NPDES) Permit IR 05000348/20240112024-04-12012 April 2024 Fire Protection Team Inspection Report 05000348/2024011 and 05000364/2024011 NL-24-0088, Application to Revise Technical Specifications Regarding Change to Containment Spray Nozzle Test Frequency2024-04-0505 April 2024 Application to Revise Technical Specifications Regarding Change to Containment Spray Nozzle Test Frequency NL-24-0115, Response to Request for Additional Information Exemption Requests for Physical.2024-04-0404 April 2024 Response to Request for Additional Information Exemption Requests for Physical. NL-24-0116, Nuclear Property Insurance Coverage as of April 1, 2024 and Licensee Guarantees of Payment of Deferred.2024-03-29029 March 2024 Nuclear Property Insurance Coverage as of April 1, 2024 and Licensee Guarantees of Payment of Deferred. ML24061A1692024-03-22022 March 2024 PM Reassignment Letter Farley March 2024 NL-24-0092, Inservice Inspection Program Owners Activity Report (OAR-1) for Outage 2R292024-03-15015 March 2024 Inservice Inspection Program Owners Activity Report (OAR-1) for Outage 2R29 2024-09-05
[Table view] Category:Safety Evaluation
MONTHYEARML24242A1332024-08-29029 August 2024 Issuance of Amendment Nos. 250 and 247, Regarding License Amendment Request to Revise Technical Specification 3.6.5, Containment Air Temperature, Actions (EPID L-2024-LLA-0098) - Non-Proprietary ML23228A1432023-11-22022 November 2023 Issuance of Amendment Nos. 249 and 246 to Revise TS 3.6.3, Surveillance Requirement 3.6.3.5 to Eliminate Event-Based Testing of Containment Purge Valves with Resilient Seals ML23164A1202023-08-30030 August 2023 Proposed Inservice Inspection Alternative FNP-ISI-ALT-05-05, Version 1.0, to the Requirements of the ASME Code ML23235A2962023-08-24024 August 2023 Issuance of Amendment Nos. 247 and 244, Regarding License Amendment Request to Revise Technical Specification 3.6.5, Containment Air Temperature, (EPID L-2023-LLA-0116) (Emergency Circumstances) ML23202A1122023-08-0202 August 2023 Units, 1 and 2; and Vogtle Units 1 and 2 - Request to Use a Provision of a Later Edition of the American Society of Mechanical Engineers Boiler and Pressure Vessel Code, Section XI ML23136B1542023-07-0303 July 2023 Issuance of Amendment Nos. 246 & 243, Regarding License Amendment Request to Revise Technical Specification 4.3, Fuel Storage, to Correct Tabulated Values from the Associated Spent Fuel Pool (SFP) Criticality Analysis ML23164A2072023-06-14014 June 2023 Draft Safety Evaluation for License Amendment Request to Revise Technical Specification 4.3, Fuel Storage, to Correct Tabulated Values from the Associated SFP Criticality Analysis (EPID L-2022-LLA-0138) - Draft Safety Evaluation ML23054A4552023-03-16016 March 2023 Issuance of Amendment Nos. 245 and 242, Regarding LAR to Revise Technical Specification 3.4.10, Pressurizer Safety Valves, to Decrease Low Side Setpoint Tolerance LCO Value ML22308A0592022-11-0808 November 2022 Issuance of Amendments Regarding Revision to Technical Specifications to Relocate Augmented Piping Inspection Program Details to a Licensee-Controlled Document ML22286A0742022-11-0808 November 2022 Issuance of Amendments Regarding Revision to Technical Specifications to Relocate Augmented Piping Inspection Program Details to a Licensee-Controlled Document ML22069A0042022-04-27027 April 2022 Issuance of Amendments Revision to TSs to Adopt TSTF-269-A, Rev. 2, Allow Administrative Means of Position Verification for Locked or Sealed Valves ML22032A2432022-03-0707 March 2022 Issuance of Amendment Nos. 241 and 238 to Eliminate the Encapsulation Vessels Around the First Containment Spray and Residual Heat Removal / Low Head Safety Injection Recirculation Suction Isolation Valves ML21349A5182022-02-0202 February 2022 Issuance of Amendments Regarding Revision to Technical Specifications to Adopt TSTF-554, Revise RCS Leakage ML21344A0032022-01-26026 January 2022 Issuance of Amendments Regarding Revision to Use Beacon Power Distribution Monitoring System ML21316A0552022-01-0505 January 2022 1 & 2, and Vogtle Electric Generating Plant, 1 & 2 - Issuance of Amendments Regarding Revision to Technical Specifications to Adopt TSTF-577, Revised Frequencies for Steam Generator Tube Inspections (EPID L-2021-LLA-0163 ML21270A0862021-11-18018 November 2021 Issuance of Amendments Regarding Revision to Technical Specifications 5.7, High Radiation, Administrative Controls ML21217A0912021-09-21021 September 2021 SNC Fleet, Issuance of Amendments Regarding Revision to Emergency Plan to Change Staffing and Extend Staff Augmentation Times for Emergency Response Organization Positions ML21167A3152021-07-30030 July 2021 Issuance of Amendments Regarding Revision to Technical Specifications to Adopt TSTF-541, Rev.2, Add Exceptions to Surveillance Requirements for Valves & Dampers Locked in Actuated Position ML21137A2472021-06-30030 June 2021 Issuance of Amendment Nos. 233 and 230, Regarding Risk-Informed Categorization and Treatment of Structures, Systems, and Components ML21161A2012021-06-22022 June 2021 Associated Independent Spent Fuel Storage Facilities - Reduction in Commitment to the Quality ML20303A1192020-12-11011 December 2020 Issuance of Amendment Nos. 232 and 229 Regarding Adoption of TSTF-567, Revision 1, Add Containment Sump TS to Address GSI-191 Issues ML20224A2852020-10-13013 October 2020 Issuance of Amendment Nos. 231 and 228 to Revise Technical Specifications 3.3.1 and 3.3.7 ML20121A2832020-10-0909 October 2020 Issuance of Amendments 230 and 227 Measurement Uncertainty Recapture Power Uprate ML20196L9292020-10-0606 October 2020 Issuance of Amendment Nos. 229 and 226 Regarding Spent Fuel Pool Criticality Safety Analysis ML20132A2072020-05-0808 May 2020 9 to the Updated Final Safety Analysis Report, Chapter 1, Introduction and General Description of the Plant and Chapter 2 (Part 1 of 3); Redacted Version ML20034E8942020-02-11011 February 2020 Relief Request Gen-ISI-ALT-2019-01 for Proposed Alternative to Use of ASME Code Case N-831-1, Ultrasonic Examination in Lieu of Radiography for Welds in Ferritic or Austenitic Pipe Section XI, Division 1 ML19337C3222020-01-29029 January 2020 Issuance of Amendments Revision to Technical Specifications to Adopt TSTF-563 ML19261A0142019-09-23023 September 2019 Correction to Safety Evaluation for Amendment Nos. 225 and 222 Regarding Implementation of NEI 06-09, Revision 0-A ML19175A2432019-08-23023 August 2019 Issuance of Amendments 225 and 222 Implementation of NEI 06-09, Risk-Informed Technical Specifications Initiative 4B, Risk-Managed Technical Specification (Rmts) Guidelines, Revision 0-A ML19213A1942019-08-0808 August 2019 Relief from Impractical American Society of Mechanical Engineers Code Requirements (FNP-ISI-RR-02) ML19192A1712019-08-0202 August 2019 Relief from Inservice Impractical ASME Code Requirements (FNP-ISI-RR-03) ML19156A2622019-07-30030 July 2019 Issuance of Amendments 224 and 221 Performance-Based Fire Protection Alternative for Thermal Insulation Material ML19071A1382019-07-16016 July 2019 Issuance of Amendments 223 and 220 Revise Technical Specification Requirements During Handling Irradiated Fuel and Core Alterations TSTF-51 and TSTF-471 ML19129A2322019-07-0101 July 2019 Inservice Inspection Alternative, FNP-ISI-ALT-05-04, Regarding Examination Frequency for Tendon Anchorhead Replacement ML19064A7742019-04-26026 April 2019 Issuance of Amendments Regarding License Amendment Request to Revise Technical Specification 5.2.2.g and Update Emergency Plan Minimum on Shift Staff Tables ML18334A2282018-12-10010 December 2018 Proposed Inservice Inspection Alternative FNP-ISI-ALT-05-03 ML18320A0572018-11-30030 November 2018 Plant, Units 1 and 2 - Proposed Inservice Inspection Alternative GEN-ISI-ALT-2017-03, Code Case N-513-4 for Moderate Pressure ML18271A2072018-11-0707 November 2018 Issuance of Amendments 221 and 218 Technical Specification 3.3.2 Regarding Steam Flow Isolation on High Steam Flow ML18183A0732018-07-26026 July 2018 Unites 1, 2, 3, and 4; and Edwin I. Hatch Nuclear Plant, Unit Nos. 1 and 2(CAC Nos. MG0188, MG0189, MG0191, MG0192, MG0193, MG0194, and MG0195; EPID L-2017-LLA-0293) ML18151A1742018-06-27027 June 2018 Issuance of Amendment Nos. 219 and 216, Adopt Technical Specification Task Force Traveler TSTF-412, Revision 3, Provide Actions for One Steam Supply to Turbine Driven Afw/Efw Pump Inoperable ML17291A7812018-03-0101 March 2018 Issuance of Amendments to Correct Non-Conservative Technical Specification 3.7.1 (CAC Nos. MF9465 and MF9466; EPID L-2017-LLA-0181) ML17261A0872018-02-28028 February 2018 Issuance of Amendments to Revise Actions of TS 5.5.17, Containment Leakage Rate Testing Program (CAC Nos. MF8844 and MF8845; EPID No. L-2016-LLA-0015) ML18022A1072018-01-25025 January 2018 Inservice Inspection Alternative GEN-ISI-ALT-2017-02, Version 1.0, Regarding the Use of ASME Code Case N-789-1 (CAC Nos. MF9942, MF9943, MF9944, and MF9945; EPID L-2017-LLR-0059) ML17354A9162017-12-28028 December 2017 Inservice Inspection Alternative FNP-ISI-ALT-05-01, Version 1, to Use ASME Code N-854 (CAC Nos. MG0107 and MF0108; EPID L-2017-LLR-0086) ML17271A2652017-12-20020 December 2017 Issuance of Amendments Adopting Alternative Source Term, TSTF-448, and TSTF-312 (CAC Nos. MF8861, MF8862, MF8916, MF8917, MF8918, MF8919; Epids Nos. L-2016-LLA-0017,L-2016-LLA-0018, L-2016-LLA-0019) ML17298A4162017-11-0101 November 2017 Relief Request FNP-ISI-ALT-22, Inservice Inspection Alternative for Code Case N-786-1 ML17269A1662017-11-0101 November 2017 Issuance of Amendments Related to NFPA 805 Supplement (CAC Nos. MG0094 and MG0095; EPID L-2017-LLA-0261) ML17214A5462017-10-0202 October 2017 Issuance of Amendments Regarding the Adoption of TSTF-547, Revision 1, Clarification of Rod Position Requirements ML17205A0202017-09-15015 September 2017 Issuance of Amendments to Revise TS 3.8.9, Distribution Systems - Operating ML17180A4392017-07-18018 July 2017 Inservice Testing Alternative for Pumps Per Code Case OMN-20 (RR-VR-01) 2024-08-29
[Table view] |
Text
UNITED STATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D.C. 20555-0001 December 28, 2017 Mr. James J. Hutto Regulatory Affairs Director Southern Nuclear Operating Company, Inc.
P.O. Box 1295 / Bin - 038 Birmingham, AL 35201-1295
SUBJECT:
JOSEPH M. FARLEY NUCLEAR PLANT, UNITS 1 AND 2 - INSERVICE INSPECTION ALTERNATIVE FNP-ISI-ALT-05-01, VERSION 1, TO USE ASME CODE CASE N-854 (CAC NOS. MG0107 AND MG0108; EPID L-2017-LLR-0086)
Dear Mr. Hutto:
By letter dated August 9, 2017, Southern Nuclear Operating Company (SNC, the licensee),
submitted a proposed alternative to certain American Society of Mechanical Engineers (ASME)
Boiler and Pressure Vessel (BPV) Code,Section XI, "Rules for inservice inspection of nuclear power plant components," requirements at Joseph M. Farley Nuclear Plant (FNP), Units 1 and 2.
Specifically, the licensee requested to use ASME Code Case N-854, "Alternative Pressure Testing Requirements for Class 2 and 3 Components Connected to the Class 1 Boundary Section XI, Division 1," as an alternative to the inservice inspection (ISi) requirements of the ASME BPV Code,Section XI, 2007 Edition with the 2008 Addenda, during the fifth 10-year ISi interval that commenced on December 1, 2017, and ends on November 30, 2027.
The licensee submitted the alternative pursuant to Title 10 of the Code of Federal Regulations (10 CFR) Part 50, Section 50.55a(z)(1 ), for which the licensee requested to use the proposed alternative on the basis that it provides an acceptable level of quality and safety.
The U.S. Nuclear Regulatory Commission (NRC) staff reviewed the subject request and has determined, as set forth in the enclosed safety evaluation, that the alternative provides an acceptable level of quality and safety. The NRC staff concludes that the licensee has adequately addressed all of the regulatory requirements set forth in 10 CFR 50.55a(z)(1 ).
Therefore, the NRC staff authorizes the proposed alternative until the end of the fifth 10-year ISi interval for FNP, Units 1 and 2.
All other requirements of the ASME BPV Code,Section XI, for which relief has not been specifically requested and approved remain applicable, including a third party review by the Authorized Nuclear lnservice Inspector.
If you have any questions, please contact the Project Manager, Shawn Williams, at 301-415-1009 or by email at Shawn.Williams@nrc.gov.
Si;:t~
Michael T. Markley, Chief Plant Licensing Branch 11-1 Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation Docket Nos. 50-348 and 50-364
Enclosure:
Safety Evaluation cc w/enclosure: Listserv
UNITED STATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D.C. 20555-0001 SAFETY EVALUATION BY THE OFFICE OF NUCLEAR REACTOR REGULATION PROPOSED ALTERNATIVE REQUEST FNP-ISI-ALT-05-01, VERSION 1.0 USE OF ASME CODE CASE N-854 SOUTHERN NUCLEAR OPERATING COMPANY, INC.
JOSEPH M. FARLEY NUCLEAR PLANT, UNITS 1 AND 2 DOCKET NOS. 50-348 AND 50-364
1.0 INTRODUCTION
By letter dated August 9, 2017 (Agencywide Documents Access and Management System, Accession No. ML17221A330), Southern Nuclear Operating Company, Inc. (SNC, the licensee),
submitted a proposed alternative to certain American Society of Mechanical Engineers (ASME)
Boiler and Pressure Vessel (BPV) Code,Section XI, "Rules for inservice inspection of nuclear power plant components," requirements at Joseph M. Farley Nuclear Plant (FNP), Units 1 and 2.
Specifically, the licensee requested to use ASME Code Case N-854, "Alternative Pressure Testing Requirements for Class 2 and 3 Components Connected to the Class 1 Boundary Section XI, Division 1," as an alternative to the inservice inspection (ISi) requirements of the ASME BPV Code,Section XI, 2007 Edition with the 2008 Addenda, during the fifth 10-year ISi interval, that commenced on December 1, 2017, and ends on November 30, 2027.
The licensee submitted the alternative pursuant to Title 10 of the Code of Federal Regulations (1 O CFR) Part 50, Section 50.55a(z)(1 ), for which the licensee requested to use the proposed alternative on the basis that it provides an acceptable level of quality and safety.
2.0 REGULATORY EVALUATION
Pursuant to 10 CFR 50.55a(g)(4), throughout the service life of a pressurized water-cooled nuclear power facility, components that are classified as ASME Code Class 1, 2, and 3 must meet the requirements, except the design and access provisions and preservice examination requirements, set forth in the ASME BPV Code,Section XI, to the extent practical, within the limitations of design, geometry, and materials of construction of the components. Further, these regulations require that inservice examination of components and system pressure tests conducted during the first 10-year interval, and subsequent intervals, comply with the requirements in the latest edition and addenda of Section XI of the ASME BPV Code, incorporated by reference in paragraph (b) of 10 CFR 50.55a, on the date 12 months prior to the start of the 120 month interval, subject to the limitations and modifications listed therein.
Enclosure
Alternatives to requirements under 10 CFR 50.55a(g) may be authorized by the U.S. Nuclear Regulatory Commission (NRC) pursuant to 10 CFR 50.55a(z)(1) or 10 CFR 50.55a(z)(2). In proposing alternatives or requests for relief, the licensee must demonstrate that: (1) the proposed alternatives would provide an acceptable level of quality and safety; or (2) compliance with the specified requirements would result in hardship or unusual difficulty, without a compensating increase in the level of quality and safety.
Based on the above, and subject to the following technical evaluation, the NRC staff finds that regulatory authority exists for the licensee to request, and the NRC to authorize, the proposed alternative requested by the licensee.
3.0 TECHNICAL EVALUATION
3.1 Applicable Code Edition and Addenda The ASME BPV Code,Section XI, 2007 Edition with the 2008 Addenda, is the applicable Code edition and addenda.
3.2 ISi Interval The request is applicable during the fifth 10-year ISi interval that commenced on December 1, 2017, and ends on November 30, 2027.
3.3 Applicable Code Components The ASME Code Class 2 and 3 components connected directly to a Class 1 system that are pressurized as part of the Class 1 system leakage test.
3.4 Applicable Code Requirements The ASME BPV Code,Section XI, IWA-5213(a), specifies the test condition holding time after pressurization to test conditions before the visual examinations commence for system pressure tests.
3.5 Licensee's Basis For Proposing an Alternative The licensee states that the ASME Code test condition hold time requirements during system leakage tests are based on the component classifications of ASME BPV Code,Section XI, Class 1, 2, or 3 components and whether the system is normally inservice. The licensee states that these requirements do not recognize when ASME Code Class 2 or 3 piping and components are pressurized as part of the ASME Code Class 1 system leakage test. As the ASME Code Class 1 system pressure test takes several hours of increasing temperature and pressure to reach the required pressure corresponding to 100 percent rated reactor power, as required in IWB-5221 to perform the test, these sections of ASME Code Class 2 or 3 piping or components would receive the same level of test performance as the ASME Code Class 1 piping. The licensee states that this time period either exceeds or is more restrictive than the required 1O minute or 4 hour4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> hold time for ASME Code Class 2 or 3 components in IWA-5213(a).
Further, the licensee states that these ASME Code Class 2 and 3 piping and components connected to the ASME Code Class 1 system are not currently addressed in the design configuration of IWA-5213(a) of the ASME BPV Code,Section XI, 2007 Edition through the 2008 Addenda. As such, the ASME Code Case N-854 was developed and approved by the ASME BPV Code Committee as an alternative, which allows the licensee to credit the performance of the ASME Code Class 1 pressure test to meet the requirements of IWA-5213(a) for the ASME Code Class 2 and 3 piping and components connected directly and normally pressurized during the ASME Code Class 1 system pressure test. As this ASME Code Case has not undergone full NRC review and approval for inclusion in NRC Regulatory Guide 1.147, "lnservice Inspection Code Case Acceptability, ASME Section XI, Division 1," the licensee proposed to use ASME Code Case N-854 at FNP, Units 1 and 2, in accordance with 10 CFR 50.55a(z)(1 ).
3.6 NRC Staff Evaluation The licensee is requesting to use ASME Code Case N-854 at FNP, Units 1 and 2, pursuant to 10 CFR 50.55a(z)(1 ), because it achieves an acceptable level of quality and safety. The NRC staff notes that while ASME Code Case N-854 has not been formally approved for inclusion into NRC Regulatory Guide 1.147 for general use by all licensees, NRC staff has participated in the ASME BPV Code meetings used to develop and approve ASME Code Case N-854. The NRC staff found no technical issues to limit or restrict the use of ASME Code Case N-854. The NRC
- staff representative on each ASME BPV Code committee has voted to approve its final acceptance. During the time it takes to formally approve ASME Code Case N-854 into NRC Regulatory Guide 1.147, a licensee can request to use ASME Code Case N-854 as an alternative the current requirements.
The ASME Code Class 2 and 3 pressure test hold times for components are based on the consideration that the system may not be fully pressurized at all times of test operation (e.g.
system pumps may not be running). Therefore, in order to maintain an effective test, hold times were incorporated to ensure sufficient time at pressure when looking for any leakage. As stated by the licensee, the ASME Code Class 1 system leakage test does not include these hold times, due to the time required to reach operational temperature and pressure for the ASME Code Class 1 system. The ASME Code Class 2 and 3 piping and components that are the subject of this proposed alternative are directly connected to the ASME Code Class 1 system and are pressurized by the same test. As the NRC has approved these pressure test conditions for the more safety significant ASME Code Class 1 systems and components to verify structural integrity and leak tightness, the NRC staff finds the use of the same requirements on ASME Code Class 2 and 3 piping and components directly connected and pressurized during the same test to also provide reasonable assurance of structural integrity and leak tightness.
Therefore, the NRC staff finds the use of ASME Code Case N-854 provides an acceptable level of quality and safety.
4.0 CONCLUSION
As set forth above, the NRC staff has determined that it has the regulatory authority to authorize the proposed alternative and that the use of ASME Code Case N-854 at FNP, Units 1 and 2, provides an acceptable level of quality and safety. Accordingly, the NRC staff concludes that the licensee has adequately addressed all of the regulatory requirements set forth in 10 CFR 50.55a(z)(1 ), and is in compliance with the ASME Code requirements. Therefore, the NRC staff authorizes FNP-ISI-ALT-05-01, Version 1.0, at FNP, Units 1 and 2, until the end of the fifth 10-year ISi interval.
All other requirements of the ASME BPV Code,Section XI, for which relief has not been specifically requested and approved remain applicable, including a third party review by the Authorized Nuclear lnservice Inspector.
Principal Contributor: Jay Collins, NRR Date: December 28, 2017
ML17354A916 *via email OFFICE DORL/LPLll-1/PM DORL/LPLll-1/LA DMLR/MPHB/BC*
JTsao NAME SWilliams KGoldstein (DAIiey for)
DATE 12/26/17 12/22/17 12/6/17 OFFICE DORL/LPLI 1-1 /BC DORL/LPLll-1/PM NAME MMarkley (MOrenak for) SWilliams DATE 12/27/17 12/28/17