August 10, 1989 D ISTRIBUTION 33 3

"Il

-3 32

~-NRC IILPDRs BGrimes 9/A/2 PD22 Rdg Fi le ACRS(10)

SVarga 14/E/4 flSinkule RI I GLainas 14/H/3 AToa1 ston 8/D/20 MBer kow

.'Rosa, 9/D/20 DNilier FHebdon 13/D/18

,GEdison ETomlinson 13/D/18 SMoffman OGC

Dear Nr. Woody:

SUBJECt:

TURKEY POINT UNITS 3 AND 4 - QUALIFICATION OF NEW EMERGENCY DIESEL GENERATORS (TAC NOS. 69023 AND 69024)

Docket Nos.

50-250 and 50-251 Nr.

C. 0.

Woody, Acting Senior Vice President-Nuclear Nuclear Energy Department Florida Power and Light Company P.O.

Box 14000 Juno Beach, Florida 33408-0420 In a submittal dated October 19, 1988, you requested NRC staff review of the proposed qualification testing program for the new emergency diesel generators (EDGs) being installed as part of the emergency power system enhancement.

In lieu of a 300 Start and Load Acceptance Test as specified in IEEE 387-1984, you proposed to accept a

30 Start and Load Acceptance Test as recommended by the EDG supplier, Morrison-Knudsen

Company, Power Systems Division.

The supplier's position is that previous qualification testing on similar EDGs is applicable to the proposed Turkey Point EDGs.

All other qualification testing, both at the factory and the site, would be performed in accordance with IEEE Standard 387-1984 and Regulatory Guide 1.9.

The NRC staff has reviewed the October 19, 1988. submittal, as well as subsequent information obtained concerning the proposed testing program.

As discussed in the enclosed Safety Evaluation, the staff finds the 30 Start and Load Acceptance Test acceptable.

Sincere ly, Original signed by

Enclosure:

As stated cc w/enclosure:

See next page Gordon E. Edison, Sr. Project Manager Project Directorate II-2 Division of Reactor Projects-I/II Office of Nuclear Reactor Regulation ITP/TAC 69023 AND 69024]

I-2 PM: PDI I-e SHoffman jd

/Q/89 08/ /9/89 PN:PDII-2 GEdison 08/IP/89 D:PD HBer w

08/(b /89

~~~a>SOSay s

PDR ADOC SS'Qggo P

o~ooozgp PDC

lj <, 1

')

V II gj H

~

% rt

'i

$4 li IJ p

,j I

.ki M

F t

I "r

- Mr. C. 0.

Woody Florida Power and Light Company Turkey Point Plant CC:

Harold F. Reis, Esquire Newman and Holtzinger, P.C.

1615 L Street, N.W.

Washington, DC 20036 Mr. Jack Shreve Office of the Public Counsel Room 4, Holland Building Ta llaha ssee, Flori da 32304 John T. Butler, Esquire

Steel, Hector and Davis 4000 Southeast Financial Center
Miami, Florida 33131-2398 Mr. K. N. Harri s, Vice Pres ident Turkey Point Nuclear Plant Florida Power and Light Company P.O.

Box 029100 Miami, Florida 33102 County Manager of Metropolitan Dade County 111 NW 1st Street, 29th Floor Miami, Florida 33128 Seni or Res ident Inspector Turkey Point Nuclear Generating Station U.S. Nuclear Regulatory Commission Post Office Box 57-1185 Miami, Flori da 33257-1185 Mr. Jacob Daniel Nash Office of Radiation Control Department of Health and Rehabilitative Services 1317 Winewood Blvd.

Tallahassee, Flori da 32399-0700 Intergovernmental Coordination and Review Office of Planning 8 Budget Executive Office of the Governor The Capitol Building Tallahassee, F 1orida 32301 Administrator Department of Environoantal Regu lati on Power Plant Siting Section State of Florida 2600 Blair Stone Road Tallahassee, Florida 32301 Regional Administrator, Region II U.S.

Nuclear Regulatory Commission 101 Marietta Street, N.W. Suite 2900 Atlanta, Georgia 30323 Attorney General Depa rtment of Legal Affairs The Capitol Tall ahassee, Flori da 32304 Plant Manager Turkey Point Nuclear Plant Florida Power and Light Company P.O.

Box 029100 Miami, Florida 33102